- Home
- Modbus register maps
- Shinko Technos
- ACS2 digital indicating controller (C5, C5W options)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus register map
Updated 17 November 2026
The ACS2 is a Shinko PID temperature controller with SV memories, program control and several PID modes. With the C5/C5W option it speaks Shinko protocol, Modbus RTU or MC protocol on RS485; all items are 16-bit holding registers. This map covers SV memories, input setup, EV1 alarm handling, control mode and key function settings, and the full read block from 03E8H (PV, MV, SV, status, error and heater current).
This page lists 47 Modbus registers for the Shinko Technos ACS2 digital indicating controller (C5, C5W options) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- ACS2 digital indicating controller (C5, C5W options)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 47 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ACS2-C5, ACS2-C5W
Integration notes: Shinko Technos ACS2 digital indicating controller (C5, C5W options)
In the Communication setting group choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Poll PV 03E8H, OUT1 MV 03E9H, status 03ECH/03EDH and errors 03F5H; write SV1 at 0001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1000 | PV | INT16 | Process value | Read |
| HR 1 | SV1 setting | INT16 | Set value SV1 | Read/write |
| HR 1001 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 1004 | Status flag 1 | BITMAP16 | Output and alarm status | Read |
| HR 1013 | Error status flag | BITMAP16 | Error status | Read |
| HR 1005 | Status flag 2 | BITMAP16 | Run mode status | Read |
Enable Modbus control & writes
Requires the C5 or C5W option. In RUN mode step through the setting groups to the Communication setting group and enter it (keys shown on p. 4), set Communication protocol to MODBUS RTU mode, then instrument number, speed, data bit/parity and stop bit.
Byte order & addressing
- Factory data format is 7 bits/Even; Modbus RTU needs an 8-bit choice.
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
- Modbus ASCII is not offered on this model; protocols are Shinko, MODBUS RTU, MC protocol and SVTC.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even.
- Speeds 9600 to 115200 bps.
Watch out for
- Data clear (00D8H) also resets communication settings, so the unit may stop answering with the current master settings.
Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV1 setting | Set value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 2doc 0002H | SV2 setting | Set value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | SV3 setting | Set value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 4doc 0004H | SV4 setting | Set value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 5doc 0005H | SV5 setting | Set value memory 5. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 6doc 0006H | SV6 setting | Set value memory 6. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 7doc 0007H | SV7 setting | Set value memory 7. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 8doc 0008H | SV8 setting | Set value memory 8. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 32doc 0020H | Input type selection | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -200.0 to 800.0 C; 2 = K -200.0 to 400.0 C; 3 = J -200 to 1000 C; 4 = J -200.0 to 400.0 C; 5 = R 0 to 1760 C; 6 = S 0 to 1760 C; 7 = B 0 to 1820 C; 8 = E -200 to 800 C; 9 = T -200.0 to 400.0 C; 10 = N -200 to 1300 C; 11 = PL-II 0 to 1390 C; 12 = C (W/Re5-26) 0 to 2315 C; 13 = Pt100 -200.0 to 850.0 C; 14 = Pt100 -200 to 850 C; 15 = Pt100 -100.0 to 100.0 C; 16 = 4-20 mA DC (built-in shunt); 17 = 0-20 mA DC (built-in shunt); 18 = 4-20 mA DC (external shunt); 19 = 0-20 mA DC (external shunt); 20 = 0-1 V DC; 21 = 0-5 V DC; 22 = 1-5 V DC; 23 = 0-10 V DC | ||||
| HR | 33doc 0021H | Temperature unit selection | INT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | ||||
| HR | 34doc 0022H | Scaling high limit setting | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 35doc 0023H | Scaling low limit setting | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 81doc 0051H | EV1 enabled/disabled when alarm set to 0 | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 82doc 0052H | EV1 hysteresis setting | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 83doc 0053H | EV1 action delay timer setting | INT16 | Read/write | |||||
| HR | 84doc 0054H | EV1 action energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 85doc 0055H | EV1 output latch selection | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 86doc 0056H | TS1 output step number | INT16 | Read/write | |||||
| HR | 87doc 0057H | TS1 OFF time setting | INT16 | Read/write | |||||
| HR | 88doc 0058H | TS1 ON time setting | INT16 | Read/write | |||||
| HR | 176doc 00B0H | Control action selection | INT16 | Read/write | 0 = 2DOF PID; 1 = Fast-PID; 2 = Slow-PID; 3 = Gap-PID | ||||
| HR | 184doc 00B8H | Integral/derivative decimal point | INT16 | Read/write | 0 = No decimal point; 1 = With decimal point | ||||
| HR | 192doc 00C0H | Set value lock selection | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2 | ||||
| HR | 193doc 00C1H | SV rise/fall rate action selection | INT16 | Read/write | 0 = SV start; 1 = PV start | ||||
