- DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
Sensor / multi-parameter controller · Modbus register map
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The diaLog DACa is ProMinent's multi-parameter measuring and control controller; its register map has two measuring and control channels plus a calculated (mathematic) channel. With the Modbus RTU option it is an RS-485 or RS-232 slave. This map covers measured values, setpoints, status, warning and error words per channel, output states, device information, stop/pause commands and the per-channel control configuration (setpoints, limits, PID terms).
This page lists 68 Modbus registers for the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ProMinent’s own free documentation (linked below) and checked against it.
- Manufacturer
- ProMinent
- Model
- DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
- Equipment type
- Sensor / multi-parameter controller
- Registers
- 68 (33 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8O1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- DACa, diaLog DACa, DULCOMETER DACa
Integration notes: ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
Read holding registers (function 03) from PDU 99: each channel block gives the measured value and setpoint as floats followed by status, warnings and the 32-bit error words. Check the endian test value at PDU 197 first. Writes use function 06 for single registers and 16 for floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 99 | Ch1 measured value | FLOAT32 ABCD | Channel 1 measured value | Read |
| HR 103 | Ch1 actual setpoint | FLOAT32 ABCD | Channel 1 setpoint | Read |
| HR 106 | Ch1 status | BITMAP16 | Channel 1 status | Read |
| HR 108 | Ch1 existing errors | UINT32 ABCD | Channel 1 existing errors | Read |
| HR 112 | Ch2 measured value | FLOAT32 ABCD | Channel 2 measured value | Read |
| HR 197 | Endian test value | UINT32 ABCD | Endian test (0xAABBCCDD) | Read |
| HR 199 | Ch1 stop | UINT16 | Channel 1 stop command | Read/write |
Enable Modbus control & writes
Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.
Byte order & addressing
- Register numbers are 1-based; subtract 1 for the PDU address.
- 32-bit values are high word first (ABCD).
- Byte-sized parameters use only the low 8 bits of the register; write the top 8 bits as 0.
- If one register in a multi-register write raises an exception, the rest of that write is ignored.
Network setup
- Factory settings: RS-485, slave address 1, 19200 baud, 8 data bits, odd parity, 1 stop bit; termination off.
- Turn on active termination in the menu when the controller is the last device on the RS-485 line.
- With no parity, 2 stop bits are required.
Watch out for
- Keep responses short at low baud rates: the manual warns that replies over about 100 bytes at 9600 baud (200 at 19200) may be corrupted.
- Read-only registers answer only to function 03.
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 99doc 100 | Ch1 measured value | Actual measured value in the channel's configured unit. | FLOAT32 | ABCD | Read | |||
| HR | 101doc 102 | Ch1 controller actuating value | INT16 | % | Read | ||||
| HR | 102doc 103 | Ch1 temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 103doc 104 | Ch1 actual setpoint | FLOAT32 | ABCD | Read | ||||
| HR | 105doc 106 | Ch1 external disturbance value | UINT16 | % | Read | ||||
| HR | 106doc 107 | Ch1 status | BITMAP16 | Read | bit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal) | ||||
| HR | 107doc 108 | Ch1 warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 108doc 109 | Ch1 existing errors | 32-bit error word, high word first. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 110doc 111 | Ch1 unconfirmed errors | Errors not yet acknowledged; same bit layout. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 112doc 113 | Ch2 measured value | Actual measured value in the channel's configured unit. | FLOAT32 | ABCD | Read | |||
| HR | 114doc 115 | Ch2 controller actuating value | INT16 | % | Read | ||||
| HR | 115doc 116 | Ch2 temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 116doc 117 | Ch2 actual setpoint | FLOAT32 | ABCD | Read | ||||
| HR | 118doc 119 | Ch2 external disturbance value | UINT16 | % | Read | ||||
| HR | 119doc 120 | Ch2 status | BITMAP16 | Read | bit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal) | ||||
| HR | 120doc 121 | Ch2 warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 121doc 122 | Ch2 existing errors | 32-bit error word, high word first. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 123doc 124 | Ch2 unconfirmed errors | Errors not yet acknowledged; same bit layout. | UINT32 | ABCD | Read | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 125doc 126 | Math channel measured value | FLOAT32 | ABCD | Read | ||||
| HR | 127doc 128 | Math channel status | Status word of the mathematic channel (no bit list given). | UINT16 | Read | ||||
| HR | 128doc 129 | Math channel warnings | BITMAP16 | Read | bit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault | ||||
| HR | 131doc 132 | Current output 1 | UINT16 | × 0.1 | mA | Read | |||
| HR | 132doc 133 | Current output 2 | UINT16 | × 0.1 | mA | Read | |||
| HR | 133doc 134 | Current output 3 | UINT16 | × 0.1 | mA | Read | |||
| HR | 134doc 135 | Dry contact relays | BITMAP16 | Read | bit 0 = Relay 1 (XR1) active; bit 1 = Relay 2 (XR2) active; bit 2 = Alarm relay (XR3) active | ||||
| HR | 135doc 136 | Pump relay 1 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 136doc 137 | Pump relay 2 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 137doc 138 | Pump relay 3 (MOSFET) | UINT16 | pulses/min | Read | ||||
| HR | 139doc 140 | Firmware | Firmware version, raw 32-bit value. | UINT32 | ABCD | Read | |||
| HR | 141doc 142 | Firmware channel 2 | UINT32 | ABCD | Read | ||||
| HR | 143doc 144 | Firmware Modbus interface | UINT32 | ABCD | Read | ||||
| HR | 145doc 146 | Serial number | UINT32 | ABCD | Read | ||||
| HR | 147doc 148 | Revision | UINT16 | Read | |||||
| HR | 148doc 149 | Revision channel 2 | UINT16 | Read | |||||
| HR | 197doc 198 | Endian test value | Always reads 0xAABBCCDD; use it to check word order. | UINT32 | ABCD | Read | |||
| HR | 199doc 200 | Ch1 stop | Write 0xFFFF to stop the channel's control. | UINT16 | Read/write | 65535 = Stop | |||
