Sensor / counter-timer (programmable counter and timer) · Modbus register map
Autonics CT series programmable counter / timer (Modbus RTU) Modbus register map
Updated 17 November 2026
Panel-mount programmable counter/timer with Modbus RTU. Coils and discrete inputs give outputs, reset and terminal inputs; input registers give model info, LED status, present value and preset values; holding registers set presets, counter and timer configuration and communication settings.
This page lists 53 Modbus registers for the Autonics CT series programmable counter / timer (Modbus RTU) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Autonics’s own free documentation (linked below) and checked against it.
- Manufacturer
- Autonics
- Model
- CT series programmable counter / timer (Modbus RTU)
- Equipment type
- Sensor / counter-timer (programmable counter and timer)
- Registers
- 53 (32 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4
Integration notes: Autonics CT series programmable counter / timer (Modbus RTU)
Read input registers 301001-301013 in one FC04 request for LED status, present value and presets; write presets at 400001-400006 and use coil 0 (FC05 FF00) to reset.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1003 | Present value of counter/timer | INT32 CDAB | Present value | Read |
| IR 1000 | LED display status | BITMAP16 | Output/LED status | Read |
| HR 0 | PRESET2 (PRESET) setting value | UINT32 CDAB | PRESET2 setpoint | Read/write |
| HR 2 | PRESET1 setting value | UINT32 CDAB | PRESET1 setpoint | Read/write |
| CO 0 | Reset | BIT | Reset | Read/write |
| IR 1005 | Display unit | UINT16 | Decimal point / time range | Read |
Enable Modbus control & writes
Set communication writing [COmW] (400156) to Enabled to allow Modbus writes; address, speed, parity and stop bits are in the communication group (also on the front panel).
Byte order & addressing
- 32-bit values are low word first.
- The bracketed hex number is the wire address; the 6-digit number is a reference only.
Network setup
- Address 1..127, 2400-38400 bps, parity and stop bits set in the communication group.
- Response waiting time 5..99 ms (RSwT).
Watch out for
- Writing counter/timer group settings resets the count.
Autonics CT series programmable counter / timer (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 000001 (0000) | Reset | Write ON (FF00) with FC05 to reset. | BIT | Read/write | 0 = OFF; 1 = ON | |||
| CO | 1doc 000002 (0001) | OUT2 output | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 2doc 000003 (0002) | OUT1 output | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 3doc 000004 (0003) | BATCH output | BATCH-output models only. | BIT | Read | 0 = OFF; 1 = ON | |||
| CO | 4doc 000005 (0004) | BATCH reset | FC05 FF00 resets the batch counter (BATCH models). | BIT | Read/write | 0 = OFF; 1 = ON | |||
| DI | 0doc 100001 (0000) | INA input status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 1doc 100002 (0001) | INB input status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 2doc 100003 (0002) | INHIBIT input status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 3doc 100004 (0003) | RESET input status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 4doc 100005 (0004) | BATCH RESET input status | BIT | Read | 0 = OFF; 1 = ON | ||||
| IR | 100doc 300101 (0064) | Product number H | Model ID, high word. | UINT16 | Read | ||||
| IR | 101doc 300102 (0065) | Product number L | Model ID, low word. | UINT16 | Read | ||||
| IR | 102doc 300103 (0066) | Hardware version | UINT16 | Read | |||||
| IR | 103doc 300104 (0067) | Software version | UINT16 | Read | |||||
| IR | 104doc 300105-300108 (0068-006B) | Model name | ASCII model text, e.g. 'CT6M-2PT'. | STRING[8] | Read | ||||
