Sensor / multi-input controller · Modbus register map

ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) Modbus register map

Updated 17 November 2026

Short answer

The AEGIS II is a ProMinent DULCOMETER controller. Its COM module, fitted in module slot 3, adds a read-only Modbus RTU slave port on RS-485. Every 32-bit value is published twice, once low word first and once high word first; this map uses the high-word-first copy (registers 901-1123) and covers the input readings A-Z, relay and pulse outputs, alarm levels, totalisers, on/off setpoints and the input, output and system state words.

This page lists 124 Modbus registers for the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ProMinent’s own free documentation (linked below) and checked against it.

Manufacturer
ProMinent
Model
DULCOMETER AEGIS II controller (Modbus RTU slave)
Equipment type
Sensor / multi-input controller
Registers
124 (0 writable)
Transport
Modbus RTU
Default unit ID
10
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module
Source document
Software manual DULCOMETER Controller AEGIS II Modbus RTU · 982395 BA DM 229 08/18 EN · rev. 2018-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)

Integration in brief

Poll holding registers (function 03) in the 901-1123 block, at most once per second. Inputs A-N are the sensor readings as high-word-first floats; the state words tell you whether each input and output is enabled, alarmed or interlocked.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 900A - Serial sensor 1 valueFLOAT32 ABCDInput A (serial sensor 1)Read
HR 904C - Module slot 1 value 1FLOAT32 ABCDInput C (module slot 1 value 1)Read
HR 912G - 4-20 mA input valueFLOAT32 ABCDInput G (4-20 mA input)Read
HR 1078A - StateBITMAP16Input A stateRead
HR 1104R1 - Control stateUINT32 ABCDR1 control stateRead
HR 1122System stateUINT32 ABCDSystem stateRead

Enable Modbus control & writes

Fit the COM module in module slot 3 and set the slave address, baud rate and parity at MENU > System > Communications. Connect the master to XB21/XB22 (the XB1 port is the module's own master port for a Pyxis ST-500 probe).

