- Home
- Modbus register maps
- Shinko Technos
- PCB1 programmable controller (C5W/C5 option)
Sensor (programmable temperature controller) · Modbus register map
Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus register map
Updated 17 November 2026
The PCB1 is a ramp/soak program controller with 10 patterns of 10 steps, 10 PID blocks and three event outputs. On RS-485 it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers all pattern, event, wait and PID-block items, engineering settings, run/hold/advance commands and the read-only monitor block.
This page lists 678 Modbus registers for the Shinko Technos PCB1 programmable controller (C5W/C5 option) — 664 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- PCB1 programmable controller (C5W/C5 option)
- Equipment type
- Sensor (programmable temperature controller)
- Registers
- 678 (664 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- PCB1
Integration notes: Shinko Technos PCB1 programmable controller (C5W/C5 option)
Select MODBUS RTU mode in Engineering setting mode 1 and give the unit a non-zero instrument number; then poll PV 9000H, current step SV 9003H, pattern/step 9005H and status 900AH-900BH, and start/stop with 8001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 36864 | PV | INT16 | Process value | Read |
| HR 36867 | Current step SV | INT16 | Current step SV | Read |
| HR 36869 | Current pattern and step | INT16 | Running pattern and step | Read |
| HR 36875 | Current unit status | BITMAP16 | Run/hold/wait status | Read |
| HR 36874 | Status flag | BITMAP16 | Output, alarm and over/underscale flags | Read |
| HR 32769 | Program control RUN/STOP | INT16 | Program RUN/STOP | Write |
| HR 32768 | Pattern number for operation | INT16 | Pattern to run | Read/write |
| HR 28675 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5W or C5 option. In Engineering setting mode 1 (down + MODE for about 3 s) set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit. These can only be set on the keypad.
Byte order & addressing
- The manual's Modicon example writes 2100H as 42101, treating the hex digits as decimal; its example frames send 2100H itself as the PDU address (CRCs check), so use the hex data item directly.
- Instrument number 0 is the Modbus broadcast address; give each unit 1-95.
- The USB console cable and RS-485 cannot be used at the same time.
Network setup
- Factory defaults: Shinko protocol, instrument number 0, 9600 bps, 7 bits/even parity, 1 stop bit, 10 ms response delay.
- For Modbus RTU choose an 8-bit data format (8 bits/no, even or odd parity).
- Do not fit a terminator; the unit has built-in pull-up/pull-down resistors.
Watch out for
- HOLD and ADVANCE return exception 17 (11H) while the program is stopped.
- Exception 18 (12H) is returned while the keypad is in setting mode.
- Non-volatile memory takes about one million writes; avoid cyclic writes of settings.
Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 8448doc 2100H | P1 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8449doc 2101H | P1 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8450doc 2102H | P1 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8451doc 2103H | P1 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8452doc 2104H | P1 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8453doc 2105H | P1 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8454doc 2106H | P1 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8455doc 2107H | P1 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8456doc 2108H | P1 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8457doc 2109H | P1 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8458doc 210AH | P1 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8459doc 210BH | P1 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8460doc 210CH | P1 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8461doc 210DH | P1 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8462doc 210EH | P1 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8463doc 210FH | P1 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8464doc 2110H | P1 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8465doc 2111H | P1 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8466doc 2112H | P1 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8467doc 2113H | P1 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8468doc 2114H | P1 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8469doc 2115H | P1 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8470doc 2116H | P1 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8471doc 2117H | P1 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8472doc 2118H | P1 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8473doc 2119H | P1 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8474doc 211AH | P1 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8475doc 211BH | P1 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8476doc 211CH | P1 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8477doc 211DH | P1 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8478doc 211EH | P1 number of repetitions | INT16 | Read/write | |||||
| HR | 8479doc 211FH | P1 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 8704doc 2200H | P2 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8705doc 2201H | P2 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8706doc 2202H | P2 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8707doc 2203H | P2 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8708doc 2204H | P2 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8709doc 2205H | P2 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8710doc 2206H | P2 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8711doc 2207H | P2 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8712doc 2208H | P2 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8713doc 2209H | P2 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8714doc 220AH | P2 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8715doc 220BH | P2 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8716doc 220CH | P2 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8717doc 220DH | P2 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8718doc 220EH | P2 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8719doc 220FH | P2 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8720doc 2210H | P2 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8721doc 2211H | P2 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8722doc 2212H | P2 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8723doc 2213H | P2 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8724doc 2214H | P2 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8725doc 2215H | P2 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8726doc 2216H | P2 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8727doc 2217H | P2 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8728doc 2218H | P2 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8729doc 2219H | P2 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8730doc 221AH | P2 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8731doc 221BH | P2 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8732doc 221CH | P2 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8733doc 221DH | P2 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8734doc 221EH | P2 number of repetitions | INT16 | Read/write | |||||
