- UTAdvanced UT35A-L limit controller
Sensor (limit controller) · Modbus register map
Yokogawa UTAdvanced UT35A-L limit controller Modbus register map
Updated 17 November 2026
The UT35A-L is a high/low limit controller in Yokogawa's UTAdvanced family that trips an output relay when the PV passes its limit setpoint. Its D registers map one-to-one onto Modbus holding registers. This map covers the process monitoring block: PV, limit setpoint, exceed and relay status, alarms, latches, exceed duration time and PV peak value.
This page lists 16 Modbus registers for the Yokogawa UTAdvanced UT35A-L limit controller — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UT35A-L limit controller
- Equipment type
- Sensor (limit controller)
- Registers
- 16 (0 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UT35A-L
Integration notes: Yokogawa UTAdvanced UT35A-L limit controller
Use the factory Modbus RTU setting, then read D2001-D2008 for errors, PV, limit setpoint and the exceed/relay status bits.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 measured value | INT16 | PV (D2003) | Read |
| HR 2001 | PV1.E_L1 PV input error status | BITMAP16 | PV input error flags (D2002) | Read |
| HR 2003 | CSP_L1 control (limit) setpoint | INT16 | Limit setpoint (D2004) | Read |
| HR 2007 | MOD_L1 operation status | BITMAP16 | Exceeded / output relay (D2008) | Read |
| HR 2010 | ALM_L1 alarm 1-3 status | BITMAP16 | Alarm status (D2011) | Read |
| HR 2036 | ALO_L1 alarm output 1-3 status | BITMAP16 | Alarm output status (D2037) | Read |
Enable Modbus control & writes
Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).
Byte order & addressing
- Wire address = D number - 1 (D2003 = 07D2H).
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1.
Watch out for
- Reading undefined (blank) D registers is not allowed and can upset the unit.
Yokogawa UTAdvanced UT35A-L limit controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 PV input error status | BITMAP16 | Read | bit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale | ||||
| HR | 2002doc D2003 | PV_L1 measured value | -5 to 105 % of input range, engineering value without decimal point. | INT16 | Read | ||||
| HR | 2003doc D2004 | CSP_L1 control (limit) setpoint | Setpoint in engineering units without decimal point. | INT16 | Read | ||||
| HR | 2007doc D2008 | MOD_L1 operation status | BITMAP16 | Read | bit 12 = Limit exceeded; bit 13 = Output relay ON | ||||
| HR | 2010doc D2011 | ALM_L1 alarm 1-3 status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON | ||||
| HR | 2036doc D2037 | ALO_L1 alarm output 1-3 status | BITMAP16 | Read | bit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed | ||||
| HR | 2065doc D2066 | DIMG message display status | BITMAP16 | Read | bit 0 = Message 1 displayed; bit 1 = Message 2 displayed; bit 2 = Message 3 displayed; bit 4 = Message 4 displayed | ||||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2069doc D2070 | OP.ER option error status | BITMAP16 | Read | bit 2 = E3 terminal hardware not responding; bit 10 = E3 communication error | ||||
| HR | 2070doc D2071 | ALOLA1_L1 alarm latch-1 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1 | ||||
| HR | 2072doc D2073 | ALOLA2_L1 alarm latch-2 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2 | ||||
| HR | 2074doc D2075 | ALOLA3_L1 alarm latch-3 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-3; bit 1 = Alarm 2 latch-3; bit 2 = Alarm 3 latch-3 | ||||
| HR | 2076doc D2077 | ALOLA4_L1 alarm latch-4 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-4; bit 1 = Alarm 2 latch-4; bit 2 = Alarm 3 latch-4 | ||||
| HR | 2080doc D2081 | TIME duration time | Duration time; unit set by parameter TMU (1 h 38 min 57 s reads 5937 s). | UINT16 | Read | ||||
| HR | 2081doc D2082 | MAX/MIN PV peak value | Maximum or minimum PV per the HI.LO limit type; no decimal point sent. | INT16 | Read |
Notes on this map
- All registers are 16-bit and read-only in this block (D2001-D2100).
- PV is sent without its decimal point; the position follows the input's decimal point setting.
- Alarm setpoints and setup parameters (D2501 onward) are not included in this map.
- Current SP group registers (D2101-D2200) are not included.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UT35A-L limit controller
What Modbus registers does the Yokogawa UTAdvanced UT35A-L limit controller have?
This map lists 16 registers: 16 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UT35A-L limit controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers; the Modbus reference is the D number with D replaced by 4 (D2003 = 42003) and the wire address is that minus 40001, as printed in the H No. column (07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT35A-L limit controller?
Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2001 PV1.E_L1 PV input error status (PV input error flags (D2002)); HR 2003 CSP_L1 control (limit) setpoint (Limit setpoint (D2004)); HR 2007 MOD_L1 operation status (Exceeded / output relay (D2008)); HR 2010 ALM_L1 alarm 1-3 status (Alarm status (D2011)); HR 2036 ALO_L1 alarm output 1-3 status (Alarm output status (D2037)).
How do I enable Modbus control of the Yokogawa UTAdvanced UT35A-L limit controller?
Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).
Where is the official Yokogawa UTAdvanced UT35A-L limit controller Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Other valves, actuators & sensors register maps
- Actuator / valve (6-way pressure-independent change-over valve)
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)
Belimo 6-way EPIV EP..R-R6+BAC on Modbus RTU, per 6-way EPIV Modbus Register en-gb 2024-01 (general notes dated 16.12.2019).
Also known as: EP..R-R6+BAC, 6-way pressure-independent valve - Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Sensor (load-cell weight transmitter)
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Laumas TLB4 with the Modbus RTU port or the Modbus/TCP option; communication protocols manual version 1.12. Direct registers only.
Also known as: TLB4, TLB4 MODBUS, TLB4 Modbus/TCP - Actuator / valve
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Rotork Modbus RTU Mk3 option module (MFU) in IQ3, SI3, SI4, CK, CVA (firmware CVA1.14 or later), CMA and K-range actuators, using the default Rotork database (register 80 = 0), per PUB091-004-00 issue 08/25.
Also known as: IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus - Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210
All valves, actuators & sensors Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.