Sensor (digital temperature controller) · Modbus register map
Fuji Electric PXR micro controller X (RS-485 Modbus option) Modbus register map
Updated 17 November 2026
The PXR is a Fuji Electric PID temperature controller. With the RS-485 option it is a Modbus RTU slave whose data appear twice: once as internal percentage values (3xxxx/4xxxx) and once in engineering units at the same numbers plus 1000. This map uses the engineering-unit block: PV, SV, MV and status in the input registers, control, alarm and ramp/soak settings in the holding registers, plus alarm bits.
This page lists 103 Modbus registers for the Fuji Electric PXR micro controller X (RS-485 Modbus option) — 82 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fuji Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fuji Electric
- Model
- PXR micro controller X (RS-485 Modbus option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 103 (82 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8O1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PXR3, PXR4, PXR5, PXR9
Integration notes: Fuji Electric PXR micro controller X (RS-485 Modbus option)
Set CoM parity and a station number on the keypad, then read input registers 31001-31010 (PV, current SV, DV, MV, status) in one request and write the setpoint to 41003.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1000 | PV | INT16 | PV (31001) | Read |
| IR 1001 | Current SV | INT16 | Current SV (31002) | Read |
| IR 1003 | MV output 1 | INT16 | Output 1 MV (31004) | Read |
| IR 1006 | Alarm status | BITMAP16 | Alarm status (31007) | Read |
| IR 1007 | Input/unit abnormal status | BITMAP16 | Input error status (31008) | Read |
| HR 1002 | Face panel SV | INT16 | Face panel SV (41003) | Read/write |
| HR 1003 | Control RUN/standby | UINT16 | RUN/standby (41004) | Read/write |
| HR 1019 | Decimal point place | UINT16 | Decimal point (41020) | Read/write |
Enable Modbus control & writes
Order the RS-485 option. On the keypad set STno (1-255; 0 stops communication), CoM (parity) and PCoL = 1 (Modbus) where shown.
Byte order & addressing
- Speed is fixed at 9600 bps with 8 data bits and 1 stop bit; only parity is selectable (0 odd, 1 even, 2 none).
- Monitor SV at 31002, not 41003: the face-panel SV differs while SV-1 or ramp/soak is active.
- When changing the decimal point over the bus, rewrite the input scale limits as well.
Network setup
- Factory defaults: station 1, odd parity, 9600 bps, 8 data bits, 1 stop bit.
Watch out for
- Every write is saved to EEPROM automatically (about 100,000 writes); avoid cyclic writes and wait a few seconds after writing before removing power.
Fuji Electric PXR micro controller X (RS-485 Modbus option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Write to non-volatile memory (FIX) | 1 = request write of settings to memory. | BIT | Read/write | ||||
| DI | 0doc 10001 | Alarm 1 ON/OFF | BIT | Read | |||||
| DI | 4doc 10005 | Alarm 2 ON/OFF | BIT | Read | |||||
| DI | 8doc 10009 | Alarm 1 relay output | BIT | Read | |||||
| DI | 9doc 10010 | Alarm 2 relay output | BIT | Read | |||||
| DI | 10doc 10011 | Alarm 3 relay output | BIT | Read | |||||
| DI | 11doc 10012 | HB alarm relay output | BIT | Read | |||||
| DI | 14doc 10015 | Alarm 3 ON/OFF | BIT | Read | |||||
| IR | 1000doc 31001 | PV | -1999 to 9999. Engineering units; decimal point per P-dP (41020). | INT16 | Read | ||||
| IR | 1001doc 31002 | Current SV | SV actually in use (ramp/soak, SV-1). Engineering units; decimal point per P-dP (41020). | INT16 | Read | ||||
| IR | 1002doc 31003 | Deviation (DV) | Engineering units; decimal point per P-dP (41020). | INT16 | Read | ||||
| IR | 1003doc 31004 | MV output 1 | INT16 | × 0.01 | % | Read | |||
| IR | 1004doc 31005 | MV output 2 | INT16 | × 0.01 | % | Read | |||
