Easy Modbus
  1. Home
  2. Modbus register maps
  3. Shinko Technos
  4. PCB1 programmable controller (C5W/C5 option)

Sensor (programmable temperature controller) · Modbus register map

Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus register map

Updated 17 November 2026

Short answer

The PCB1 is a ramp/soak program controller with 10 patterns of 10 steps, 10 PID blocks and three event outputs. On RS-485 it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers all pattern, event, wait and PID-block items, engineering settings, run/hold/advance commands and the read-only monitor block.

This page lists 678 Modbus registers for the Shinko Technos PCB1 programmable controller (C5W/C5 option) — 664 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
PCB1 programmable controller (C5W/C5 option)
Equipment type
Sensor (programmable temperature controller)
Registers
678 (664 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
PCB1
Source document
Communication Instruction Manual PCB1 (C5W, C5) · No. PCB1CE3 · rev. 2019-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos PCB1 programmable controller (C5W/C5 option)

Integration in brief

Select MODBUS RTU mode in Engineering setting mode 1 and give the unit a non-zero instrument number; then poll PV 9000H, current step SV 9003H, pattern/step 9005H and status 900AH-900BH, and start/stop with 8001H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 36864PVINT16Process valueRead
HR 36867Current step SVINT16Current step SVRead
HR 36869Current pattern and stepINT16Running pattern and stepRead
HR 36875Current unit statusBITMAP16Run/hold/wait statusRead
HR 36874Status flagBITMAP16Output, alarm and over/underscale flagsRead
HR 32769Program control RUN/STOPINT16Program RUN/STOPWrite
HR 32768Pattern number for operationINT16Pattern to runRead/write
HR 28675Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C5W or C5 option. In Engineering setting mode 1 (down + MODE for about 3 s) set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit. These can only be set on the keypad.

