Variable frequency drive (HVAC / pump) · Modbus register map

Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

FRENIC-HVAC and FRENIC-AQUA drives for fans and pumps speak Modbus RTU on their RS-485 port. Every function code (F, E, H, y, S, M ...) is a holding register found by a fixed group/number rule; the S codes carry frequency, run and PID commands and the M codes carry monitors, status words and alarm history. This map lists the communication command and monitor codes and the link settings.

This page lists 53 Modbus registers for the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fuji Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Fuji Electric
Model
FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Equipment type
Variable frequency drive (HVAC / pump)
Registers
53 (17 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
derived from parameter numbers
Also known as
FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ
Source document
RS-485 Communication User's Manual (FRENIC-HVAC / FRENIC-AQUA) · 24A7-E-0021b
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)

Integration in brief

Set y10 = 0 (Modbus RTU), y01 address and y04/y06 serial settings, and H30 = 3 so frequency and run commands come from RS-485. Write S05 (Hz) or S01 (p.u.) for speed and S06 bit 0/1 for run forward/reverse; poll M09, M11, M14 and M16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1797Frequency reference (0.01 Hz)UINT16S05 frequency commandRead/write
HR 1798Operation commandBITMAP16S06 run commandRead/write
HR 1806Alarm reset commandUINT16S14 alarm resetRead/write
HR 2057Output frequencyUINT16M09 output frequencyRead
HR 2059Output current (effective)UINT16M11 output currentRead
HR 2062Operation statusBITMAP16M14 statusRead
HR 2064Latest alarm codeUINT16M16 latest alarmRead
HR 1054Communications link function (mode selection)UINT16H30 link modeRead/write

Enable Modbus control & writes

Select Modbus RTU with y10 = 0 and set H30 (communications link function) so the frequency and/or run command come from RS-485 (3 = both from the RJ-45 port). If a digital input is assigned to LE (enable communications link), it must be ON.

Communication loss & watchdog

y08 sets a no-response detection time (0 = off, 1-60 s); y02/y03 choose whether the drive trips at once, after a timer, or keeps running.

