Sensor (digital indicating temperature controller) · Modbus register map

Yokogawa UTAdvanced UT75A digital indicating controller Modbus register map

Updated 19 November 2026

Short answer

The UT75A is the high-end UTAdvanced PID controller with up to two loops, 20 SP groups and a simple program function. Its data live in D registers that map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers the process data block, the current SP/PID group for both loops and the operation-mode switches.

This page lists 66 Modbus registers for the Yokogawa UTAdvanced UT75A digital indicating controller — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UT75A digital indicating controller
Equipment type
Sensor (digital indicating temperature controller)
Registers
66 (35 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UT75A
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UT75A digital indicating controller

Integration in brief

Read D2001-D2013 in one block for errors, PV, SP, output and alarms; write the target setpoint to D2101 (loop 2: D2151) and switch AUTO/MAN, RUN/STOP and REMOTE/LOCAL with D2301, D2304 and D2306.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 loop-1 measured valueINT16Loop-1 PV (D2003)Read
HR 2003CSP_L1 loop-1 control setpointINT16Loop-1 control setpoint (D2004)Read
HR 2004OUT_L1 loop-1 control outputINT16Loop-1 output (D2005)Read
HR 2007MOD_L1 loop-1 operation mode statusBITMAP16Operation mode status (D2008)Read
HR 2010ALM_L1 loop-1 alarm 1-8 statusBITMAP16Loop-1 alarm status (D2011)Read
HR 2100SP_L1 loop-1 target setpointINT16Loop-1 target setpoint (D2101)Read/write
HR 2300A.M_L1 loop-1 AUTO/MAN switchUINT16AUTO/MAN (D2301)Read/write
HR 2303S.R_L1 loop-1 STOP/RUN switchUINT16RUN/STOP (D2304)Read/write

Enable Modbus control & writes

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UT75A digital indicating controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

