Easy Modbus
  1. Home
  2. Modbus register maps
  3. Shinko Technos
  4. JCL-33A digital indicating controller (C5 option)

Sensor (digital temperature controller) · Modbus register map

Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The JCL-33A is a digital indicating temperature controller; with the C5 option it talks Shinko protocol, Modbus ASCII or Modbus RTU over RS485. Every value is a signed 16-bit holding register. This map covers the set value, PID and alarm settings, input type, run/stop, program steps, PV, MV and the status flags.

This page lists 61 Modbus registers for the Shinko Technos JCL-33A digital indicating controller (C5 option) — 54 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
JCL-33A digital indicating controller (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
61 (54 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
JCL-33A-C5, JCL-33A C5
Source document
Communication Instruction Manual JCL-33A (C5) · No.JCL3CE3 · rev. 2018-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos JCL-33A digital indicating controller (C5 option)

Integration in brief

Pick Modbus RTU in Auxiliary function setting mode 1, give each unit a non-zero instrument number, then read PV at 0080H and status at 0085H with function 03; write SV1 at 0001H with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 1SV1INT16Set value SV1Read/write
HR 129OUT1 MVINT16OUT1 manipulated valueRead
HR 133Status flagBITMAP16Output/alarm/error status bitsRead
HR 55ON/OFF (RUN/STOP)INT16Control on/off (run/stop)Read/write
HR 26Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C5 communication option. Set Communication protocol to Modbus RTU (not the Block Read/Write variant) in Auxiliary function setting mode 1, then instrument number, speed, parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

61 of 61 shown
Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV1Main set value. Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HAT perform/cancelINT16Read/write0 = AT cancel; 1 = AT perform
HR4doc 0004HOUT1 proportional bandINT16Read/write
HR5doc 0005HOUT2 proportional bandINT16Read/write
HR6doc 0006HIntegral timeINT16Read/write
HR7doc 0007HDerivative timeINT16Read/write
HR8doc 0008HOUT1 proportional cycleINT16Read/write
HR9doc 0009HOUT2 proportional cycleINT16Read/write
HR10doc 000AHManual resetINT16Read/write
HR11doc 000BHA1 valueAlarm 1 setting. Raw integer; apply the decimal point setting.INT16Read/write
HR12doc 000CHA2 valueAlarm 2 setting. Raw integer; apply the decimal point setting.INT16Read/write
HR18doc 0012HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR21doc 0015HSensor correctionINT16Read/write
HR22doc 0016HOverlap/dead bandINT16Read/write
HR24doc 0018HScaling high limitINT16Read/write
HR25doc 0019HScaling low limitINT16Read/write
HR26doc 001AHDecimal point placeINT16Read/write0 = No decimal point; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR27doc 001BHPV filter time constantINT16Read/write
HR28doc 001CHOUT1 high limitINT16Read/write
HR29doc 001DHOUT1 low limitINT16Read/write
HR30doc 001EHOUT1 ON/OFF hysteresisINT16Read/write
HR34doc 0022HOUT2 ON/OFF hysteresisINT16Read/write
HR35doc 0023HA1 typeChanging the type resets the A1 value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby; 10 = Timer function; 11 = Pattern end output
HR36doc 0024HA2 typeChanging the type resets the A2 value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby; 10 = Timer function; 11 = Pattern end output
HR37doc 0025HA1 hysteresisINT16Read/write
HR38doc 0026HA2 hysteresisINT16Read/write
HR41doc 0029HA1 delay timeINT16Read/write
HR42doc 002AHA2 delay timeINT16Read/write
HR55doc 0037HON/OFF (RUN/STOP)Control output on/off; the manual pairs ON with STOP and OFF with RUN.INT16Read/write0 = ON (STOP); 1 = OFF (RUN)
HR66doc 0042HAlarm HOLD functionINT16Read/write0 = Alarm not holding; 1 = Alarm holding
HR68doc 0044HInput typeINT16Read/write0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC; 31 = 0-20 mA DC; 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC
HR69doc 0045HDirect/reverse actionINT16Read/write0 = Reverse (heating); 1 = Direct (cooling)
HR71doc 0047HAT biasINT16Read/write
HR72doc 0048HARWAnti-reset windup.INT16Read/write
HR111doc 006FHKey lockINT16Read/write0 = Key enabled; 1 = Key locked
HR112doc 0070HKey operation change flag clearingINT16Write0 = No action; 1 = Clear the flag
HR128doc 0080HPVProcess value. Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HOUT1 MVCurrent OUT1 manipulated value; resolution not stated.INT16Read
HR130doc 0082HOUT2 MVCurrent OUT2 manipulated value; resolution not stated.INT16Read
HR131doc 0083HCurrent SVSV in use now. Raw integer; apply the decimal point setting.INT16Read
HR132doc 0084HRunning step remaining timeINT16Read
HR133doc 0085HStatus flagBITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 8 = Overscale; bit 9 = Underscale; bit 10 = 1 = OFF (RUN), 0 = ON (STOP); bit 11 = AT running; bit 12 = OUT/OFF key: 1 = program control, 0 = output on/off; bit 13 = 1 = converter, 0 = controller; bit 15 = Settings changed by keypad
HR134doc 0086HRunning stepINT16Read
HR4368doc 1110HStep 1 SVSame as SV1. Program step set value.INT16Read/write
HR4369doc 1111HStep 1 timeINT16Read/write
HR4384doc 1120HStep 2 SVProgram step set value.INT16Read/write
HR4385doc 1121HStep 2 timeINT16Read/write
HR4400doc 1130HStep 3 SVProgram step set value.INT16Read/write
HR4401doc 1131HStep 3 timeINT16Read/write
HR4416doc 1140HStep 4 SVProgram step set value.INT16Read/write
HR4417doc 1141HStep 4 timeINT16Read/write
HR4432doc 1150HStep 5 SVProgram step set value.INT16Read/write
HR4433doc 1151HStep 5 timeINT16Read/write
HR4448doc 1160HStep 6 SVProgram step set value.INT16Read/write
HR4449doc 1161HStep 6 timeINT16Read/write
HR4464doc 1170HStep 7 SVProgram step set value.INT16Read/write
HR4465doc 1171HStep 7 timeINT16Read/write
HR4480doc 1180HStep 8 SVProgram step set value.INT16Read/write
HR4481doc 1181HStep 8 timeINT16Read/write
HR4496doc 1190HStep 9 SVProgram step set value.INT16Read/write
HR4497doc 1191HStep 9 timeINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos JCL-33A digital indicating controller (C5 option)

What Modbus registers does the Shinko Technos JCL-33A digital indicating controller (C5 option) have?

This map lists 61 registers: 61 holding registers. 54 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos JCL-33A digital indicating controller (C5 option)?

Start with HR 128 PV (Process value); HR 1 SV1 (Set value SV1); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output/alarm/error status bits); HR 55 ON/OFF (RUN/STOP) (Control on/off (run/stop)); HR 26 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos JCL-33A digital indicating controller (C5 option)?

Requires the C5 communication option. Set Communication protocol to Modbus RTU (not the Block Read/Write variant) in Auxiliary function setting mode 1, then instrument number, speed, parity and stop bit.

Where is the official Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual JCL-33A (C5) (No.JCL3CE3), revision 2018-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JCL3CE3.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual JCL-33A (C5) · No.JCL3CE3 · rev. 2018-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.