| IR | 1000doc 301001 (03E8) | LED display status | BITMAP16 | Read | bit 5 = BA.O; bit 6 = OUT2; bit 7 = OUT1; bit 10 = BA.S; bit 11 = LOCK; bit 12 = PRESET2; bit 13 = PRESET1; bit 14 = TMR; bit 15 = CNT | ||||
| IR | 1001doc 301002-301003 (03E9-03EA) | Present value of BATCH counter | 0..999999. BATCH-output models. | UINT32 | CDAB | Read | |||
| IR | 1003doc 301004-301005 (03EB-03EC) | Present value of counter/timer | Display count; decimal point per register 301006 / 400058. | INT32 | CDAB | Read | |||
| IR | 1005doc 301006 (03ED) | Display unit | Counter: decimal point code (400058); timer: time range (400102). | UINT16 | Read | ||||
| IR | 1006doc 301007-301008 (03EE-03EF) | PRESET2 (PRESET) setting value | INT32 | CDAB | Read | ||||
| IR | 1008doc 301009-301010 (03F0-03F1) | PRESET1 setting value | INT32 | CDAB | Read | ||||
| IR | 1010doc 301011-301012 (03F2-03F3) | Setting value of BATCH counter | 0..999999. | UINT32 | CDAB | Read | |||
| IR | 1012doc 301013 (03F4) | Checking the input logic | UINT16 | Read | 0 = NPN; 1 = PNP | ||||
| HR | 0doc 400001-400002 (0000-0001) | PRESET2 (PRESET) setting value | Counter 0..999999 (4-digit 0..9999); timer within its range. | UINT32 | CDAB | Read/write | |||
| HR | 2doc 400003-400004 (0002-0003) | PRESET1 setting value | UINT32 | CDAB | Read/write | ||||
| HR | 4doc 400005-400006 (0004-0005) | BATCH counter setting value | 0..999999. | UINT32 | CDAB | Read/write | |||
| HR | 50doc 400051 (0032) | Counter/Timer [C-T] | UINT16 | Read/write | 0 = COUN (counter); 1 = TIME (timer) | ||||
| HR | 51doc 400052 (0033) | Input mode [IN] | UINT16 | Read/write | 0 = UP; 1 = UP-1; 2 = UP-2; 3 = DN; 4 = DN-1; 5 = DN-2; 6 = UD-A; 7 = UD-B; 8 = UD-C | ||||
| HR | 52doc 400053 (0034) | Indication mode [DIsM] | Indicator models. | UINT16 | Read/write | 0 = TOTAL; 1 = HOLD | |||
| HR | 53doc 400054 (0035) | Output mode [OUtM] | UINT16 | Read/write | 0 = F; 1 = N; 2 = C; 3 = R; 4 = K; 5 = P; 6 = Q; 7 = A; 8 = S; 9 = T; 10 = D | ||||
| HR | 54doc 400055 (0036) | Max. counting speed [CPS] | UINT16 | Read/write | 0 = 1 cps; 1 = 30 cps; 2 = 1K cps; 3 = 5K cps; 4 = 10K cps | ||||
| HR | 55doc 400056 (0037) | OUT2 (OUT) output time | Raw 1..99 in 10 ms steps. | UINT16 | × 10 | ms | Read/write | ||
| HR | 56doc 400057 (0038) | OUT1 output time | Raw 1..99 in 10 ms steps. | UINT16 | × 10 | ms | Read/write | ||
| HR | 57doc 400058 (0039) | Decimal point [DP] | 0 = none, 1..5 = 1..5 decimals (6-digit; 4-digit 0..3). | UINT16 | Read/write | ||||
| HR | 58doc 400059 (003A) | Min. reset time [RST] | UINT16 | Read/write | 0 = 1 ms; 1 = 20 ms | ||||
| HR | 64doc 400065 (0040) | Memory protection [DATA] (counter) | UINT16 | Read/write | 0 = CLR; 1 = REC | ||||
| HR | 65doc 400066 (0041) | Lock key [LOCK] (counter) | UINT16 | Read/write | 0 = LOFF; 1 = LOC1; 2 = LOC2; 3 = LOC3 | ||||
| HR | 100doc 400101 (0064) | Count/Timer [C-T] (timer group) | UINT16 | Read/write | 0 = COUN; 1 = TIME | ||||
| HR | 101doc 400102 (0065) | Time range [HOUR/MIN/SEC] | Range code; tables differ for 4- and 6-digit models. | UINT16 | Read/write | ||||
| HR | 102doc 400103 (0066) | Up/Down mode [U-D] | UINT16 | Read/write | 0 = UP; 1 = DN | ||||
| HR | 103doc 400104 (0067) | Timer output mode [OUTM] | UINT16 | Read/write | 0 = OND; 1 = ONd1; 2 = ONd2; 3 = FLK; 4 = FLk1; 5 = FLk2; 6 = INT; 7 = INt1; 8 = INt2; 9 = OFD; 10 = NFD; 11 = NFd1; 12 = INTG | ||||
| HR | 104doc 400105 (0068) | Timer OUT2 (OUT) output time | Raw 1..99 x 10 ms; 0 = HOLD. | UINT16 | × 10 | ms | Read/write | ||
| HR | 105doc 400106 (0069) | Timer OUT1 output time | Raw 1..99 x 10 ms; 0 = HOLD. | UINT16 | × 10 | ms | Read/write | ||
| HR | 106doc 400107 (006A) | Input signal time [INT] | UINT16 | Read/write | 0 = 1 ms; 1 = 20 ms | ||||
| HR | 107doc 400108 (006B) | Memory protection [DATA] (timer) | UINT16 | Read/write | 0 = CLR; 1 = REC | ||||