| IR | 1005doc 31006 | Station No. | UINT16 | Read | |||||
| IR | 1006doc 31007 | Alarm status | BITMAP16 | Read | bit 0 = Alarm 1 relay output; bit 1 = Alarm 2 relay output; bit 2 = Alarm 3 relay output; bit 3 = HB alarm relay output; bit 4 = Alarm 1 ON; bit 5 = Alarm 2 ON; bit 6 = Alarm 3 ON; bit 7 = HB alarm relay output | ||||
| IR | 1007doc 31008 | Input/unit abnormal status | BITMAP16 | Read | bit 0 = Input lower open circuit; bit 1 = Input upper open circuit; bit 2 = Input under-range; bit 3 = Input over-range; bit 6 = Setting range error; bit 7 = EEPROM error | ||||
| IR | 1008doc 31009 | Ramp/soak running position | 0 to 17. | UINT16 | Read | ||||
| IR | 1009doc 31010 | Heater current | UINT16 | × 0.1 | A | Read | |||
| IR | 1010doc 31011 | Timer 1 current count | UINT16 | s | Read | ||||
| IR | 1011doc 31012 | Timer 2 current count | UINT16 | s | Read | ||||
| IR | 1012doc 31013 | Timer 3 current count | UINT16 | s | Read | ||||
| IR | 1036doc 31037 | Remote SV input value | Engineering units; decimal point per P-dP (41020). | INT16 | Read | ||||
| HR | 1000doc 41001 | Non-volatile memory write-in (FIX) | UINT16 | Read/write | 0 = No request; 1 = Request write | ||||
| HR | 1001doc 41002 | PID/FUZZY/SELF selection | Do not change while controlling. | UINT16 | Read/write | 0 = PID; 1 = FUZZY; 2 = SELF tuning | |||
| HR | 1002doc 41003 | Face panel SV | -1999 to 9999 within SV limits. Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1003doc 41004 | Control RUN/standby | UINT16 | Read/write | 0 = RUN; 1 = Standby | ||||
| HR | 1004doc 41005 | Auto tuning command | UINT16 | Read/write | 0 = Disabled / stop; 1 = Standard AT; 2 = Low PV type AT | ||||
| HR | 1005doc 41006 | P | UINT16 | × 0.1 | % | Read/write | |||
| HR | 1006doc 41007 | I | UINT16 | × 0.1 | s | Read/write | |||
| HR | 1007doc 41008 | D | UINT16 | × 0.1 | s | Read/write | |||
| HR | 1008doc 41009 | Hysteresis (two-position) | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1009doc 41010 | COOL | UINT16 | × 0.1 | Read/write | ||||
| HR | 1010doc 41011 | Dead band | INT16 | × 0.01 | % | Read/write | |||
| HR | 1011doc 41012 | Anti-reset windup | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1012doc 41013 | Output convergence value | INT16 | × 0.01 | % | Read/write | |||
| HR | 1013doc 41014 | PV shift | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1014doc 41015 | SV offset | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1015doc 41016 | Input type code | 0 to 16. | UINT16 | Read/write | ||||
| HR | 1016doc 41017 | Temperature unit | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 1017doc 41018 | Input scale lower limit | -1999 to 9999. | INT16 | Read/write | ||||
| HR | 1018doc 41019 | Input scale upper limit | -1999 to 9999. | INT16 | Read/write | ||||
| HR | 1019doc 41020 | Decimal point place | 0 to 2 digits. | UINT16 | Read/write | ||||
| HR | 1021doc 41022 | Input filter time constant | UINT16 | × 0.1 | s | Read/write | |||
| HR | 1022doc 41023 | RCJ compensation | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1023doc 41024 | MV limit kind | 0 to 15. | UINT16 | Read/write | ||||
| HR | 1024doc 41025 | Output 1 lower limit | INT16 | × 0.01 | % | Read/write | |||
| HR | 1025doc 41026 | Output 1 upper limit | INT16 | × 0.01 | % | Read/write | |||
| HR | 1026doc 41027 | Output 2 lower limit | INT16 | × 0.01 | % | Read/write | |||
| HR | 1027doc 41028 | Output 2 upper limit | INT16 | × 0.01 | % | Read/write | |||
| HR | 1030doc 41031 | SV lower limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1031doc 41032 | SV upper limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1038doc 41039 | Heater burnout alarm set value | UINT16 | × 0.1 | A | Read/write | |||
