Motor management and protection relay · Modbus register map
Siemens SIMOCODE pro V Modbus RTU basic unit Modbus register map
Updated 17 November 2026
SIMOCODE pro V Modbus is a motor management and protection system whose basic unit has a built-in RS-485 Modbus RTU slave. Its data sets are mapped into one bit memory area (coils/discrete inputs) and one register memory area. This map covers the cyclic command and monitoring bits, motor currents, voltages and power, statistics and the device diagnostic bits.
This page lists 258 Modbus registers for the Siemens SIMOCODE pro V Modbus RTU basic unit — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- SIMOCODE pro V Modbus RTU basic unit
- Equipment type
- Motor management and protection relay
- Registers
- 258 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- 126
- Default serial
- 19200 baud
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU
Integration notes: Siemens SIMOCODE pro V Modbus RTU basic unit
Set the address (default 126) and baud (default 19200), then read holding registers 0x0806-0x081D for currents, voltages and power, and discrete inputs 0x1C08 onward for status. Control the motor through coils 0x0000-0x0002 (ON<, OFF, ON> in the default process image).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2055 | Current I_L1 | UINT16 | Current L1 (% of Is) | Read |
| HR 2054 | Max. current I_max | UINT16 | Max. phase current | Read |
| HR 2074 | Active power P | UINT32 ABCD | Active power | Read |
| DI 7176 | Status - group fault | BIT | Group fault | Read |
| DI 7186 | Status - Off | BIT | Status Off | Read |
| CO 2 | Cyclic receive bit 0.2 | BIT | Command ON> (default) | Read/write |
| CO 1 | Cyclic receive bit 0.1 | BIT | Command OFF (default) | Read/write |
Enable Modbus control & writes
Set the Modbus address with the addressing plug (DIP switches 1-247, press TEST/RESET) or in SIMOCODE ES (Parameter > Modbus), together with baud rate, port configuration (8E1/8O1/8N2/8N1) and wait time. Remote control over the bus needs the operating mode Remote (mode selector S1 = 1 and S2 = 1).
Communication loss & watchdog
Watchdog / watchdog time in the Modbus parameters: if no valid read or write arrives within the time, the unit restarts its baud search (auto baud) and, with Bus monitoring enabled, raises 'Fault - bus'. 'PLC/PCS monitoring' raises 'Fault - PLC/PCS' when its input (normally cyclic receive bit 0.7) drops in Remote mode.
Byte order & addressing
- Addresses are hex offsets sent as-is.
- D words are big-endian, high word first.
- Currents are percent of the set current Is, not amps.
Network setup
- Default address 126, default baud 19200; 300-57600 baud or auto (4.8-57.6 kbps, needs the watchdog on).
- RS-485 via terminals A/B/SPE or the 9-pin sub-D (alternatives, not both).
- Port configuration 8E1, 8O1, 8N2 or 8N1.
Watch out for
- Coil writes accept only 0x0000 and 0xFF00.
- A writable bit block cannot be written across read-only bits.
- Auto baud detection works only with the watchdog enabled.