| HR | 194doc 00C2H | SV rise/fall rate time unit | INT16 | Read/write | 0 = Minutes; 1 = Seconds | ||||
| HR | 195doc 00C3H | SV rise rate setting | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 196doc 00C4H | SV fall rate setting | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 198doc 00C6H | SV display method selection | INT16 | Read/write | 0 = Set target value; 1 = Target value during ramp/program | ||||
| HR | 199doc 00C7H | Indication when control output OFF | INT16 | Read/write | 0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV indication + any alarm active | ||||
| HR | 200doc 00C8H | OUT/OFF key function selection | INT16 | Read/write | 0 = No function; 1 = Auto/Manual control; 2 = Control output OFF function; 3 = Remote/Local selection; 4 = RUN/STOP (program control) | ||||
| HR | 201doc 00C9H | PF key function selection | INT16 | Read/write | 0 = No function; 1 = Auto/Manual control; 2 = Control output OFF function; 3 = Remote/Local selection; 4 = RUN/STOP (program control) | ||||
| HR | 1000doc 03E8H | PV | Process value. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1001doc 03E9H | OUT1 MV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1002doc 03EAH | OUT2 MV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1003doc 03EBH | Current SV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1004doc 03ECH | Status flag 1 | BITMAP16 | Read | bit 0 = OUT1 output on; bit 1 = OUT2 output on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 4 = EV3 output on; bit 10 = Operating terminal short-circuit alarm; bit 11 = Heater burnout alarm; bit 12 = Loop break alarm; bit 13 = Input high limit alarm; bit 14 = Input low limit alarm; bit 15 = Settings changed by keypad | ||||
| HR | 1005doc 03EDH | Status flag 2 | BITMAP16 | Read | bit 0 = Warm-up; bit 1 = E1 input on; bit 2 = E2 input on; bit 3 = E3 input on; bit 4 = E4 input on; bit 5 = USB power (0 = instrument power); bit 7 = Control permitted; bit 8 = AT running; bit 9 = Manual control; bit 10 = Remote; bit 11 = Program control mode; bit 12 = Program running; bit 13 = Wait function on; bit 14 = Hold function on; bit 15 = Pattern end function on | ||||
| HR | 1006doc 03EEH | CT1 current value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1007doc 03EFH | CT2 current value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1008doc 03F0H | Ambient temperature | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 1009doc 03F1H | Setting value memory number | INT16 | Read | |||||
| HR | 1010doc 03F2H | Program operation step number | INT16 | Read | |||||
| HR | 1011doc 03F3H | Program operation remaining time | INT16 | Read | |||||
| HR | 1012doc 03F4H | Program operation number of repetitions | INT16 | Read | |||||
| HR | 1013doc 03F5H | Error status flag | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 4 = Heater burnout alarm; bit 5 = Operation terminal short-circuit alarm; bit 6 = Loop break alarm; bit 7 = Sensor error; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Cold junction error; bit 11 = Non-volatile IC memory error; bit 12 = Hardware error | ||||
| HR | 1020doc 03FCH | EVT input display | INT16 | Read | |||||
| HR | 1021doc 03FDH | Key operation change item reading | Data item last changed from the keypad. | INT16 | Read |
Notes on this map
- Only a subset of the setting table is mapped: PID terms, EV2/EV3, output and many other setting items on pp. 22-27 are left out, as are program pattern commands (section 7.1.3 onward).
- All data are 16-bit two's complement. Items marked 'decimal point ignored' are whole numbers; apply the decimal point of the input range.
- Error status flag (03F5H): the manual states 0 = normal, 1 = error only for bit 11; the other bits are listed without a polarity legend.
- Writing data clear (00D8H) restores factory settings including communication settings; not mapped here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos ACS2 digital indicating controller (C5, C5W options)
What Modbus registers does the Shinko Technos ACS2 digital indicating controller (C5, C5W options) have?
This map lists 47 registers: 47 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos ACS2 digital indicating controller (C5, C5W options)?
Start with HR 1000 PV (Process value); HR 1 SV1 setting (Set value SV1); HR 1001 OUT1 MV (OUT1 manipulated value); HR 1004 Status flag 1 (Output and alarm status); HR 1013 Error status flag (Error status); HR 1005 Status flag 2 (Run mode status).
How do I enable Modbus control of the Shinko Technos ACS2 digital indicating controller (C5, C5W options)?
Requires the C5 or C5W option. In RUN mode step through the setting groups to the Communication setting group and enter it (keys shown on p. 4), set Communication protocol to MODBUS RTU mode, then instrument number, speed, data bit/parity and stop bit.
Where is the official Shinko Technos ACS2 digital indicating controller (C5, C5W options) Modbus documentation?
The source is Communication Instruction Manual ACS2 (C5W, C5) (No. ACS2CE3), revision 2026-08, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACS2CE3.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9 - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual ACS2 (C5W, C5) · No. ACS2CE3 · rev. 2026-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.