Sensor (digital indicating temperature controller) · Modbus register map
Yokogawa UTAdvanced UT75A digital indicating controller Modbus register map
Updated 19 November 2026
The UT75A is the high-end UTAdvanced PID controller with up to two loops, 20 SP groups and a simple program function. Its data live in D registers that map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers the process data block, the current SP/PID group for both loops and the operation-mode switches.
This page lists 66 Modbus registers for the Yokogawa UTAdvanced UT75A digital indicating controller — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UT75A digital indicating controller
- Equipment type
- Sensor (digital indicating temperature controller)
- Registers
- 66 (35 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UT75A
Integration notes: Yokogawa UTAdvanced UT75A digital indicating controller
Read D2001-D2013 in one block for errors, PV, SP, output and alarms; write the target setpoint to D2101 (loop 2: D2151) and switch AUTO/MAN, RUN/STOP and REMOTE/LOCAL with D2301, D2304 and D2306.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 loop-1 measured value | INT16 | Loop-1 PV (D2003) | Read |
| HR 2003 | CSP_L1 loop-1 control setpoint | INT16 | Loop-1 control setpoint (D2004) | Read |
| HR 2004 | OUT_L1 loop-1 control output | INT16 | Loop-1 output (D2005) | Read |
| HR 2007 | MOD_L1 loop-1 operation mode status | BITMAP16 | Operation mode status (D2008) | Read |
| HR 2010 | ALM_L1 loop-1 alarm 1-8 status | BITMAP16 | Loop-1 alarm status (D2011) | Read |
| HR 2100 | SP_L1 loop-1 target setpoint | INT16 | Loop-1 target setpoint (D2101) | Read/write |
| HR 2300 | A.M_L1 loop-1 AUTO/MAN switch | UINT16 | AUTO/MAN (D2301) | Read/write |
| HR 2303 | S.R_L1 loop-1 STOP/RUN switch | UINT16 | RUN/STOP (D2304) | Read/write |
Enable Modbus control & writes
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Byte order & addressing
- Address D register n at wire address n-1 (D2101 = 0834H).
- Write values without the decimal point (50.0 with one decimal place = 500).
- To take the setpoint from communication, put the loop in REMOTE (D2306 = 1) with the remote source set to communication, then write D2331.
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1.
Watch out for
- Available registers depend on the suffix code (single/dual loop, options) and parameter settings; blank addresses must not be read or written.
Yokogawa UTAdvanced UT75A digital indicating controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status 1 | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 1 = PV2 input (E1) A/D converter error; bit 2 = AIN2 input (E2) A/D converter error; bit 4 = AIN4 input (E4) A/D converter error; bit 5 = PV input RJC error; bit 6 = PV2 input RJC error; bit 8 = PV input burnout error; bit 9 = PV2 input (E1) burnout error; bit 10 = AIN2 input (E2) burnout error; bit 12 = AIN4 input (E4) burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 loop-1 PV input error status | BITMAP16 | Read | bit 0 = Loop-1 PV input burnout; bit 1 = Loop-1 PV2 input burnout; bit 2 = Burnout of loop-1 PV2 input used for control; bit 4 = Loop-1 PV over-scale; bit 5 = Loop-1 PV under-scale; bit 14 = Loop-1 auto-tuning timeout error | ||||
| HR | 2002doc D2003 | PV_L1 loop-1 measured value | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2003doc D2004 | CSP_L1 loop-1 control setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2004doc D2005 | OUT_L1 loop-1 control output | -5.0 to 105.0 %; valve opening in position-proportional control. | INT16 | × 0.1 | % | Read | ||
| HR | 2005doc D2006 | H.OUT_L1 heating-side output | Heating/cooling control. | INT16 | × 0.1 | % | Read | ||
| HR | 2006doc D2007 | C.OUT_L1 cooling-side output | 0.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2007doc D2008 | MOD_L1 loop-1 operation mode status | BITMAP16 | Read | bit 0 = A.M (0 AUTO, 1 MAN); bit 1 = R.L (0 local, 1 remote); bit 2 = S.R (0 run, 1 stop); bit 4 = CAS (cascade modes); bit 5 = AUTO (cascade modes); bit 6 = MAN (cascade modes); bit 8 = Output tracking; bit 14 = Auto-tuning ON | ||||
| HR | 2008doc D2009 | PID_L1 current PID number (loop 1) | Bits 0-4 hold the PID number; reads 0 for reference PID. | UINT16 | Read | ||||
| HR | 2009doc D2010 | CSPNO. current control setpoint number | Bits 0-4 hold the SP number. | UINT16 | Read | ||||
| HR | 2010doc D2011 | ALM_L1 loop-1 alarm 1-8 status | BITMAP16 | Read | bit 0 = Alarm 1 ON (loop 1); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON | ||||
