- Home
- Modbus register maps
- Fuji Electric
- FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Variable frequency drive (HVAC / pump) · Modbus register map
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus register map
Updated 19 November 2026
FRENIC-HVAC and FRENIC-AQUA drives for fans and pumps speak Modbus RTU on their RS-485 port. Every function code (F, E, H, y, S, M ...) is a holding register found by a fixed group/number rule; the S codes carry frequency, run and PID commands and the M codes carry monitors, status words and alarm history. This map lists the communication command and monitor codes and the link settings.
This page lists 53 Modbus registers for the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fuji Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fuji Electric
- Model
- FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
- Equipment type
- Variable frequency drive (HVAC / pump)
- Registers
- 53 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- derived from parameter numbers
- Also known as
- FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ
Integration notes: Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Set y10 = 0 (Modbus RTU), y01 address and y04/y06 serial settings, and H30 = 3 so frequency and run commands come from RS-485. Write S05 (Hz) or S01 (p.u.) for speed and S06 bit 0/1 for run forward/reverse; poll M09, M11, M14 and M16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1797 | Frequency reference (0.01 Hz) | UINT16 | S05 frequency command | Read/write |
| HR 1798 | Operation command | BITMAP16 | S06 run command | Read/write |
| HR 1806 | Alarm reset command | UINT16 | S14 alarm reset | Read/write |
| HR 2057 | Output frequency | UINT16 | M09 output frequency | Read |
| HR 2059 | Output current (effective) | UINT16 | M11 output current | Read |
| HR 2062 | Operation status | BITMAP16 | M14 status | Read |
| HR 2064 | Latest alarm code | UINT16 | M16 latest alarm | Read |
| HR 1054 | Communications link function (mode selection) | UINT16 | H30 link mode | Read/write |
Enable Modbus control & writes
Select Modbus RTU with y10 = 0 and set H30 (communications link function) so the frequency and/or run command come from RS-485 (3 = both from the RJ-45 port). If a digital input is assigned to LE (enable communications link), it must be ON.
Communication loss & watchdog
y08 sets a no-response detection time (0 = off, 1-60 s); y02/y03 choose whether the drive trips at once, after a timer, or keeps running.
Byte order & addressing
- Addresses are function-code based: wire address = group code x 256 + number (for example H30 = 4 x 256 + 30 = 1054).
- Reads are limited to 50 words and do not cross a function code group; unused codes read as 0.
- Reading S codes returns the last value written over comms, not the live command; read the M codes for the live value.
- Alarm reset through S06 needs bit 15 set then cleared; S14 = 1 resets in one write.
- S14 = 1 resets an alarm even when H30, y98, y99 or the LE terminal block the link; S06 bit 15 only works when the link is enabled.
Network setup
- y01 station address 1-247, y04 baud (0-4 = 2400-38400 bps), y06 parity (stop bits follow parity in Modbus RTU), data length fixed at 8 bits.
- y09 adds a response interval (0.00-1.00 s) for slow masters.
Watch out for
- If S01 is not 0 it overrides S05; write 0 to S01 when using S05.
- Writing an alarm reset while a run command is still set restarts the drive immediately.
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1054doc H30 | Communications link function (mode selection) | Selects frequency and run command sources when the link is enabled. | UINT16 | Read/write | 0 = Freq: inverter / Run: inverter; 1 = Freq: RS-485 (RJ-45) / Run: inverter; 2 = Freq: inverter / Run: RS-485 (RJ-45); 3 = Freq: RS-485 (RJ-45) / Run: RS-485 (RJ-45); 4 = Freq: RS-485 port 2 / Run: inverter; 5 = Freq: RS-485 port 2 / Run: RS-485 (RJ-45); 6 = Freq: inverter / Run: RS-485 port 2; 7 = Freq: RS-485 (RJ-45) / Run: RS-485 port 2; 8 = Freq: RS-485 port 2 / Run: RS-485 port 2 | |||
| HR | 1793doc S01 | Frequency reference (p.u.) | +/-20000 = maximum frequency. Takes priority over S05 when not 0. | INT16 | Read/write | ||||
| HR | 1797doc S05 | Frequency reference (0.01 Hz) | Frequency command in 0.01 Hz steps. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 1798doc S06 | Operation command | Run, direction, X terminals and reset (format 14). | BITMAP16 | Read/write | bit 0 = FWD run forward; bit 1 = REV run reverse; bit 2 = X1; bit 3 = X2; bit 4 = X3; bit 5 = X4; bit 6 = X5; bit 7 = X6; bit 8 = X7; bit 11 = EN; bit 13 = XF (FWD terminal function); bit 14 = XR (REV terminal function); bit 15 = RST alarm reset | |||
| HR | 1799doc S07 | Universal DO | Command to DO terminals assigned as universal DO. | BITMAP16 | Read/write | ||||