| HR | 8735doc 221FH | P2 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 8960doc 2300H | P3 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8961doc 2301H | P3 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8962doc 2302H | P3 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8963doc 2303H | P3 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8964doc 2304H | P3 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8965doc 2305H | P3 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8966doc 2306H | P3 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8967doc 2307H | P3 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8968doc 2308H | P3 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8969doc 2309H | P3 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8970doc 230AH | P3 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8971doc 230BH | P3 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8972doc 230CH | P3 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8973doc 230DH | P3 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8974doc 230EH | P3 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8975doc 230FH | P3 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8976doc 2310H | P3 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8977doc 2311H | P3 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8978doc 2312H | P3 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8979doc 2313H | P3 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8980doc 2314H | P3 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8981doc 2315H | P3 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8982doc 2316H | P3 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8983doc 2317H | P3 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8984doc 2318H | P3 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8985doc 2319H | P3 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8986doc 231AH | P3 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8987doc 231BH | P3 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 8988doc 231CH | P3 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 8989doc 231DH | P3 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 8990doc 231EH | P3 number of repetitions | INT16 | Read/write | |||||
| HR | 8991doc 231FH | P3 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 9216doc 2400H | P4 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9217doc 2401H | P4 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9218doc 2402H | P4 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9219doc 2403H | P4 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9220doc 2404H | P4 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9221doc 2405H | P4 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9222doc 2406H | P4 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9223doc 2407H | P4 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9224doc 2408H | P4 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9225doc 2409H | P4 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9226doc 240AH | P4 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9227doc 240BH | P4 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9228doc 240CH | P4 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9229doc 240DH | P4 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9230doc 240EH | P4 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9231doc 240FH | P4 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9232doc 2410H | P4 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9233doc 2411H | P4 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9234doc 2412H | P4 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9235doc 2413H | P4 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9236doc 2414H | P4 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9237doc 2415H | P4 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9238doc 2416H | P4 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9239doc 2417H | P4 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9240doc 2418H | P4 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9241doc 2419H | P4 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9242doc 241AH | P4 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9243doc 241BH | P4 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9244doc 241CH | P4 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9245doc 241DH | P4 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9246doc 241EH | P4 number of repetitions | INT16 | Read/write | |||||
| HR | 9247doc 241FH | P4 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 9472doc 2500H | P5 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9473doc 2501H | P5 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9474doc 2502H | P5 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9475doc 2503H | P5 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9476doc 2504H | P5 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9477doc 2505H | P5 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9478doc 2506H | P5 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9479doc 2507H | P5 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9480doc 2508H | P5 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9481doc 2509H | P5 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9482doc 250AH | P5 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9483doc 250BH | P5 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9484doc 250CH | P5 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9485doc 250DH | P5 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9486doc 250EH | P5 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9487doc 250FH | P5 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9488doc 2510H | P5 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9489doc 2511H | P5 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9490doc 2512H | P5 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9491doc 2513H | P5 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9492doc 2514H | P5 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9493doc 2515H | P5 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9494doc 2516H | P5 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9495doc 2517H | P5 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9496doc 2518H | P5 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9497doc 2519H | P5 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9498doc 251AH | P5 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9499doc 251BH | P5 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9500doc 251CH | P5 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9501doc 251DH | P5 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9502doc 251EH | P5 number of repetitions | INT16 | Read/write | |||||
