Sensor / counter-timer (programmable counter and timer) · Modbus register map

Autonics CT series programmable counter / timer (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Panel-mount programmable counter/timer with Modbus RTU. Coils and discrete inputs give outputs, reset and terminal inputs; input registers give model info, LED status, present value and preset values; holding registers set presets, counter and timer configuration and communication settings.

This page lists 53 Modbus registers for the Autonics CT series programmable counter / timer (Modbus RTU) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Autonics’s own free documentation (linked below) and checked against it.

Manufacturer
Autonics
Model
CT series programmable counter / timer (Modbus RTU)
Equipment type
Sensor / counter-timer (programmable counter and timer)
Registers
53 (32 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4
Source document
User Manual for Communication - Counters/Timers CT Series · MCC-CTC1-V1.3-EN · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Autonics CT series programmable counter / timer (Modbus RTU)

Integration in brief

Read input registers 301001-301013 in one FC04 request for LED status, present value and presets; write presets at 400001-400006 and use coil 0 (FC05 FF00) to reset.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 1003Present value of counter/timerINT32 CDABPresent valueRead
IR 1000LED display statusBITMAP16Output/LED statusRead
HR 0PRESET2 (PRESET) setting valueUINT32 CDABPRESET2 setpointRead/write
HR 2PRESET1 setting valueUINT32 CDABPRESET1 setpointRead/write
CO 0ResetBITResetRead/write
IR 1005Display unitUINT16Decimal point / time rangeRead

Enable Modbus control & writes

Set communication writing [COmW] (400156) to Enabled to allow Modbus writes; address, speed, parity and stop bits are in the communication group (also on the front panel).

Byte order & addressing

Network setup

Watch out for

Autonics CT series programmable counter / timer (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