Byte order & addressing

Network setup

Watch out for

Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

678 of 678 shown
Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR8448doc 2100HP1 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8449doc 2101HP1 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8450doc 2102HP1 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8451doc 2103HP1 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8452doc 2104HP1 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8453doc 2105HP1 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8454doc 2106HP1 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8455doc 2107HP1 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8456doc 2108HP1 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8457doc 2109HP1 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8458doc 210AHP1 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8459doc 210BHP1 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8460doc 210CHP1 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8461doc 210DHP1 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8462doc 210EHP1 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8463doc 210FHP1 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8464doc 2110HP1 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8465doc 2111HP1 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8466doc 2112HP1 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8467doc 2113HP1 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8468doc 2114HP1 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8469doc 2115HP1 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8470doc 2116HP1 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8471doc 2117HP1 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8472doc 2118HP1 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8473doc 2119HP1 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8474doc 211AHP1 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8475doc 211BHP1 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8476doc 211CHP1 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8477doc 211DHP1 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8478doc 211EHP1 number of repetitionsINT16Read/write
HR8479doc 211FHP1 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR8704doc 2200HP2 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8705doc 2201HP2 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8706doc 2202HP2 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8707doc 2203HP2 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8708doc 2204HP2 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8709doc 2205HP2 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8710doc 2206HP2 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8711doc 2207HP2 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8712doc 2208HP2 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8713doc 2209HP2 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8714doc 220AHP2 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8715doc 220BHP2 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8716doc 220CHP2 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8717doc 220DHP2 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8718doc 220EHP2 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8719doc 220FHP2 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8720doc 2210HP2 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8721doc 2211HP2 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8722doc 2212HP2 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8723doc 2213HP2 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8724doc 2214HP2 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8725doc 2215HP2 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8726doc 2216HP2 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8727doc 2217HP2 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8728doc 2218HP2 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8729doc 2219HP2 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8730doc 221AHP2 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8731doc 221BHP2 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8732doc 221CHP2 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8733doc 221DHP2 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8734doc 221EHP2 number of repetitionsINT16Read/write
HR8735doc 221FHP2 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR8960doc 2300HP3 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8961doc 2301HP3 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8962doc 2302HP3 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8963doc 2303HP3 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8964doc 2304HP3 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8965doc 2305HP3 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8966doc 2306HP3 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8967doc 2307HP3 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8968doc 2308HP3 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8969doc 2309HP3 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8970doc 230AHP3 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8971doc 230BHP3 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8972doc 230CHP3 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8973doc 230DHP3 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8974doc 230EHP3 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8975doc 230FHP3 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8976doc 2310HP3 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8977doc 2311HP3 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8978doc 2312HP3 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8979doc 2313HP3 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8980doc 2314HP3 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8981doc 2315HP3 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8982doc 2316HP3 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8983doc 2317HP3 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8984doc 2318HP3 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8985doc 2319HP3 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8986doc 231AHP3 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8987doc 231BHP3 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR8988doc 231CHP3 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR8989doc 231DHP3 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR8990doc 231EHP3 number of repetitionsINT16Read/write
HR8991doc 231FHP3 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR9216doc 2400HP4 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9217doc 2401HP4 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9218doc 2402HP4 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9219doc 2403HP4 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9220doc 2404HP4 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9221doc 2405HP4 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9222doc 2406HP4 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9223doc 2407HP4 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9224doc 2408HP4 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9225doc 2409HP4 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9226doc 240AHP4 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9227doc 240BHP4 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9228doc 240CHP4 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9229doc 240DHP4 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9230doc 240EHP4 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9231doc 240FHP4 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9232doc 2410HP4 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9233doc 2411HP4 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9234doc 2412HP4 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9235doc 2413HP4 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9236doc 2414HP4 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9237doc 2415HP4 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9238doc 2416HP4 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9239doc 2417HP4 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9240doc 2418HP4 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9241doc 2419HP4 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9242doc 241AHP4 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9243doc 241BHP4 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9244doc 241CHP4 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9245doc 241DHP4 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9246doc 241EHP4 number of repetitionsINT16Read/write
