Easy Modbus
  1. Home
  2. Modbus register maps
  3. Yokogawa
  4. UTAdvanced UT35A-L limit controller

Sensor (limit controller) · Modbus register map

Yokogawa UTAdvanced UT35A-L limit controller Modbus register map

Updated 17 November 2026

Short answer

The UT35A-L is a high/low limit controller in Yokogawa's UTAdvanced family that trips an output relay when the PV passes its limit setpoint. Its D registers map one-to-one onto Modbus holding registers. This map covers the process monitoring block: PV, limit setpoint, exceed and relay status, alarms, latches, exceed duration time and PV peak value.

This page lists 16 Modbus registers for the Yokogawa UTAdvanced UT35A-L limit controller — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UT35A-L limit controller
Equipment type
Sensor (limit controller)
Registers
16 (0 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UT35A-L
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UT35A-L limit controller

Integration in brief

Use the factory Modbus RTU setting, then read D2001-D2008 for errors, PV, limit setpoint and the exceed/relay status bits.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 measured valueINT16PV (D2003)Read
HR 2001PV1.E_L1 PV input error statusBITMAP16PV input error flags (D2002)Read
HR 2003CSP_L1 control (limit) setpointINT16Limit setpoint (D2004)Read
HR 2007MOD_L1 operation statusBITMAP16Exceeded / output relay (D2008)Read
HR 2010ALM_L1 alarm 1-3 statusBITMAP16Alarm status (D2011)Read
HR 2036ALO_L1 alarm output 1-3 statusBITMAP16Alarm output status (D2037)Read

Enable Modbus control & writes

Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UT35A-L limit controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
Yokogawa UTAdvanced UT35A-L limit controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error statusBITMAP16Readbit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error
HR2001doc D2002PV1.E_L1 PV input error statusBITMAP16Readbit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale
HR2002doc D2003PV_L1 measured value-5 to 105 % of input range, engineering value without decimal point.INT16Read
HR2003doc D2004CSP_L1 control (limit) setpointSetpoint in engineering units without decimal point.INT16Read
HR2007doc D2008MOD_L1 operation statusBITMAP16Readbit 12 = Limit exceeded; bit 13 = Output relay ON
HR2010doc D2011ALM_L1 alarm 1-3 statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON
HR2036doc D2037ALO_L1 alarm output 1-3 statusBITMAP16Readbit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed
HR2065doc D2066DIMG message display statusBITMAP16Readbit 0 = Message 1 displayed; bit 1 = Message 2 displayed; bit 2 = Message 3 displayed; bit 4 = Message 4 displayed
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2069doc D2070OP.ER option error statusBITMAP16Readbit 2 = E3 terminal hardware not responding; bit 10 = E3 communication error
HR2070doc D2071ALOLA1_L1 alarm latch-1 output statusBITMAP16Readbit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1
HR2072doc D2073ALOLA2_L1 alarm latch-2 output statusBITMAP16Readbit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2
HR2074doc D2075ALOLA3_L1 alarm latch-3 output statusBITMAP16Readbit 0 = Alarm 1 latch-3; bit 1 = Alarm 2 latch-3; bit 2 = Alarm 3 latch-3
HR2076doc D2077ALOLA4_L1 alarm latch-4 output statusBITMAP16Readbit 0 = Alarm 1 latch-4; bit 1 = Alarm 2 latch-4; bit 2 = Alarm 3 latch-4
HR2080doc D2081TIME duration timeDuration time; unit set by parameter TMU (1 h 38 min 57 s reads 5937 s).UINT16Read
HR2081doc D2082MAX/MIN PV peak valueMaximum or minimum PV per the HI.LO limit type; no decimal point sent.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UT35A-L limit controller

What Modbus registers does the Yokogawa UTAdvanced UT35A-L limit controller have?

This map lists 16 registers: 16 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UT35A-L limit controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers; the Modbus reference is the D number with D replaced by 4 (D2003 = 42003) and the wire address is that minus 40001, as printed in the H No. column (07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT35A-L limit controller?

Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2001 PV1.E_L1 PV input error status (PV input error flags (D2002)); HR 2003 CSP_L1 control (limit) setpoint (Limit setpoint (D2004)); HR 2007 MOD_L1 operation status (Exceeded / output relay (D2008)); HR 2010 ALM_L1 alarm 1-3 status (Alarm status (D2011)); HR 2036 ALO_L1 alarm output 1-3 status (Alarm output status (D2037)).

How do I enable Modbus control of the Yokogawa UTAdvanced UT35A-L limit controller?

Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).

Where is the official Yokogawa UTAdvanced UT35A-L limit controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.