Sensor (digital temperature controller) · Modbus register map
Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The JCL-33A is a digital indicating temperature controller; with the C5 option it talks Shinko protocol, Modbus ASCII or Modbus RTU over RS485. Every value is a signed 16-bit holding register. This map covers the set value, PID and alarm settings, input type, run/stop, program steps, PV, MV and the status flags.
This page lists 61 Modbus registers for the Shinko Technos JCL-33A digital indicating controller (C5 option) — 54 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- JCL-33A digital indicating controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 61 (54 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- JCL-33A-C5, JCL-33A C5
Integration notes: Shinko Technos JCL-33A digital indicating controller (C5 option)
Pick Modbus RTU in Auxiliary function setting mode 1, give each unit a non-zero instrument number, then read PV at 0080H and status at 0085H with function 03; write SV1 at 0001H with function 06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 1 | SV1 | INT16 | Set value SV1 | Read/write |
| HR 129 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 133 | Status flag | BITMAP16 | Output/alarm/error status bits | Read |
| HR 55 | ON/OFF (RUN/STOP) | INT16 | Control on/off (run/stop) | Read/write |
| HR 26 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5 communication option. Set Communication protocol to Modbus RTU (not the Block Read/Write variant) in Auxiliary function setting mode 1, then instrument number, speed, parity and stop bit.
Byte order & addressing
- Instrument number 0 is the factory default but is the Modbus broadcast address, so set 1-95 before polling.
- Writable registers accept writes even when the keypad set value lock is on.
- ON/OFF register 0037H: 0 = ON (STOP), 1 = OFF (RUN).
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.
- Modbus RTU uses 8 data bits; parity and stop bit are selectable.
- Up to 31 units per RS485 line, 1.2 km maximum.
Watch out for
- Settings are stored in non-volatile memory rated for about 1,000,000 writes; don't write SV cyclically.
- Undefined data items may return random data or errors; use only listed items.
Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV1 | Main set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | AT perform/cancel | INT16 | Read/write | 0 = AT cancel; 1 = AT perform | ||||
| HR | 4doc 0004H | OUT1 proportional band | INT16 | Read/write | |||||
| HR | 5doc 0005H | OUT2 proportional band | INT16 | Read/write | |||||
| HR | 6doc 0006H | Integral time | INT16 | Read/write | |||||
| HR | 7doc 0007H | Derivative time | INT16 | Read/write | |||||
| HR | 8doc 0008H | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 9doc 0009H | OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 10doc 000AH | Manual reset | INT16 | Read/write | |||||
| HR | 11doc 000BH | A1 value | Alarm 1 setting. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 12doc 000CH | A2 value | Alarm 2 setting. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 18doc 0012H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 21doc 0015H | Sensor correction | INT16 | Read/write | |||||
| HR | 22doc 0016H | Overlap/dead band | INT16 | Read/write | |||||
| HR | 24doc 0018H | Scaling high limit | INT16 | Read/write | |||||
| HR | 25doc 0019H | Scaling low limit | INT16 | Read/write | |||||
| HR | 26doc 001AH | Decimal point place | INT16 | Read/write | 0 = No decimal point; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places | ||||
| HR | 27doc 001BH | PV filter time constant | INT16 | Read/write | |||||
| HR | 28doc 001CH | OUT1 high limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | OUT1 low limit | INT16 | Read/write | |||||
| HR | 30doc 001EH | OUT1 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 34doc 0022H | OUT2 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 35doc 0023H | A1 type | Changing the type resets the A1 value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby; 10 = Timer function; 11 = Pattern end output | |||
| HR | 36doc 0024H | A2 type | Changing the type resets the A2 value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby; 10 = Timer function; 11 = Pattern end output | |||
| HR | 37doc 0025H | A1 hysteresis | INT16 | Read/write | |||||
| HR | 38doc 0026H | A2 hysteresis | INT16 | Read/write | |||||
| HR | 41doc 0029H | A1 delay time | INT16 | Read/write | |||||
| HR | 42doc 002AH | A2 delay time | INT16 | Read/write | |||||
| HR | 55doc 0037H | ON/OFF (RUN/STOP) | Control output on/off; the manual pairs ON with STOP and OFF with RUN. | INT16 | Read/write | 0 = ON (STOP); 1 = OFF (RUN) | |||
| HR | 66doc 0042H | Alarm HOLD function | INT16 | Read/write | 0 = Alarm not holding; 1 = Alarm holding | ||||