| HR | 9503doc 251FH | P5 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 9728doc 2600H | P6 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9729doc 2601H | P6 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9730doc 2602H | P6 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9731doc 2603H | P6 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9732doc 2604H | P6 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9733doc 2605H | P6 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9734doc 2606H | P6 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9735doc 2607H | P6 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9736doc 2608H | P6 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9737doc 2609H | P6 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9738doc 260AH | P6 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9739doc 260BH | P6 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9740doc 260CH | P6 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9741doc 260DH | P6 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9742doc 260EH | P6 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9743doc 260FH | P6 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9744doc 2610H | P6 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9745doc 2611H | P6 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9746doc 2612H | P6 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9747doc 2613H | P6 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9748doc 2614H | P6 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9749doc 2615H | P6 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9750doc 2616H | P6 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9751doc 2617H | P6 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9752doc 2618H | P6 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9753doc 2619H | P6 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9754doc 261AH | P6 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9755doc 261BH | P6 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9756doc 261CH | P6 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9757doc 261DH | P6 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9758doc 261EH | P6 number of repetitions | INT16 | Read/write | |||||
| HR | 9759doc 261FH | P6 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 9984doc 2700H | P7 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9985doc 2701H | P7 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9986doc 2702H | P7 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9987doc 2703H | P7 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9988doc 2704H | P7 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9989doc 2705H | P7 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9990doc 2706H | P7 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9991doc 2707H | P7 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9992doc 2708H | P7 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9993doc 2709H | P7 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9994doc 270AH | P7 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9995doc 270BH | P7 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9996doc 270CH | P7 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 9997doc 270DH | P7 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 9998doc 270EH | P7 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 9999doc 270FH | P7 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10000doc 2710H | P7 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10001doc 2711H | P7 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10002doc 2712H | P7 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10003doc 2713H | P7 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10004doc 2714H | P7 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10005doc 2715H | P7 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10006doc 2716H | P7 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10007doc 2717H | P7 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10008doc 2718H | P7 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10009doc 2719H | P7 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10010doc 271AH | P7 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10011doc 271BH | P7 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10012doc 271CH | P7 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10013doc 271DH | P7 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10014doc 271EH | P7 number of repetitions | INT16 | Read/write | |||||
| HR | 10015doc 271FH | P7 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 10240doc 2800H | P8 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10241doc 2801H | P8 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10242doc 2802H | P8 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10243doc 2803H | P8 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10244doc 2804H | P8 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10245doc 2805H | P8 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10246doc 2806H | P8 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10247doc 2807H | P8 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10248doc 2808H | P8 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10249doc 2809H | P8 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10250doc 280AH | P8 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10251doc 280BH | P8 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10252doc 280CH | P8 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10253doc 280DH | P8 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10254doc 280EH | P8 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10255doc 280FH | P8 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10256doc 2810H | P8 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10257doc 2811H | P8 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10258doc 2812H | P8 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10259doc 2813H | P8 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10260doc 2814H | P8 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10261doc 2815H | P8 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10262doc 2816H | P8 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10263doc 2817H | P8 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10264doc 2818H | P8 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10265doc 2819H | P8 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10266doc 281AH | P8 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10267doc 281BH | P8 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10268doc 281CH | P8 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10269doc 281DH | P8 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10270doc 281EH | P8 number of repetitions | INT16 | Read/write | |||||