| HR | 108doc 400109 (006C) | Lock key [LOCK] (timer) | UINT16 | Read/write | 0 = LOFF; 1 = LOC1; 2 = LOC2; 3 = LOC3 | ||||
| HR | 109doc 400110 (006D) | Indication mode [DSpM] (timer) | UINT16 | Read/write | 0 = TOTAL; 1 = HOLD; 2 = ONtD | ||||
| HR | 150doc 400151 (0096) | Comm. address [ADDR] | 1..127. | UINT16 | Read/write | ||||
| HR | 151doc 400152 (0097) | Comm. speed [BPS] | UINT16 | Read/write | 0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps; 4 = 38400 bps | ||||
| HR | 152doc 400153 (0098) | Comm. parity bit [PRTY] | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 153doc 400154 (0099) | Comm. stop bit [STP] | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 154doc 400155 (009A) | Response waiting time [RSwT] | 5..99 ms. | UINT16 | ms | Read/write | |||
| HR | 155doc 400156 (009B) | Comm. writing [COmW] | UINT16 | Read/write | 0 = Enabled; 1 = Disabled |
Notes on this map
- Autonics does not offer a static public link to this manual (downloads go through its website); this is the unaltered Autonics document hosted by the distributor AutomationDirect.
- Word order: the manual states that for two-word data the upper data sits at the higher address, e.g. 301004 = present value low word and 301005 = high word (CDAB).
- Present and preset values are display counts; apply the decimal point from 400058 (counter) or the time range from 400102 (timer) yourself.
- Changing counter or timer group parameters over Modbus resets the current value; preset and communication changes keep it.
- Left out: prescale decimal point, prescale value and start value (400060-400064) and the time-range code table, whose printed layout is too garbled to transcribe reliably.
- Broadcast commands are not supported. Autonics recommends FC06 over FC16 for PLC/HMI writes.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Autonics CT series programmable counter / timer (Modbus RTU)
What Modbus registers does the Autonics CT series programmable counter / timer (Modbus RTU) have?
This map lists 53 registers: 5 coils, 5 discrete inputs, 13 input registers, 30 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Autonics CT series programmable counter / timer (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints a 6-digit reference (000001/100001/300001/400001 style) followed by the hex protocol address in brackets, e.g. 301004 (03EB); the bracketed hex value is the wire address.
What byte order does the Autonics CT series programmable counter / timer (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Autonics CT series programmable counter / timer (Modbus RTU)?
Start with IR 1003 Present value of counter/timer (Present value); IR 1000 LED display status (Output/LED status); HR 0 PRESET2 (PRESET) setting value (PRESET2 setpoint); HR 2 PRESET1 setting value (PRESET1 setpoint); CO 0 Reset (Reset); IR 1005 Display unit (Decimal point / time range).
How do I enable Modbus control of the Autonics CT series programmable counter / timer (Modbus RTU)?
Set communication writing [COmW] (400156) to Enabled to allow Modbus writes; address, speed, parity and stop bits are in the communication group (also on the front panel).
Where is the official Autonics CT series programmable counter / timer (Modbus RTU) Modbus documentation?
The source is User Manual for Communication - Counters/Timers CT Series (MCC-CTC1-V1.3-EN). Autonics doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/autonics/autonicscommmanual.pdf. It may be an older revision, so check it against the live unit.
More Autonics Modbus register maps
Other temperature & process controllers register maps
- Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5
All temperature & process controllers Modbus register maps →
Source: User Manual for Communication - Counters/Timers CT Series · MCC-CTC1-V1.3-EN · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.