| HR | 200doc 201 | Ch1 pause | UINT16 | Read/write | 1 = Pause; 2 = Pause/HOLD | ||||
| HR | 201doc 202 | Ch2 stop | Write 0xFFFF to stop the channel's control. | UINT16 | Read/write | 65535 = Stop | |||
| HR | 202doc 203 | Ch2 pause | UINT16 | Read/write | 1 = Pause; 2 = Pause/HOLD | ||||
| HR | 203doc 204 | Ch1 configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal) | ||||
| HR | 204doc 205 | Ch1 remote setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 206doc 207 | Ch1 limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 208doc 209 | Ch1 limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 210doc 211 | Ch1 Xp | Proportional band. | FLOAT32 | ABCD | Read/write | |||
| HR | 212doc 213 | Ch1 Ti | Integral time, 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 213doc 214 | Ch1 Td | Derivative time, 0-999 s. | UINT16 | s | Read/write | |||
| HR | 215doc 216 | Ch1 control output limitation | UINT16 | Read/write | 1 = On | ||||
| HR | 216doc 217 | Ch1 delay after stop | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 217doc 218 | Ch1 delay after reboot | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 218doc 219 | Ch1 remote setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 220doc 221 | Ch2 configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal) | ||||
| HR | 221doc 222 | Ch2 remote setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 223doc 224 | Ch2 limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 225doc 226 | Ch2 limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 227doc 228 | Ch2 Xp | Proportional band. | FLOAT32 | ABCD | Read/write | |||
| HR | 229doc 230 | Ch2 Ti | Integral time, 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 230doc 231 | Ch2 Td | Derivative time, 0-999 s. | UINT16 | s | Read/write | |||
| HR | 231doc 232 | Ch2 additive basic load | -100 to +100 %. | INT16 | % | Read/write | |||
| HR | 232doc 233 | Ch2 control output limitation | UINT16 | Read/write | 1 = On | ||||
| HR | 233doc 234 | Ch2 delay after stop | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 234doc 235 | Ch2 delay after reboot | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 235doc 236 | Ch2 remote setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 237doc 238 | Math channel configuration | BITMAP16 | Read/write | bit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low) | ||||
| HR | 238doc 239 | Math channel limit 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 240doc 241 | Math channel limit 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 242doc 243 | Error confirmation channel 1 | Error acknowledgement word for channel 1, same bit layout as the error word. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 244doc 245 | Error confirmation channel 2 | Error acknowledgement word for channel 2. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error | ||
| HR | 246doc 247 | Error confirmation channel 3 | Error acknowledgement word for channel 3. | UINT32 | ABCD | Read/write | bit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error |
Notes on this map
- 32-bit values (FLOAT32 and UINT32) put bits 31-16 in the first register and bits 15-0 in the second, so the word order is ABCD; bytes are sent high byte first. Register 198 (PDU 197) always reads 0xAABBCCDD as a check.
- Measured value, setpoint, limits and Xp are floats in whatever unit the channel is configured for (pH, mV, ppm and so on); the manual does not list units for them.
- Left out: Pump relay 4 (register 139), because its printed PDU address (hex 90) does not match register 139 (which would be hex 8A); the identity-code registers 150-161, because their text encoding is not described; the math-channel error registers 130/131, which the manual marks as reserved for later use; and channel 1 'Additive basic load' (215), printed as UINT16 although its range is -100 to +100 % (channels 2 and 3 are INT16).
- Channel 1 temperature is printed as INT16 and the other channels' temperature as UINT16; both are in 0.1 °C steps and are listed exactly as printed.
- Configuration word: the manual's listing of the control-type code (bits 3-6) is garbled in this edition, so only bits 0, 1, 14 and 15 are given here. The later DACb manual lists the codes cleanly.
- The table lists an 'Error confirmation channel 3' register (247) although DACa has two measuring channels; it is kept as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
What Modbus registers does the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) have?
This map lists 68 registers: 68 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a decimal 'Register' number plus the hex PDU address; the PDU address is the register minus 1 (register 100 is requested at PDU address 99, hex 63). The 'address' field here is the PDU address.
What byte order does the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)?
Start with HR 99 Ch1 measured value (Channel 1 measured value); HR 103 Ch1 actual setpoint (Channel 1 setpoint); HR 106 Ch1 status (Channel 1 status); HR 108 Ch1 existing errors (Channel 1 existing errors); HR 112 Ch2 measured value (Channel 2 measured value); HR 197 Endian test value (Endian test (0xAABBCCDD)); HR 199 Ch1 stop (Channel 1 stop command).
How do I enable Modbus control of the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)?
Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.
Where is the official ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus documentation?
The source is Software manual DULCOMETER Multi-parameter Controller diaLog DACa Modbus RTU (984163 BA DM 212 12/15 EN), revision 2015-12, published free by ProMinent at https://www.prominent.com/resources/OperatingInstructions/English/15023/984163-BA-DM-212-12-15-EN-Modbus-RTU-DACa-EN.pdf.
More ProMinent Modbus register maps
- Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
diaLog DACb controllers with the Modbus RTU interface option, per software manual BA DM 232 01/19.
Also known as: DACb, diaLog DACb, DULCOMETER DACb
Other power & energy meters register maps
- Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200
All power & energy meters Modbus register maps →
Source: Software manual DULCOMETER Multi-parameter Controller diaLog DACa Modbus RTU · 984163 BA DM 212 12/15 EN · rev. 2015-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.