Sensor (digital temperature controller) · Modbus register map

Shinko Technos DCL-33A digital indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The DCL-33A is a PID temperature controller. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485. The map covers SV, PID, alarm, heater-burnout and loop-break settings, input type, PV, MV and the status word.

This page lists 42 Modbus registers for the Shinko Technos DCL-33A digital indicating controller (C5 option) — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
DCL-33A digital indicating controller (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
42 (38 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
DCL-33A-C5, DCL-33A C5
Source document
Communication Instruction Manual DCL-33A (C5) · No.DCL32CE3 · rev. 2019-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos DCL-33A digital indicating controller (C5 option)

Integration in brief

Set the protocol to MODBUS RTU in Auxiliary function setting mode 1, give the unit a non-zero instrument number, then read PV 0080H, MV 0081H and status 0085H with function 03 and write SV1 (0001H) with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 1SV1INT16Set value SV1Read/write
HR 129OUT1 MV (MV1)INT16OUT1 manipulated valueRead
HR 133Status flagBITMAP16Status bitsRead
HR 26Decimal point placeINT16Decimal point for scalingRead/write
HR 11Alarm 1 valueINT16Alarm 1 valueRead/write

Enable Modbus control & writes

Requires the C5 option. Hold the two keys shown in the manual (p. 3) together for about 3 s to reach Auxiliary function setting mode 1, then set Communication protocol to MODBUS RTU mode (not the Block Read/Write variant), instrument number, speed, parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos DCL-33A digital indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

42 of 42 shown
Shinko Technos DCL-33A digital indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV1Main set value. Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HAT perform/cancelINT16Read/write0 = AT cancel; 1 = AT perform
HR4doc 0004HOUT1 proportional bandINT16Read/write
HR5doc 0005HOUT2 proportional bandINT16Read/write
HR6doc 0006HIntegral timeINT16Read/write
HR7doc 0007HDerivative timeINT16Read/write
HR8doc 0008HOUT1 proportional cycleINT16Read/write
HR9doc 0009HOUT2 proportional cycleINT16Read/write
HR10doc 000AHManual resetINT16Read/write
HR11doc 000BHAlarm 1 valueRaw integer; apply the decimal point setting.INT16Read/write
HR15doc 000FHHeater burnout alarm valueINT16Read/write
HR16doc 0010HLoop break alarm timeINT16Read/write
HR17doc 0011HLoop break alarm bandINT16Read/write
HR18doc 0012HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR21doc 0015HSensor correctionINT16Read/write
HR22doc 0016HOverlap/dead bandINT16Read/write
HR24doc 0018HScaling high limitINT16Read/write
HR25doc 0019HScaling low limitINT16Read/write
HR26doc 001AHDecimal point placeINT16Read/write0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX
HR27doc 001BHPV filter time constantINT16Read/write
HR28doc 001CHOUT1 high limitINT16Read/write
HR29doc 001DHOUT1 low limitINT16Read/write
HR30doc 001EHOUT1 ON/OFF hysteresisINT16Read/write
HR31doc 001FHOUT2 cooling methodINT16Read/write0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power)
HR32doc 0020HOUT2 high limitINT16Read/write
HR33doc 0021HOUT2 low limitINT16Read/write
HR34doc 0022HOUT2 ON/OFF hysteresisINT16Read/write
HR35doc 0023HAlarm 1 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby; 10 = High/Low limits independent; 11 = High/Low limit range independent; 12 = High/Low limits with standby independent
HR37doc 0025HAlarm 1 hysteresisINT16Read/write
HR41doc 0029HAlarm 1 delay timeINT16Read/write
HR64doc 0040HAlarm 1 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR66doc 0042HAlarm 1 HOLD functionINT16Read/write0 = Not holding; 1 = Holding
HR68doc 0044HInput typeINT16Read/write0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC (external shunt); 31 = 0-20 mA DC (external shunt); 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC; 36 = 0-20 mA DC (built-in shunt); 37 = 0-20 mA DC (built-in shunt)
HR69doc 0045HDirect/reverse actionINT16Read/write0 = Heating (reverse); 1 = Cooling (direct)
HR71doc 0047HAT biasINT16Read/write
HR72doc 0048HARWAnti-reset windup.INT16Read/write
HR111doc 006FHKey lockINT16Read/write0 = Key enabled; 1 = Key locked
HR112doc 0070HKey operation change flag clearingINT16Write0 = No action; 1 = Clear the flag
HR128doc 0080HPVProcess value. Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HOUT1 MV (MV1)INT16Read
HR130doc 0082HOUT2 MV (MV2)INT16Read
HR133doc 0085HStatus flagBITMAP16Readbit 0 = OUT1 on; bit 2 = Alarm 1 output on; bit 6 = Heater burnout alarm output on; bit 7 = Loop break alarm output on; bit 8 = Overscale; bit 9 = Underscale; bit 11 = AT running; bit 13 = 1 = converter, 0 = controller; bit 15 = Settings changed by keypad

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos DCL-33A digital indicating controller (C5 option)

What Modbus registers does the Shinko Technos DCL-33A digital indicating controller (C5 option) have?

This map lists 42 registers: 42 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos DCL-33A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos DCL-33A digital indicating controller (C5 option)?

Start with HR 128 PV (Process value); HR 1 SV1 (Set value SV1); HR 129 OUT1 MV (MV1) (OUT1 manipulated value); HR 133 Status flag (Status bits); HR 26 Decimal point place (Decimal point for scaling); HR 11 Alarm 1 value (Alarm 1 value).

How do I enable Modbus control of the Shinko Technos DCL-33A digital indicating controller (C5 option)?

Requires the C5 option. Hold the two keys shown in the manual (p. 3) together for about 3 s to reach Auxiliary function setting mode 1, then set Communication protocol to MODBUS RTU mode (not the Block Read/Write variant), instrument number, speed, parity and stop bit.

Where is the official Shinko Technos DCL-33A digital indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual DCL-33A (C5) (No.DCL32CE3), revision 2019-09, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/DCL32CE3.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual DCL-33A (C5) · No.DCL32CE3 · rev. 2019-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.