Siemens SIMOCODE pro V Modbus RTU basic unit Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | Cyclic receive bit 0.0 | Default assignment: Control station PLC/PCS ON<. | BIT | Read/write | ||||
| CO | 1doc 0x0001 | Cyclic receive bit 0.1 | Default assignment: Control station PLC/PCS OFF. | BIT | Read/write | ||||
| CO | 2doc 0x0002 | Cyclic receive bit 0.2 | Default assignment: Control station PLC/PCS ON>. | BIT | Read/write | ||||
| CO | 3doc 0x0003 | Cyclic receive bit 0.3 | Default assignment: Test 1. | BIT | Read/write | ||||
| CO | 4doc 0x0004 | Cyclic receive bit 0.4 | Default assignment: Motor protection emergency start. | BIT | Read/write | ||||
| CO | 5doc 0x0005 | Cyclic receive bit 0.5 | Default assignment: Mode selector S1. | BIT | Read/write | ||||
| CO | 6doc 0x0006 | Cyclic receive bit 0.6 | Default assignment: Reset 1. | BIT | Read/write | ||||
| CO | 7doc 0x0007 | Cyclic receive bit 0.7 | Default assignment: Unassigned (bit 0.7). | BIT | Read/write | ||||
| DI | 1024doc 0x0400 | Cyclic send bit 0.0 | Default assignment: Status - On<. | BIT | Read | ||||
| DI | 1025doc 0x0401 | Cyclic send bit 0.1 | Default assignment: Status - Off. | BIT | Read | ||||
| DI | 1026doc 0x0402 | Cyclic send bit 0.2 | Default assignment: Status - On>. | BIT | Read | ||||
| DI | 1027doc 0x0403 | Cyclic send bit 0.3 | Default assignment: Event - overload operation. | BIT | Read | ||||
| DI | 1028doc 0x0404 | Cyclic send bit 0.4 | Default assignment: Status - Interlocking time active. | BIT | Read | ||||
| DI | 1029doc 0x0405 | Cyclic send bit 0.5 | Default assignment: Status - Remote mode. | BIT | Read | ||||
| DI | 1030doc 0x0406 | Cyclic send bit 0.6 | Default assignment: Status - group fault. | BIT | Read | ||||
| DI | 1031doc 0x0407 | Cyclic send bit 0.7 | Default assignment: Status - group warning. | BIT | Read | ||||
| DI | 7176doc 0x1C08 | Status - group fault | BIT | Read | |||||
| DI | 7177doc 0x1C09 | Status - group warning | BIT | Read | |||||
| DI | 7178doc 0x1C0A | Status - device | BIT | Read | |||||
| DI | 7179doc 0x1C0B | Status - bus | BIT | Read | |||||
| DI | 7180doc 0x1C0C | Status - PLC/PCS | BIT | Read | |||||
| DI | 7181doc 0x1C0D | Status - current flowing | BIT | Read | |||||
| DI | 7182doc 0x1C0E | Status - PE command Start_Pause pending | BIT | Read | |||||
| DI | 7183doc 0x1C0F | Status - PE energy saving mode active | BIT | Read | |||||
| DI | 7184doc 0x1C10 | Status - On<< | BIT | Read | |||||
| DI | 7185doc 0x1C11 | Status - On< | BIT | Read | |||||
| DI | 7186doc 0x1C12 | Status - Off | BIT | Read | |||||
| DI | 7187doc 0x1C13 | Status - On> | BIT | Read | |||||
| DI | 7188doc 0x1C14 | Status - On>> | BIT | Read | |||||
| DI | 7189doc 0x1C15 | Status - start active | BIT | Read | |||||
| DI | 7190doc 0x1C16 | Status - Interlocking time active | BIT | Read | |||||
| DI | 7191doc 0x1C17 | Status - Change-over pause active | BIT | Read | |||||
| DI | 7192doc 0x1C18 | Status - Runs in open direction | BIT | Read | |||||
| DI | 7193doc 0x1C19 | Status - Runs in close direction | BIT | Read | |||||
| DI | 7194doc 0x1C1A | Status - FC | BIT | Read | |||||
| DI | 7195doc 0x1C1B | Status - FO | BIT | Read | |||||
| DI | 7196doc 0x1C1C | Status - TC | BIT | Read | |||||
| DI | 7197doc 0x1C1D | Status - TO | BIT | Read | |||||