Byte order & addressing

Network setup

Watch out for

ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

124 of 124 shown
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR900doc 901A - Serial sensor 1 valueInput A reading in its configured user unit.FLOAT32ABCDRead
HR902doc 903B - Serial sensor 2 valueInput B reading in its configured user unit.FLOAT32ABCDRead
HR904doc 905C - Module slot 1 value 1Input C reading in its configured user unit.FLOAT32ABCDRead
HR906doc 907D - Module slot 1 value 2Input D reading in its configured user unit.FLOAT32ABCDRead
HR908doc 909E - Module slot 2 value 1Input E reading in its configured user unit.FLOAT32ABCDRead
HR910doc 911F - Module slot 2 value 2Input F reading in its configured user unit.FLOAT32ABCDRead
HR912doc 913G - 4-20 mA input valueInput G reading in its configured user unit.FLOAT32ABCDRead
HR914doc 915H - 10 mV/°C temperature input valueInput H reading in its configured user unit.FLOAT32ABCDRead
HR916doc 917I - Module slot 3 value 1Input I reading in its configured user unit.FLOAT32ABCDRead
HR918doc 919J - Module slot 3 value 2Input J reading in its configured user unit.FLOAT32ABCDRead
HR920doc 921K - Phantom sensor K (slot 3 COM plug-in value 1)Input K reading in its configured user unit.FLOAT32ABCDRead
HR922doc 923L - Phantom sensor L (slot 3 COM plug-in value 2)Input L reading in its configured user unit.FLOAT32ABCDRead
HR924doc 925M - Phantom sensor M (Pyxis ST-500 probe)Input M reading in its configured user unit.FLOAT32ABCDRead
HR926doc 927N - Phantom sensor NInput N reading in its configured user unit.FLOAT32ABCDRead
HR928doc 929O - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR930doc 931P - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR932doc 933Q - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR934doc 935R - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR936doc 937S - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR938doc 939T - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR940doc 941U - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR942doc 943V - Volume meter (daily) / contact inputToday's volume in user units, or 1.0 closed / 0.0 open for a contact input.FLOAT32ABCDRead
HR944doc 945W - Phantom volume meter / contact input1.0 = on, 0.0 = off for contact use.FLOAT32ABCDRead
HR946doc 947X - Phantom volume meter / contact input1.0 = on, 0.0 = off for contact use.FLOAT32ABCDRead
HR948doc 949Y - Phantom volume meter / contact input1.0 = on, 0.0 = off for contact use.FLOAT32ABCDRead
HR950doc 951Z - Phantom volume meter / contact input1.0 = on, 0.0 = off for contact use.FLOAT32ABCDRead
HR952doc 953R1 - Line powered control relay stateRelay output state as a float.FLOAT32ABCDRead
HR954doc 955R2 - Line powered control relay stateRelay output state as a float.FLOAT32ABCDRead
HR956doc 957R3 - Dry or line powered control relay stateRelay output state as a float.FLOAT32ABCDRead
HR958doc 959R4 - Dry or line powered control relay stateRelay output state as a float.FLOAT32ABCDRead
HR960doc 961R5 - Dry or line powered control relay stateRelay output state as a float.FLOAT32ABCDRead
HR962doc 963P6 - Pulse / on-off control outputPulse control: dosing rate 0-100 % (0 = off).FLOAT32ABCD%Read
HR964doc 965P7 - Pulse / on-off control outputPulse control: dosing rate 0-100 % (0 = off).FLOAT32ABCD%Read
HR966doc 967P8 - Pulse / on-off control outputPulse control: dosing rate 0-100 % (0 = off).FLOAT32ABCD%Read
HR968doc 969P9 - Pulse / on-off control outputPulse control: dosing rate 0-100 % (0 = off).FLOAT32ABCD%Read
HR970doc 971A - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR972doc 973A - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR974doc 975B - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR976doc 977B - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR978doc 979C - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR980doc 981C - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR982doc 983D - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR984doc 985D - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR986doc 987E - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR988doc 989E - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR990doc 991F - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR992doc 993F - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR994doc 995G - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR996doc 997G - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR998doc 999H - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1000doc 1001H - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1002doc 1003I - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1004doc 1005I - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1006doc 1007J - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1008doc 1009J - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1010doc 1011K - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1012doc 1013K - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1014doc 1015L - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1016doc 1017L - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1018doc 1019M - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1020doc 1021M - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1022doc 1023N - High alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1024doc 1025N - Low alarm levelReads 0 when the alarm is disabled.FLOAT32ABCDRead
HR1026doc 1027O - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1028doc 1029P - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1030doc 1031Q - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1032doc 1033R - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1034doc 1035S - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1036doc 1037T - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1038doc 1039U - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1040doc 1041V - Total counterTotal volume; 0 if the input is disabled or a contact input.FLOAT32ABCDRead
HR1042doc 1043R1 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1044doc 1045R1 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1046doc 1047R2 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1048doc 1049R2 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1050doc 1051R3 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1052doc 1053R3 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1054doc 1055R4 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1056doc 1057R4 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1058doc 1059R5 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1060doc 1061R5 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1062doc 1063P6 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1064doc 1065P6 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1066doc 1067P7 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1068doc 1069P7 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1070doc 1071P8 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1072doc 1073P8 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1074doc 1075P9 - Turn on setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1076doc 1077P9 - Turn off setpointReads 0 when the output is locked.FLOAT32ABCDRead
HR1078doc 1079A - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1079doc 1080B - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1080doc 1081C - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1081doc 1082D - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1082doc 1083E - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1083doc 1084F - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1084doc 1085G - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1085doc 1086H - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1086doc 1087I - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1087doc 1088J - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1088doc 1089K - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1089doc 1090L - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1090doc 1091M - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1091doc 1092N - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1092doc 1093O - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1093doc 1094P - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1094doc 1095Q - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1095doc 1096R - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1096doc 1097S - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1097doc 1098T - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1098doc 1099U - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1099doc 1100V - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1100doc 1101W - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1101doc 1102X - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1102doc 1103Y - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1103doc 1104Z - StateReads 0 when the parameter is disabled.BITMAP16Readbit 0 = Parameter enabled; bit 1 = Alarmed (alarm action executing); bit 3 = Trips the alarm relay on alarm; bit 10 = Calibration sample capture active; bit 11 = Linked: web user calibrating
HR1104doc 1105R1 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1106doc 1107R2 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1108doc 1109R3 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1110doc 1111R4 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1112doc 1113R5 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1114doc 1115P6 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1118doc 1119P8 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1120doc 1121P9 - Control state32-bit control state word; 0 when output disabled.UINT32ABCDReadbit 0 = Output on (relay on or pulsing); bit 1 = Interlocked by contact input U-Z; bit 2 = Locked out on time; bit 3 = Varying cycle control; bit 4 = Frequency output used as digital output; bit 5 = Turn off on alarm; bit 6 = Interlocked by another relay; bit 8 = Special control active; bit 9 = Second phase of a sequential volume control; bit 10 = Forced on by prebleed; bit 11 = Time owed; bit 13 = Blocking another output; bit 14 = Oxidant event active (assist, pH lockout or alternate control); bit 15 = Flow switch delay active; bit 16 = Driver card communication timeout; bit 17 = Prebleed active; bit 18 = Test (key held); bit 19 = Prime active; bit 20 = On setpoint tripped, waiting for off setpoint; bit 21 = Oxidant event setpoints override control setpoints; bit 22 = Alarm: phantom contact set auto-removed; bit 23 = Latched (contact set control holds state in dead time)
HR1122doc 1123System stateCommon controller state word.UINT32ABCDReadbit 1 = Restart after software reset (watchdog, Ethernet, user); bit 2 = I/O reset to factory; bit 6 = Midnight passed (also while off); bit 7 = New year passed (also while off); bit 9 = Software restart; bit 10 = USB host port active (pumps off); bit 14 = Locked out after failed passwords (resets 07:00); bit 15 = Real-time clock error; bit 16 = No Wi-Fi module response at power-on; bit 17 = microSD file system up; bit 21 = Running (power-on timer expired); bit 22 = Loading new I/O configuration (outputs off); bit 23 = Manufacturing mode; bit 26 = All digital inputs set to contact sets (manufacturing); bit 27 = File system fault / no microSD; bit 29 = No fan: inputs powered down, outputs off; bit 30 = Manufacturing override of SD/fan alarms

