Sensor (digital temperature controller) · Modbus register map

Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The JCx-33A series are PID temperature controllers sharing one command set. With the C5 option they speak Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and every item is a signed 16-bit holding register. The map covers SV and limits, PID, alarm, heater burnout and loop break settings, auto/manual and output OFF, PV, MV and the status word.

This page lists 50 Modbus registers for the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
50 (46 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A
Source document
Communication Instruction Manual JCS, JCM, JCR, JCD-33A (C5) · No.JC3CE11 · rev. 2013-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)

Integration in brief

Set Communication protocol to Modbus RTU in Auxiliary function setting mode 1 and give the unit a non-zero instrument number; then poll PV 0080H, OUT1 MV 0081H and status 0085H and write SV1 at 0001H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 1SV1INT16Set value SV1Read/write
HR 129OUT1 MVINT16OUT1 manipulated valueRead
HR 133Status flagBITMAP16Output, alarm and error statusRead
HR 55Control output OFFINT16Control output OFFRead/write
HR 26Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C5 option. Enter Auxiliary function setting mode 1 by holding the key pair shown on p. 2 for about 3 s, press the advance key 4 times to reach Communication protocol, and choose Modbus RTU; then set instrument number, speed, parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV1Set value. Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HAT/Auto-resetINT16Read/write0 = Cancel; 1 = Perform
HR4doc 0004HOUT1 proportional bandINT16Read/write
HR5doc 0005HOUT2 proportional bandINT16Read/write
HR6doc 0006HIntegral timeINT16Read/write
HR7doc 0007HDerivative timeINT16Read/write
HR8doc 0008HOUT1 proportional cycleINT16Read/write
HR9doc 0009HOUT2 proportional cycleINT16Read/write
HR11doc 000BHA1 valueRaw integer; apply the decimal point setting.INT16Read/write
HR12doc 000CHA2 valueRaw integer; apply the decimal point setting.INT16Read/write
HR15doc 000FHHeater burnout alarm valueINT16Read/write
HR16doc 0010HLoop break alarm timeINT16Read/write
HR17doc 0011HLoop break alarm spanINT16Read/write
HR18doc 0012HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR19doc 0013HSV high limitRaw integer; apply the decimal point setting.INT16Read/write
HR20doc 0014HSV low limitRaw integer; apply the decimal point setting.INT16Read/write
HR21doc 0015HSensor correction valueINT16Read/write
HR22doc 0016HOverlap/dead bandINT16Read/write
HR24doc 0018HScaling high limitINT16Read/write
HR25doc 0019HScaling low limitINT16Read/write
HR26doc 001AHDecimal point placeINT16Read/write0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX
HR27doc 001BHPV filter time constantINT16Read/write
HR28doc 001CHOUT1 high limitINT16Read/write
HR29doc 001DHOUT1 low limitINT16Read/write
HR30doc 001EHOUT1 ON/OFF hysteresisINT16Read/write
HR31doc 001FHOUT2 action modeINT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR32doc 0020HOUT2 high limitINT16Read/write
HR33doc 0021HOUT2 low limitINT16Read/write
HR34doc 0022HOUT2 ON/OFF hysteresisINT16Read/write
HR35doc 0023HA1 typeChanging it resets the A1 value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR36doc 0024HA2 typeChanging it resets the A2 value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR37doc 0025HA1 hysteresisINT16Read/write
HR38doc 0026HA2 hysteresisINT16Read/write
HR41doc 0029HA1 action delay timeINT16Read/write
HR42doc 002AHA2 action delay timeINT16Read/write
HR55doc 0037HControl output OFFINT16Read/write0 = ON; 1 = OFF
HR56doc 0038HAuto/manual controlINT16Read/write0 = Automatic control; 1 = Manual control
HR57doc 0039HManual control MVINT16Read/write
HR64doc 0040HA1 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR65doc 0041HA2 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR68doc 0044HInput typeChanging it re-initialises SV, PID, alarm values etc.INT16Read/write0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC; 31 = 0-20 mA DC; 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC
HR69doc 0045HDirect/reverse actionINT16Read/write0 = Heating (reverse); 1 = Cooling (direct)
HR71doc 0047HAT biasINT16Read/write
HR72doc 0048HARWAnti-reset windup.INT16Read/write
HR111doc 006FHKey lockINT16Read/write0 = Key enabled; 1 = Key locked
HR112doc 0070HKey operation change flag clearingINT16Write0 = No action; 1 = Clear all
HR128doc 0080HPVProcess value. Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HOUT1 MVINT16Read
HR130doc 0082HOUT2 MVINT16Read
HR133doc 0085HStatus flagBITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 6 = Heater burnout alarm output; bit 7 = Loop break alarm output; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Control output OFF; bit 11 = AT/Auto-reset running; bit 12 = OUT/OFF key = auto/manual (0 = output OFF); bit 14 = Manual control; bit 15 = Settings changed by keypad

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)

What Modbus registers does the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) have?

This map lists 50 registers: 50 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)?

Start with HR 128 PV (Process value); HR 1 SV1 (Set value SV1); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output, alarm and error status); HR 55 Control output OFF (Control output OFF); HR 26 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)?

Requires the C5 option. Enter Auxiliary function setting mode 1 by holding the key pair shown on p. 2 for about 3 s, press the advance key 4 times to reach Communication protocol, and choose Modbus RTU; then set instrument number, speed, parity and stop bit.

Where is the official Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual JCS, JCM, JCR, JCD-33A (C5) (No.JC3CE11), revision 2013-01, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JC3CE11.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual JCS, JCM, JCR, JCD-33A (C5) · No.JC3CE11 · rev. 2013-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.