| DI | 7198doc 0x1C1E | Status - Cold run TPF | BIT | Read | |||||
| DI | 7199doc 0x1C1F | Status - OPO | BIT | Read | |||||
| DI | 7200doc 0x1C20 | Status - Auto mode | BIT | Read | |||||
| DI | 7201doc 0x1C21 | Status - Emergency start executed | BIT | Read | |||||
| DI | 7202doc 0x1C22 | Status - Cooling down period active | BIT | Read | |||||
| DI | 7203doc 0x1C23 | Status - Pause time active | BIT | Read | |||||
| DI | 7204doc 0x1C24 | Status - Device test active | BIT | Read | |||||
| DI | 7205doc 0x1C25 | Status - Phase sequence 1-2-3 | BIT | Read | |||||
| DI | 7206doc 0x1C26 | Status - Phase sequence 3-2-1 | BIT | Read | |||||
| DI | 7207doc 0x1C27 | Status - DM-F enabling circuit | BIT | Read | |||||
| DI | 7208doc 0x1C28 | Event - overload operation | BIT | Read | |||||
| DI | 7209doc 0x1C29 | Event - unbalance | BIT | Read | |||||
| DI | 7210doc 0x1C2A | Event - overload | BIT | Read | |||||
| DI | 7211doc 0x1C2B | Event - overload + phase failure | BIT | Read | |||||
| DI | 7212doc 0x1C2C | Event - internal ground fault | BIT | Read | |||||
| DI | 7213doc 0x1C2D | Event - external ground fault | BIT | Read | |||||
| DI | 7214doc 0x1C2E | Event - external ground fault warning | BIT | Read | |||||
| DI | 7215doc 0x1C2F | Event - thermistor overload | BIT | Read | |||||
| DI | 7216doc 0x1C30 | Event - thermistor short circuit | BIT | Read | |||||
| DI | 7217doc 0x1C31 | Event - thermistor open circuit | BIT | Read | |||||
| DI | 7218doc 0x1C32 | Event - TM warning T> | BIT | Read | |||||
| DI | 7219doc 0x1C33 | Event - TM trip T> | BIT | Read | |||||
| DI | 7220doc 0x1C34 | Event - TM sensor fault | BIT | Read | |||||
| DI | 7221doc 0x1C35 | Event - TM out of range | BIT | Read | |||||
| DI | 7222doc 0x1C36 | Event - EM+ open circuit | BIT | Read | |||||
| DI | 7223doc 0x1C37 | Event - EM+ short-circuit | BIT | Read | |||||
| DI | 7224doc 0x1C38 | Event - Warning I> | BIT | Read | |||||
| DI | 7225doc 0x1C39 | Event - Warning I< | BIT | Read | |||||
| DI | 7226doc 0x1C3A | Event - Warning P> | BIT | Read | |||||
| DI | 7227doc 0x1C3B | Event - Warning P< | BIT | Read | |||||
| DI | 7228doc 0x1C3C | Event - Warning cos phi< | BIT | Read | |||||
| DI | 7229doc 0x1C3D | Event - Warning U< | BIT | Read | |||||
| DI | 7230doc 0x1C3E | Event - warning 0/4 - 20mA> | BIT | Read | |||||
| DI | 7231doc 0x1C3F | Event - warning 0/4 - 20mA< | BIT | Read | |||||
| DI | 7232doc 0x1C40 | Event - Trip I> | BIT | Read | |||||
| DI | 7233doc 0x1C41 | Event - Trip I< | BIT | Read | |||||
| DI | 7234doc 0x1C42 | Event - Trip P> | BIT | Read | |||||
| DI | 7235doc 0x1C43 | Event - Trip P< | BIT | Read | |||||
| DI | 7236doc 0x1C44 | Event - Trip cos phi< | BIT | Read | |||||
| DI | 7237doc 0x1C45 | Event - Trip U< | BIT | Read | |||||
| DI | 7238doc 0x1C46 | Event - Trip 0/4-20 mA> 1 | BIT | Read | |||||
| DI | 7239doc 0x1C47 | Event - Trip 0/4-20 mA< 1 | BIT | Read | |||||
| DI | 7240doc 0x1C48 | Event - Stalled rotor | BIT | Read | |||||
| DI | 7243doc 0x1C4B | Event - no start permitted | BIT | Read | |||||
| DI | 7244doc 0x1C4C | Event - No. of starts > | BIT | Read | |||||
| DI | 7245doc 0x1C4D | Event - Just one start possible | BIT | Read | |||||
| DI | 7246doc 0x1C4E | Event - Motor operating hours > | BIT | Read | |||||
| DI | 7247doc 0x1C4F | Event - Motor stop time > | BIT | Read | |||||