| HR | 68doc 0044H | Input type | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC; 31 = 0-20 mA DC; 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC | ||||
| HR | 69doc 0045H | Direct/reverse action | INT16 | Read/write | 0 = Reverse (heating); 1 = Direct (cooling) | ||||
| HR | 71doc 0047H | AT bias | INT16 | Read/write | |||||
| HR | 72doc 0048H | ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 111doc 006FH | Key lock | INT16 | Read/write | 0 = Key enabled; 1 = Key locked | ||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear the flag | ||||
| HR | 128doc 0080H | PV | Process value. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | OUT1 MV | Current OUT1 manipulated value; resolution not stated. | INT16 | Read | ||||
| HR | 130doc 0082H | OUT2 MV | Current OUT2 manipulated value; resolution not stated. | INT16 | Read | ||||
| HR | 131doc 0083H | Current SV | SV in use now. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 132doc 0084H | Running step remaining time | INT16 | Read | |||||
| HR | 133doc 0085H | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 8 = Overscale; bit 9 = Underscale; bit 10 = 1 = OFF (RUN), 0 = ON (STOP); bit 11 = AT running; bit 12 = OUT/OFF key: 1 = program control, 0 = output on/off; bit 13 = 1 = converter, 0 = controller; bit 15 = Settings changed by keypad | ||||
| HR | 134doc 0086H | Running step | INT16 | Read | |||||
| HR | 4368doc 1110H | Step 1 SV | Same as SV1. Program step set value. | INT16 | Read/write | ||||
| HR | 4369doc 1111H | Step 1 time | INT16 | Read/write | |||||
| HR | 4384doc 1120H | Step 2 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4385doc 1121H | Step 2 time | INT16 | Read/write | |||||
| HR | 4400doc 1130H | Step 3 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4401doc 1131H | Step 3 time | INT16 | Read/write | |||||
| HR | 4416doc 1140H | Step 4 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4417doc 1141H | Step 4 time | INT16 | Read/write | |||||
| HR | 4432doc 1150H | Step 5 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4433doc 1151H | Step 5 time | INT16 | Read/write | |||||
| HR | 4448doc 1160H | Step 6 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4449doc 1161H | Step 6 time | INT16 | Read/write | |||||
| HR | 4464doc 1170H | Step 7 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4465doc 1171H | Step 7 time | INT16 | Read/write | |||||
| HR | 4480doc 1180H | Step 8 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4481doc 1181H | Step 8 time | INT16 | Read/write | |||||
| HR | 4496doc 1190H | Step 9 SV | Program step set value. | INT16 | Read/write | ||||
| HR | 4497doc 1191H | Step 9 time | INT16 | Read/write |
Notes on this map
- This map is for the plain 'Modbus RTU mode' / 'Modbus ASCII mode' protocol setting. The 'Block Read/Write available' protocol settings use a different register layout (section 7.2 of the manual) and are not covered here.
- All data are 16-bit; negatives are two's complement. Values with a decimal point are sent as whole numbers, so apply the decimal point place (001AH) or the input type range.
- Units of PID times, cycles and MV are not printed in the command table; they match the keypad settings described in the main instruction manual.
- Protocol, instrument number, speed, parity and stop bit can only be set from the keypad, not over Modbus.
- Writes during keypad setting mode return exception 18 (12H); writes the unit cannot accept now (e.g. during AT) return exception 17 (11H).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos JCL-33A digital indicating controller (C5 option)
What Modbus registers does the Shinko Technos JCL-33A digital indicating controller (C5 option) have?
This map lists 61 registers: 61 holding registers. 54 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos JCL-33A digital indicating controller (C5 option)?
Start with HR 128 PV (Process value); HR 1 SV1 (Set value SV1); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output/alarm/error status bits); HR 55 ON/OFF (RUN/STOP) (Control on/off (run/stop)); HR 26 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos JCL-33A digital indicating controller (C5 option)?
Requires the C5 communication option. Set Communication protocol to Modbus RTU (not the Block Read/Write variant) in Auxiliary function setting mode 1, then instrument number, speed, parity and stop bit.
Where is the official Shinko Technos JCL-33A digital indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual JCL-33A (C5) (No.JCL3CE3), revision 2018-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JCL3CE3.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual JCL-33A (C5) · No.JCL3CE3 · rev. 2018-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.