HR9247doc 241FHP4 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR9472doc 2500HP5 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9473doc 2501HP5 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9474doc 2502HP5 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9475doc 2503HP5 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9476doc 2504HP5 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9477doc 2505HP5 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9478doc 2506HP5 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9479doc 2507HP5 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9480doc 2508HP5 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9481doc 2509HP5 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9482doc 250AHP5 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9483doc 250BHP5 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9484doc 250CHP5 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9485doc 250DHP5 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9486doc 250EHP5 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9487doc 250FHP5 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9488doc 2510HP5 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9489doc 2511HP5 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9490doc 2512HP5 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9491doc 2513HP5 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9492doc 2514HP5 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9493doc 2515HP5 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9494doc 2516HP5 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9495doc 2517HP5 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9496doc 2518HP5 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9497doc 2519HP5 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9498doc 251AHP5 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9499doc 251BHP5 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9500doc 251CHP5 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9501doc 251DHP5 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9502doc 251EHP5 number of repetitionsINT16Read/write
HR9503doc 251FHP5 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR9728doc 2600HP6 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9729doc 2601HP6 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9730doc 2602HP6 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9731doc 2603HP6 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9732doc 2604HP6 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9733doc 2605HP6 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9734doc 2606HP6 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9735doc 2607HP6 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9736doc 2608HP6 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9737doc 2609HP6 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9738doc 260AHP6 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9739doc 260BHP6 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9740doc 260CHP6 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9741doc 260DHP6 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9742doc 260EHP6 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9743doc 260FHP6 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9744doc 2610HP6 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9745doc 2611HP6 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9746doc 2612HP6 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9747doc 2613HP6 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9748doc 2614HP6 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9749doc 2615HP6 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9750doc 2616HP6 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9751doc 2617HP6 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9752doc 2618HP6 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9753doc 2619HP6 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9754doc 261AHP6 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9755doc 261BHP6 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9756doc 261CHP6 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9757doc 261DHP6 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9758doc 261EHP6 number of repetitionsINT16Read/write
HR9759doc 261FHP6 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR9984doc 2700HP7 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9985doc 2701HP7 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9986doc 2702HP7 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9987doc 2703HP7 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9988doc 2704HP7 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9989doc 2705HP7 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9990doc 2706HP7 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9991doc 2707HP7 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9992doc 2708HP7 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9993doc 2709HP7 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9994doc 270AHP7 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9995doc 270BHP7 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9996doc 270CHP7 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR9997doc 270DHP7 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR9998doc 270EHP7 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR9999doc 270FHP7 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10000doc 2710HP7 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10001doc 2711HP7 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10002doc 2712HP7 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10003doc 2713HP7 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10004doc 2714HP7 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10005doc 2715HP7 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10006doc 2716HP7 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10007doc 2717HP7 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10008doc 2718HP7 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10009doc 2719HP7 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10010doc 271AHP7 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10011doc 271BHP7 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10012doc 271CHP7 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10013doc 271DHP7 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10014doc 271EHP7 number of repetitionsINT16Read/write
HR10015doc 271FHP7 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR10240doc 2800HP8 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10241doc 2801HP8 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10242doc 2802HP8 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10243doc 2803HP8 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10244doc 2804HP8 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10245doc 2805HP8 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10246doc 2806HP8 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10247doc 2807HP8 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10248doc 2808HP8 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10249doc 2809HP8 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10250doc 280AHP8 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10251doc 280BHP8 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10252doc 280CHP8 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10253doc 280DHP8 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10254doc 280EHP8 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10255doc 280FHP8 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10256doc 2810HP8 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10257doc 2811HP8 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10258doc 2812HP8 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10259doc 2813HP8 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10260doc 2814HP8 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10261doc 2815HP8 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10262doc 2816HP8 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10263doc 2817HP8 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10264doc 2818HP8 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10265doc 2819HP8 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10266doc 281AHP8 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10267doc 281BHP8 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10268doc 281CHP8 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10269doc 281DHP8 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10270doc 281EHP8 number of repetitionsINT16Read/write
