- Home
- Modbus register maps
- Yokogawa
Manufacturer
Yokogawa Modbus register maps
Updated 19 November 2026
7 Yokogawa models, 300 registers in all, each re-typed from Yokogawa’s own free documentation and checked against it.
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Yokogawa: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| UTAdvanced UM33A digital indicator with alarms | RTU/ASCII | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 12 |
| UTAdvanced UP35A / UP32A program controller | RTU/ASCII/TCP | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 40 |
| UTAdvanced UP55A program controller | RTU/ASCII/TCP | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 51 |
| UTAdvanced UT35A / UT32A digital indicating controller | RTU/ASCII/TCP | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 52 |
| UTAdvanced UT35A-L limit controller | RTU/ASCII | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 16 |
| UTAdvanced UT55A / UT52A digital indicating controller | RTU/ASCII/TCP | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 63 |
| UTAdvanced UT75A digital indicating controller | RTU/ASCII/TCP | 1 | 19200 baud, 8E1 | 16-bit only | 1-based | 66 |