| HR | 1804doc S12 | Universal AO | +/-20000 = full scale. | INT16 | Read/write | ||||
| HR | 1805doc S13 | PID command | +/-20000 = +/-100 %. | INT16 | Read/write | ||||
| HR | 1806doc S14 | Alarm reset command | Write 1 to reset; always reads 0. | UINT16 | Read/write | 0 = No action; 1 = Reset | |||
| HR | 1811doc S19 | Speed command | INT16 | rpm | Read/write | ||||
| HR | 1823doc S31 | External PID command 1 | +/-20000 = +/-100 %. | INT16 | Read/write | ||||
| HR | 2049doc M01 | Frequency reference, final (p.u.) | +/-20000 = maximum frequency. | INT16 | Read | ||||
| HR | 2053doc M05 | Frequency reference, final (0.01 Hz) | UINT16 | × 0.01 | Hz | Read | |||
| HR | 2054doc M06 | Output frequency 1 (p.u.) | +/-20000 = maximum frequency, before slip compensation. | INT16 | Read | ||||
| HR | 2055doc M07 | Torque real value | % of motor rated torque. | INT16 | × 0.01 | % | Read | ||
| HR | 2057doc M09 | Output frequency | 0.00-655.35 Hz over Modbus RTU (unsigned). | UINT16 | × 0.01 | Hz | Read | ||
| HR | 2058doc M10 | Input power | % of nominal applicable motor output. | UINT16 | × 0.01 | % | Read | ||
| HR | 2059doc M11 | Output current (effective) | % of inverter rated current. | UINT16 | × 0.01 | % | Read | ||
| HR | 2060doc M12 | Output voltage (effective) | Resolution 1 V in practice. | UINT16 | × 0.1 | V | Read | ||
| HR | 2061doc M13 | Operation command, final | Combined keypad/terminal/comms command, format 14. | BITMAP16 | Read | bit 0 = FWD run forward; bit 1 = REV run reverse; bit 2 = X1; bit 3 = X2; bit 4 = X3; bit 5 = X4; bit 6 = X5; bit 7 = X6; bit 8 = X7; bit 11 = EN; bit 13 = XF (FWD terminal function); bit 14 = XR (REV terminal function); bit 15 = RST alarm reset | |||
| HR | 2062doc M14 | Operation status | Format 16. | BITMAP16 | Read | bit 0 = FWD during forward rotation; bit 1 = REV during reverse rotation; bit 2 = EXT during DC braking / pre-exciting; bit 3 = INT inverter shut down; bit 4 = BRK during braking; bit 5 = NUV DC link voltage established (0 = undervoltage); bit 7 = VL during voltage limiting; bit 8 = IL during current limiting; bit 9 = ACC during acceleration; bit 10 = DEC during deceleration; bit 11 = ALM alarm relay (any fault); bit 12 = RL communications effective; bit 15 = BUSY writing function code data | |||
| HR | 2063doc M15 | General-purpose output terminals | Format 15. | BITMAP16 | Read | bit 0 = Y1; bit 1 = Y2; bit 2 = Y3; bit 3 = Y4; bit 4 = Y5; bit 8 = 30 (alarm relay) | |||
| HR | 2064doc M16 | Latest alarm code | Alarm code 0-254. | UINT16 | Read | ||||
| HR | 2065doc M17 | Last alarm code | UINT16 | Read | |||||
| HR | 2066doc M18 | Second last alarm code | UINT16 | Read | |||||
| HR | 2067doc M19 | Third last alarm code | UINT16 | Read | |||||
| HR | 2068doc M20 | Cumulative operation time | UINT16 | h | Read | ||||
| HR | 2069doc M21 | DC link bus voltage | UINT16 | V | Read | ||||
| HR | 2071doc M23 | Model code | Series, generation, destination and supply in four hex digits. | UINT16 | Read | ||||
| HR | 2072doc M24 | Capacity code | UINT16 | Read | |||||
| HR | 2073doc M25 | ROM version | UINT16 | Read | |||||
| HR | 2074doc M26 | Transmission error code | RS-485 communications error code, 0-127. | UINT16 | Read | ||||
| HR | 2092doc M44 | Inverter internal air temperature on alarm | UINT16 | °C | Read | ||||
| HR | 2093doc M45 | Heat sink temperature on alarm | UINT16 | °C | Read | ||||
| HR | 2094doc M46 | Life of main circuit capacitor | Remaining capacity, 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 2095doc M47 | Life of PC board capacitor | Cumulative run time in 10 h steps. | UINT16 | × 10 | h | Read | ||
| HR | 2096doc M48 | Life of heat sink cooling fan | Cumulative run time in 10 h steps. | UINT16 | × 10 | h | Read | ||
| HR | 2109doc M61 | Inverter internal air temperature | Current value. | UINT16 | °C | Read | |||
| HR | 2110doc M62 | Heat sink temperature | Current value. | UINT16 | °C | Read | |||
| HR | 2111doc M63 | Load factor | INT16 | × 0.01 | % | Read | |||
| HR | 2112doc M64 | Motor output | INT16 | × 0.01 | % | Read | |||
| HR | 2116doc M68 | PID final command | +/-20000 = +/-100 %. | INT16 | Read | ||||
| HR | 2120doc M72 | PID feedback value | +/-20000 = +/-100 %. | INT16 | Read | ||||
| HR | 2121doc M73 | PID output | +/-20000 = +/-100 %. | INT16 | Read | ||||
| HR | 2126doc M78 | Rotation speed command | Speed command in rpm (min-1). | INT16 | rpm | Read | |||
| HR | 2127doc M79 | Rotation speed | Output rotation speed in rpm (min-1). | INT16 | rpm | Read | |||
| HR | 2134doc M86 | Latest light alarm code | Low byte = light alarm code, high byte = consecutive repeat count (format 41). | UINT16 | Read | ||||
| HR | 3585doc y01 | RS-485 port 1 station address | 1-247 for Modbus RTU. | UINT16 | Read/write | ||||