66 of 66 shown
Yokogawa UTAdvanced UT75A digital indicating controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error status 1BITMAP16Readbit 0 = PV input A/D converter error; bit 1 = PV2 input (E1) A/D converter error; bit 2 = AIN2 input (E2) A/D converter error; bit 4 = AIN4 input (E4) A/D converter error; bit 5 = PV input RJC error; bit 6 = PV2 input RJC error; bit 8 = PV input burnout error; bit 9 = PV2 input (E1) burnout error; bit 10 = AIN2 input (E2) burnout error; bit 12 = AIN4 input (E4) burnout error
HR2001doc D2002PV1.E_L1 loop-1 PV input error statusBITMAP16Readbit 0 = Loop-1 PV input burnout; bit 1 = Loop-1 PV2 input burnout; bit 2 = Burnout of loop-1 PV2 input used for control; bit 4 = Loop-1 PV over-scale; bit 5 = Loop-1 PV under-scale; bit 14 = Loop-1 auto-tuning timeout error
HR2002doc D2003PV_L1 loop-1 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2003doc D2004CSP_L1 loop-1 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2004doc D2005OUT_L1 loop-1 control output-5.0 to 105.0 %; valve opening in position-proportional control.INT16× 0.1%Read
HR2005doc D2006H.OUT_L1 heating-side outputHeating/cooling control.INT16× 0.1%Read
HR2006doc D2007C.OUT_L1 cooling-side output0.0 to 105.0 %.INT16× 0.1%Read
HR2007doc D2008MOD_L1 loop-1 operation mode statusBITMAP16Readbit 0 = A.M (0 AUTO, 1 MAN); bit 1 = R.L (0 local, 1 remote); bit 2 = S.R (0 run, 1 stop); bit 4 = CAS (cascade modes); bit 5 = AUTO (cascade modes); bit 6 = MAN (cascade modes); bit 8 = Output tracking; bit 14 = Auto-tuning ON
HR2008doc D2009PID_L1 current PID number (loop 1)Bits 0-4 hold the PID number; reads 0 for reference PID.UINT16Read
HR2009doc D2010CSPNO. current control setpoint numberBits 0-4 hold the SP number.UINT16Read
HR2010doc D2011ALM_L1 loop-1 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 1); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2011doc D2012LA.ER ladder error statusBITMAP16Readbit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end)
HR2012doc D2013ALM_L2 loop-2 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 2); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2017doc D2018PV2.E_L2 loop-2 PV input error statusBITMAP16Readbit 0 = Loop-2 PV input burnout; bit 1 = Loop-2 PV2 input burnout; bit 2 = Burnout of loop-2 PV2 input used for control; bit 4 = Loop-2 PV over-scale; bit 5 = Loop-2 PV under-scale; bit 14 = Loop-2 auto-tuning timeout error
HR2018doc D2019PV_L2 loop-2 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2019doc D2020CSP_L2 loop-2 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2020doc D2021OUT_L2 loop-2 control output-5.0 to 105.0 %.INT16× 0.1%Read
HR2021doc D2022H.OUT_L2 loop-2 heating-side outputINT16× 0.1%Read
HR2022doc D2023C.OUT_L2 loop-2 cooling-side outputINT16× 0.1%Read
HR2023doc D2024MOD_L2 loop-2 operation mode statusBITMAP16Readbit 0 = A.M_L2 (0 AUTO, 1 MAN); bit 1 = R.L_L2 (0 local, 1 remote); bit 2 = S.R_L2 (0 run, 1 stop); bit 14 = Loop-2 auto-tuning ON
HR2024doc D2025PID_L2 current PID number (loop 2)Bits 0-4 hold the PID number.UINT16Read
HR2028doc D2029SEG.N current program segment0 = not executing, 1-20.UINT16Read
HR2029doc D2030SEG_RTIME remaining segment time0-59999; unit (min or s) set by TMU.UINT16Read
HR2034doc D2035DEV_L1 loop-1 deviation-105.0 to 105.0 % of span, sent as engineering value without decimal point.INT16Read
HR2035doc D2036DEV_L2 loop-2 deviationSame format as DEV_L1.INT16Read
HR2036doc D2037ALO_L1 loop-1 alarm output 1-8 status1 = relay contact closed.BITMAP16Readbit 0 = Alarm output 1 contact closed (loop 1); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed
HR2037doc D2038ALO_L2 loop-2 alarm output 1-8 status1 = relay contact closed.BITMAP16Readbit 0 = Alarm output 1 contact closed (loop 2); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed
HR2063doc D2064VALV valve statusPosition-proportional control.BITMAP16Readbit 0 = Estimating-type operation (0 = feedback input); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment running
HR2064doc D2065AD2.E A/D converter error status 2BITMAP16Readbit 0 = Feedback input resistor/current burnout; bit 1 = Valve position automatic adjustment error
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2069doc D2070OP.ER option error statusBITMAP16Readbit 0 = E1 terminal hardware not responding; bit 1 = E2 terminal hardware not responding; bit 2 = E3 terminal hardware not responding; bit 4 = E4 terminal hardware not responding; bit 10 = E3 communication error; bit 12 = E4 communication error