| HR | 10271doc 281FH | P8 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 10496doc 2900H | P9 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10497doc 2901H | P9 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10498doc 2902H | P9 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10499doc 2903H | P9 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10500doc 2904H | P9 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10501doc 2905H | P9 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10502doc 2906H | P9 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10503doc 2907H | P9 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10504doc 2908H | P9 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10505doc 2909H | P9 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10506doc 290AH | P9 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10507doc 290BH | P9 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10508doc 290CH | P9 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10509doc 290DH | P9 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10510doc 290EH | P9 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10511doc 290FH | P9 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10512doc 2910H | P9 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10513doc 2911H | P9 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10514doc 2912H | P9 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10515doc 2913H | P9 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10516doc 2914H | P9 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10517doc 2915H | P9 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10518doc 2916H | P9 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10519doc 2917H | P9 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10520doc 2918H | P9 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10521doc 2919H | P9 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10522doc 291AH | P9 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10523doc 291BH | P9 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10524doc 291CH | P9 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10525doc 291DH | P9 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10526doc 291EH | P9 number of repetitions | INT16 | Read/write | |||||
| HR | 10527doc 291FH | P9 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 10752doc 2A00H | P10 step 1 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10753doc 2A01H | P10 step 1 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10754doc 2A02H | P10 step 1 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10755doc 2A03H | P10 step 2 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10756doc 2A04H | P10 step 2 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10757doc 2A05H | P10 step 2 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10758doc 2A06H | P10 step 3 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10759doc 2A07H | P10 step 3 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10760doc 2A08H | P10 step 3 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10761doc 2A09H | P10 step 4 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10762doc 2A0AH | P10 step 4 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10763doc 2A0BH | P10 step 4 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10764doc 2A0CH | P10 step 5 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10765doc 2A0DH | P10 step 5 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10766doc 2A0EH | P10 step 5 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10767doc 2A0FH | P10 step 6 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10768doc 2A10H | P10 step 6 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10769doc 2A11H | P10 step 6 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10770doc 2A12H | P10 step 7 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10771doc 2A13H | P10 step 7 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10772doc 2A14H | P10 step 7 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10773doc 2A15H | P10 step 8 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10774doc 2A16H | P10 step 8 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10775doc 2A17H | P10 step 8 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10776doc 2A18H | P10 step 9 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10777doc 2A19H | P10 step 9 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10778doc 2A1AH | P10 step 9 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10779doc 2A1BH | P10 step 10 SV | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 10780doc 2A1CH | P10 step 10 time | In the smaller unit of 7018H (minutes or seconds); FFFFH = hold. | INT16 | Read/write | ||||
| HR | 10781doc 2A1DH | P10 step 10 PID block | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 10782doc 2A1EH | P10 number of repetitions | INT16 | Read/write | |||||
| HR | 10783doc 2A1FH | P10 pattern link | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 12544doc 3100H | P1 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12545doc 3101H | P1 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12546doc 3102H | P1 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12547doc 3103H | P1 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12548doc 3104H | P1 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12549doc 3105H | P1 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12550doc 3106H | P1 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12551doc 3107H | P1 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12552doc 3108H | P1 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12553doc 3109H | P1 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12554doc 310AH | P1 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12555doc 310BH | P1 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12800doc 3200H | P2 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12801doc 3201H | P2 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12802doc 3202H | P2 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12803doc 3203H | P2 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12804doc 3204H | P2 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12805doc 3205H | P2 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12806doc 3206H | P2 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12807doc 3207H | P2 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12808doc 3208H | P2 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12809doc 3209H | P2 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 12810doc 320AH | P2 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 12811doc 320BH | P2 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13056doc 3300H | P3 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13057doc 3301H | P3 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13058doc 3302H | P3 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13059doc 3303H | P3 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13060doc 3304H | P3 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13061doc 3305H | P3 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13062doc 3306H | P3 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13063doc 3307H | P3 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13064doc 3308H | P3 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13065doc 3309H | P3 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13066doc 330AH | P3 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13067doc 330BH | P3 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13312doc 3400H | P4 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13313doc 3401H | P4 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13314doc 3402H | P4 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13315doc 3403H | P4 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13316doc 3404H | P4 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13317doc 3405H | P4 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13318doc 3406H | P4 