| HR | 2011doc D2012 | LA.ER ladder error status | BITMAP16 | Read | bit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end) | ||||
| HR | 2012doc D2013 | ALM_L2 loop-2 alarm 1-8 status | BITMAP16 | Read | bit 0 = Alarm 1 ON (loop 2); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON | ||||
| HR | 2017doc D2018 | PV2.E_L2 loop-2 PV input error status | BITMAP16 | Read | bit 0 = Loop-2 PV input burnout; bit 1 = Loop-2 PV2 input burnout; bit 2 = Burnout of loop-2 PV2 input used for control; bit 4 = Loop-2 PV over-scale; bit 5 = Loop-2 PV under-scale; bit 14 = Loop-2 auto-tuning timeout error | ||||
| HR | 2018doc D2019 | PV_L2 loop-2 measured value | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2019doc D2020 | CSP_L2 loop-2 control setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2020doc D2021 | OUT_L2 loop-2 control output | -5.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2021doc D2022 | H.OUT_L2 loop-2 heating-side output | INT16 | × 0.1 | % | Read | |||
| HR | 2022doc D2023 | C.OUT_L2 loop-2 cooling-side output | INT16 | × 0.1 | % | Read | |||
| HR | 2023doc D2024 | MOD_L2 loop-2 operation mode status | BITMAP16 | Read | bit 0 = A.M_L2 (0 AUTO, 1 MAN); bit 1 = R.L_L2 (0 local, 1 remote); bit 2 = S.R_L2 (0 run, 1 stop); bit 14 = Loop-2 auto-tuning ON | ||||
| HR | 2024doc D2025 | PID_L2 current PID number (loop 2) | Bits 0-4 hold the PID number. | UINT16 | Read | ||||
| HR | 2028doc D2029 | SEG.N current program segment | 0 = not executing, 1-20. | UINT16 | Read | ||||
| HR | 2029doc D2030 | SEG_RTIME remaining segment time | 0-59999; unit (min or s) set by TMU. | UINT16 | Read | ||||
| HR | 2034doc D2035 | DEV_L1 loop-1 deviation | -105.0 to 105.0 % of span, sent as engineering value without decimal point. | INT16 | Read | ||||
| HR | 2035doc D2036 | DEV_L2 loop-2 deviation | Same format as DEV_L1. | INT16 | Read | ||||
| HR | 2036doc D2037 | ALO_L1 loop-1 alarm output 1-8 status | 1 = relay contact closed. | BITMAP16 | Read | bit 0 = Alarm output 1 contact closed (loop 1); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed | |||
| HR | 2037doc D2038 | ALO_L2 loop-2 alarm output 1-8 status | 1 = relay contact closed. | BITMAP16 | Read | bit 0 = Alarm output 1 contact closed (loop 2); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed | |||
| HR | 2063doc D2064 | VALV valve status | Position-proportional control. | BITMAP16 | Read | bit 0 = Estimating-type operation (0 = feedback input); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment running | |||
| HR | 2064doc D2065 | AD2.E A/D converter error status 2 | BITMAP16 | Read | bit 0 = Feedback input resistor/current burnout; bit 1 = Valve position automatic adjustment error | ||||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2069doc D2070 | OP.ER option error status | BITMAP16 | Read | bit 0 = E1 terminal hardware not responding; bit 1 = E2 terminal hardware not responding; bit 2 = E3 terminal hardware not responding; bit 4 = E4 terminal hardware not responding; bit 10 = E3 communication error; bit 12 = E4 communication error | ||||
| HR | 2100doc D2101 | SP_L1 loop-1 target setpoint | Current SP group. Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2101doc D2102 | SUB sub-target setpoint | Offset from SP in two-position two-level control. | INT16 | Read/write | ||||
| HR | 2102doc D2103 | PIDN_L1 loop-1 PID number selection | PID group number to use. | UINT16 | Read/write | ||||
| HR | 2103doc D2104 | A1_L1 loop-1 alarm-1 setpoint | -19999 to 30000, decimal point per input. | INT16 | Read/write | ||||
| HR | 2104doc D2105 | A2_L1 loop-1 alarm-2 setpoint | INT16 | Read/write | |||||
| HR | 2105doc D2106 | A3_L1 loop-1 alarm-3 setpoint | INT16 | Read/write | |||||
| HR | 2106doc D2107 | A4_L1 loop-1 alarm-4 setpoint | INT16 | Read/write | |||||
| HR | 2113doc D2114 | P_L1 proportional band | 0.0-999.9 % (heating side in heating/cooling). | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2114doc D2115 | I_L1 integral time | 0 = off, 1-6000 s. | UINT16 | s | Read/write | |||
| HR | 2115doc D2116 | D_L1 derivative time | 0 = off, 1-6000 s. | UINT16 | s | Read/write | |||
| HR | 2116doc D2117 | OH_L1 control output high limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2117doc D2118 | OL_L1 control output low limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2118doc D2119 | MR_L1 manual reset | Used when integral time is off. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2123doc D2124 | DR_L1 direct/reverse action | UINT16 | Read/write | 0 = RVS reverse action; 1 = DIR direct action | ||||
