Sensor (digital temperature controller) · Modbus register map
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The JCx-33A series are PID temperature controllers sharing one command set. With the C5 option they speak Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and every item is a signed 16-bit holding register. The map covers SV and limits, PID, alarm, heater burnout and loop break settings, auto/manual and output OFF, PV, MV and the status word.
This page lists 50 Modbus registers for the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 50 (46 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A
Integration notes: Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Set Communication protocol to Modbus RTU in Auxiliary function setting mode 1 and give the unit a non-zero instrument number; then poll PV 0080H, OUT1 MV 0081H and status 0085H and write SV1 at 0001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 1 | SV1 | INT16 | Set value SV1 | Read/write |
| HR 129 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 133 | Status flag | BITMAP16 | Output, alarm and error status | Read |
| HR 55 | Control output OFF | INT16 | Control output OFF | Read/write |
| HR 26 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5 option. Enter Auxiliary function setting mode 1 by holding the key pair shown on p. 2 for about 3 s, press the advance key 4 times to reach Communication protocol, and choose Modbus RTU; then set instrument number, speed, parity and stop bit.
Byte order & addressing
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
- Send alarm type before alarm value and input type before other settings, because changing them resets dependent values.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.
- Speeds 2400, 4800, 9600, 19200 bps; no terminator needed, the unit has built-in pull-up/pull-down resistors.
Watch out for
- Clearing the key-change flag during keypad setting mode returns exception 18 (12H).
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV1 | Set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | AT/Auto-reset | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 4doc 0004H | OUT1 proportional band | INT16 | Read/write | |||||
| HR | 5doc 0005H | OUT2 proportional band | INT16 | Read/write | |||||
| HR | 6doc 0006H | Integral time | INT16 | Read/write | |||||
| HR | 7doc 0007H | Derivative time | INT16 | Read/write | |||||
| HR | 8doc 0008H | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 9doc 0009H | OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 11doc 000BH | A1 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 12doc 000CH | A2 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 15doc 000FH | Heater burnout alarm value | INT16 | Read/write | |||||
| HR | 16doc 0010H | Loop break alarm time | INT16 | Read/write | |||||
| HR | 17doc 0011H | Loop break alarm span | INT16 | Read/write | |||||
| HR | 18doc 0012H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 19doc 0013H | SV high limit | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 20doc 0014H | SV low limit | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 21doc 0015H | Sensor correction value | INT16 | Read/write | |||||
| HR | 22doc 0016H | Overlap/dead band | INT16 | Read/write | |||||
| HR | 24doc 0018H | Scaling high limit | INT16 | Read/write | |||||
| HR | 25doc 0019H | Scaling low limit | INT16 | Read/write | |||||
| HR | 26doc 001AH | Decimal point place | INT16 | Read/write | 0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX | ||||
| HR | 27doc 001BH | PV filter time constant | INT16 | Read/write | |||||
| HR | 28doc 001CH | OUT1 high limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | OUT1 low limit | INT16 | Read/write | |||||
| HR | 30doc 001EH | OUT1 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 31doc 001FH | OUT2 action mode | INT16 | Read/write | 0 = Air cooling; 1 = Oil cooling; 2 = Water cooling | ||||
| HR | 32doc 0020H | OUT2 high limit | INT16 | Read/write | |||||
| HR | 33doc 0021H | OUT2 low limit | INT16 | Read/write | |||||
| HR | 34doc 0022H | OUT2 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 35doc 0023H | A1 type | Changing it resets the A1 value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 36doc 0024H | A2 type | Changing it resets the A2 value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 37doc 0025H | A1 hysteresis | INT16 | Read/write | |||||
| HR | 38doc 0026H | A2 hysteresis | INT16 | Read/write | |||||
| HR | 41doc 0029H | A1 action delay time | INT16 | Read/write | |||||
| HR | 42doc 002AH | A2 action delay time | INT16 | Read/write | |||||
| HR | 55doc 0037H | Control output OFF | INT16 | Read/write | 0 = ON; 1 = OFF | ||||
| HR | 56doc 0038H | Auto/manual control | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 57doc 0039H | Manual control MV | INT16 | Read/write | |||||
| HR | 64doc 0040H | A1 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 65doc 0041H | A2 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 68doc 0044H | Input type | Changing it re-initialises SV, PID, alarm values etc. | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC; 31 = 0-20 mA DC; 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC | |||
| HR | 69doc 0045H | Direct/reverse action | INT16 | Read/write | 0 = Heating (reverse); 1 = Cooling (direct) | ||||
| HR | 71doc 0047H | AT bias | INT16 | Read/write | |||||
| HR | 72doc 0048H | ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 111doc 006FH | Key lock | INT16 | Read/write | 0 = Key enabled; 1 = Key locked | ||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear all | ||||
| HR | 128doc 0080H | PV | Process value. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | OUT1 MV | INT16 | Read | |||||
| HR | 130doc 0082H | OUT2 MV | INT16 | Read | |||||
| HR | 133doc 0085H | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 6 = Heater burnout alarm output; bit 7 = Loop break alarm output; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Control output OFF; bit 11 = AT/Auto-reset running; bit 12 = OUT/OFF key = auto/manual (0 = output OFF); bit 14 = Manual control; bit 15 = Settings changed by keypad |
Notes on this map
- All data are 16-bit two's complement. Values with a decimal point are sent as whole numbers; apply the decimal point place (001AH).
- Units of PID times, cycles and MV are not printed in the command table.
- PID values are updated after AT ends; read them once status bit 11 returns to 0.
- Protocol, instrument number, speed, parity and stop bit are keypad-only settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
What Modbus registers does the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) have?
This map lists 50 registers: 50 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)?
Start with HR 128 PV (Process value); HR 1 SV1 (Set value SV1); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output, alarm and error status); HR 55 Control output OFF (Control output OFF); HR 26 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)?
Requires the C5 option. Enter Auxiliary function setting mode 1 by holding the key pair shown on p. 2 for about 3 s, press the advance key 4 times to reach Communication protocol, and choose Modbus RTU; then set instrument number, speed, parity and stop bit.
Where is the official Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual JCS, JCM, JCR, JCD-33A (C5) (No.JC3CE11), revision 2013-01, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JC3CE11.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual JCS, JCM, JCR, JCD-33A (C5) · No.JC3CE11 · rev. 2013-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.