Sensor / multi-parameter controller · Modbus register map

ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The diaLog DACb is ProMinent's multi-parameter measuring and control controller with up to three measuring and control channels plus a calculated (mathematic) channel. With the Modbus RTU option it is an RS-485 or RS-232 slave. This map covers the measured values, setpoints, status, warning and error words per channel, output states, device information, stop/pause commands, the per-channel control configuration (setpoints, limits, PID terms) and calibration values.

This page lists 95 Modbus registers for the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) — 47 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ProMinent’s own free documentation (linked below) and checked against it.

Manufacturer
ProMinent
Model
DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
Equipment type
Sensor / multi-parameter controller
Registers
95 (47 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8O1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
DACb, diaLog DACb, DULCOMETER DACb
Source document
Software manual DULCOMETER Multi-parameter controller diaLog DACb Modbus RTU · 982017 BA DM 232 01/19 EN · rev. 2019-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)

Integration in brief

Read holding registers (function 03) from PDU 99: each channel block gives the measured value and setpoint as floats followed by status, warnings and the 32-bit error words. Check the endian test value at PDU 197 first. Writes use function 06 for single registers and 16 for floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 99Ch1 measured valueFLOAT32 ABCDChannel 1 measured valueRead
HR 103Ch1 actual setpointFLOAT32 ABCDChannel 1 setpointRead
HR 106Ch1 statusBITMAP16Channel 1 statusRead
HR 108Ch1 existing errorsUINT32 ABCDChannel 1 existing errorsRead
HR 112Ch2 measured valueFLOAT32 ABCDChannel 2 measured valueRead
HR 197Endian test valueUINT32 ABCDEndian test (0xAABBCCDD)Read
HR 199Ch1 stopUINT16Channel 1 stop commandRead/write

Enable Modbus control & writes

Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.

