Sensor (digital temperature controller) · Modbus register map

Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus register map

Updated 17 November 2026

Short answer

The ACS2 is a Shinko PID temperature controller with SV memories, program control and several PID modes. With the C5/C5W option it speaks Shinko protocol, Modbus RTU or MC protocol on RS485; all items are 16-bit holding registers. This map covers SV memories, input setup, EV1 alarm handling, control mode and key function settings, and the full read block from 03E8H (PV, MV, SV, status, error and heater current).

This page lists 47 Modbus registers for the Shinko Technos ACS2 digital indicating controller (C5, C5W options) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
ACS2 digital indicating controller (C5, C5W options)
Equipment type
Sensor (digital temperature controller)
Registers
47 (31 writable)
Transport
Modbus RTU
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
ACS2-C5, ACS2-C5W
Source document
Communication Instruction Manual ACS2 (C5W, C5) · No. ACS2CE3 · rev. 2026-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos ACS2 digital indicating controller (C5, C5W options)

Integration in brief

In the Communication setting group choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Poll PV 03E8H, OUT1 MV 03E9H, status 03ECH/03EDH and errors 03F5H; write SV1 at 0001H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1000PVINT16Process valueRead
HR 1SV1 settingINT16Set value SV1Read/write
HR 1001OUT1 MVINT16OUT1 manipulated valueRead
HR 1004Status flag 1BITMAP16Output and alarm statusRead
HR 1013Error status flagBITMAP16Error statusRead
HR 1005Status flag 2BITMAP16Run mode statusRead

Enable Modbus control & writes

Requires the C5 or C5W option. In RUN mode step through the setting groups to the Communication setting group and enter it (keys shown on p. 4), set Communication protocol to MODBUS RTU mode, then instrument number, speed, data bit/parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