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13319doc 3407H | P4 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13320doc 3408H | P4 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13321doc 3409H | P4 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13322doc 340AH | P4 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13323doc 340BH | P4 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13568doc 3500H | P5 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13569doc 3501H | P5 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13570doc 3502H | P5 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13571doc 3503H | P5 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13572doc 3504H | P5 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13573doc 3505H | P5 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13574doc 3506H | P5 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13575doc 3507H | P5 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13576doc 3508H | P5 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13577doc 3509H | P5 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13578doc 350AH | P5 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13579doc 350BH | P5 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13824doc 3600H | P6 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13825doc 3601H | P6 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13826doc 3602H | P6 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13827doc 3603H | P6 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13828doc 3604H | P6 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13829doc 3605H | P6 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13830doc 3606H | P6 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13831doc 3607H | P6 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13832doc 3608H | P6 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13833doc 3609H | P6 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 13834doc 360AH | P6 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 13835doc 360BH | P6 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14080doc 3700H | P7 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14081doc 3701H | P7 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14082doc 3702H | P7 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14083doc 3703H | P7 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14084doc 3704H | P7 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14085doc 3705H | P7 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14086doc 3706H | P7 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14087doc 3707H | P7 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14088doc 3708H | P7 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14089doc 3709H | P7 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14090doc 370AH | P7 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14091doc 370BH | P7 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14336doc 3800H | P8 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14337doc 3801H | P8 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14338doc 3802H | P8 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14339doc 3803H | P8 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14340doc 3804H | P8 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14341doc 3805H | P8 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14342doc 3806H | P8 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14343doc 3807H | P8 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14344doc 3808H | P8 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14345doc 3809H | P8 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14346doc 380AH | P8 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14347doc 380BH | P8 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14592doc 3900H | P9 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14593doc 3901H | P9 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14594doc 3902H | P9 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14595doc 3903H | P9 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14596doc 3904H | P9 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14597doc 3905H | P9 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14598doc 3906H | P9 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14599doc 3907H | P9 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14600doc 3908H | P9 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14601doc 3909H | P9 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14602doc 390AH | P9 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14603doc 390BH | P9 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14848doc 3A00H | P10 EV1 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14849doc 3A01H | P10 EV1 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14850doc 3A02H | P10 TS1 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14851doc 3A03H | P10 TS1 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14852doc 3A04H | P10 EV2 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14853doc 3A05H | P10 EV2 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14854doc 3A06H | P10 TS2 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14855doc 3A07H | P10 TS2 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14856doc 3A08H | P10 EV3 alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14857doc 3A09H | P10 EV3 high limit alarm value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 14858doc 3A0AH | P10 TS3 output OFF time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 14859doc 3A0BH | P10 TS3 output ON time | Time signal; smaller unit of 7018H. | INT16 | Read/write | ||||
| HR | 16384doc 4000H | AT Perform/Cancel | INT16 | Read/write | 0 = AT Cancel; 1 = AT Perform | ||||
| HR | 16385doc 4001H | PID block number | INT16 | Read/write | 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10 | ||||
| HR | 16386doc 4002H | OUT1 proportional cycle | 0-120 s; 0 means 0.5 s. | INT16 | s | Read/write | |||
| HR | 16387doc 4003H | OUT1 ON/OFF hysteresis | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 16388doc 4004H | OUT1 high limit | INT16 | Read/write | |||||
| HR | 16389doc 4005H | OUT1 low limit | INT16 | Read/write | |||||
| HR | 16390doc 4006H | OUT1 rate-of-change | INT16 | Read/write | |||||
| HR | 16391doc 4007H | OUT2 cooling method | INT16 | Read/write | 0 = Air cooling; 1 = Oil cooling; 2 = Water cooling | ||||
| HR | 16392doc 4008H | OUT2 proportional cycle | 0-120 s; 0 means 0.5 s. | INT16 | s | Read/write | |||
| HR | 16393doc 4009H | OUT2 ON/OFF hysteresis | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 16394doc 400AH | OUT2 high limit | INT16 | Read/write | |||||
| HR | 16395doc 400BH | OUT2 low limit | INT16 | Read/write | |||||
| HR | 16396doc 400CH | Overlap/Dead band | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 16397doc 400DH | Direct/Reverse action | INT16 | Read/write | 0 = Reverse action; 1 = Direct action | ||||
| HR | 16398doc 400EH | Heater burnout alarm 1 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16399doc 400FH | Heater burnout alarm 2 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16400doc 4010H | Loop break alarm time | INT16 | Read/write | |||||