| HR | 3586doc y02 | RS-485 port 1 communications error processing | What the drive does on a comms error while running from the link. | UINT16 | Read/write | 0 = Trip Er8 at once; 1 = Run for the y03 time, then trip Er8; 2 = Run for the y03 time; trip Er8 only if comms not restored; 3 = Keep running | |||
| HR | 3587doc y03 | RS-485 port 1 error processing timer | Timer used by y02 settings 1 and 2, 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3588doc y04 | RS-485 port 1 baud rate | UINT16 | Read/write | 0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps; 4 = 38400 bps | ||||
| HR | 3590doc y06 | RS-485 port 1 parity | In Modbus RTU the stop bits follow the parity choice. | UINT16 | Read/write | 0 = No parity (2 stop bits); 1 = Even parity (1 stop bit); 2 = Odd parity (1 stop bit); 3 = No parity (1 stop bit) | |||
| HR | 3592doc y08 | RS-485 port 1 no-response error detection time | 0 = disabled, 1-60 s. | UINT16 | s | Read/write | |||
| HR | 3594doc y10 | RS-485 port 1 protocol selection | UINT16 | Read/write | 0 = Modbus RTU; 1 = Loader commands; 2 = Fuji general-purpose inverter protocol; 3 = Metasys N2; 5 = BACnet |
Notes on this map
- All function code data are single 16-bit words; no 32-bit values are used in this map.
- Per-unit values (S01, S12, S13, M01, M06, M68, M72, M73) use +/-20000 = 100 % or maximum frequency; convert with the drive's maximum frequency (F03).
- M09 output frequency is unsigned over Modbus RTU (0.00-655.35 Hz); the signed range in the table applies to the Fuji general-purpose inverter protocol.
- Codes marked not supported on HVAC/AQUA in the manual (torque and flux commands, motor temperature M22) are left out.
- Accel/decel times (F07/F08, S08/S09) use Fuji's packed floating-point format [12] and are not listed.
- M14 bit 6 (TL, torque limiting) is left out: the bit table lists it, but the bit diagram of format 16 shows bit 6 as unused (0).
- M86 uses alarm-history format 41: the low byte is the light alarm code and the high byte counts consecutive repeats of the same alarm.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
What Modbus registers does the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) have?
This map lists 53 registers: 53 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each function code is a holding register at 40000 + group code x 256 + number (manual Table 3.2: F=0, E=1, H=4, S=7, M=8, y=14). In the frame the high byte is the group code and the low byte the number, so the wire address is group x 256 + number; the manual's examples send 08 06 for M06 and 07 01 for S01.
What are the minimum Modbus registers to integrate the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)?
Start with HR 1797 Frequency reference (0.01 Hz) (S05 frequency command); HR 1798 Operation command (S06 run command); HR 1806 Alarm reset command (S14 alarm reset); HR 2057 Output frequency (M09 output frequency); HR 2059 Output current (effective) (M11 output current); HR 2062 Operation status (M14 status); HR 2064 Latest alarm code (M16 latest alarm); HR 1054 Communications link function (mode selection) (H30 link mode).
How do I enable Modbus control of the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)?
Select Modbus RTU with y10 = 0 and set H30 (communications link function) so the frequency and/or run command come from RS-485 (3 = both from the RJ-45 port). If a digital input is assigned to LE (enable communications link), it must be ON.
What happens when the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) loses Modbus communication?
y08 sets a no-response detection time (0 = off, 1-60 s); y02/y03 choose whether the drive trips at once, after a timer, or keeps running.
Where is the official Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus documentation?
The source is RS-485 Communication User's Manual (FRENIC-HVAC / FRENIC-AQUA) (24A7-E-0021b), published free by Fuji Electric at https://americas.fujielectric.com/files/24A7-E-0021b.pdf.
More Fuji Electric Modbus register maps
- Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9
Other variable frequency drives register maps
- Variable frequency drive
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
Invertek Optidrive Coolvert HVAC compressor drives on the terminal or RJ45 Modbus RTU port, per user guide version 2.01.
Also known as: Optidrive CoolVert, Coolvert - Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE - Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTP-B inverters on the RJ45 Modbus RTU port (no communication or encoder option card fitted), per product manual 31554814/EN edition 10/2023.
Also known as: MOVITRAC LTP-B, LTP-B, MC LTP B
All variable frequency drives Modbus register maps →
Source: RS-485 Communication User's Manual (FRENIC-HVAC / FRENIC-AQUA) · 24A7-E-0021b. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.