HR10271doc 281FHP8 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR10496doc 2900HP9 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10497doc 2901HP9 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10498doc 2902HP9 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10499doc 2903HP9 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10500doc 2904HP9 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10501doc 2905HP9 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10502doc 2906HP9 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10503doc 2907HP9 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10504doc 2908HP9 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10505doc 2909HP9 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10506doc 290AHP9 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10507doc 290BHP9 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10508doc 290CHP9 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10509doc 290DHP9 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10510doc 290EHP9 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10511doc 290FHP9 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10512doc 2910HP9 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10513doc 2911HP9 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10514doc 2912HP9 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10515doc 2913HP9 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10516doc 2914HP9 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10517doc 2915HP9 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10518doc 2916HP9 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10519doc 2917HP9 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10520doc 2918HP9 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10521doc 2919HP9 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10522doc 291AHP9 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10523doc 291BHP9 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10524doc 291CHP9 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10525doc 291DHP9 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10526doc 291EHP9 number of repetitionsINT16Read/write
HR10527doc 291FHP9 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR10752doc 2A00HP10 step 1 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10753doc 2A01HP10 step 1 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10754doc 2A02HP10 step 1 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10755doc 2A03HP10 step 2 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10756doc 2A04HP10 step 2 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10757doc 2A05HP10 step 2 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10758doc 2A06HP10 step 3 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10759doc 2A07HP10 step 3 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10760doc 2A08HP10 step 3 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10761doc 2A09HP10 step 4 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10762doc 2A0AHP10 step 4 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10763doc 2A0BHP10 step 4 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10764doc 2A0CHP10 step 5 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10765doc 2A0DHP10 step 5 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10766doc 2A0EHP10 step 5 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10767doc 2A0FHP10 step 6 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10768doc 2A10HP10 step 6 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10769doc 2A11HP10 step 6 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10770doc 2A12HP10 step 7 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10771doc 2A13HP10 step 7 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10772doc 2A14HP10 step 7 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10773doc 2A15HP10 step 8 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10774doc 2A16HP10 step 8 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10775doc 2A17HP10 step 8 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10776doc 2A18HP10 step 9 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10777doc 2A19HP10 step 9 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10778doc 2A1AHP10 step 9 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10779doc 2A1BHP10 step 10 SVRaw integer; apply decimal point place (7003H).INT16Read/write
HR10780doc 2A1CHP10 step 10 timeIn the smaller unit of 7018H (minutes or seconds); FFFFH = hold.INT16Read/write
HR10781doc 2A1DHP10 step 10 PID blockINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR10782doc 2A1EHP10 number of repetitionsINT16Read/write
HR10783doc 2A1FHP10 pattern linkINT16Read/write0 = Disabled; 1 = Enabled
HR12544doc 3100HP1 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12545doc 3101HP1 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12546doc 3102HP1 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12547doc 3103HP1 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR12548doc 3104HP1 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12549doc 3105HP1 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12550doc 3106HP1 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12551doc 3107HP1 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR12552doc 3108HP1 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12553doc 3109HP1 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12554doc 310AHP1 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12555doc 310BHP1 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR12800doc 3200HP2 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12801doc 3201HP2 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12802doc 3202HP2 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12803doc 3203HP2 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR12804doc 3204HP2 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12805doc 3205HP2 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12806doc 3206HP2 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12807doc 3207HP2 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR12808doc 3208HP2 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12809doc 3209HP2 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR12810doc 320AHP2 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR12811doc 320BHP2 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13056doc 3300HP3 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13057doc 3301HP3 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13058doc 3302HP3 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13059doc 3303HP3 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13060doc 3304HP3 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13061doc 3305HP3 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13062doc 3306HP3 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13063doc 3307HP3 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13064doc 3308HP3 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13065doc 3309HP3 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13066doc 330AHP3 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13067doc 