Siemens SIMOCODE pro V Modbus RTU basic unit Modbus register map

Updated 17 November 2026

Short answer

SIMOCODE pro V Modbus is a motor management and protection system whose basic unit has a built-in RS-485 Modbus RTU slave. Its data sets are mapped into one bit memory area (coils/discrete inputs) and one register memory area. This map covers the cyclic command and monitoring bits, motor currents, voltages and power, statistics and the device diagnostic bits.

This page lists 258 Modbus registers for the Siemens SIMOCODE pro V Modbus RTU basic unit — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
SIMOCODE pro V Modbus RTU basic unit
Equipment type
Motor management and protection relay
Registers
258 (14 writable)
Transport
Modbus RTU
Default unit ID
126
Default serial
19200 baud
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU
Source document
SIMOCODE pro Modbus RTU Configuration Manual · A5E33498234002A/RS-AA/001 · rev. 2015-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens SIMOCODE pro V Modbus RTU basic unit

Integration in brief

Set the address (default 126) and baud (default 19200), then read holding registers 0x0806-0x081D for currents, voltages and power, and discrete inputs 0x1C08 onward for status. Control the motor through coils 0x0000-0x0002 (ON<, OFF, ON> in the default process image).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2055Current I_L1UINT16Current L1 (% of Is)Read
HR 2054Max. current I_maxUINT16Max. phase currentRead
HR 2074Active power PUINT32 ABCDActive powerRead
DI 7176Status - group faultBITGroup faultRead
DI 7186Status - OffBITStatus OffRead
CO 2Cyclic receive bit 0.2BITCommand ON> (default)Read/write
CO 1Cyclic receive bit 0.1BITCommand OFF (default)Read/write

Enable Modbus control & writes

Set the Modbus address with the addressing plug (DIP switches 1-247, press TEST/RESET) or in SIMOCODE ES (Parameter > Modbus), together with baud rate, port configuration (8E1/8O1/8N2/8N1) and wait time. Remote control over the bus needs the operating mode Remote (mode selector S1 = 1 and S2 = 1).

Communication loss & watchdog

Watchdog / watchdog time in the Modbus parameters: if no valid read or write arrives within the time, the unit restarts its baud search (auto baud) and, with Bus monitoring enabled, raises 'Fault - bus'. 'PLC/PCS monitoring' raises 'Fault - PLC/PCS' when its input (normally cyclic receive bit 0.7) drops in Remote mode.

Byte order & addressing

Network setup

Watch out for

Siemens SIMOCODE pro V Modbus RTU basic unit Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

