Sensor / multi-parameter controller · Modbus register map

ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The diaLog DACa is ProMinent's multi-parameter measuring and control controller; its register map has two measuring and control channels plus a calculated (mathematic) channel. With the Modbus RTU option it is an RS-485 or RS-232 slave. This map covers measured values, setpoints, status, warning and error words per channel, output states, device information, stop/pause commands and the per-channel control configuration (setpoints, limits, PID terms).

This page lists 68 Modbus registers for the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ProMinent’s own free documentation (linked below) and checked against it.

Manufacturer
ProMinent
Model
DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
Equipment type
Sensor / multi-parameter controller
Registers
68 (33 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8O1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
DACa, diaLog DACa, DULCOMETER DACa
Source document
Software manual DULCOMETER Multi-parameter Controller diaLog DACa Modbus RTU · 984163 BA DM 212 12/15 EN · rev. 2015-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)

Integration in brief

Read holding registers (function 03) from PDU 99: each channel block gives the measured value and setpoint as floats followed by status, warnings and the 32-bit error words. Check the endian test value at PDU 197 first. Writes use function 06 for single registers and 16 for floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 99Ch1 measured valueFLOAT32 ABCDChannel 1 measured valueRead
HR 103Ch1 actual setpointFLOAT32 ABCDChannel 1 setpointRead
HR 106Ch1 statusBITMAP16Channel 1 statusRead
HR 108Ch1 existing errorsUINT32 ABCDChannel 1 existing errorsRead
HR 112Ch2 measured valueFLOAT32 ABCDChannel 2 measured valueRead
HR 197Endian test valueUINT32 ABCDEndian test (0xAABBCCDD)Read
HR 199Ch1 stopUINT16Channel 1 stop commandRead/write

Enable Modbus control & writes

Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.