| DI | 7248doc 0x1C50 | Event - Limit 1 | BIT | Read | |||||
| DI | 7249doc 0x1C51 | Event - Limit 2 | BIT | Read | |||||
| DI | 7250doc 0x1C52 | Event - Limit 3 | BIT | Read | |||||
| DI | 7251doc 0x1C53 | Event - Limit 4 | BIT | Read | |||||
| DI | 7252doc 0x1C54 | Event - External fault 1 | BIT | Read | |||||
| DI | 7253doc 0x1C55 | Event - External fault 2 | BIT | Read | |||||
| DI | 7254doc 0x1C56 | Event - External fault 3 | BIT | Read | |||||
| DI | 7255doc 0x1C57 | Event - External fault 4 | BIT | Read | |||||
| DI | 7256doc 0x1C58 | Event - External fault 5 | BIT | Read | |||||
| DI | 7257doc 0x1C59 | Event - External fault 6 | BIT | Read | |||||
| DI | 7260doc 0x1C5C | Event - AM1 open circuit | BIT | Read | |||||
| DI | 7261doc 0x1C5D | Event - DM-F safety-related tripping | BIT | Read | |||||
| DI | 7262doc 0x1C5E | Event - DM-F - Test requirement | BIT | Read | |||||
| DI | 7264doc 0x1C60 | Event - timestamp function active + ok | BIT | Read | |||||
| DI | 7266doc 0x1C62 | Event - DM-FL safety ok | BIT | Read | |||||
| DI | 7268doc 0x1C64 | Event - Configured operator panel missing | BIT | Read | |||||
| DI | 7269doc 0x1C65 | Event - Module not supported | BIT | Read | |||||
| DI | 7270doc 0x1C66 | Event - module voltage missing | BIT | Read | |||||
| DI | 7272doc 0x1C68 | Event - memory module read in | BIT | Read | |||||
| DI | 7273doc 0x1C69 | Event - memory module programmed | BIT | Read | |||||
| DI | 7274doc 0x1C6A | Event - Memory module erased | BIT | Read | |||||
| DI | 7276doc 0x1C6C | Event - Initialization module read in | BIT | Read | |||||
| DI | 7277doc 0x1C6D | Event - Initialization module programmed | BIT | Read | |||||
| DI | 7278doc 0x1C6E | Event - Initialization module cleared | BIT | Read | |||||
| DI | 7279doc 0x1C6F | Event - Addressing plug read in | BIT | Read | |||||
| DI | 7280doc 0x1C70 | Event - startup parameter block active | BIT | Read | |||||
| DI | 7281doc 0x1C71 | Event - parameter changes not allowed in the current operating state | BIT | Read | |||||
| DI | 7282doc 0x1C72 | Event - Device does not support the required functions | BIT | Read | |||||
| DI | 7283doc 0x1C73 | Event - Bad parameter | BIT | Read | |||||
| DI | 7284doc 0x1C74 | Event - Password wrong | BIT | Read | |||||
| DI | 7285doc 0x1C75 | Event - Password protection active | BIT | Read | |||||
| DI | 7286doc 0x1C76 | Event - Factory settings | BIT | Read | |||||
| DI | 7287doc 0x1C77 | Event - Parameterization active | BIT | Read | |||||
| DI | 7296doc 0x1C80 | Event - DM-FL configuration operation | BIT | Read | |||||
| DI | 7297doc 0x1C81 | Event - DM-FL actual and set configuration are different | BIT | Read | |||||
| DI | 7298doc 0x1C82 | Event - DM-FL waiting for start-up test | BIT | Read | |||||
| DI | 7300doc 0x1C84 | Event - initialization module write-protected, parameter changes not allowed | BIT | Read | |||||
| DI | 7301doc 0x1C85 | Event - memory module write-protected | BIT | Read | |||||
| DI | 7302doc 0x1C86 | Event - initialization module write-protected | BIT | Read | |||||
| DI | 7303doc 0x1C87 | Event - initialization module ident. data write protected | BIT | Read | |||||
| DI | 7304doc 0x1C88 | Warning - overload operation | BIT | Read | |||||
| DI | 7305doc 0x1C89 | Warning - Unbalance | BIT | Read | |||||
| DI | 7306doc 0x1C8A | Warning - Overload | BIT | Read | |||||
