- DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
Sensor / multi-parameter controller · Modbus register map
ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The diaLog DACb is ProMinent's multi-parameter measuring and control controller with up to three measuring and control channels plus a calculated (mathematic) channel. With the Modbus RTU option it is an RS-485 or RS-232 slave. This map covers the measured values, setpoints, status, warning and error words per channel, output states, device information, stop/pause commands, the per-channel control configuration (setpoints, limits, PID terms) and calibration values.
This page lists 95 Modbus registers for the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) — 47 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ProMinent’s own free documentation (linked below) and checked against it.
- Manufacturer
- ProMinent
- Model
- DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
- Equipment type
- Sensor / multi-parameter controller
- Registers
- 95 (47 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8O1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- DACb, diaLog DACb, DULCOMETER DACb
Integration notes: ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
Read holding registers (function 03) from PDU 99: each channel block gives the measured value and setpoint as floats followed by status, warnings and the 32-bit error words. Check the endian test value at PDU 197 first. Writes use function 06 for single registers and 16 for floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 99 | Ch1 measured value | FLOAT32 ABCD | Channel 1 measured value | Read |
| HR 103 | Ch1 actual setpoint | FLOAT32 ABCD | Channel 1 setpoint | Read |
| HR 106 | Ch1 status | BITMAP16 | Channel 1 status | Read |
| HR 108 | Ch1 existing errors | UINT32 ABCD | Channel 1 existing errors | Read |
| HR 112 | Ch2 measured value | FLOAT32 ABCD | Channel 2 measured value | Read |
| HR 197 | Endian test value | UINT32 ABCD | Endian test (0xAABBCCDD) | Read |
| HR 199 | Ch1 stop | UINT16 | Channel 1 stop command | Read/write |
Enable Modbus control & writes
Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.
Byte order & addressing
- Register numbers are 1-based; subtract 1 for the PDU address.
- 32-bit values are high word first (ABCD).
- Byte-sized parameters use only the low 8 bits of the register; write the top 8 bits as 0.
- If one register in a multi-register write raises an exception, the rest of that write is ignored.
Network setup
- Factory settings: RS-485, slave address 1, 19200 baud, 8 data bits, odd parity, 1 stop bit; termination off.
- Turn on active termination in the menu when the controller is the last device on the RS-485 line.
- With no parity, 2 stop bits are required.
Watch out for
- Keep responses short at low baud rates: the manual warns that replies over about 100 bytes at 9600 baud (200 at 19200) may be corrupted.
- Read-only registers answer only to function 03.
ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 99doc 100 | Ch1 measured value | Actual measured value in the channel's configured unit. | FLOAT32 | ABCD | Read | |||
| HR | 101doc 102 | Ch1 controller actuating value | INT16 | % | Read | ||||
| HR | 102doc 103 | Ch1 temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 103doc 104 | Ch1 actual setpoint | FLOAT32 | ABCD | Read | ||||
| HR | 105doc 106 | Ch1 external disturbance value | UINT16 | % | Read | ||||
| HR | 106doc 107 | Ch1 status | BITMAP16 | Read | bit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal) | ||||
| HR | 107doc 108 | Ch1 warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 108doc 109 | Ch1 existing errors | 32-bit error word, high word first. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 110doc 111 | Ch1 unconfirmed errors | Errors not yet acknowledged; same bit layout. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 112doc 113 | Ch2 measured value | Actual measured value in the channel's configured unit. | FLOAT32 | ABCD | Read | |||
| HR | 114doc 115 | Ch2 controller actuating value | INT16 | % | Read | ||||
| HR | 115doc 116 | Ch2 temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 116doc 117 | Ch2 actual setpoint | FLOAT32 | ABCD | Read | ||||
| HR | 118doc 119 | Ch2 external disturbance value | UINT16 | % | Read | ||||
| HR | 119doc 120 | Ch2 status | BITMAP16 | Read | bit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal) | ||||
| HR | 120doc 121 | Ch2 warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 121doc 122 | Ch2 existing errors | 32-bit error word, high word first. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 123doc 124 | Ch2 unconfirmed errors | Errors not yet acknowledged; same bit layout. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 125doc 126 | Math channel measured value | FLOAT32 | ABCD | Read | ||||
| HR | 127doc 128 | Math channel status | Status word of the mathematic channel (no bit list given). | UINT16 | Read | ||||
| HR | 128doc 129 | Math channel warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 131doc 132 | Current output 1 | UINT16 | × 0.1 | mA | Read | |||
| HR | 132doc 133 | Current output 2 | UINT16 | × 0.1 | mA | Read | |||
| HR | 133doc 134 | Current output 3 | UINT16 | × 0.1 | mA | Read | |||