330BHP3 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13312doc 3400HP4 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13313doc 3401HP4 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13314doc 3402HP4 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13315doc 3403HP4 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13316doc 3404HP4 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13317doc 3405HP4 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13318doc 3406HP4 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13319doc 3407HP4 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13320doc 3408HP4 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13321doc 3409HP4 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13322doc 340AHP4 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13323doc 340BHP4 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13568doc 3500HP5 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13569doc 3501HP5 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13570doc 3502HP5 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13571doc 3503HP5 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13572doc 3504HP5 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13573doc 3505HP5 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13574doc 3506HP5 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13575doc 3507HP5 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13576doc 3508HP5 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13577doc 3509HP5 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13578doc 350AHP5 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13579doc 350BHP5 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13824doc 3600HP6 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13825doc 3601HP6 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13826doc 3602HP6 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13827doc 3603HP6 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13828doc 3604HP6 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13829doc 3605HP6 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13830doc 3606HP6 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13831doc 3607HP6 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR13832doc 3608HP6 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13833doc 3609HP6 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR13834doc 360AHP6 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR13835doc 360BHP6 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14080doc 3700HP7 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14081doc 3701HP7 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14082doc 3702HP7 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14083doc 3703HP7 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14084doc 3704HP7 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14085doc 3705HP7 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14086doc 3706HP7 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14087doc 3707HP7 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14088doc 3708HP7 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14089doc 3709HP7 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14090doc 370AHP7 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14091doc 370BHP7 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14336doc 3800HP8 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14337doc 3801HP8 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14338doc 3802HP8 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14339doc 3803HP8 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14340doc 3804HP8 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14341doc 3805HP8 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14342doc 3806HP8 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14343doc 3807HP8 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14344doc 3808HP8 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14345doc 3809HP8 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14346doc 380AHP8 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14347doc 380BHP8 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14592doc 3900HP9 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14593doc 3901HP9 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14594doc 3902HP9 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14595doc 3903HP9 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14596doc 3904HP9 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14597doc 3905HP9 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14598doc 3906HP9 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14599doc 3907HP9 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14600doc 3908HP9 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14601doc 3909HP9 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14602doc 390AHP9 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14603doc 390BHP9 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14848doc 3A00HP10 EV1 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14849doc 3A01HP10 EV1 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14850doc 3A02HP10 TS1 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14851doc 3A03HP10 TS1 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14852doc 3A04HP10 EV2 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14853doc 3A05HP10 EV2 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14854doc 3A06HP10 TS2 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14855doc 3A07HP10 TS2 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR14856doc 3A08HP10 EV3 alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14857doc 3A09HP10 EV3 high limit alarm valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR14858doc 3A0AHP10 TS3 output OFF timeTime signal; smaller unit of 7018H.INT16Read/write
HR14859doc 3A0BHP10 TS3 output ON timeTime signal; smaller unit of 7018H.INT16Read/write
HR16384doc 4000HAT Perform/CancelINT16Read/write0 = AT Cancel; 1 = AT Perform
HR16385doc 4001HPID block numberINT16Read/write1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10
HR16386doc 4002HOUT1 proportional cycle0-120 s; 0 means 0.5 s.INT16sRead/write
HR16387doc 4003HOUT1 ON/OFF hysteresisRaw integer; apply decimal point place (7003H).INT16Read/write
HR16388doc 4004HOUT1 high limitINT16Read/write
HR16389doc 4005HOUT1 low limitINT16Read/write
HR16390doc 4006HOUT1 rate-of-changeINT16Read/write
HR16391doc 4007HOUT2 cooling methodINT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR16392doc 4008HOUT2 proportional cycle0-120 s; 0 means 0.5 s.INT16sRead/write
HR16393doc 4009HOUT2 ON/OFF hysteresisRaw integer; apply decimal point place (7003H).INT16Read/write
HR16394doc 400AHOUT2 high limitINT16Read/write
HR16395doc 400BHOUT2 low limitINT16Read/write
HR16396doc 400CHOverlap/Dead bandRaw integer; apply decimal point place (7003H).INT16Read/write
HR16397doc 400DHDirect/Reverse actionINT16Read/write0 = Reverse action; 1 = Direct action
HR16398doc 400EHHeater burnout alarm 1 valueDecimal point ignored.INT16Read/write
HR16399doc 400FHHeater burnout alarm 2 valueDecimal point ignored.INT16Read/write
HR16400doc 4010HLoop break alarm timeINT16Read/write
HR16401doc 4011HLoop break alarm bandRaw integer; apply decimal point place (7003H).INT16Read/write
HR16658doc 4112HBlock 1 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR16659doc 4113HBlock 1 integral timeINT16Read/write
HR16660doc 4114HBlock 1 derivative timeINT16Read/write
HR16661doc 4115HBlock 1 ARWINT16Read/write
HR16662doc 4116HBlock 1 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR16914doc 4212HBlock 2 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR16915doc 4213HBlock 2 integral timeINT16Read/write
HR16916doc 4214HBlock 2 derivative timeINT16Read/write
HR16917doc 4215HBlock 2 ARWINT16Read/write
HR16918doc 4216HBlock 2 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR17170doc 4312HBlock 3 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR17171doc 4313HBlock 3 integral timeINT16Read/write
HR17172doc 4314HBlock 3 derivative timeINT16Read/write
HR17173doc 4315HBlock 3 ARWINT16Read/write
