- PXH digital controller (Modbus RTU, monitoring map)
Sensor (digital process controller) · Modbus register map
Fuji Electric PXH digital controller (Modbus RTU, monitoring map) Modbus register map
Updated 17 November 2026
The PXH is a Fuji Electric digital process controller. Every Modbus value is a 32-bit integer spread over two registers, low word first. This map covers the read-only monitoring block: control mode, PV, SV, deviation, MV, input error, alarm and relay states, ramp/soak position, extra inputs/outputs and DI/DO status.
This page lists 35 Modbus registers for the Fuji Electric PXH digital controller (Modbus RTU, monitoring map) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fuji Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fuji Electric
- Model
- PXH digital controller (Modbus RTU, monitoring map)
- Equipment type
- Sensor (digital process controller)
- Registers
- 35 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8O1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- PXH
Integration notes: Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Read input registers 30257-30269 with function 04 (control mode, PV, SV, DV, MV, input error) as 32-bit values with the low word first, two registers per value.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 258 | PV1 control PV | INT32 CDAB | PV1 (30259) | Read |
| IR 260 | SV1 current setpoint | INT32 CDAB | SV1 (30261) | Read |
| IR 264 | MV1 manipulated value | INT32 CDAB | MV1 (30265) | Read |
| IR 268 | FAULT1 input error status | INT32 CDAB | Input error (30269) | Read |
| IR 256 | PID MODE1 current control mode | UINT32 CDAB | Control mode bits (30257) | Read |
| IR 832 | ALM1 status | INT32 CDAB | Alarm 1 status (30833) | Read |
Enable Modbus control & writes
Set SPD4 (speed), BIT4 (parity) and STN4 (station 0-255; 0 stops communication) for the RS-485 channel on the front keys, then cycle power.
Byte order & addressing
- 32-bit values are low word first; a single-register write (06) only changes the lower word.
- The PC-loader port always uses station 1.
Network setup
- Factory defaults (RS-485): 38400 bps, 8 data bits, 1 stop bit, odd parity, station 1.
- Turn power off and on after changing the communication settings.
Watch out for
- After changing the input range over the bus, a FIX command and a power cycle or reset are needed before the new range applies.
Fuji Electric PXH digital controller (Modbus RTU, monitoring map) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 256doc 30257 | PID MODE1 current control mode | Status flags: each bit is 1 while that mode or state is active. | UINT32 | CDAB | Read | bit 0 = Fault; bit 1 = Standby; bit 2 = Remote ack; bit 3 = Other than auto mode; bit 4 = Auto mode request; bit 5 = Remote mode request; bit 6 = Auto tuning; bit 7 = Normal operation; bit 8 = PV tracking; bit 9 = Local SV; bit 10 = Remote SV; bit 11 = Local + PV tracking; bit 12 = Forced manual mode; bit 13 = EX-MV mode; bit 14 = Manual mode | ||
| IR | 258doc 30259 | PV1 control PV | -5 to 105 % FS; pinned there on over/under range. Input-range decimal point. | INT32 | CDAB | Read | |||
| IR | 260doc 30261 | SV1 current setpoint | Decimal point set by the input range (PV1D/UCD1 per template). | INT32 | CDAB | Read | |||
| IR | 262doc 30263 | DV1 current deviation | Decimal point set by the input range (PV1D/UCD1 per template). | INT32 | CDAB | Read | |||
| IR | 264doc 30265 | MV1 manipulated value | -25.0 to 125.0 %. | INT32 | CDAB | × 0.1 | % | Read | |
| IR | 268doc 30269 | FAULT1 input error status | INT32 | CDAB | Read | 0 = Normal; 1 = Over; 2 = Under | |||
| IR | 784doc 30785 | ALM1 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 786doc 30787 | ALM2 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 788doc 30789 | ALM3 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 790doc 30791 | ALM4 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 792doc 30793 | ALM5 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 794doc 30795 | ALM6 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 796doc 30797 | ALM7 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 798doc 30799 | ALM8 relay status | INT32 | CDAB | Read | 0 = Non-excitation; 1 = Excitation | |||