| HR | 134doc 135 | Dry contact relays | BITMAP16 | Read | bit 0 = Relay 1 (XR1) active; bit 1 = Relay 2 (XR2) active; bit 2 = Alarm relay (XR3) active | ||||
| HR | 135doc 136 | Pump relay 1 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 136doc 137 | Pump relay 2 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 137doc 138 | Pump relay 3 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 139doc 140 | Firmware | Firmware version, raw 32-bit value. | UINT32 | ABCD | Read | |||
| HR | 141doc 142 | Firmware channel 2 | UINT32 | ABCD | Read | ||||
| HR | 143doc 144 | Firmware Modbus interface | UINT32 | ABCD | Read | ||||
| HR | 145doc 146 | Serial number | UINT32 | ABCD | Read | ||||
| HR | 147doc 148 | Revision | UINT16 | Read | |||||
| HR | 148doc 149 | Revision channel 2 | UINT16 | Read | |||||
| HR | 197doc 198 | Endian test value | Always reads 0xAABBCCDD; use it to check word order. | UINT32 | ABCD | Read | |||
| HR | 199doc 200 | Ch1 stop | Write 0xFFFF to stop the channel's control. | UINT16 | Read/write | 65535 = Stop | |||
| HR | 200doc 201 | Ch1 pause | UINT16 | Read/write | 1 = Pause; 2 = Pause/HOLD | ||||
| HR | 201doc 202 | Ch2 stop | Write 0xFFFF to stop the channel's control. | UINT16 | Read/write | 65535 = Stop | |||
| HR | 202doc 203 | Ch2 pause | UINT16 | Read/write | 1 = Pause; 2 = Pause/HOLD | ||||
| HR | 203doc 204 | Ch1 configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 3 = Bits 3-6: control type code (only when bit 15 = 1, see notes); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on; bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal) | ||||
| HR | 204doc 205 | Ch1 remote setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 206doc 207 | Ch1 limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 208doc 209 | Ch1 limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 210doc 211 | Ch1 Xp | Proportional band. | FLOAT32 | ABCD | Read/write | |||
| HR | 212doc 213 | Ch1 Ti | Integral time, 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 213doc 214 | Ch1 Td | Derivative time, 0-999 s. | UINT16 | s | Read/write | |||
| HR | 215doc 216 | Ch1 control output limitation | UINT16 | Read/write | 1 = On | ||||
| HR | 216doc 217 | Ch1 delay after stop | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 217doc 218 | Ch1 delay after reboot | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 218doc 219 | Ch1 remote setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 220doc 221 | Ch2 configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 3 = Bits 3-6: control type code (only when bit 15 = 1, see notes); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on; bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal) | ||||
| HR | 221doc 222 | Ch2 remote setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 223doc 224 | Ch2 limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 225doc 226 | Ch2 limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 227doc 228 | Ch2 Xp | Proportional band. | FLOAT32 | ABCD | Read/write | |||
| HR | 229doc 230 | Ch2 Ti | Integral time, 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 230doc 231 | Ch2 Td | Derivative time, 0-999 s. | UINT16 | s | Read/write | |||
| HR | 231doc 232 | Ch2 additive basic load | -100 to +100 %. | INT16 | % | Read/write | |||
| HR | 232doc 233 | Ch2 control output limitation | UINT16 | Read/write | 1 = On | ||||
| HR | 233doc 234 | Ch2 delay after stop | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 234doc 235 | Ch2 delay after reboot | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 235doc 236 | Ch2 remote setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 237doc 238 | Math channel configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on | ||||
| HR | 238doc 239 | Math channel limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 240doc 241 | Math channel limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 242doc 243 | Error confirmation channel 1 | Error acknowledgement word for channel 1, same bit layout as the error word. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 244doc 245 | Error confirmation channel 2 | Error acknowledgement word for channel 2. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 246doc 247 | Error confirmation channel 3 | Error acknowledgement word for channel 3. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 248doc 249 | Ch3 measured value | Actual measured value in the channel's configured unit. | FLOAT32 | ABCD | Read | |||
| HR | 250doc 251 | Ch3 controller actuating value | INT16 | % | Read | ||||
| HR | 251doc 252 | Ch3 temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 252doc 253 | Ch3 actual setpoint | FLOAT32 | ABCD | Read | ||||
| HR | 254doc 255 | Ch3 external disturbance value | UINT16 | % | Read | ||||
| HR | 255doc 256 | Ch3 status | BITMAP16 | Read | bit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal) | ||||
| HR | 256doc 257 | Ch3 warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 257doc 258 | Ch3 existing errors | 32-bit error word, high word first. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 259doc 260 | Ch3 unconfirmed errors | Errors not yet acknowledged; same bit layout. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 261doc 262 | Ch3 stop | Write 0xFFFF to stop the channel's control. | UINT16 | Read/write | 65535 = Stop | |||