Byte order & addressing

Network setup

Watch out for

ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

95 of 95 shown
ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR99doc 100Ch1 measured valueActual measured value in the channel's configured unit.FLOAT32ABCDRead
HR101doc 102Ch1 controller actuating valueINT16%Read
HR102doc 103Ch1 temperatureINT16× 0.1°CRead
HR103doc 104Ch1 actual setpointFLOAT32ABCDRead
HR105doc 106Ch1 external disturbance valueUINT16%Read
HR106doc 107Ch1 statusBITMAP16Readbit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal)
HR107doc 108Ch1 warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR108doc 109Ch1 existing errors32-bit error word, high word first.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR110doc 111Ch1 unconfirmed errorsErrors not yet acknowledged; same bit layout.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR112doc 113Ch2 measured valueActual measured value in the channel's configured unit.FLOAT32ABCDRead
HR114doc 115Ch2 controller actuating valueINT16%Read
HR115doc 116Ch2 temperatureUINT16× 0.1°CRead
HR116doc 117Ch2 actual setpointFLOAT32ABCDRead
HR118doc 119Ch2 external disturbance valueUINT16%Read
HR119doc 120Ch2 statusBITMAP16Readbit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal)
HR120doc 121Ch2 warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR121doc 122Ch2 existing errors32-bit error word, high word first.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR123doc 124Ch2 unconfirmed errorsErrors not yet acknowledged; same bit layout.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR125doc 126Math channel measured valueFLOAT32ABCDRead
HR127doc 128Math channel statusStatus word of the mathematic channel (no bit list given).UINT16Read
HR128doc 129Math channel warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR131doc 132Current output 1UINT16× 0.1mARead
HR132doc 133Current output 2UINT16× 0.1mARead
HR133doc 134Current output 3UINT16× 0.1mARead
HR134doc 135Dry contact relaysBITMAP16Readbit 0 = Relay 1 (XR1) active; bit 1 = Relay 2 (XR2) active; bit 2 = Alarm relay (XR3) active
HR135doc 136Pump relay 1 (MOSFET)UINT16pulses/minRead
HR136doc 137Pump relay 2 (MOSFET)UINT16pulses/minRead
HR137doc 138Pump relay 3 (MOSFET)UINT16pulses/minRead
HR139doc 140FirmwareFirmware version, raw 32-bit value.UINT32ABCDRead
HR141doc 142Firmware channel 2UINT32ABCDRead
HR143doc 144Firmware Modbus interfaceUINT32ABCDRead
HR145doc 146Serial numberUINT32ABCDRead
HR147doc 148RevisionUINT16Read
HR148doc 149Revision channel 2UINT16Read
HR197doc 198Endian test valueAlways reads 0xAABBCCDD; use it to check word order.UINT32ABCDRead
HR199doc 200Ch1 stopWrite 0xFFFF to stop the channel's control.UINT16Read/write65535 = Stop
HR200doc 201Ch1 pauseUINT16Read/write1 = Pause; 2 = Pause/HOLD
HR201doc 202Ch2 stopWrite 0xFFFF to stop the channel's control.UINT16Read/write65535 = Stop
HR202doc 203Ch2 pauseUINT16Read/write1 = Pause; 2 = Pause/HOLD
HR203doc 204Ch1 configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 3 = Bits 3-6: control type code (only when bit 15 = 1, see notes); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on; bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal)
HR204doc 205Ch1 remote setpointFLOAT32ABCDRead/write
HR206doc 207Ch1 limit 1FLOAT32ABCDRead/write
HR208doc 209Ch1 limit 2FLOAT32ABCDRead/write
HR210doc 211Ch1 XpProportional band.FLOAT32ABCDRead/write
HR212doc 213Ch1 TiIntegral time, 0-9999 s.UINT16sRead/write
HR213doc 214Ch1 TdDerivative time, 0-999 s.UINT16sRead/write
HR215doc 216Ch1 control output limitationUINT16Read/write1 = On
HR216doc 217Ch1 delay after stop0-9999 s.UINT16sRead/write
HR217doc 218Ch1 delay after reboot0-9999 s.UINT16sRead/write
HR218doc 219Ch1 remote setpoint 2FLOAT32ABCDRead/write
HR220doc 221Ch2 configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 3 = Bits 3-6: control type code (only when bit 15 = 1, see notes); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on; bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal)
HR221doc 222Ch2 remote setpointFLOAT32ABCDRead/write
HR223doc 224Ch2 limit 1FLOAT32ABCDRead/write
HR225doc 226Ch2 limit 2FLOAT32ABCDRead/write
HR227doc 228Ch2 XpProportional band.FLOAT32ABCDRead/write
HR229doc 230Ch2 TiIntegral time, 0-9999 s.UINT16sRead/write
HR230doc 231Ch2 TdDerivative time, 0-999 s.UINT16sRead/write
HR231doc 232Ch2 additive basic load-100 to +100 %.INT16%Read/write
HR232doc 233Ch2 control output limitationUINT16Read/write1 = On
HR233doc 234Ch2 delay after stop0-9999 s.UINT16sRead/write
HR234doc 235Ch2 delay after reboot0-9999 s.UINT16sRead/write
HR235doc 236Ch2 remote setpoint 2FLOAT32ABCDRead/write
HR237doc 238Math channel configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on
HR238doc 239Math channel limit 1FLOAT32ABCDRead/write
HR240doc 241Math channel limit 2FLOAT32ABCDRead/write
HR242doc 243Error confirmation channel 1Error acknowledgement word for channel 1, same bit layout as the error word.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR244doc 245Error confirmation channel 2Error acknowledgement word for channel 2.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR246doc 247Error confirmation channel 3Error acknowledgement word for channel 3.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR248doc 249Ch3 measured valueActual measured value in the channel's configured unit.FLOAT32ABCDRead
HR250doc 251Ch3 controller actuating valueINT16%Read
HR251doc 252Ch3 temperatureUINT16× 0.1°CRead
HR252doc 253Ch3 actual setpointFLOAT32ABCDRead
HR254doc 255Ch3 external disturbance valueUINT16%Read
HR255doc 256Ch3 statusBITMAP16Readbit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal)
HR256doc 257Ch3 warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR257doc 258Ch3 existing errors32-bit error word, high word first.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR259doc 260Ch3 unconfirmed errorsErrors not yet acknowledged; same bit layout.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR261doc 262Ch3 stopWrite 0xFFFF to stop the channel's control.UINT16Read/write65535 = Stop
HR262doc 263Ch3 pauseUINT16Read/write1 = Pause; 2 = Pause/HOLD
HR263doc 264Ch3 configurationBits 3-6, 14 and 15 exist only on channels 1 and 2.BITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on
HR264doc 265Ch3 remote setpointFLOAT32ABCDRead/write
HR266doc 267Ch3 limit 1FLOAT32ABCDRead/write
HR268doc 269Ch3 limit 2FLOAT32ABCDRead/write
HR270doc 271Ch3 XpProportional band.FLOAT32ABCDRead/write
HR272doc 273Ch3 TiIntegral time, 0-9999 s.UINT16sRead/write
HR273doc 274Ch3 TdDerivative time, 0-999 s.UINT16sRead/write
HR274doc 275Ch3 additive basic load-100 to +100 %.INT16%Read/write
HR275doc 276Ch3 control output limitationUINT16Read/write1 = On
HR276doc 277Ch3 delay after stop0-9999 s.UINT16sRead/write
HR277doc 278Ch3 delay after reboot0-9999 s.UINT16sRead/write
HR278doc 279Ch3 remote setpoint 2FLOAT32ABCDRead/write
HR282doc 283Slope channel 1Calibration slope.FLOAT32ABCDRead
HR284doc 285Zero point channel 1Calibration zero point.FLOAT32ABCDRead
HR286doc 287Slope channel 2FLOAT32ABCDRead
HR288doc 289Zero point channel 2FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)

What Modbus registers does the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) have?

This map lists 95 registers: 95 holding registers. 47 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a decimal 'Register' number plus the hex PDU address; the PDU address is the register minus 1 (register 100 is requested at PDU address 99, hex 63). The 'address' field here is the PDU address.

What byte order does the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)?

Start with HR 99 Ch1 measured value (Channel 1 measured value); HR 103 Ch1 actual setpoint (Channel 1 setpoint); HR 106 Ch1 status (Channel 1 status); HR 108 Ch1 existing errors (Channel 1 existing errors); HR 112 Ch2 measured value (Channel 2 measured value); HR 197 Endian test value (Endian test (0xAABBCCDD)); HR 199 Ch1 stop (Channel 1 stop command).

How do I enable Modbus control of the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)?

Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.

Where is the official ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus documentation?

The source is Software manual DULCOMETER Multi-parameter controller diaLog DACb Modbus RTU (982017 BA DM 232 01/19 EN), revision 2019-01, published free by ProMinent at https://www.prominent.com/resources/OperatingInstructions/English/19397/982017-BA-DM-232-01-19-EN-Modbus-RTU-DACb-EN.pdf.