HR17174doc 4316HBlock 3 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR17426doc 4412HBlock 4 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR17427doc 4413HBlock 4 integral timeINT16Read/write
HR17428doc 4414HBlock 4 derivative timeINT16Read/write
HR17429doc 4415HBlock 4 ARWINT16Read/write
HR17430doc 4416HBlock 4 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR17682doc 4512HBlock 5 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR17683doc 4513HBlock 5 integral timeINT16Read/write
HR17684doc 4514HBlock 5 derivative timeINT16Read/write
HR17685doc 4515HBlock 5 ARWINT16Read/write
HR17686doc 4516HBlock 5 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR17938doc 4612HBlock 6 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR17939doc 4613HBlock 6 integral timeINT16Read/write
HR17940doc 4614HBlock 6 derivative timeINT16Read/write
HR17941doc 4615HBlock 6 ARWINT16Read/write
HR17942doc 4616HBlock 6 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR18194doc 4712HBlock 7 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR18195doc 4713HBlock 7 integral timeINT16Read/write
HR18196doc 4714HBlock 7 derivative timeINT16Read/write
HR18197doc 4715HBlock 7 ARWINT16Read/write
HR18198doc 4716HBlock 7 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR18450doc 4812HBlock 8 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR18451doc 4813HBlock 8 integral timeINT16Read/write
HR18452doc 4814HBlock 8 derivative timeINT16Read/write
HR18453doc 4815HBlock 8 ARWINT16Read/write
HR18454doc 4816HBlock 8 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR18706doc 4912HBlock 9 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR18707doc 4913HBlock 9 integral timeINT16Read/write
HR18708doc 4914HBlock 9 derivative timeINT16Read/write
HR18709doc 4915HBlock 9 ARWINT16Read/write
HR18710doc 4916HBlock 9 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR18962doc 4A12HBlock 10 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR18963doc 4A13HBlock 10 integral timeINT16Read/write
HR18964doc 4A14HBlock 10 derivative timeINT16Read/write
HR18965doc 4A15HBlock 10 ARWINT16Read/write
HR18966doc 4A16HBlock 10 OUT2 proportional bandDecimal point ignored.INT16Read/write
HR20736doc 5100HP1 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR20737doc 5101HP1 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20738doc 5102HP1 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20739doc 5103HP1 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20740doc 5104HP1 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20741doc 5105HP1 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20742doc 5106HP1 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20743doc 5107HP1 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20744doc 5108HP1 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20745doc 5109HP1 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20746doc 510AHP1 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20992doc 5200HP2 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR20993doc 5201HP2 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20994doc 5202HP2 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20995doc 5203HP2 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20996doc 5204HP2 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20997doc 5205HP2 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20998doc 5206HP2 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR20999doc 5207HP2 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21000doc 5208HP2 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21001doc 5209HP2 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21002doc 520AHP2 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21248doc 5300HP3 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR21249doc 5301HP3 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21250doc 5302HP3 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21251doc 5303HP3 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21252doc 5304HP3 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21253doc 5305HP3 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21254doc 5306HP3 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21255doc 5307HP3 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21256doc 5308HP3 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21257doc 5309HP3 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21258doc 530AHP3 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21504doc 5400HP4 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR21505doc 5401HP4 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21506doc 5402HP4 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21507doc 5403HP4 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21508doc 5404HP4 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21509doc 5405HP4 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21510doc 5406HP4 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21511doc 5407HP4 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21512doc 5408HP4 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21513doc 5409HP4 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21514doc 540AHP4 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21760doc 5500HP5 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR21761doc 5501HP5 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21762doc 5502HP5 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21763doc 5503HP5 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21764doc 5504HP5 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21765doc 5505HP5 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21766doc 5506HP5 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21767doc 5507HP5 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21768doc 5508HP5 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21769doc 5509HP5 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR21770doc 550AHP5 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22016doc 5600HP6 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR22017doc 5601HP6 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22018doc 5602HP6 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22019doc 5603HP6 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22020doc 5604HP6 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22021doc 5605HP6 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22022doc 5606HP6 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22023doc 5607HP6 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22024doc 5608HP6 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22025doc 5609HP6 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22026doc 560AHP6 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22272doc 5700HP7 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR22273doc 5701HP7 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22274doc 5702HP7 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22275doc 5703HP7 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22276doc 5704HP7 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22277doc 5705HP7 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22278doc 5706HP7 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22279doc 5707HP7 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22280doc 5708HP7 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22281doc 5709HP7 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22282doc 570AHP7 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22528doc 5800HP8 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR22529doc 5801HP8 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22530doc 5802HP8 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22531doc 5803HP8 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22532doc 5804HP8 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22533doc 5805HP8 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22534doc 5806HP8 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22535doc 5807HP8 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22536doc 5808HP8 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22537doc 5809HP8 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22538doc 580AHP8 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22784doc 5900HP9 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR22785doc 5901HP9 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22786doc 5902HP9 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22787doc 5903HP9 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22788doc 5904HP9 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22789doc 5905HP9 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22790doc 5906HP9 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22791doc 5907HP9 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22792doc 5908HP9 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22793doc 5909HP9 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR22794doc 590AHP9 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23040doc 5A00HP10 wait valueRaw integer; apply decimal point place (7003H).INT16Read/write