47 of 47 shown
Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV1 settingSet value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR2doc 0002HSV2 settingSet value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HSV3 settingSet value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR4doc 0004HSV4 settingSet value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR5doc 0005HSV5 settingSet value memory 5. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR6doc 0006HSV6 settingSet value memory 6. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR7doc 0007HSV7 settingSet value memory 7. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR8doc 0008HSV8 settingSet value memory 8. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR32doc 0020HInput type selectionINT16Read/write0 = K -200 to 1370 C; 1 = K -200.0 to 800.0 C; 2 = K -200.0 to 400.0 C; 3 = J -200 to 1000 C; 4 = J -200.0 to 400.0 C; 5 = R 0 to 1760 C; 6 = S 0 to 1760 C; 7 = B 0 to 1820 C; 8 = E -200 to 800 C; 9 = T -200.0 to 400.0 C; 10 = N -200 to 1300 C; 11 = PL-II 0 to 1390 C; 12 = C (W/Re5-26) 0 to 2315 C; 13 = Pt100 -200.0 to 850.0 C; 14 = Pt100 -200 to 850 C; 15 = Pt100 -100.0 to 100.0 C; 16 = 4-20 mA DC (built-in shunt); 17 = 0-20 mA DC (built-in shunt); 18 = 4-20 mA DC (external shunt); 19 = 0-20 mA DC (external shunt); 20 = 0-1 V DC; 21 = 0-5 V DC; 22 = 1-5 V DC; 23 = 0-10 V DC
HR33doc 0021HTemperature unit selectionINT16Read/write0 = Celsius; 1 = Fahrenheit
HR34doc 0022HScaling high limit settingDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR35doc 0023HScaling low limit settingDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR81doc 0051HEV1 enabled/disabled when alarm set to 0INT16Read/write0 = Disabled; 1 = Enabled
HR82doc 0052HEV1 hysteresis settingDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR83doc 0053HEV1 action delay timer settingINT16Read/write
HR84doc 0054HEV1 action energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR85doc 0055HEV1 output latch selectionINT16Read/write0 = Disabled; 1 = Enabled
HR86doc 0056HTS1 output step numberINT16Read/write
HR87doc 0057HTS1 OFF time settingINT16Read/write
HR88doc 0058HTS1 ON time settingINT16Read/write
HR176doc 00B0HControl action selectionINT16Read/write0 = 2DOF PID; 1 = Fast-PID; 2 = Slow-PID; 3 = Gap-PID
HR184doc 00B8HIntegral/derivative decimal pointINT16Read/write0 = No decimal point; 1 = With decimal point
HR192doc 00C0HSet value lock selectionINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2
HR193doc 00C1HSV rise/fall rate action selectionINT16Read/write0 = SV start; 1 = PV start
HR194doc 00C2HSV rise/fall rate time unitINT16Read/write0 = Minutes; 1 = Seconds
HR195doc 00C3HSV rise rate settingDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR196doc 00C4HSV fall rate settingDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR198doc 00C6HSV display method selectionINT16Read/write0 = Set target value; 1 = Target value during ramp/program
HR199doc 00C7HIndication when control output OFFINT16Read/write0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV indication + any alarm active
HR200doc 00C8HOUT/OFF key function selectionINT16Read/write0 = No function; 1 = Auto/Manual control; 2 = Control output OFF function; 3 = Remote/Local selection; 4 = RUN/STOP (program control)
HR201doc 00C9HPF key function selectionINT16Read/write0 = No function; 1 = Auto/Manual control; 2 = Control output OFF function; 3 = Remote/Local selection; 4 = RUN/STOP (program control)
HR1000doc 03E8HPVProcess value. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1001doc 03E9HOUT1 MVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1002doc 03EAHOUT2 MVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1003doc 03EBHCurrent SVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1004doc 03ECHStatus flag 1BITMAP16Readbit 0 = OUT1 output on; bit 1 = OUT2 output on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 4 = EV3 output on; bit 10 = Operating terminal short-circuit alarm; bit 11 = Heater burnout alarm; bit 12 = Loop break alarm; bit 13 = Input high limit alarm; bit 14 = Input low limit alarm; bit 15 = Settings changed by keypad
HR1005doc 03EDHStatus flag 2BITMAP16Readbit 0 = Warm-up; bit 1 = E1 input on; bit 2 = E2 input on; bit 3 = E3 input on; bit 4 = E4 input on; bit 5 = USB power (0 = instrument power); bit 7 = Control permitted; bit 8 = AT running; bit 9 = Manual control; bit 10 = Remote; bit 11 = Program control mode; bit 12 = Program running; bit 13 = Wait function on; bit 14 = Hold function on; bit 15 = Pattern end function on
HR1006doc 03EEHCT1 current valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1007doc 03EFHCT2 current valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1008doc 03F0HAmbient temperatureDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR1009doc 03F1HSetting value memory numberINT16Read
HR1010doc 03F2HProgram operation step numberINT16Read
HR1011doc 03F3HProgram operation remaining timeINT16Read
HR1012doc 03F4HProgram operation number of repetitionsINT16Read
HR1013doc 03F5HError status flagBITMAP16Readbit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 4 = Heater burnout alarm; bit 5 = Operation terminal short-circuit alarm; bit 6 = Loop break alarm; bit 7 = Sensor error; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Cold junction error; bit 11 = Non-volatile IC memory error; bit 12 = Hardware error
HR1020doc 03FCHEVT input displayINT16Read
HR1021doc 03FDHKey operation change item readingData item last changed from the keypad.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos ACS2 digital indicating controller (C5, C5W options)

What Modbus registers does the Shinko Technos ACS2 digital indicating controller (C5, C5W options) have?

This map lists 47 registers: 47 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos ACS2 digital indicating controller (C5, C5W options)?

Start with HR 1000 PV (Process value); HR 1 SV1 setting (Set value SV1); HR 1001 OUT1 MV (OUT1 manipulated value); HR 1004 Status flag 1 (Output and alarm status); HR 1013 Error status flag (Error status); HR 1005 Status flag 2 (Run mode status).

How do I enable Modbus control of the Shinko Technos ACS2 digital indicating controller (C5, C5W options)?

Requires the C5 or C5W option. In RUN mode step through the setting groups to the Communication setting group and enter it (keys shown on p. 4), set Communication protocol to MODBUS RTU mode, then instrument number, speed, data bit/parity and stop bit.

Where is the official Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus documentation?

The source is Communication Instruction Manual ACS2 (C5W, C5) (No. ACS2CE3), revision 2026-08, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACS2CE3.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual ACS2 (C5W, C5) · No. ACS2CE3 · rev. 2026-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.