| DI | 7307doc 0x1C8B | Warning - Overload + phase failure | BIT | Read | |||||
| DI | 7308doc 0x1C8C | Warning - Internal ground fault | BIT | Read | |||||
| DI | 7309doc 0x1C8D | Warning - external ground fault | BIT | Read | |||||
| DI | 7311doc 0x1C8F | Warning - Thermistor overload | BIT | Read | |||||
| DI | 7312doc 0x1C90 | Warning - Thermistor short circuit | BIT | Read | |||||
| DI | 7313doc 0x1C91 | Warning - Thermistor open circuit | BIT | Read | |||||
| DI | 7314doc 0x1C92 | Warning - TM1 warning T > | BIT | Read | |||||
| DI | 7316doc 0x1C94 | Warning - TM1 sensor fault | BIT | Read | |||||
| DI | 7317doc 0x1C95 | Warning - TM1 out of range | BIT | Read | |||||
| DI | 7318doc 0x1C96 | Warning - EM+ open circuit | BIT | Read | |||||
| DI | 7319doc 0x1C97 | Warning - EM+ short circuit | BIT | Read | |||||
| DI | 7320doc 0x1C98 | Warning - Warning I> | BIT | Read | |||||
| DI | 7321doc 0x1C99 | Warning - Warning I< | BIT | Read | |||||
| DI | 7322doc 0x1C9A | Warning - Warning P> | BIT | Read | |||||
| DI | 7323doc 0x1C9B | Warning - Warning P< | BIT | Read | |||||
| DI | 7324doc 0x1C9C | Warning - Warning cos phi< | BIT | Read | |||||
| DI | 7325doc 0x1C9D | Warning - Warning U< | BIT | Read | |||||
| DI | 7326doc 0x1C9E | Warning - Warning 0/4 - 20mA> | BIT | Read | |||||
| DI | 7327doc 0x1C9F | Warning - Warning 0/4 - 20mA< | BIT | Read | |||||
| DI | 7328doc 0x1CA0 | Warning - Stalled rotor | BIT | Read | |||||
| DI | 7331doc 0x1CA3 | Warning - No start possible | BIT | Read | |||||
| DI | 7332doc 0x1CA4 | Warning - Number of starts > | BIT | Read | |||||
| DI | 7333doc 0x1CA5 | Warning - Just one start possible | BIT | Read | |||||
| DI | 7334doc 0x1CA6 | Warning - Motor operating hours> | BIT | Read | |||||
| DI | 7335doc 0x1CA7 | Warning - Motor stop time > | BIT | Read | |||||
| DI | 7336doc 0x1CA8 | Warning - External fault 1 | BIT | Read | |||||
| DI | 7337doc 0x1CA9 | Warning - External fault 2 | BIT | Read | |||||
| DI | 7338doc 0x1CAA | Warning - External fault 3 | BIT | Read | |||||
| DI | 7339doc 0x1CAB | Warning - External fault 4 | BIT | Read | |||||
| DI | 7340doc 0x1CAC | Warning - External fault 5 | BIT | Read | |||||
| DI | 7341doc 0x1CAD | Warning - External fault 6 | BIT | Read | |||||
| DI | 7344doc 0x1CB0 | Warning - AM1 open circuit | BIT | Read | |||||
| DI | 7345doc 0x1CB1 | Warning - DM-F safety-related tripping | BIT | Read | |||||
| DI | 7346doc 0x1CB2 | Warning - DM-F test requirement | BIT | Read | |||||
| DI | 7350doc 0x1CB6 | Warning - DM-F feedback circuit | BIT | Read | |||||
| DI | 7351doc 0x1CB7 | Warning - DM-FL simultaneity | BIT | Read | |||||
| DI | 7352doc 0x1CB8 | Fault - hardware fault basic unit | BIT | Read | |||||
| DI | 7353doc 0x1CB9 | Fault - Module fault | BIT | Read | |||||
| DI | 7354doc 0x1CBA | Fault - Temporary components | BIT | Read | |||||
| DI | 7355doc 0x1CBB | Fault - configuration error | BIT | Read | |||||
| DI | 7356doc 0x1CBC | Fault - Parameterization | BIT | Read | |||||
| DI | 7357doc 0x1CBD | Fault - bus | BIT | Read | |||||
| DI | 7358doc 0x1CBE | Fault - PLC/PCS | BIT | Read | |||||
| DI | 7360doc 0x1CC0 | Fault - execution ON command | BIT | Read | |||||
| DI | 7361doc 0x1CC1 | Fault - execution STOP command | BIT | Read | |||||
| DI | 7362doc 0x1CC2 | Fault - feedback (FB) ON | BIT | Read | |||||