| HR | 16401doc 4011H | Loop break alarm band | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 16658doc 4112H | Block 1 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16659doc 4113H | Block 1 integral time | INT16 | Read/write | |||||
| HR | 16660doc 4114H | Block 1 derivative time | INT16 | Read/write | |||||
| HR | 16661doc 4115H | Block 1 ARW | INT16 | Read/write | |||||
| HR | 16662doc 4116H | Block 1 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16914doc 4212H | Block 2 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16915doc 4213H | Block 2 integral time | INT16 | Read/write | |||||
| HR | 16916doc 4214H | Block 2 derivative time | INT16 | Read/write | |||||
| HR | 16917doc 4215H | Block 2 ARW | INT16 | Read/write | |||||
| HR | 16918doc 4216H | Block 2 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17170doc 4312H | Block 3 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17171doc 4313H | Block 3 integral time | INT16 | Read/write | |||||
| HR | 17172doc 4314H | Block 3 derivative time | INT16 | Read/write | |||||
| HR | 17173doc 4315H | Block 3 ARW | INT16 | Read/write | |||||
| HR | 17174doc 4316H | Block 3 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17426doc 4412H | Block 4 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17427doc 4413H | Block 4 integral time | INT16 | Read/write | |||||
| HR | 17428doc 4414H | Block 4 derivative time | INT16 | Read/write | |||||
| HR | 17429doc 4415H | Block 4 ARW | INT16 | Read/write | |||||
| HR | 17430doc 4416H | Block 4 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17682doc 4512H | Block 5 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17683doc 4513H | Block 5 integral time | INT16 | Read/write | |||||
| HR | 17684doc 4514H | Block 5 derivative time | INT16 | Read/write | |||||
| HR | 17685doc 4515H | Block 5 ARW | INT16 | Read/write | |||||
| HR | 17686doc 4516H | Block 5 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17938doc 4612H | Block 6 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17939doc 4613H | Block 6 integral time | INT16 | Read/write | |||||
| HR | 17940doc 4614H | Block 6 derivative time | INT16 | Read/write | |||||
| HR | 17941doc 4615H | Block 6 ARW | INT16 | Read/write | |||||
| HR | 17942doc 4616H | Block 6 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18194doc 4712H | Block 7 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18195doc 4713H | Block 7 integral time | INT16 | Read/write | |||||
| HR | 18196doc 4714H | Block 7 derivative time | INT16 | Read/write | |||||
| HR | 18197doc 4715H | Block 7 ARW | INT16 | Read/write | |||||
| HR | 18198doc 4716H | Block 7 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18450doc 4812H | Block 8 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18451doc 4813H | Block 8 integral time | INT16 | Read/write | |||||
| HR | 18452doc 4814H | Block 8 derivative time | INT16 | Read/write | |||||
| HR | 18453doc 4815H | Block 8 ARW | INT16 | Read/write | |||||
| HR | 18454doc 4816H | Block 8 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18706doc 4912H | Block 9 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18707doc 4913H | Block 9 integral time | INT16 | Read/write | |||||
| HR | 18708doc 4914H | Block 9 derivative time | INT16 | Read/write | |||||
| HR | 18709doc 4915H | Block 9 ARW | INT16 | Read/write | |||||
| HR | 18710doc 4916H | Block 9 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18962doc 4A12H | Block 10 OUT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18963doc 4A13H | Block 10 integral time | INT16 | Read/write | |||||
| HR | 18964doc 4A14H | Block 10 derivative time | INT16 | Read/write | |||||
| HR | 18965doc 4A15H | Block 10 ARW | INT16 | Read/write | |||||
| HR | 18966doc 4A16H | Block 10 OUT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 20736doc 5100H | P1 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 20737doc 5101H | P1 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20738doc 5102H | P1 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20739doc 5103H | P1 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20740doc 5104H | P1 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20741doc 5105H | P1 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20742doc 5106H | P1 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20743doc 5107H | P1 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20744doc 5108H | P1 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20745doc 5109H | P1 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20746doc 510AH | P1 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20992doc 5200H | P2 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 20993doc 5201H | P2 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20994doc 5202H | P2 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20995doc 5203H | P2 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20996doc 5204H | P2 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20997doc 5205H | P2 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20998doc 5206H | P2 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 20999doc 5207H | P2 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21000doc 5208H | P2 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21001doc 5209H | P2 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21002doc 520AH | P2 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21248doc 5300H | P3 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 21249doc 5301H | P3 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21250doc 5302H | P3 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21251doc 5303H | P3 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21252doc 5304H | P3 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21253doc 5305H | P3 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21254doc 5306H | P3 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21255doc 5307H | P3 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21256doc 5308H | P3 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21257doc 5309H | P3 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21258doc 530AH | P3 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21504doc 5400H | P4 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 21505doc 5401H | P4 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21506doc 5402H | P4 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21507doc 5403H | P4 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21508doc 5404H | P4 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21509doc 5405H | P4 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21510doc 5406H | P4 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21511doc 5407H | P4 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21512doc 5408H | P4 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21513doc 5409H | P4 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21514doc 540AH | P4 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21760doc 5500H | P5 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 21761doc 5501H | P5 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21762doc 5502H | P5 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21763doc 5503H | P5 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21764doc 5504H | P5 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21765doc 5505H | P5 