HR23041doc 5A01HP10 step 1 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23042doc 5A02HP10 step 2 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23043doc 5A03HP10 step 3 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23044doc 5A04HP10 step 4 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23045doc 5A05HP10 step 5 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23046doc 5A06HP10 step 6 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23047doc 5A07HP10 step 7 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23048doc 5A08HP10 step 8 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23049doc 5A09HP10 step 9 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR23050doc 5A0AHP10 step 10 wait functionINT16Read/write0 = Disabled; 1 = Enabled
HR24576doc 6000HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3; 4 = Lock 4; 5 = Lock 5
HR24577doc 6001HChangeable in set value lockINT16Read/write0 = Step SV + step time; 1 = Step SV + step time + EV alarm value
HR24578doc 6002HSensor correction coefficientDecimal point ignored.INT16Read/write
HR24579doc 6003HSensor correctionRaw integer; apply decimal point place (7003H).INT16Read/write
HR24580doc 6004HPV filter time constantDecimal point ignored.INT16Read/write
HR24581doc 6005HResponse delay timeINT16msRead/write
HR24582doc 6006HSVTC biasRaw integer; apply decimal point place (7003H).INT16Read/write
HR28672doc 7000HInput typeINT16Read/write0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -328 to 2498 F; 16 = K -328.0 to 752.0 F; 17 = J -328 to 1832 F; 18 = R 32 to 3200 F; 19 = S 32 to 3200 F; 20 = B 32 to 3308 F; 21 = E -328 to 1472 F; 22 = T -328.0 to 752.0 F; 23 = N -328 to 2372 F; 24 = PL-II 32 to 2534 F; 25 = C (W/Re5-26) 32 to 4199 F; 26 = Pt100 -328.0 to 1562.0 F; 27 = JPt100 -328.0 to 932.0 F; 28 = Pt100 -328 to 1562 F; 29 = JPt100 -328 to 932 F; 30 = 4 to 20 mA (-2000 to 10000); 31 = 0 to 20 mA (-2000 to 10000); 32 = 0 to 1 V (-2000 to 10000); 33 = 0 to 5 V (-2000 to 10000); 34 = 1 to 5 V (-2000 to 10000); 35 = 0 to 10 V (-2000 to 10000)
HR28673doc 7001HScaling high limitRaw integer; apply decimal point place (7003H).INT16Read/write
HR28674doc 7002HScaling low limitRaw integer; apply decimal point place (7003H).INT16Read/write
HR28675doc 7003HDecimal point placeINT16Read/write0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits
HR28676doc 7004HEvent output EV1 allocationChanging it clears this event's alarm settings.INT16Read/write0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output
HR28677doc 7005HEV1 alarm value 0 enabledINT16Read/write0 = Disabled; 1 = Enabled
HR28678doc 7006HEV1 alarm hysteresisRaw integer; apply decimal point place (7003H).INT16Read/write
HR28679doc 7007HEV1 alarm delay timeINT16Read/write
HR28680doc 7008HEV1 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR28681doc 7009HEvent output EV2 allocationChanging it clears this event's alarm settings.INT16Read/write0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output; 20 = Heating/Cooling control output
HR28682doc 700AHEV2 alarm value 0 enabledINT16Read/write0 = Disabled; 1 = Enabled
HR28683doc 700BHEV2 alarm hysteresisRaw integer; apply decimal point place (7003H).INT16Read/write
HR28684doc 700CHEV2 alarm delay timeINT16Read/write
HR28685doc 700DHEV2 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR28686doc 700EHEvent output EV3 allocationChanging it clears this event's alarm settings.INT16Read/write0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output
HR28687doc 700FHEV3 alarm value 0 enabledINT16Read/write0 = Disabled; 1 = Enabled
HR28688doc 7010HEV3 alarm hysteresisRaw integer; apply decimal point place (7003H).INT16Read/write
HR28689doc 7011HEV3 alarm delay timeINT16Read/write
HR28690doc 7012HEV3 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR28691doc 7013HEvent input DI1 allocationINT16Read/write0 = No event; 1 = Pattern number selection; 2 = Direct/Reverse action; 3 = Program control RUN/STOP; 4 = Program control holding/not holding; 5 = Program control advance function
HR28692doc 7014HEvent input DI2 allocationINT16Read/write0 = No event; 1 = Pattern number selection; 2 = Direct/Reverse action; 3 = Program control RUN/STOP; 4 = Program control holding/not holding; 5 = Program control advance function
HR28693doc 7015HTransmission outputINT16Read/write0 = PV transmission; 1 = SV transmission; 2 = MV transmission
HR28694doc 7016HTransmission output high limitDecimal point ignored.INT16Read/write
HR28695doc 7017HTransmission output low limitDecimal point ignored.INT16Read/write
HR28696doc 7018HStep time unitINT16Read/write0 = Hours:Minutes; 1 = Minutes:Seconds
HR28697doc 7019HPower restore actionINT16Read/write0 = Stop; 1 = Continue (resume); 2 = Suspend (hold)
HR28698doc 701AHStep SV when program control startsRaw integer; apply decimal point place (7003H).INT16Read/write
HR28699doc 701BHProgram control start typeINT16Read/write0 = PV start; 1 = PVR start; 2 = SV start
HR28700doc 701CHPattern end output timeINT16Read/write
HR28701doc 701DHAT biasRaw integer; apply decimal point place (7003H).INT16Read/write
HR28702doc 701EHOutput status on input errorINT16Read/write0 = Output OFF; 1 = Output ON
HR28703doc 701FHIndication timeINT16sRead/write
HR28704doc 7020HError indicationINT16Read/write0 = Disabled; 1 = Enabled
HR32768doc 8000HPattern number for operationWritable only in program STOP and when DI selects pattern 1.INT16Read/write1 = Pattern 1; 2 = Pattern 2; 3 = Pattern 3; 4 = Pattern 4; 5 = Pattern 5; 6 = Pattern 6; 7 = Pattern 7; 8 = Pattern 8; 9 = Pattern 9; 10 = Pattern 10
HR32769doc 8001HProgram control RUN/STOPWrite-only (06/10H).INT16Write0 = STOP; 1 = RUN (cancels HOLD)
HR32770doc 8002HProgram control HOLDWrite-only; rejected in STOP.INT16Write1 = HOLD
HR32771doc 8003HProgram control ADVANCEWrite-only; rejected in STOP.INT16Write1 = ADVANCE
HR32772doc 8004HOutput by communicationDrives EV outputs allocated to 'output by communication'.BITMAP16Writebit 0 = EV1 output; bit 1 = EV2 output; bit 2 = EV3 output
HR32773doc 8005HKey operation change flag clearingINT16Write1 = Clear flag
HR36864doc 9000HPVProcess value. Raw integer; apply decimal point place (7003H).INT16Read
HR36865doc 9001HOUT1 MVDecimal point ignored.INT16Read
HR36866doc 9002HOUT2 MVDecimal point ignored.INT16Read
HR36867doc 9003HCurrent step SVRaw integer; apply decimal point place (7003H).INT16Read
HR36868doc 9004HCurrent step remaining timeINT16Read
HR36869doc 9005HCurrent pattern and stepLowest hex digit = pattern, next hex digit = step (0 when stopped).INT16Read
HR36870doc 9006HCurrent number of repetitionsINT16Read
HR36871doc 9007HPattern selected by event inputINT16Read
HR36872doc 9008HCT1 current valueDecimal point ignored.INT16Read
HR36873doc 9009HCT2 current valueDecimal point ignored.INT16Read
HR36874doc 900AHStatus flagBITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 4 = EV3 output on; bit 6 = Loop break alarm output; bit 7 = Overscale; bit 8 = Underscale; bit 9 = Heater burnout alarm output; bit 15 = Changed by keypad
HR36875doc 900BHCurrent unit statusBITMAP16Readbit 0 = Program control (fixed); bit 1 = AT performing; bit 2 = Program control RUN; bit 3 = HOLD; bit 4 = WAIT; bit 5 = Pattern end output on
HR36876doc 900CHError status flag 1BITMAP16Readbit 0 = Error 01; bit 1 = Error 02; bit 4 = Error 05; bit 5 = Error 06; bit 6 = Error 07; bit 9 = Error 10
HR36877doc 900DHError status flag 2BITMAP16Readbit 3 = Error 20