| HR | 1039doc 41040 | Setting lock | 0 to 5. | UINT16 | Read/write | ||||
| HR | 1040doc 41041 | Alarm 1 type | Type code 0 to 34. | UINT16 | Read/write | ||||
| HR | 1041doc 41042 | Alarm 2 type | Type code 0 to 34. | UINT16 | Read/write | ||||
| HR | 1042doc 41043 | Alarm 3 type | Type code 0 to 34. | UINT16 | Read/write | ||||
| HR | 1043doc 41044 | Alarm 1 set value / lower limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1044doc 41045 | Alarm 2 set value / lower limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1045doc 41046 | Alarm 3 set value / lower limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1046doc 41047 | Alarm 1 upper limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1047doc 41048 | Alarm 2 upper limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1048doc 41049 | Alarm 3 upper limit | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1049doc 41050 | Alarm 1 hysteresis | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1050doc 41051 | Alarm 2 hysteresis | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1051doc 41052 | Alarm 3 hysteresis | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1052doc 41053 | Alarm 1 ON-delay | UINT16 | s | Read/write | ||||
| HR | 1053doc 41054 | Alarm 2 ON-delay | UINT16 | s | Read/write | ||||
| HR | 1054doc 41055 | Alarm 3 ON-delay | UINT16 | s | Read/write | ||||
| HR | 1056doc 41057 | Ramp/soak 1 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1057doc 41058 | Ramp/soak 2 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1058doc 41059 | Ramp/soak 3 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1059doc 41060 | Ramp/soak 4 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1060doc 41061 | Ramp/soak 5 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1061doc 41062 | Ramp/soak 6 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1062doc 41063 | Ramp/soak 7 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1063doc 41064 | Ramp/soak 8 target value | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1064doc 41065 | Ramp/soak 1 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1065doc 41066 | Ramp/soak 1 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1066doc 41067 | Ramp/soak 2 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1067doc 41068 | Ramp/soak 2 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1068doc 41069 | Ramp/soak 3 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1069doc 41070 | Ramp/soak 3 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1070doc 41071 | Ramp/soak 4 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1071doc 41072 | Ramp/soak 4 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1072doc 41073 | Ramp/soak 5 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1073doc 41074 | Ramp/soak 5 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1074doc 41075 | Ramp/soak 6 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1075doc 41076 | Ramp/soak 6 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1076doc 41077 | Ramp/soak 7 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1077doc 41078 | Ramp/soak 7 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1078doc 41079 | Ramp/soak 8 ramp time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1079doc 41080 | Ramp/soak 8 soak time | Minutes (keypad shows hh:mm). | UINT16 | min | Read/write | |||
| HR | 1080doc 41081 | Ramp/soak mode | 0 to 15. | UINT16 | Read/write | ||||
| HR | 1081doc 41082 | Ramp/soak command | Write 0-2; reading 3 means the program ended. | UINT16 | Read/write | 0 = oFF (stop); 1 = rUn (run); 2 = HLd (hold); 3 = End (read only) | |||
| HR | 1082doc 41083 | Ramp/soak pattern selection | UINT16 | Read/write | 0 = Steps 1-4; 1 = Steps 5-8; 2 = Steps 1-8 | ||||