Byte order & addressing

Network setup

Watch out for

ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

68 of 68 shown
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR99doc 100Ch1 measured valueActual measured value in the channel's configured unit.FLOAT32ABCDRead
HR101doc 102Ch1 controller actuating valueINT16%Read
HR102doc 103Ch1 temperatureINT16× 0.1°CRead
HR103doc 104Ch1 actual setpointFLOAT32ABCDRead
HR105doc 106Ch1 external disturbance valueUINT16%Read
HR106doc 107Ch1 statusBITMAP16Readbit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal)
HR107doc 108Ch1 warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR108doc 109Ch1 existing errors32-bit error word, high word first.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR110doc 111Ch1 unconfirmed errorsErrors not yet acknowledged; same bit layout.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR112doc 113Ch2 measured valueActual measured value in the channel's configured unit.FLOAT32ABCDRead
HR114doc 115Ch2 controller actuating valueINT16%Read
HR115doc 116Ch2 temperatureUINT16× 0.1°CRead
HR116doc 117Ch2 actual setpointFLOAT32ABCDRead
HR118doc 119Ch2 external disturbance valueUINT16%Read
HR119doc 120Ch2 statusBITMAP16Readbit 0 = Channel active (0 = inactive or not connectable); bit 1 = Local stop active; bit 8 = Local control set 2 active (0 = set 1); bit 9 = SD card present; bit 10 = SD card less than 20 % free; bit 11 = SD card full; bit 12 = Warning present; bit 13 = Error present; bit 15 = Channel uses bus control parameters (0 = internal)
HR120doc 121Ch2 warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR121doc 122Ch2 existing errors32-bit error word, high word first.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR123doc 124Ch2 unconfirmed errorsErrors not yet acknowledged; same bit layout.UINT32ABCDReadbit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR125doc 126Math channel measured valueFLOAT32ABCDRead
HR127doc 128Math channel statusStatus word of the mathematic channel (no bit list given).UINT16Read
HR128doc 129Math channel warningsBITMAP16Readbit 0 = Warning 1: below limit; bit 1 = Warning 2: limit exceeded; bit 2 = Warning 3: wash timer expired, maintenance due; bit 3 = Warning 4: channel not calibrated; bit 4 = Warning 71: replace battery; bit 5 = Warning 72: check the clock; bit 6 = Warning 73: fan fault
HR131doc 132Current output 1UINT16× 0.1mARead
HR132doc 133Current output 2UINT16× 0.1mARead
HR133doc 134Current output 3UINT16× 0.1mARead
HR134doc 135Dry contact relaysBITMAP16Readbit 0 = Relay 1 (XR1) active; bit 1 = Relay 2 (XR2) active; bit 2 = Alarm relay (XR3) active
HR135doc 136Pump relay 1 (MOSFET)UINT16pulses/minRead
HR136doc 137Pump relay 2 (MOSFET)UINT16pulses/minRead
HR137doc 138Pump relay 3 (MOSFET)UINT16pulses/minRead
HR139doc 140FirmwareFirmware version, raw 32-bit value.UINT32ABCDRead
HR141doc 142Firmware channel 2UINT32ABCDRead
HR143doc 144Firmware Modbus interfaceUINT32ABCDRead
HR145doc 146Serial numberUINT32ABCDRead
HR147doc 148RevisionUINT16Read
HR148doc 149Revision channel 2UINT16Read
HR197doc 198Endian test valueAlways reads 0xAABBCCDD; use it to check word order.UINT32ABCDRead
HR199doc 200Ch1 stopWrite 0xFFFF to stop the channel's control.UINT16Read/write65535 = Stop
HR200doc 201Ch1 pauseUINT16Read/write1 = Pause; 2 = Pause/HOLD
HR201doc 202Ch2 stopWrite 0xFFFF to stop the channel's control.UINT16Read/write65535 = Stop
HR202doc 203Ch2 pauseUINT16Read/write1 = Pause; 2 = Pause/HOLD
HR203doc 204Ch1 configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal)
HR204doc 205Ch1 remote setpointFLOAT32ABCDRead/write
HR206doc 207Ch1 limit 1FLOAT32ABCDRead/write
HR208doc 209Ch1 limit 2FLOAT32ABCDRead/write
HR210doc 211Ch1 XpProportional band.FLOAT32ABCDRead/write
HR212doc 213Ch1 TiIntegral time, 0-9999 s.UINT16sRead/write
HR213doc 214Ch1 TdDerivative time, 0-999 s.UINT16sRead/write
HR215doc 216Ch1 control output limitationUINT16Read/write1 = On
HR216doc 217Ch1 delay after stop0-9999 s.UINT16sRead/write
HR217doc 218Ch1 delay after reboot0-9999 s.UINT16sRead/write
HR218doc 219Ch1 remote setpoint 2FLOAT32ABCDRead/write
HR220doc 221Ch2 configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low); bit 14 = Use internal parameter set 2 (0 = set 1; only when bit 15 = 0); bit 15 = Use remote (bus) control parameters (0 = internal)
HR221doc 222Ch2 remote setpointFLOAT32ABCDRead/write
HR223doc 224Ch2 limit 1FLOAT32ABCDRead/write
HR225doc 226Ch2 limit 2FLOAT32ABCDRead/write
HR227doc 228Ch2 XpProportional band.FLOAT32ABCDRead/write
HR229doc 230Ch2 TiIntegral time, 0-9999 s.UINT16sRead/write
HR230doc 231Ch2 TdDerivative time, 0-999 s.UINT16sRead/write
HR231doc 232Ch2 additive basic load-100 to +100 %.INT16%Read/write
HR232doc 233Ch2 control output limitationUINT16Read/write1 = On
HR233doc 234Ch2 delay after stop0-9999 s.UINT16sRead/write
HR234doc 235Ch2 delay after reboot0-9999 s.UINT16sRead/write
HR235doc 236Ch2 remote setpoint 2FLOAT32ABCDRead/write
HR237doc 238Math channel configurationBITMAP16Read/writebit 0 = Limit 1 configured high (0 = low); bit 1 = Limit 2 configured high (0 = low)
HR238doc 239Math channel limit 1FLOAT32ABCDRead/write
HR240doc 241Math channel limit 2FLOAT32ABCDRead/write
HR242doc 243Error confirmation channel 1Error acknowledgement word for channel 1, same bit layout as the error word.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR244doc 245Error confirmation channel 2Error acknowledgement word for channel 2.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error
HR246doc 247Error confirmation channel 3Error acknowledgement word for channel 3.UINT32ABCDRead/writebit 0 = Error 1: mV input too low; bit 1 = Error 2: mV input too high; bit 2 = Error 3: temperature too low; bit 3 = Error 4: temperature too high; bit 4 = Error 5: calibration error; bit 5 = Error 6: no sensor; bit 6 = Error 7: check sensor for glass breakage; bit 7 = Error 8: check time exceeded; bit 8 = Error 9: mA input above 20 mA; bit 9 = Error 10: mA input below 4 mA; bit 10 = Error 11: limit error still present after delay; bit 11 = Error 12: sample water fault (e.g. no flow); bit 12 = Error 13: controller in PAUSE; bit 13 = Error 14: controller in PAUSE/HOLD; bit 14 = Error 15: mA input supply overloaded; bit 15 = Error 16: mA input overloaded; bit 16 = Error 17: tank 1 level low; bit 17 = Error 18: tank 2 level low; bit 18 = Error 19: tank 3 level low; bit 19 = Error 34: wrong correction variable; bit 20 = Error 88: expansion module connection fault; bit 31 = Error 99: system error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)

What Modbus registers does the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) have?

This map lists 68 registers: 68 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a decimal 'Register' number plus the hex PDU address; the PDU address is the register minus 1 (register 100 is requested at PDU address 99, hex 63). The 'address' field here is the PDU address.

What byte order does the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)?

Start with HR 99 Ch1 measured value (Channel 1 measured value); HR 103 Ch1 actual setpoint (Channel 1 setpoint); HR 106 Ch1 status (Channel 1 status); HR 108 Ch1 existing errors (Channel 1 existing errors); HR 112 Ch2 measured value (Channel 2 measured value); HR 197 Endian test value (Endian test (0xAABBCCDD)); HR 199 Ch1 stop (Channel 1 stop command).

How do I enable Modbus control of the ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)?

Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.

Where is the official ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU) Modbus documentation?

The source is Software manual DULCOMETER Multi-parameter Controller diaLog DACa Modbus RTU (984163 BA DM 212 12/15 EN), revision 2015-12, published free by ProMinent at https://www.prominent.com/resources/OperatingInstructions/English/15023/984163-BA-DM-212-12-15-EN-Modbus-RTU-DACa-EN.pdf.

More ProMinent Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Software manual DULCOMETER Multi-parameter Controller diaLog DACa Modbus RTU · 984163 BA DM 212 12/15 EN · rev. 2015-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.