HR2100doc D2101SP_L1 loop-1 target setpointCurrent SP group. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2101doc D2102SUB sub-target setpointOffset from SP in two-position two-level control.INT16Read/write
HR2102doc D2103PIDN_L1 loop-1 PID number selectionPID group number to use.UINT16Read/write
HR2103doc D2104A1_L1 loop-1 alarm-1 setpoint-19999 to 30000, decimal point per input.INT16Read/write
HR2104doc D2105A2_L1 loop-1 alarm-2 setpointINT16Read/write
HR2105doc D2106A3_L1 loop-1 alarm-3 setpointINT16Read/write
HR2106doc D2107A4_L1 loop-1 alarm-4 setpointINT16Read/write
HR2113doc D2114P_L1 proportional band0.0-999.9 % (heating side in heating/cooling).UINT16× 0.1%Read/write
HR2114doc D2115I_L1 integral time0 = off, 1-6000 s.UINT16sRead/write
HR2115doc D2116D_L1 derivative time0 = off, 1-6000 s.UINT16sRead/write
HR2116doc D2117OH_L1 control output high limitINT16× 0.1%Read/write
HR2117doc D2118OL_L1 control output low limitINT16× 0.1%Read/write
HR2118doc D2119MR_L1 manual resetUsed when integral time is off.INT16× 0.1%Read/write
HR2123doc D2124DR_L1 direct/reverse actionUINT16Read/write0 = RVS reverse action; 1 = DIR direct action
HR2132doc D2133PO_L1 preset outputOutput used in STOP mode, -5.0 to 105.0 %.INT16× 0.1%Read/write
HR2150doc D2151SP_L2 loop-2 target setpointSame as D2101 for loop 2.INT16Read/write
HR2163doc D2164P_L2 loop-2 proportional bandUINT16× 0.1%Read/write
HR2164doc D2165I_L2 loop-2 integral timeUINT16sRead/write
HR2165doc D2166D_L2 loop-2 derivative timeUINT16sRead/write
HR2300doc D2301A.M_L1 loop-1 AUTO/MAN switchNot for cascade modes.UINT16Read/write0 = AUTO; 1 = MAN
HR2301doc D2302A.M_L2 loop-2 AUTO/MAN switchUINT16Read/write0 = AUTO; 1 = MAN
HR2302doc D2303C.A.M CAS/AUTO/MAN switchCascade control modes.UINT16Read/write0 = AUTO; 1 = MAN; 2 = CAS
HR2303doc D2304S.R_L1 loop-1 STOP/RUN switchPreset output is used in STOP.UINT16Read/write0 = RUN; 1 = STOP
HR2304doc D2305S.R_L2 loop-2 STOP/RUN switchUINT16Read/write0 = RUN; 1 = STOP
HR2305doc D2306R.L_L1 loop-1 REMOTE/LOCAL switchUINT16Read/write0 = LCL (local); 1 = REM (remote)
HR2306doc D2307R.L_L2 loop-2 REMOTE/LOCAL switchUINT16Read/write0 = LCL (local); 1 = REM (remote)
HR2307doc D2308AT_L1 loop-1 auto-tuning switch0 = off, 1-16 = tune into that PID, 17 = reference PID.UINT16Read/write
HR2308doc D2309AT_L2 loop-2 auto-tuning switchSame as AT_L1.UINT16Read/write
HR2311doc D2312SPNO. SP number selection1-8.UINT16Read/write
HR2313doc D2314TRK_ON_L1 loop-1 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2314doc D2315TRK_ON_L2 loop-2 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2330doc D2331C.RSP_L1 loop-1 communication remote setpointUsed when remote mode takes SP from comms. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2331doc D2332C.RSP_L2 loop-2 communication remote setpointINT16Read/write
HR2332doc D2333MOUT_L1 loop-1 manual outputHeating-side output in MAN mode.INT16× 0.1%Read/write
HR2334doc D2335MOUT_L2 loop-2 manual outputHeating-side output in MAN mode.INT16× 0.1%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UT75A digital indicating controller

What Modbus registers does the Yokogawa UTAdvanced UT75A digital indicating controller have?

This map lists 66 registers: 66 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UT75A digital indicating controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT75A digital indicating controller?

Start with HR 2002 PV_L1 loop-1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 loop-1 control setpoint (Loop-1 control setpoint (D2004)); HR 2004 OUT_L1 loop-1 control output (Loop-1 output (D2005)); HR 2007 MOD_L1 loop-1 operation mode status (Operation mode status (D2008)); HR 2010 ALM_L1 loop-1 alarm 1-8 status (Loop-1 alarm status (D2011)); HR 2100 SP_L1 loop-1 target setpoint (Loop-1 target setpoint (D2101)); HR 2300 A.M_L1 loop-1 AUTO/MAN switch (AUTO/MAN (D2301)); HR 2303 S.R_L1 loop-1 STOP/RUN switch (RUN/STOP (D2304)).

How do I enable Modbus control of the Yokogawa UTAdvanced UT75A digital indicating controller?

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Where is the official Yokogawa UTAdvanced UT75A digital indicating controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.