Sensor (room humidity / temperature) · Modbus register map
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) Modbus register map
Updated 17 November 2026
The QFA3150/MO is a wall-mounted room sensor for temperature and relative humidity with a Modbus RTU (RS-485) slave port. Readings and settings are 16-bit holding registers. The map covers the two measurements with their reliability flags, the temperature unit, the communication settings and the firmware version.
This page lists 10 Modbus registers for the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- QFA3150/MO room humidity and temperature sensor (Modbus RTU)
- Equipment type
- Sensor (room humidity / temperature)
- Registers
- 10 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- QFA3150/MO, S55720-S535
Integration notes: Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
With DIP2 switch 7 OFF the sensor answers at address 1, 8E1, auto baud; read holding registers 0-3 with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Temperature value | INT16 | Temperature | Read |
| HR 2 | Relative humidity value | UINT16 | Relative humidity | Read |
| HR 1 | Temperature reliability | UINT16 | Temperature reliability | Read |
| HR 3 | Humidity reliability | UINT16 | Humidity reliability | Read |
Enable Modbus control & writes
DIP2 switch 7 OFF = configure over Modbus (registers 764-766); ON = DIP switch configuration (DIP1 address, DIP2 baud/parity/stop).
Byte order & addressing
- Register number minus 1 = wire address.
- Temperature follows the unit in register 401.
Network setup
- Bus termination is set with a jumper.
Watch out for
- Invalid DIP address: new communication settings are not applied.
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Temperature value | Signed, hundredths of a degree in the selected unit. | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 1doc 2 | Temperature reliability | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | ||||
| HR | 2doc 3 | Relative humidity value | UINT16 | × 0.01 | % | Read | |||
| HR | 3doc 4 | Humidity reliability | UINT16 | Read | 0 = No error; 1 = Bad reliability / unavailable | ||||
| HR | 400doc 401 | System unit | Temperature unit. | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 763doc 764 | Modbus address | 1-247. | UINT16 | Read/write | ||||
| HR | 764doc 765 | Baud rate | UINT16 | Read/write | 0 = Auto; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 76800; 6 = 115200 | ||||
| HR | 765doc 766 | Transmission format | Start-data-parity-stop bits. | UINT16 | Read/write | 0 = 1-8-E-1; 1 = 1-8-O-1; 2 = 1-8-N-1; 3 = 1-8-N-2 | |||
| HR | 1285doc 1286 | SW version major/minor | Major in high byte, minor in low byte. | UINT16 | Read | ||||
| HR | 1286doc 1287 | SW version build | UINT16 | Read |
Notes on this map
- Only 16-bit registers are published.
- Default baud is Auto; default format 1-8-E-1; default address 1.
- Registers 764-766 are read-only to the master while DIP2 switch 7 is ON.
- Temperature is treated as signed because the published range goes below zero.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
What Modbus registers does the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) have?
This map lists 10 registers: 10 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The source states that register numbers count from 1, so register 1 (temperature) is wire address 0.
What are the minimum Modbus registers to integrate the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)?
Start with HR 0 Temperature value (Temperature); HR 2 Relative humidity value (Relative humidity); HR 1 Temperature reliability (Temperature reliability); HR 3 Humidity reliability (Humidity reliability).
How do I enable Modbus control of the Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)?
DIP2 switch 7 OFF = configure over Modbus (registers 764-766); ON = DIP switch configuration (DIP1 address, DIP2 baud/parity/stop).
Where is the official Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU) Modbus documentation?
The source is QFA3150/MO Room relative humidity and temperature sensor Modbus RTU (RS-485) Basic Documentation (A6V12297475_en--_a), revision 2021-01-20, published free by Siemens at https://sid.siemens.com/api/khub/documents/wrAPGtzMEtAbUJc00QyHYA/content.
More Siemens Modbus register maps
- Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other valves, actuators & sensors register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series
All valves, actuators & sensors Modbus register maps →
Source: QFA3150/MO Room relative humidity and temperature sensor Modbus RTU (RS-485) Basic Documentation · A6V12297475_en--_a · rev. 2021-01-20. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.