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)

What Modbus registers does the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) have?

This map lists 124 registers: 124 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a decimal 'Register' and its PDU address; the PDU address is the register minus 1 (ProMinent register 100 is fetched at PDU 99). Here 'address' is the PDU address, e.g. input A in the high-word-first block is register 901, PDU 900.

What byte order does the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)?

Start with HR 900 A - Serial sensor 1 value (Input A (serial sensor 1)); HR 904 C - Module slot 1 value 1 (Input C (module slot 1 value 1)); HR 912 G - 4-20 mA input value (Input G (4-20 mA input)); HR 1078 A - State (Input A state); HR 1104 R1 - Control state (R1 control state); HR 1122 System state (System state).

How do I enable Modbus control of the ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)?

Fit the COM module in module slot 3 and set the slave address, baud rate and parity at MENU > System > Communications. Connect the master to XB21/XB22 (the XB1 port is the module's own master port for a Pyxis ST-500 probe).

Where is the official ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave) Modbus documentation?

The source is Software manual DULCOMETER Controller AEGIS II Modbus RTU (982395 BA DM 229 08/18 EN), revision 2018-08, published free by ProMinent at https://www.prominent.com/resources/OperatingInstructions/English/19079/982395-BA-DM-229-08-18-EN-Modbus-RTU-Aegis-II-EN.pdf.