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21766doc 5506H | P5 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21767doc 5507H | P5 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21768doc 5508H | P5 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21769doc 5509H | P5 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 21770doc 550AH | P5 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22016doc 5600H | P6 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 22017doc 5601H | P6 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22018doc 5602H | P6 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22019doc 5603H | P6 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22020doc 5604H | P6 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22021doc 5605H | P6 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22022doc 5606H | P6 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22023doc 5607H | P6 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22024doc 5608H | P6 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22025doc 5609H | P6 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22026doc 560AH | P6 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22272doc 5700H | P7 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 22273doc 5701H | P7 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22274doc 5702H | P7 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22275doc 5703H | P7 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22276doc 5704H | P7 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22277doc 5705H | P7 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22278doc 5706H | P7 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22279doc 5707H | P7 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22280doc 5708H | P7 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22281doc 5709H | P7 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22282doc 570AH | P7 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22528doc 5800H | P8 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 22529doc 5801H | P8 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22530doc 5802H | P8 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22531doc 5803H | P8 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22532doc 5804H | P8 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22533doc 5805H | P8 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22534doc 5806H | P8 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22535doc 5807H | P8 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22536doc 5808H | P8 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22537doc 5809H | P8 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22538doc 580AH | P8 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22784doc 5900H | P9 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 22785doc 5901H | P9 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22786doc 5902H | P9 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22787doc 5903H | P9 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22788doc 5904H | P9 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22789doc 5905H | P9 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22790doc 5906H | P9 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22791doc 5907H | P9 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22792doc 5908H | P9 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22793doc 5909H | P9 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 22794doc 590AH | P9 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23040doc 5A00H | P10 wait value | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 23041doc 5A01H | P10 step 1 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23042doc 5A02H | P10 step 2 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23043doc 5A03H | P10 step 3 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23044doc 5A04H | P10 step 4 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23045doc 5A05H | P10 step 5 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23046doc 5A06H | P10 step 6 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23047doc 5A07H | P10 step 7 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23048doc 5A08H | P10 step 8 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23049doc 5A09H | P10 step 9 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 23050doc 5A0AH | P10 step 10 wait function | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 24576doc 6000H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3; 4 = Lock 4; 5 = Lock 5 | ||||
| HR | 24577doc 6001H | Changeable in set value lock | INT16 | Read/write | 0 = Step SV + step time; 1 = Step SV + step time + EV alarm value | ||||
| HR | 24578doc 6002H | Sensor correction coefficient | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 24579doc 6003H | Sensor correction | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 24580doc 6004H | PV filter time constant | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 24581doc 6005H | Response delay time | INT16 | ms | Read/write | ||||
| HR | 24582doc 6006H | SVTC bias | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28672doc 7000H | Input type | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -328 to 2498 F; 16 = K -328.0 to 752.0 F; 17 = J -328 to 1832 F; 18 = R 32 to 3200 F; 19 = S 32 to 3200 F; 20 = B 32 to 3308 F; 21 = E -328 to 1472 F; 22 = T -328.0 to 752.0 F; 23 = N -328 to 2372 F; 24 = PL-II 32 to 2534 F; 25 = C (W/Re5-26) 32 to 4199 F; 26 = Pt100 -328.0 to 1562.0 F; 27 = JPt100 -328.0 to 932.0 F; 28 = Pt100 -328 to 1562 F; 29 = JPt100 -328 to 932 F; 30 = 4 to 20 mA (-2000 to 10000); 31 = 0 to 20 mA (-2000 to 10000); 32 = 0 to 1 V (-2000 to 10000); 33 = 0 to 5 V (-2000 to 10000); 34 = 1 to 5 V (-2000 to 10000); 35 = 0 to 10 V (-2000 to 10000) | ||||
| HR | 28673doc 7001H | Scaling high limit | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28674doc 7002H | Scaling low limit | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28675doc 7003H | Decimal point place | INT16 | Read/write | 0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits | ||||
| HR | 28676doc 7004H | Event output EV1 allocation | Changing it clears this event's alarm settings. | INT16 | Read/write | 0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output | |||
| HR | 28677doc 7005H | EV1 alarm value 0 enabled | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 28678doc 7006H | EV1 alarm hysteresis | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28679doc 7007H | EV1 alarm delay time | INT16 | Read/write | |||||
| HR | 28680doc 7008H | EV1 alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 28681doc 7009H | Event output EV2 allocation | Changing it clears this event's alarm settings. | INT16 | Read/write | 0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output; 20 = Heating/Cooling control output | |||
| HR | 28682doc 700AH | EV2 alarm value 0 enabled | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 28683doc 700BH | EV2 alarm hysteresis | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28684doc 700CH | EV2 alarm delay time | INT16 | Read/write | |||||