| DI | 7363doc 0x1CC3 | Fault - feedback (FB) OFF | BIT | Read | |||||
| DI | 7364doc 0x1CC4 | Fault - stalled positioner | BIT | Read | |||||
| DI | 7365doc 0x1CC5 | Fault - double 0 | BIT | Read | |||||
| DI | 7366doc 0x1CC6 | Fault - double 1 | BIT | Read | |||||
| DI | 7367doc 0x1CC7 | Fault - end position | BIT | Read | |||||
| DI | 7368doc 0x1CC8 | Fault - antivalence | BIT | Read | |||||
| DI | 7369doc 0x1CC9 | Fault - Cold run (TPF) error | BIT | Read | |||||
| DI | 7370doc 0x1CCA | Fault - power failure (UVO) | BIT | Read | |||||
| DI | 7371doc 0x1CCB | Fault - Operational Protection Off (OPO) | BIT | Read | |||||
| DI | 7377doc 0x1CD1 | Fault - unbalance | BIT | Read | |||||
| DI | 7378doc 0x1CD2 | Fault - overload | BIT | Read | |||||
| DI | 7379doc 0x1CD3 | Fault - overload + phase failure | BIT | Read | |||||
| DI | 7380doc 0x1CD4 | Fault - int. ground fault | BIT | Read | |||||
| DI | 7381doc 0x1CD5 | Fault - ext. ground fault | BIT | Read | |||||
| DI | 7383doc 0x1CD7 | Fault - thermistor overload | BIT | Read | |||||
| DI | 7384doc 0x1CD8 | Fault - thermistor short circuit | BIT | Read | |||||
| DI | 7385doc 0x1CD9 | Fault - thermistor open circuit | BIT | Read | |||||
| DI | 7387doc 0x1CDB | Trip - TM1 trip T> | BIT | Read | |||||
| DI | 7388doc 0x1CDC | Trip - TM1 sensor fault | BIT | Read | |||||
| DI | 7389doc 0x1CDD | Trip - TM1 out of range | BIT | Read | |||||
| DI | 7390doc 0x1CDE | Fault - EM+ open circuit | BIT | Read | |||||
| DI | 7391doc 0x1CDF | Fault - EM+ short circuit | BIT | Read | |||||
| DI | 7392doc 0x1CE0 | Fault - trip I> | BIT | Read | |||||
| DI | 7393doc 0x1CE1 | Fault - trip I< | BIT | Read | |||||
| DI | 7394doc 0x1CE2 | Fault - trip P> | BIT | Read | |||||
| DI | 7395doc 0x1CE3 | Fault - trip P< | BIT | Read | |||||
| DI | 7396doc 0x1CE4 | Fault - trip cos phi< | BIT | Read | |||||
| DI | 7397doc 0x1CE5 | Fault - trip U< | BIT | Read | |||||
| DI | 7398doc 0x1CE6 | Fault - Trip 0/4 - 20mA> | BIT | Read | |||||
| DI | 7399doc 0x1CE7 | Fault - Trip 0/4 - 20mA< | BIT | Read | |||||
| DI | 7400doc 0x1CE8 | Fault - stalled rotor | BIT | Read | |||||
| DI | 7404doc 0x1CEC | Fault - Number of starts > | BIT | Read | |||||
| DI | 7408doc 0x1CF0 | Fault - External fault 1 | BIT | Read | |||||
| DI | 7409doc 0x1CF1 | Fault - External fault 2 | BIT | Read | |||||
| DI | 7410doc 0x1CF2 | Fault - External fault 3 | BIT | Read | |||||
| DI | 7411doc 0x1CF3 | Fault - External fault 4 | BIT | Read | |||||
| DI | 7412doc 0x1CF4 | Fault - External fault 5 | BIT | Read | |||||
| DI | 7413doc 0x1CF5 | Fault - External fault 6 | BIT | Read | |||||
| DI | 7416doc 0x1CF8 | Fault - AM1 open circuit | BIT | Read | |||||
| DI | 7417doc 0x1CF9 | Fault - test trip | BIT | Read | |||||
| DI | 7418doc 0x1CFA | Fault - DM-F safety-related tripping | BIT | Read | |||||
| DI | 7419doc 0x1CFB | Fault - DM-F wiring | BIT | Read | |||||
| DI | 7420doc 0x1CFC | Fault - DM-FL cross circuit | BIT | Read | |||||
| HR | 1doc 0x0001 | Cyclic receive - analog value | Unassigned by default. | UINT16 | Read/write | ||||
| HR | 1025doc 0x0401 | PLC/PCS analog input 1 | Default: maximum current I_max. | UINT16 | Read | ||||
| HR | 1026doc 0x0402 | PLC/PCS analog input 2 | Unassigned by default. | UINT16 | Read | ||||