| HR | 1084doc 41085 | PV stable range | Engineering units; decimal point per P-dP (41020). | INT16 | Read/write | ||||
| HR | 1086doc 41087 | Communication DI action request | Bits 0-1: 00 = face panel SV, 01 = SV-1; held until changed or power off. | BITMAP16 | Read/write | bit 0 = Select SV-1; bit 5 = Cancel alarm 1 latch; bit 6 = Cancel alarm 2 latch; bit 7 = Cancel alarm 3 latch; bit 8 = ALM1 relay timer DI; bit 9 = ALM2 relay timer DI; bit 10 = ALM3 relay timer DI | |||
| HR | 1087doc 41088 | Control action type code | 0 to 19. | UINT16 | Read/write | ||||
| HR | 1088doc 41089 | Output 1 proportional cycle | 0 = current output; 1-150 s. | UINT16 | s | Read/write | |||
| HR | 1089doc 41090 | Output 2 proportional cycle | UINT16 | s | Read/write | ||||
| HR | 1096doc 41097 | Hysteresis mode | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 1113doc 41114 | Re-transmission output type | UINT16 | Read/write | 0 = PV; 1 = SV; 2 = MV; 3 = DV | ||||
| HR | 1116doc 41117 | Local/remote | UINT16 | Read/write | 0 = Local; 1 = Remote |
Notes on this map
- Only the engineering-unit block (31001+, 41001+) is listed. The internal-value block at 30001/40001 holds the same items as 0.00-100.00 % of the input range for range-dependent data.
- Values carry no decimal point. PV/SV-type values use the P-dP decimal point (41020); P, D, filter and heater current have one decimal; MV, output limits, dead band and output convergence have two.
- On over/under-range or open input the PV reads 105 % or -5 % of the range; check 31008.
- Reserved/'do not use' registers and the display-mask items (41101-41113) are omitted; DI and alarm option codes are not reproduced.
- Writes are accepted beyond the setting range without error; keep values in range.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fuji Electric PXR micro controller X (RS-485 Modbus option)
What Modbus registers does the Fuji Electric PXR micro controller X (RS-485 Modbus option) have?
This map lists 103 registers: 1 coil, 7 discrete inputs, 14 input registers, 81 holding registers. 82 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fuji Electric PXR micro controller X (RS-485 Modbus option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed Modicon-style with the relative (wire) address beside them; the manual says the wire address is the lower four digits minus 1 (41001 = 03E8H).
What are the minimum Modbus registers to integrate the Fuji Electric PXR micro controller X (RS-485 Modbus option)?
Start with IR 1000 PV (PV (31001)); IR 1001 Current SV (Current SV (31002)); IR 1003 MV output 1 (Output 1 MV (31004)); IR 1006 Alarm status (Alarm status (31007)); IR 1007 Input/unit abnormal status (Input error status (31008)); HR 1002 Face panel SV (Face panel SV (41003)); HR 1003 Control RUN/standby (RUN/standby (41004)); HR 1019 Decimal point place (Decimal point (41020)).
How do I enable Modbus control of the Fuji Electric PXR micro controller X (RS-485 Modbus option)?
Order the RS-485 option. On the keypad set STno (1-255; 0 stops communication), CoM (parity) and PCoL = 1 (Modbus) where shown.
Where is the official Fuji Electric PXR micro controller X (RS-485 Modbus option) Modbus documentation?
The source is Micro Controller X Communication Functions (RS-485 MODBUS) Type PXR (INP-TN512642d-E), published free by Fuji Electric at https://americas.fujielectric.com/files/prod_selector_v/Micro%20Controller%20X%20Communication%20Functions%20%28MODBUS%29%20Model%20PXR%20%28TN512642d-E%29.pdf.
More Fuji Electric Modbus register maps
- Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A
All temperature & process controllers Modbus register maps →
Source: Micro Controller X Communication Functions (RS-485 MODBUS) Type PXR · INP-TN512642d-E. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.