| HR | 28685doc 700DH | EV2 alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 28686doc 700EH | Event output EV3 allocation | Changing it clears this event's alarm settings. | INT16 | Read/write | 0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby alarm; 10 = Low limit with standby alarm; 11 = High/Low limits with standby alarm; 12 = High/Low limits with standby independent alarm; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command (8004H); 19 = RUN output | |||
| HR | 28687doc 700FH | EV3 alarm value 0 enabled | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 28688doc 7010H | EV3 alarm hysteresis | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28689doc 7011H | EV3 alarm delay time | INT16 | Read/write | |||||
| HR | 28690doc 7012H | EV3 alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 28691doc 7013H | Event input DI1 allocation | INT16 | Read/write | 0 = No event; 1 = Pattern number selection; 2 = Direct/Reverse action; 3 = Program control RUN/STOP; 4 = Program control holding/not holding; 5 = Program control advance function | ||||
| HR | 28692doc 7014H | Event input DI2 allocation | INT16 | Read/write | 0 = No event; 1 = Pattern number selection; 2 = Direct/Reverse action; 3 = Program control RUN/STOP; 4 = Program control holding/not holding; 5 = Program control advance function | ||||
| HR | 28693doc 7015H | Transmission output | INT16 | Read/write | 0 = PV transmission; 1 = SV transmission; 2 = MV transmission | ||||
| HR | 28694doc 7016H | Transmission output high limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 28695doc 7017H | Transmission output low limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 28696doc 7018H | Step time unit | INT16 | Read/write | 0 = Hours:Minutes; 1 = Minutes:Seconds | ||||
| HR | 28697doc 7019H | Power restore action | INT16 | Read/write | 0 = Stop; 1 = Continue (resume); 2 = Suspend (hold) | ||||
| HR | 28698doc 701AH | Step SV when program control starts | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28699doc 701BH | Program control start type | INT16 | Read/write | 0 = PV start; 1 = PVR start; 2 = SV start | ||||
| HR | 28700doc 701CH | Pattern end output time | INT16 | Read/write | |||||
| HR | 28701doc 701DH | AT bias | Raw integer; apply decimal point place (7003H). | INT16 | Read/write | ||||
| HR | 28702doc 701EH | Output status on input error | INT16 | Read/write | 0 = Output OFF; 1 = Output ON | ||||
| HR | 28703doc 701FH | Indication time | INT16 | s | Read/write | ||||
| HR | 28704doc 7020H | Error indication | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 32768doc 8000H | Pattern number for operation | Writable only in program STOP and when DI selects pattern 1. | INT16 | Read/write | 1 = Pattern 1; 2 = Pattern 2; 3 = Pattern 3; 4 = Pattern 4; 5 = Pattern 5; 6 = Pattern 6; 7 = Pattern 7; 8 = Pattern 8; 9 = Pattern 9; 10 = Pattern 10 | |||
| HR | 32769doc 8001H | Program control RUN/STOP | Write-only (06/10H). | INT16 | Write | 0 = STOP; 1 = RUN (cancels HOLD) | |||
| HR | 32770doc 8002H | Program control HOLD | Write-only; rejected in STOP. | INT16 | Write | 1 = HOLD | |||
| HR | 32771doc 8003H | Program control ADVANCE | Write-only; rejected in STOP. | INT16 | Write | 1 = ADVANCE | |||
| HR | 32772doc 8004H | Output by communication | Drives EV outputs allocated to 'output by communication'. | BITMAP16 | Write | bit 0 = EV1 output; bit 1 = EV2 output; bit 2 = EV3 output | |||
| HR | 32773doc 8005H | Key operation change flag clearing | INT16 | Write | 1 = Clear flag | ||||
| HR | 36864doc 9000H | PV | Process value. Raw integer; apply decimal point place (7003H). | INT16 | Read | ||||
| HR | 36865doc 9001H | OUT1 MV | Decimal point ignored. | INT16 | Read | ||||
| HR | 36866doc 9002H | OUT2 MV | Decimal point ignored. | INT16 | Read | ||||
| HR | 36867doc 9003H | Current step SV | Raw integer; apply decimal point place (7003H). | INT16 | Read | ||||
| HR | 36868doc 9004H | Current step remaining time | INT16 | Read | |||||
| HR | 36869doc 9005H | Current pattern and step | Lowest hex digit = pattern, next hex digit = step (0 when stopped). | INT16 | Read | ||||
| HR | 36870doc 9006H | Current number of repetitions | INT16 | Read | |||||
| HR | 36871doc 9007H | Pattern selected by event input | INT16 | Read | |||||
| HR | 36872doc 9008H | CT1 current value | Decimal point ignored. | INT16 | Read | ||||
| HR | 36873doc 9009H | CT2 current value | Decimal point ignored. | INT16 | Read | ||||
| HR | 36874doc 900AH | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 4 = EV3 output on; bit 6 = Loop break alarm output; bit 7 = Overscale; bit 8 = Underscale; bit 9 = Heater burnout alarm output; bit 15 = Changed by keypad | ||||
| HR | 36875doc 900BH | Current unit status | BITMAP16 | Read | bit 0 = Program control (fixed); bit 1 = AT performing; bit 2 = Program control RUN; bit 3 = HOLD; bit 4 = WAIT; bit 5 = Pattern end output on | ||||
| HR | 36876doc 900CH | Error status flag 1 | BITMAP16 | Read | bit 0 = Error 01; bit 1 = Error 02; bit 4 = Error 05; bit 5 = Error 06; bit 6 = Error 07; bit 9 = Error 10 | ||||
| HR | 36877doc 900DH | Error status flag 2 | BITMAP16 | Read | bit 3 = Error 20 |
Notes on this map
- Addresses with a pattern or block number follow the manual's digit scheme: 2p00H (pattern p = 1-A), 3p00H, 5p00H, and 4k12H-4k16H for PID block k = 1-A. Step n of a pattern uses 2p00H + (n-1) x 3.
- The manual's PCD-33A compatible command set (section 7.2, 0001H-00A3H) is not repeated here; see the pcd-33a map for that layout.
- All data are 16-bit two's complement; values with a decimal point are sent as whole numbers.
- Units of PID times and limits are not printed in the command table.
- Changing an EV allocation clears that event's alarm value-0, hysteresis, delay and energized settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos PCB1 programmable controller (C5W/C5 option)
What Modbus registers does the Shinko Technos PCB1 programmable controller (C5W/C5 option) have?
This map lists 678 registers: 678 holding registers. 664 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Data items are hex (9000H) and are sent unchanged as the Modbus holding-register address. The manual says the Modicon number is the data item plus 40001. The RTU examples read PV at 9000H and write pattern 1 step 1 SV at 2100H (CRCs A90AH and 83E1H checked).
What are the minimum Modbus registers to integrate the Shinko Technos PCB1 programmable controller (C5W/C5 option)?
Start with HR 36864 PV (Process value); HR 36867 Current step SV (Current step SV); HR 36869 Current pattern and step (Running pattern and step); HR 36875 Current unit status (Run/hold/wait status); HR 36874 Status flag (Output, alarm and over/underscale flags); HR 32769 Program control RUN/STOP (Program RUN/STOP); HR 32768 Pattern number for operation (Pattern to run); HR 28675 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos PCB1 programmable controller (C5W/C5 option)?
Requires the C5W or C5 option. In Engineering setting mode 1 (down + MODE for about 3 s) set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit. These can only be set on the keypad.
Where is the official Shinko Technos PCB1 programmable controller (C5W/C5 option) Modbus documentation?
The source is Communication Instruction Manual PCB1 (C5W, C5) (No. PCB1CE3), revision 2019-09, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/PCB1CE3.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual PCB1 (C5W, C5) · No. PCB1CE3 · rev. 2019-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.