| HR | 262doc 263 | Ch3 pause | UINT16 | Read/write | 1 = Pause; 2 = Pause/HOLD | ||||
| HR | 263doc 264 | Ch3 configuration | Bits 3-6, 14 and 15 exist only on channels 1 and 2. | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 7 = Limit 1 configuration on; bit 8 = Limit 2 configuration on | |||
| HR | 264doc 265 | Ch3 remote setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 266doc 267 | Ch3 limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 268doc 269 | Ch3 limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 270doc 271 | Ch3 Xp | Proportional band. | FLOAT32 | ABCD | Read/write | |||
| HR | 272doc 273 | Ch3 Ti | Integral time, 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 273doc 274 | Ch3 Td | Derivative time, 0-999 s. | UINT16 | s | Read/write | |||
| HR | 274doc 275 | Ch3 additive basic load | -100 to +100 %. | INT16 | % | Read/write | |||
| HR | 275doc 276 | Ch3 control output limitation | UINT16 | Read/write | 1 = On | ||||
| HR | 276doc 277 | Ch3 delay after stop | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 277doc 278 | Ch3 delay after reboot | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 278doc 279 | Ch3 remote setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 282doc 283 | Slope channel 1 | Calibration slope. | FLOAT32 | ABCD | Read | |||
| HR | 284doc 285 | Zero point channel 1 | Calibration zero point. | FLOAT32 | ABCD | Read | |||
| HR | 286doc 287 | Slope channel 2 | FLOAT32 | ABCD | Read | ||||
| HR | 288doc 289 | Zero point channel 2 | FLOAT32 | ABCD | Read |
Notes on this map
- 32-bit values (FLOAT32 and UINT32) put bits 31-16 in the first register and bits 15-0 in the second, so the word order is ABCD; bytes are sent high byte first. Register 198 (PDU 197) always reads 0xAABBCCDD as a check.
- Measured value, setpoint, limits and Xp are floats in whatever unit the channel is configured for (pH, mV, ppm and so on); the manual does not list units for them.
- Left out: Pump relay 4 (register 139), because its printed PDU address (hex 90) does not match register 139 (which would be hex 8A); the identity-code registers 150-161, because their text encoding is not described; the math-channel error registers 130/131, which the manual marks as reserved for later use; and channel 1 'Additive basic load' (215), printed as UINT16 although its range is -100 to +100 % (channels 2 and 3 are INT16).
- Channel 1 temperature is printed as INT16 and the other channels' temperature as UINT16; both are in 0.1 °C steps and are listed exactly as printed.
- Configuration word bits 3-6 (channels 1 and 2 only, valid only when bit 15 = 1) hold the control type: 0 off, 1 manual, 2 P one-way increase, 3 P one-way decrease, 4 P two-way standard, 5 P two-way dead zone, 6 PID one-way increase, 7 PID one-way decrease, 8 PID two-way standard, 9 PID two-way dead zone.
- Left out: registers 291 and 293, which the manual labels 'Slope Channel 1' and 'Zero point Channel 1' a second time (probably channel 3).
- The text of section 1.7 calls the byte-order test register 'Register 199', but the register table prints it as register 198 (PDU hex C5); the table value is used here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
What Modbus registers does the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) have?
This map lists 95 registers: 95 holding registers. 47 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a decimal 'Register' number plus the hex PDU address; the PDU address is the register minus 1 (register 100 is requested at PDU address 99, hex 63). The 'address' field here is the PDU address.
What byte order does the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)?
Start with HR 99 Ch1 measured value (Channel 1 measured value); HR 103 Ch1 actual setpoint (Channel 1 setpoint); HR 106 Ch1 status (Channel 1 status); HR 108 Ch1 existing errors (Channel 1 existing errors); HR 112 Ch2 measured value (Channel 2 measured value); HR 197 Endian test value (Endian test (0xAABBCCDD)); HR 199 Ch1 stop (Channel 1 stop command).
How do I enable Modbus control of the ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)?
Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.
Where is the official ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU) Modbus documentation?
The source is Software manual DULCOMETER Multi-parameter controller diaLog DACb Modbus RTU (982017 BA DM 232 01/19 EN), revision 2019-01, published free by ProMinent at https://www.prominent.com/resources/OperatingInstructions/English/19397/982017-BA-DM-232-01-19-EN-Modbus-RTU-DACb-EN.pdf.
More ProMinent Modbus register maps
- Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa
Other power & energy meters register maps
- Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Energy meter (multifunction)
SATEC EM133-R residential multifunction meter
SATEC EM133-R (and EM133-XM) multifunction meters, per Modbus reference guide BG0520 Rev. A6 (Oct 2018).
Also known as: EM133, EM133-R, EM133-XM, SATEC EM133 - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16
All power & energy meters Modbus register maps →
Source: Software manual DULCOMETER Multi-parameter controller diaLog DACb Modbus RTU · 982017 BA DM 232 01/19 EN · rev. 2019-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.