| IR | 832doc 30833 | ALM1 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 834doc 30835 | ALM2 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 836doc 30837 | ALM3 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 838doc 30839 | ALM4 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 840doc 30841 | ALM5 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 842doc 30843 | ALM6 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 844doc 30845 | ALM7 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 846doc 30847 | ALM8 status | INT32 | CDAB | Read | 0 = OFF; 1 = ON | |||
| IR | 962doc 30963 | Ramp/soak elapsed time | 0-5999 (minutes or seconds). | INT32 | CDAB | Read | |||
| IR | 964doc 30965 | Current pattern No. | 0-30. | INT32 | CDAB | Read | |||
| IR | 966doc 30967 | Pattern No. selected by DI | 0-30. | INT32 | CDAB | Read | |||
| IR | 1024doc 31025 | PV1 measurement value | Decimal point set by the input range (PV1D/UCD1 per template). | INT32 | CDAB | Read | |||
| IR | 1026doc 31027 | PV2 measurement value | Decimal point per PV2D. | INT32 | CDAB | Read | |||
| IR | 1030doc 31031 | AI1 measurement value | Decimal point per AI1D. | INT32 | CDAB | Read | |||
| IR | 1104doc 31105 | AO1 output value | -25.0 to 125.0 %. | INT32 | CDAB | × 0.1 | % | Read | |
| IR | 1106doc 31107 | AO2 output value | -25.0 to 125.0 %. | INT32 | CDAB | × 0.1 | % | Read | |
| IR | 1136doc 31137 | DI1-4 input status | UINT32 | CDAB | Read | bit 12 = DI4; bit 13 = DI3; bit 14 = DI2; bit 15 = DI1 | |||
| IR | 1138doc 31139 | DI11-15 input status | UINT32 | CDAB | Read | bit 11 = DI15; bit 12 = DI14; bit 13 = DI13; bit 14 = DI12; bit 15 = DI11 | |||
| IR | 1232doc 31233 | DO1-4 output status | UINT32 | CDAB | Read | bit 0 = DO1; bit 1 = DO2; bit 2 = DO3; bit 3 = DO4 | |||
| IR | 1234doc 31235 | DO11-15 output status | UINT32 | CDAB | Read | bit 0 = DO11; bit 1 = DO12; bit 2 = DO13; bit 3 = DO14; bit 4 = DO15 | |||
| IR | 1396doc 31397 | MVrb valve aperture monitor | -5.0 to 105.0 %. | INT32 | CDAB | × 0.1 | % | Read |
Notes on this map
- All PXH data are two registers per value; the manual's read and write examples put the lower word first (CDAB). Read both registers in one request.
- Function 04 reads at most 15 registers per request; 03 reads up to 32.
- Holding-register parameters (40001-45001) are not included: their decimal-point table could not be tied to each register with certainty.
- Values carry no decimal point; PV-type values follow the input range decimal point setting.
- Heating/cooling MV (30625-30643), totalizer and timer monitors are omitted.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
What Modbus registers does the Fuji Electric PXH digital controller (Modbus RTU, monitoring map) have?
This map lists 35 registers: 35 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fuji Electric PXH digital controller (Modbus RTU, monitoring map) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed Modicon-style (30259) with the relative wire address beside them (0102H = 30259 - 30001).
What byte order does the Fuji Electric PXH digital controller (Modbus RTU, monitoring map) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Fuji Electric PXH digital controller (Modbus RTU, monitoring map)?
Start with IR 258 PV1 control PV (PV1 (30259)); IR 260 SV1 current setpoint (SV1 (30261)); IR 264 MV1 manipulated value (MV1 (30265)); IR 268 FAULT1 input error status (Input error (30269)); IR 256 PID MODE1 current control mode (Control mode bits (30257)); IR 832 ALM1 status (Alarm 1 status (30833)).
How do I enable Modbus control of the Fuji Electric PXH digital controller (Modbus RTU, monitoring map)?
Set SPD4 (speed), BIT4 (parity) and STN4 (station 0-255; 0 stops communication) for the RS-485 channel on the front keys, then cycle power.
Where is the official Fuji Electric PXH digital controller (Modbus RTU, monitoring map) Modbus documentation?
The source is Digital Controller Communication Functions (MODBUS) Type PXH (INP-TN514207c-E), published free by Fuji Electric at https://americas.fujielectric.com/wp-content/uploads/2018/12/PXH-Digital-Controller-Communication-FunctionsMODBUS-TN514207c-E-.pdf.
More Fuji Electric Modbus register maps
- Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A
All temperature & process controllers Modbus register maps →
Source: Digital Controller Communication Functions (MODBUS) Type PXH · INP-TN514207c-E. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.