| HR | 1027doc 0x0403 | PLC/PCS analog input 3 | Unassigned by default. | UINT16 | Read | ||||
| HR | 1028doc 0x0404 | PLC/PCS analog input 4 | Unassigned by default. | UINT16 | Read | ||||
| HR | 2054doc 0x0806 | Max. current I_max | Percent of set current Is. | UINT16 | % | Read | |||
| HR | 2055doc 0x0807 | Current I_L1 | Percent of set current Is. | UINT16 | % | Read | |||
| HR | 2056doc 0x0808 | Current I_L2 | Percent of set current Is. | UINT16 | % | Read | |||
| HR | 2057doc 0x0809 | Current I_L3 | Percent of set current Is. | UINT16 | % | Read | |||
| HR | 2058doc 0x080A | Last trip current | Percent of set current Is. | UINT16 | % | Read | |||
| HR | 2059doc 0x080B | Time to trip | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 2060doc 0x080C | Cooling down period | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 2061doc 0x080D | Voltage U_L1 | UINT16 | V | Read | ||||
| HR | 2062doc 0x080E | Voltage U_L2 | UINT16 | V | Read | ||||
| HR | 2063doc 0x080F | Voltage U_L3 | UINT16 | V | Read | ||||
| HR | 2064doc 0x0810 | AM1 - output | S7 format: 0/4 mA = 0, 20 mA = 27648. | UINT16 | Read | ||||
| HR | 2068doc 0x0814 | TM1 - temperature | Temperature module 1, in kelvin. | UINT16 | K | Read | |||
| HR | 2074doc 0x081A | Active power P | UINT32 | ABCD | W | Read | |||
| HR | 2076doc 0x081C | Apparent power S | UINT32 | ABCD | VA | Read | |||
| HR | 3076doc 0x0C04 | Number of parameterizations | UINT16 | Read | |||||
| HR | 3077doc 0x0C05 | Number of overload trips | UINT16 | Read/write | |||||
| HR | 3078doc 0x0C06 | Number of internal overload trips | UINT16 | Read | |||||
| HR | 3079doc 0x0C07 | Stop time | UINT16 | h | Read/write | ||||
| HR | 3080doc 0x0C08 | Timer 1 actual value | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 3081doc 0x0C09 | Timer 2 actual value | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 3082doc 0x0C0A | Timer 3 actual value | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 3083doc 0x0C0B | Timer 4 actual value | Printed unit 100 ms. | UINT16 | × 0.1 | s | Read | ||
| HR | 3084doc 0x0C0C | Counter 1 actual value | UINT16 | Read | |||||
| HR | 3085doc 0x0C0D | Counter 2 actual value | UINT16 | Read | |||||
| HR | 3086doc 0x0C0E | Counter 3 actual value | UINT16 | Read | |||||
| HR | 3087doc 0x0C0F | Counter 4 actual value | UINT16 | Read | |||||
| HR | 3088doc 0x0C10 | Calculator 1 output | UINT16 | Read | |||||
| HR | 3089doc 0x0C11 | Calculator 2 output | UINT16 | Read | |||||
| HR | 3092doc 0x0C14 | Motor operating hours | Counted in seconds despite the name. | UINT32 | ABCD | s | Read/write | ||
| HR | 3094doc 0x0C16 | Internal motor operating hours | Counted in seconds despite the name. | UINT32 | ABCD | s | Read | ||
| HR | 3096doc 0x0C18 | Device operating hours | Counted in seconds despite the name. | UINT32 | ABCD | s | Read | ||
| HR | 3098doc 0x0C1A | Number of starts | UINT32 | ABCD | Read/write | ||||
| HR | 3100doc 0x0C1C | Number of internal starts CW | UINT32 | ABCD | Read | ||||
| HR | 3102doc 0x0C1E | Number of internal starts CCW | UINT32 | ABCD | Read | ||||
| HR | 3104doc 0x0C20 | Energy W | UINT32 | ABCD | kWh | Read/write |
Notes on this map
- Word order: the manual says data longer than one byte is stored big-endian (figure 4-1), so the D word values (power, operating hours, starts, energy) are high word first (ABCD).