| HR | 2132doc D2133 | PO_L1 preset output | Output used in STOP mode, -5.0 to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2150doc D2151 | SP_L2 loop-2 target setpoint | Same as D2101 for loop 2. | INT16 | Read/write | ||||
| HR | 2163doc D2164 | P_L2 loop-2 proportional band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 2164doc D2165 | I_L2 loop-2 integral time | UINT16 | s | Read/write | ||||
| HR | 2165doc D2166 | D_L2 loop-2 derivative time | UINT16 | s | Read/write | ||||
| HR | 2300doc D2301 | A.M_L1 loop-1 AUTO/MAN switch | Not for cascade modes. | UINT16 | Read/write | 0 = AUTO; 1 = MAN | |||
| HR | 2301doc D2302 | A.M_L2 loop-2 AUTO/MAN switch | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 2302doc D2303 | C.A.M CAS/AUTO/MAN switch | Cascade control modes. | UINT16 | Read/write | 0 = AUTO; 1 = MAN; 2 = CAS | |||
| HR | 2303doc D2304 | S.R_L1 loop-1 STOP/RUN switch | Preset output is used in STOP. | UINT16 | Read/write | 0 = RUN; 1 = STOP | |||
| HR | 2304doc D2305 | S.R_L2 loop-2 STOP/RUN switch | UINT16 | Read/write | 0 = RUN; 1 = STOP | ||||
| HR | 2305doc D2306 | R.L_L1 loop-1 REMOTE/LOCAL switch | UINT16 | Read/write | 0 = LCL (local); 1 = REM (remote) | ||||
| HR | 2306doc D2307 | R.L_L2 loop-2 REMOTE/LOCAL switch | UINT16 | Read/write | 0 = LCL (local); 1 = REM (remote) | ||||
| HR | 2307doc D2308 | AT_L1 loop-1 auto-tuning switch | 0 = off, 1-16 = tune into that PID, 17 = reference PID. | UINT16 | Read/write | ||||
| HR | 2308doc D2309 | AT_L2 loop-2 auto-tuning switch | Same as AT_L1. | UINT16 | Read/write | ||||
| HR | 2311doc D2312 | SPNO. SP number selection | 1-8. | UINT16 | Read/write | ||||
| HR | 2313doc D2314 | TRK_ON_L1 loop-1 output tracking | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 2314doc D2315 | TRK_ON_L2 loop-2 output tracking | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 2330doc D2331 | C.RSP_L1 loop-1 communication remote setpoint | Used when remote mode takes SP from comms. Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2331doc D2332 | C.RSP_L2 loop-2 communication remote setpoint | INT16 | Read/write | |||||
| HR | 2332doc D2333 | MOUT_L1 loop-1 manual output | Heating-side output in MAN mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2334doc D2335 | MOUT_L2 loop-2 manual output | Heating-side output in MAN mode. | INT16 | × 0.1 | % | Read/write |
Notes on this map
- All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).
- D2001-D2100 are read-only. D2101-D2112 / D2151-D2163 act on the SP group in use (1-20); D2114-D2135 / D2164-D2185 on the PID group in use (1-16 or R).
- Program-operation registers (D2031, D2327-D2329, pattern area D7701-D7900), ramp-rate registers D2112/D2113 and the GREEN-series compatible area (D0001-D2000) are not included.
- Only part of the D-register space is listed; alarm setpoints 5-8, cooling-side PID terms, SP/PID groups 9-20 (D9001 onward) and the setup parameter areas (D2501 onward) are left out.
- Modbus/TCP applies only to units with the Ethernet communication option.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UT75A digital indicating controller
What Modbus registers does the Yokogawa UTAdvanced UT75A digital indicating controller have?
This map lists 66 registers: 66 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UT75A digital indicating controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT75A digital indicating controller?
Start with HR 2002 PV_L1 loop-1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 loop-1 control setpoint (Loop-1 control setpoint (D2004)); HR 2004 OUT_L1 loop-1 control output (Loop-1 output (D2005)); HR 2007 MOD_L1 loop-1 operation mode status (Operation mode status (D2008)); HR 2010 ALM_L1 loop-1 alarm 1-8 status (Loop-1 alarm status (D2011)); HR 2100 SP_L1 loop-1 target setpoint (Loop-1 target setpoint (D2101)); HR 2300 A.M_L1 loop-1 AUTO/MAN switch (AUTO/MAN (D2301)); HR 2303 S.R_L1 loop-1 STOP/RUN switch (RUN/STOP (D2304)).
How do I enable Modbus control of the Yokogawa UTAdvanced UT75A digital indicating controller?
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Where is the official Yokogawa UTAdvanced UT75A digital indicating controller Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5
All temperature & process controllers Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.