53 of 53 shown
Autonics CT series programmable counter / timer (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 000001 (0000)ResetWrite ON (FF00) with FC05 to reset.BITRead/write0 = OFF; 1 = ON
CO1doc 000002 (0001)OUT2 outputBITRead0 = OFF; 1 = ON
CO2doc 000003 (0002)OUT1 outputBITRead0 = OFF; 1 = ON
CO3doc 000004 (0003)BATCH outputBATCH-output models only.BITRead0 = OFF; 1 = ON
CO4doc 000005 (0004)BATCH resetFC05 FF00 resets the batch counter (BATCH models).BITRead/write0 = OFF; 1 = ON
DI0doc 100001 (0000)INA input statusBITRead0 = OFF; 1 = ON
DI1doc 100002 (0001)INB input statusBITRead0 = OFF; 1 = ON
DI2doc 100003 (0002)INHIBIT input statusBITRead0 = OFF; 1 = ON
DI3doc 100004 (0003)RESET input statusBITRead0 = OFF; 1 = ON
DI4doc 100005 (0004)BATCH RESET input statusBITRead0 = OFF; 1 = ON
IR100doc 300101 (0064)Product number HModel ID, high word.UINT16Read
IR101doc 300102 (0065)Product number LModel ID, low word.UINT16Read
IR102doc 300103 (0066)Hardware versionUINT16Read
IR103doc 300104 (0067)Software versionUINT16Read
IR104doc 300105-300108 (0068-006B)Model nameASCII model text, e.g. 'CT6M-2PT'.STRING[8]Read
IR1000doc 301001 (03E8)LED display statusBITMAP16Readbit 5 = BA.O; bit 6 = OUT2; bit 7 = OUT1; bit 10 = BA.S; bit 11 = LOCK; bit 12 = PRESET2; bit 13 = PRESET1; bit 14 = TMR; bit 15 = CNT
IR1001doc 301002-301003 (03E9-03EA)Present value of BATCH counter0..999999. BATCH-output models.UINT32CDABRead
IR1003doc 301004-301005 (03EB-03EC)Present value of counter/timerDisplay count; decimal point per register 301006 / 400058.INT32CDABRead
IR1005doc 301006 (03ED)Display unitCounter: decimal point code (400058); timer: time range (400102).UINT16Read
IR1006doc 301007-301008 (03EE-03EF)PRESET2 (PRESET) setting valueINT32CDABRead
IR1008doc 301009-301010 (03F0-03F1)PRESET1 setting valueINT32CDABRead
IR1010doc 301011-301012 (03F2-03F3)Setting value of BATCH counter0..999999.UINT32CDABRead
IR1012doc 301013 (03F4)Checking the input logicUINT16Read0 = NPN; 1 = PNP
HR0doc 400001-400002 (0000-0001)PRESET2 (PRESET) setting valueCounter 0..999999 (4-digit 0..9999); timer within its range.UINT32CDABRead/write
HR2doc 400003-400004 (0002-0003)PRESET1 setting valueUINT32CDABRead/write
HR4doc 400005-400006 (0004-0005)BATCH counter setting value0..999999.UINT32CDABRead/write
HR50doc 400051 (0032)Counter/Timer [C-T]UINT16Read/write0 = COUN (counter); 1 = TIME (timer)
HR51doc 400052 (0033)Input mode [IN]UINT16Read/write0 = UP; 1 = UP-1; 2 = UP-2; 3 = DN; 4 = DN-1; 5 = DN-2; 6 = UD-A; 7 = UD-B; 8 = UD-C
HR52doc 400053 (0034)Indication mode [DIsM]Indicator models.UINT16Read/write0 = TOTAL; 1 = HOLD
HR53doc 400054 (0035)Output mode [OUtM]UINT16Read/write0 = F; 1 = N; 2 = C; 3 = R; 4 = K; 5 = P; 6 = Q; 7 = A; 8 = S; 9 = T; 10 = D
HR54doc 400055 (0036)Max. counting speed [CPS]UINT16Read/write0 = 1 cps; 1 = 30 cps; 2 = 1K cps; 3 = 5K cps; 4 = 10K cps
HR55doc 400056 (0037)OUT2 (OUT) output timeRaw 1..99 in 10 ms steps.UINT16× 10msRead/write
HR56doc 400057 (0038)OUT1 output timeRaw 1..99 in 10 ms steps.UINT16× 10msRead/write
HR57doc 400058 (0039)Decimal point [DP]0 = none, 1..5 = 1..5 decimals (6-digit; 4-digit 0..3).UINT16Read/write
HR58doc 400059 (003A)Min. reset time [RST]UINT16Read/write0 = 1 ms; 1 = 20 ms
HR64doc 400065 (0040)Memory protection [DATA] (counter)UINT16Read/write0 = CLR; 1 = REC
HR65doc 400066 (0041)Lock key [LOCK] (counter)UINT16Read/write0 = LOFF; 1 = LOC1; 2 = LOC2; 3 = LOC3
HR100doc 400101 (0064)Count/Timer [C-T] (timer group)UINT16Read/write0 = COUN; 1 = TIME
HR101doc 400102 (0065)Time range [HOUR/MIN/SEC]Range code; tables differ for 4- and 6-digit models.UINT16Read/write
HR102doc 400103 (0066)Up/Down mode [U-D]UINT16Read/write0 = UP; 1 = DN
HR103doc 400104 (0067)Timer output mode [OUTM]UINT16Read/write0 = OND; 1 = ONd1; 2 = ONd2; 3 = FLK; 4 = FLk1; 5 = FLk2; 6 = INT; 7 = INt1; 8 = INt2; 9 = OFD; 10 = NFD; 11 = NFd1; 12 = INTG
HR104doc 400105 (0068)Timer OUT2 (OUT) output timeRaw 1..99 x 10 ms; 0 = HOLD.UINT16× 10msRead/write
HR105doc 400106 (0069)Timer OUT1 output timeRaw 1..99 x 10 ms; 0 = HOLD.UINT16× 10msRead/write
HR106doc 400107 (006A)Input signal time [INT]UINT16Read/write0 = 1 ms; 1 = 20 ms
HR107doc 400108 (006B)Memory protection [DATA] (timer)UINT16Read/write0 = CLR; 1 = REC
HR108doc 400109 (006C)Lock key [LOCK] (timer)UINT16Read/write0 = LOFF; 1 = LOC1; 2 = LOC2; 3 = LOC3
HR109doc 400110 (006D)Indication mode [DSpM] (timer)UINT16Read/write0 = TOTAL; 1 = HOLD; 2 = ONtD
HR150doc 400151 (0096)Comm. address [ADDR]1..127.UINT16Read/write
HR151doc 400152 (0097)Comm. speed [BPS]UINT16Read/write0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps; 4 = 38400 bps
HR152doc 400153 (0098)Comm. parity bit [PRTY]UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR153doc 400154 (0099)Comm. stop bit [STP]UINT16Read/write0 = 1; 1 = 2
HR154doc 400155 (009A)Response waiting time [RSwT]5..99 ms.UINT16msRead/write
HR155doc 400156 (009B)Comm. writing [COmW]UINT16Read/write0 = Enabled; 1 = Disabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Autonics CT series programmable counter / timer (Modbus RTU)

What Modbus registers does the Autonics CT series programmable counter / timer (Modbus RTU) have?

This map lists 53 registers: 5 coils, 5 discrete inputs, 13 input registers, 30 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Autonics CT series programmable counter / timer (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints a 6-digit reference (000001/100001/300001/400001 style) followed by the hex protocol address in brackets, e.g. 301004 (03EB); the bracketed hex value is the wire address.

What byte order does the Autonics CT series programmable counter / timer (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Autonics CT series programmable counter / timer (Modbus RTU)?

Start with IR 1003 Present value of counter/timer (Present value); IR 1000 LED display status (Output/LED status); HR 0 PRESET2 (PRESET) setting value (PRESET2 setpoint); HR 2 PRESET1 setting value (PRESET1 setpoint); CO 0 Reset (Reset); IR 1005 Display unit (Decimal point / time range).

How do I enable Modbus control of the Autonics CT series programmable counter / timer (Modbus RTU)?

Set communication writing [COmW] (400156) to Enabled to allow Modbus writes; address, speed, parity and stop bits are in the communication group (also on the front panel).

Where is the official Autonics CT series programmable counter / timer (Modbus RTU) Modbus documentation?

The source is User Manual for Communication - Counters/Timers CT Series (MCC-CTC1-V1.3-EN). Autonics doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/autonics/autonicscommmanual.pdf. It may be an older revision, so check it against the live unit.

More Autonics Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: User Manual for Communication - Counters/Timers CT Series · MCC-CTC1-V1.3-EN · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.