Byte order & addressing

Network setup

Watch out for

Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

53 of 53 shown
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1054doc H30Communications link function (mode selection)Selects frequency and run command sources when the link is enabled.UINT16Read/write0 = Freq: inverter / Run: inverter; 1 = Freq: RS-485 (RJ-45) / Run: inverter; 2 = Freq: inverter / Run: RS-485 (RJ-45); 3 = Freq: RS-485 (RJ-45) / Run: RS-485 (RJ-45); 4 = Freq: RS-485 port 2 / Run: inverter; 5 = Freq: RS-485 port 2 / Run: RS-485 (RJ-45); 6 = Freq: inverter / Run: RS-485 port 2; 7 = Freq: RS-485 (RJ-45) / Run: RS-485 port 2; 8 = Freq: RS-485 port 2 / Run: RS-485 port 2
HR1793doc S01Frequency reference (p.u.)+/-20000 = maximum frequency. Takes priority over S05 when not 0.INT16Read/write
HR1797doc S05Frequency reference (0.01 Hz)Frequency command in 0.01 Hz steps.UINT16× 0.01HzRead/write
HR1798doc S06Operation commandRun, direction, X terminals and reset (format 14).BITMAP16Read/writebit 0 = FWD run forward; bit 1 = REV run reverse; bit 2 = X1; bit 3 = X2; bit 4 = X3; bit 5 = X4; bit 6 = X5; bit 7 = X6; bit 8 = X7; bit 11 = EN; bit 13 = XF (FWD terminal function); bit 14 = XR (REV terminal function); bit 15 = RST alarm reset
HR1799doc S07Universal DOCommand to DO terminals assigned as universal DO.BITMAP16Read/write
HR1804doc S12Universal AO+/-20000 = full scale.INT16Read/write
HR1805doc S13PID command+/-20000 = +/-100 %.INT16Read/write
HR1806doc S14Alarm reset commandWrite 1 to reset; always reads 0.UINT16Read/write0 = No action; 1 = Reset
HR1811doc S19Speed commandINT16rpmRead/write
HR1823doc S31External PID command 1+/-20000 = +/-100 %.INT16Read/write
HR2049doc M01Frequency reference, final (p.u.)+/-20000 = maximum frequency.INT16Read
HR2053doc M05Frequency reference, final (0.01 Hz)UINT16× 0.01HzRead
HR2054doc M06Output frequency 1 (p.u.)+/-20000 = maximum frequency, before slip compensation.INT16Read
HR2055doc M07Torque real value% of motor rated torque.INT16× 0.01%Read
HR2057doc M09Output frequency0.00-655.35 Hz over Modbus RTU (unsigned).UINT16× 0.01HzRead
HR2058doc M10Input power% of nominal applicable motor output.UINT16× 0.01%Read
HR2059doc M11Output current (effective)% of inverter rated current.UINT16× 0.01%Read
HR2060doc M12Output voltage (effective)Resolution 1 V in practice.UINT16× 0.1VRead
HR2061doc M13Operation command, finalCombined keypad/terminal/comms command, format 14.BITMAP16Readbit 0 = FWD run forward; bit 1 = REV run reverse; bit 2 = X1; bit 3 = X2; bit 4 = X3; bit 5 = X4; bit 6 = X5; bit 7 = X6; bit 8 = X7; bit 11 = EN; bit 13 = XF (FWD terminal function); bit 14 = XR (REV terminal function); bit 15 = RST alarm reset
HR2062doc M14Operation statusFormat 16.BITMAP16Readbit 0 = FWD during forward rotation; bit 1 = REV during reverse rotation; bit 2 = EXT during DC braking / pre-exciting; bit 3 = INT inverter shut down; bit 4 = BRK during braking; bit 5 = NUV DC link voltage established (0 = undervoltage); bit 7 = VL during voltage limiting; bit 8 = IL during current limiting; bit 9 = ACC during acceleration; bit 10 = DEC during deceleration; bit 11 = ALM alarm relay (any fault); bit 12 = RL communications effective; bit 15 = BUSY writing function code data
HR2063doc M15General-purpose output terminalsFormat 15.BITMAP16Readbit 0 = Y1; bit 1 = Y2; bit 2 = Y3; bit 3 = Y4; bit 4 = Y5; bit 8 = 30 (alarm relay)
HR2064doc M16Latest alarm codeAlarm code 0-254.UINT16Read
HR2065doc M17Last alarm codeUINT16Read
HR2066doc M18Second last alarm codeUINT16Read
HR2067doc M19Third last alarm codeUINT16Read
HR2068doc M20Cumulative operation timeUINT16hRead
HR2069doc M21DC link bus voltageUINT16VRead
HR2071doc M23Model codeSeries, generation, destination and supply in four hex digits.UINT16Read
HR2072doc M24Capacity codeUINT16Read
HR2073doc M25ROM versionUINT16Read
HR2074doc M26Transmission error codeRS-485 communications error code, 0-127.UINT16Read
HR2092doc M44Inverter internal air temperature on alarmUINT16°CRead
HR2093doc M45Heat sink temperature on alarmUINT16°CRead
HR2094doc M46Life of main circuit capacitorRemaining capacity, 0.0-100.0 %.UINT16× 0.1%Read
HR2095doc M47Life of PC board capacitorCumulative run time in 10 h steps.UINT16× 10hRead
HR2096doc M48Life of heat sink cooling fanCumulative run time in 10 h steps.UINT16× 10hRead
HR2109doc M61Inverter internal air temperatureCurrent value.UINT16°CRead
HR2110doc M62Heat sink temperatureCurrent value.UINT16°CRead
HR2111doc M63Load factorINT16× 0.01%Read
HR2112doc M64Motor outputINT16× 0.01%Read
HR2116doc M68PID final command+/-20000 = +/-100 %.INT16Read
HR2120doc M72PID feedback value+/-20000 = +/-100 %.INT16Read
HR2121doc M73PID output+/-20000 = +/-100 %.INT16Read
HR2126doc M78Rotation speed commandSpeed command in rpm (min-1).INT16rpmRead
HR2127doc M79Rotation speedOutput rotation speed in rpm (min-1).INT16rpmRead
HR2134doc M86Latest light alarm codeLow byte = light alarm code, high byte = consecutive repeat count (format 41).UINT16Read
HR3585doc y01RS-485 port 1 station address1-247 for Modbus RTU.UINT16Read/write
HR3586doc y02RS-485 port 1 communications error processingWhat the drive does on a comms error while running from the link.UINT16Read/write0 = Trip Er8 at once; 1 = Run for the y03 time, then trip Er8; 2 = Run for the y03 time; trip Er8 only if comms not restored; 3 = Keep running
HR3587doc y03RS-485 port 1 error processing timerTimer used by y02 settings 1 and 2, 0.0-60.0 s.UINT16× 0.1sRead/write
HR3588doc y04RS-485 port 1 baud rateUINT16Read/write0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps; 4 = 38400 bps
HR3590doc y06RS-485 port 1 parityIn Modbus RTU the stop bits follow the parity choice.UINT16Read/write0 = No parity (2 stop bits); 1 = Even parity (1 stop bit); 2 = Odd parity (1 stop bit); 3 = No parity (1 stop bit)
HR3592doc y08RS-485 port 1 no-response error detection time0 = disabled, 1-60 s.UINT16sRead/write
HR3594doc y10RS-485 port 1 protocol selectionUINT16Read/write0 = Modbus RTU; 1 = Loader commands; 2 = Fuji general-purpose inverter protocol; 3 = Metasys N2; 5 = BACnet

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)

What Modbus registers does the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) have?

This map lists 53 registers: 53 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each function code is a holding register at 40000 + group code x 256 + number (manual Table 3.2: F=0, E=1, H=4, S=7, M=8, y=14). In the frame the high byte is the group code and the low byte the number, so the wire address is group x 256 + number; the manual's examples send 08 06 for M06 and 07 01 for S01.

What are the minimum Modbus registers to integrate the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)?

Start with HR 1797 Frequency reference (0.01 Hz) (S05 frequency command); HR 1798 Operation command (S06 run command); HR 1806 Alarm reset command (S14 alarm reset); HR 2057 Output frequency (M09 output frequency); HR 2059 Output current (effective) (M11 output current); HR 2062 Operation status (M14 status); HR 2064 Latest alarm code (M16 latest alarm); HR 1054 Communications link function (mode selection) (H30 link mode).

How do I enable Modbus control of the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)?

Select Modbus RTU with y10 = 0 and set H30 (communications link function) so the frequency and/or run command come from RS-485 (3 = both from the RJ-45 port). If a digital input is assigned to LE (enable communications link), it must be ON.

What happens when the Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) loses Modbus communication?

y08 sets a no-response detection time (0 = off, 1-60 s); y02/y03 choose whether the drive trips at once, after a timer, or keeps running.

Where is the official Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU) Modbus documentation?

The source is RS-485 Communication User's Manual (FRENIC-HVAC / FRENIC-AQUA) (24A7-E-0021b), published free by Fuji Electric at https://americas.fujielectric.com/files/24A7-E-0021b.pdf.