- Function codes 03 and 04 return the same register data, and 01 and 02 the same bit data; registers are listed as holding registers and read-only bits as discrete inputs.
- The coil and input-bit assignments shown are the factory defaults of the process image; they can be reassigned in SIMOCODE ES.
- Each diagnostic register 0x1C00-0x1C0F also holds 16 of the diagnostic bits (bit address = 0x1C00 + 16 x register offset + bit). Only the bit addresses are listed, because the manual's FC 01 example confirms them.
- Left out: byte-packed values (thermal motor model, phase unbalance and cos phi in 0x0802-0x0803, permissible starts in 0x0C02), AM1 inputs, TM1 temperatures 1-3 and EM+ currents (no unit printed), error/event memory, trace data, I&M records and the device parameters from 0x4180 (parameter writes need the full tables on pp. 58-77).
- Several operating-hour values are counted in seconds (unit 1 s) even though their name says hours.
- The FC 03 example on p. 27 prints the start address of the currents as 0x07 although the text says 0x0807; the table address 0x0807 is used here.
- Max per request: 2000 bits, 125 registers; the command image accepts at most 2 registers / 16 coils per access and measured values 16 registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens SIMOCODE pro V Modbus RTU basic unit
What Modbus registers does the Siemens SIMOCODE pro V Modbus RTU basic unit have?
This map lists 258 registers: 8 coils, 210 discrete inputs, 40 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens SIMOCODE pro V Modbus RTU basic unit Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as hex offsets and sent unchanged as the start address. The manual's examples read device status bits with start address 0x1C08 (FC 01) and write the cooling-down period at 0x419A (FC 06). In a 1-based tool add 1 (0x0807 = 2055 -> 42056).
What byte order does the Siemens SIMOCODE pro V Modbus RTU basic unit use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens SIMOCODE pro V Modbus RTU basic unit?
Start with HR 2055 Current I_L1 (Current L1 (% of Is)); HR 2054 Max. current I_max (Max. phase current); HR 2074 Active power P (Active power); DI 7176 Status - group fault (Group fault); DI 7186 Status - Off (Status Off); CO 2 Cyclic receive bit 0.2 (Command ON> (default)); CO 1 Cyclic receive bit 0.1 (Command OFF (default)).
How do I enable Modbus control of the Siemens SIMOCODE pro V Modbus RTU basic unit?
Set the Modbus address with the addressing plug (DIP switches 1-247, press TEST/RESET) or in SIMOCODE ES (Parameter > Modbus), together with baud rate, port configuration (8E1/8O1/8N2/8N1) and wait time. Remote control over the bus needs the operating mode Remote (mode selector S1 = 1 and S2 = 1).
What happens when the Siemens SIMOCODE pro V Modbus RTU basic unit loses Modbus communication?
Watchdog / watchdog time in the Modbus parameters: if no valid read or write arrives within the time, the unit restarts its baud search (auto baud) and, with Bus monitoring enabled, raises 'Fault - bus'. 'PLC/PCS monitoring' raises 'Fault - PLC/PCS' when its input (normally cyclic receive bit 0.7) drops in Remote mode.
Where is the official Siemens SIMOCODE pro V Modbus RTU basic unit Modbus documentation?
The source is SIMOCODE pro Modbus RTU Configuration Manual (A5E33498234002A/RS-AA/001), revision 2015-04, published free by Siemens at https://cache.industry.siemens.com/dl/files/641/108681641/att_840815/v1/Manual_SIMOCODE_pro_Modbus_en-US.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other soft starters & protection relays register maps
- Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370
All soft starters & protection relays Modbus register maps →
Source: SIMOCODE pro Modbus RTU Configuration Manual · A5E33498234002A/RS-AA/001 · rev. 2015-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.