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos PCB1 programmable controller (C5W/C5 option)

What Modbus registers does the Shinko Technos PCB1 programmable controller (C5W/C5 option) have?

This map lists 678 registers: 678 holding registers. 664 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Data items are hex (9000H) and are sent unchanged as the Modbus holding-register address. The manual says the Modicon number is the data item plus 40001. The RTU examples read PV at 9000H and write pattern 1 step 1 SV at 2100H (CRCs A90AH and 83E1H checked).

What are the minimum Modbus registers to integrate the Shinko Technos PCB1 programmable controller (C5W/C5 option)?

Start with HR 36864 PV (Process value); HR 36867 Current step SV (Current step SV); HR 36869 Current pattern and step (Running pattern and step); HR 36875 Current unit status (Run/hold/wait status); HR 36874 Status flag (Output, alarm and over/underscale flags); HR 32769 Program control RUN/STOP (Program RUN/STOP); HR 32768 Pattern number for operation (Pattern to run); HR 28675 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos PCB1 programmable controller (C5W/C5 option)?

Requires the C5W or C5 option. In Engineering setting mode 1 (down + MODE for about 3 s) set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit. These can only be set on the keypad.

Where is the official Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus documentation?

The source is Communication Instruction Manual PCB1 (C5W, C5) (No. PCB1CE3), revision 2019-09, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/PCB1CE3.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual PCB1 (C5W, C5) · No. PCB1CE3 · rev. 2019-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.