258 of 258 shown
Siemens SIMOCODE pro V Modbus RTU basic unit Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0000Cyclic receive bit 0.0Default assignment: Control station PLC/PCS ON<.BITRead/write
CO1doc 0x0001Cyclic receive bit 0.1Default assignment: Control station PLC/PCS OFF.BITRead/write
CO2doc 0x0002Cyclic receive bit 0.2Default assignment: Control station PLC/PCS ON>.BITRead/write
CO3doc 0x0003Cyclic receive bit 0.3Default assignment: Test 1.BITRead/write
CO4doc 0x0004Cyclic receive bit 0.4Default assignment: Motor protection emergency start.BITRead/write
CO5doc 0x0005Cyclic receive bit 0.5Default assignment: Mode selector S1.BITRead/write
CO6doc 0x0006Cyclic receive bit 0.6Default assignment: Reset 1.BITRead/write
CO7doc 0x0007Cyclic receive bit 0.7Default assignment: Unassigned (bit 0.7).BITRead/write
DI1024doc 0x0400Cyclic send bit 0.0Default assignment: Status - On<.BITRead
DI1025doc 0x0401Cyclic send bit 0.1Default assignment: Status - Off.BITRead
DI1026doc 0x0402Cyclic send bit 0.2Default assignment: Status - On>.BITRead
DI1027doc 0x0403Cyclic send bit 0.3Default assignment: Event - overload operation.BITRead
DI1028doc 0x0404Cyclic send bit 0.4Default assignment: Status - Interlocking time active.BITRead
DI1029doc 0x0405Cyclic send bit 0.5Default assignment: Status - Remote mode.BITRead
DI1030doc 0x0406Cyclic send bit 0.6Default assignment: Status - group fault.BITRead
DI1031doc 0x0407Cyclic send bit 0.7Default assignment: Status - group warning.BITRead
DI7176doc 0x1C08Status - group faultBITRead
DI7177doc 0x1C09Status - group warningBITRead
DI7178doc 0x1C0AStatus - deviceBITRead
DI7179doc 0x1C0BStatus - busBITRead
DI7180doc 0x1C0CStatus - PLC/PCSBITRead
DI7181doc 0x1C0DStatus - current flowingBITRead
DI7182doc 0x1C0EStatus - PE command Start_Pause pendingBITRead
DI7183doc 0x1C0FStatus - PE energy saving mode activeBITRead
DI7184doc 0x1C10Status - On<<BITRead
DI7185doc 0x1C11Status - On<BITRead
DI7186doc 0x1C12Status - OffBITRead
DI7187doc 0x1C13Status - On>BITRead
DI7188doc 0x1C14Status - On>>BITRead
DI7189doc 0x1C15Status - start activeBITRead
DI7190doc 0x1C16Status - Interlocking time activeBITRead
DI7191doc 0x1C17Status - Change-over pause activeBITRead
DI7192doc 0x1C18Status - Runs in open directionBITRead
DI7193doc 0x1C19Status - Runs in close directionBITRead
DI7194doc 0x1C1AStatus - FCBITRead
DI7195doc 0x1C1BStatus - FOBITRead
DI7196doc 0x1C1CStatus - TCBITRead
DI7197doc 0x1C1DStatus - TOBITRead
DI7198doc 0x1C1EStatus - Cold run TPFBITRead
DI7199doc 0x1C1FStatus - OPOBITRead
DI7200doc 0x1C20Status - Auto modeBITRead
DI7201doc 0x1C21Status - Emergency start executedBITRead
DI7202doc 0x1C22Status - Cooling down period activeBITRead
DI7203doc 0x1C23Status - Pause time activeBITRead
DI7204doc 0x1C24Status - Device test activeBITRead
DI7205doc 0x1C25Status - Phase sequence 1-2-3BITRead
DI7206doc 0x1C26Status - Phase sequence 3-2-1BITRead
DI7207doc 0x1C27Status - DM-F enabling circuitBITRead
DI7208doc 0x1C28Event - overload operationBITRead
DI7209doc 0x1C29Event - unbalanceBITRead
DI7210doc 0x1C2AEvent - overloadBITRead
DI7211doc 0x1C2BEvent - overload + phase failureBITRead
DI7212doc 0x1C2CEvent - internal ground faultBITRead
DI7213doc 0x1C2DEvent - external ground faultBITRead
DI7214doc 0x1C2EEvent - external ground fault warningBITRead
DI7215doc 0x1C2FEvent - thermistor overloadBITRead
DI7216doc 0x1C30Event - thermistor short circuitBITRead
DI7217doc 0x1C31Event - thermistor open circuitBITRead
DI7218doc 0x1C32Event - TM warning T>BITRead
DI7219doc 0x1C33Event - TM trip T>BITRead
DI7220doc 0x1C34Event - TM sensor faultBITRead
DI7221doc 0x1C35Event - TM out of rangeBITRead
DI7222doc 0x1C36Event - EM+ open circuitBITRead
DI7223doc 0x1C37Event - EM+ short-circuitBITRead
DI7224doc 0x1C38Event - Warning I>BITRead
DI7225doc 0x1C39Event - Warning I<BITRead
DI7226doc 0x1C3AEvent - Warning P>BITRead
DI7227doc 0x1C3BEvent - Warning P<BITRead
DI7228doc 0x1C3CEvent - Warning cos phi<BITRead
DI7229doc 0x1C3DEvent - Warning U<BITRead
DI7230doc 0x1C3EEvent - warning 0/4 - 20mA>BITRead
DI7231doc 0x1C3FEvent - warning 0/4 - 20mA<BITRead
DI7232doc 0x1C40Event - Trip I>BITRead
DI7233doc 0x1C41Event - Trip I<BITRead
DI7234doc 0x1C42Event - Trip P>BITRead
DI7235doc 0x1C43Event - Trip P<BITRead
DI7236doc 0x1C44Event - Trip cos phi<BITRead
DI7237doc 0x1C45Event - Trip U<BITRead
DI7238doc 0x1C46Event - Trip 0/4-20 mA> 1BITRead
DI7239doc 0x1C47Event - Trip 0/4-20 mA< 1BITRead
DI7240doc 0x1C48Event - Stalled rotorBITRead
DI7243doc 0x1C4BEvent - no start permittedBITRead
DI7244doc 0x1C4CEvent - No. of starts >BITRead
DI7245doc 0x1C4DEvent - Just one start possibleBITRead
DI7246doc 0x1C4EEvent - Motor operating hours >BITRead
DI7247doc 0x1C4FEvent - Motor stop time >BITRead
DI7248doc 0x1C50Event - Limit 1BITRead
DI7249doc 0x1C51Event - Limit 2BITRead
DI7250doc 0x1C52Event - Limit 3BITRead
DI7251doc 0x1C53Event - Limit 4BITRead
DI7252doc 0x1C54Event - External fault 1BITRead
DI7253doc 0x1C55Event - External fault 2BITRead
DI7254doc 0x1C56Event - External fault 3BITRead
DI7255doc 0x1C57Event - External fault 4BITRead
DI7256doc 0x1C58Event - External fault 5BITRead
DI7257doc 0x1C59Event - External fault 6BITRead
DI7260doc 0x1C5CEvent - AM1 open circuitBITRead
DI7261doc 0x1C5DEvent - DM-F safety-related trippingBITRead
DI7262doc 0x1C5EEvent - DM-F - Test requirementBITRead
DI7264doc 0x1C60Event - timestamp function active + okBITRead
DI7266doc 0x1C62Event - DM-FL safety okBITRead
DI7268doc 0x1C64Event - Configured operator panel missingBITRead
DI7269doc 0x1C65Event - Module not supportedBITRead
DI7270doc 0x1C66Event - module voltage missingBITRead
DI7272doc 0x1C68Event - memory module read inBITRead
DI7273doc 0x1C69Event - memory module programmedBITRead
DI7274doc 0x1C6AEvent - Memory module erasedBITRead
DI7276doc 0x1C6CEvent - Initialization module read inBITRead
DI7277doc 0x1C6DEvent - Initialization module programmedBITRead
DI7278doc 0x1C6EEvent - Initialization module clearedBITRead
DI7279doc 0x1C6FEvent - Addressing plug read inBITRead
DI7280doc 0x1C70Event - startup parameter block activeBITRead
DI7281doc 0x1C71Event - parameter changes not allowed in the current operating stateBITRead
DI7282doc 0x1C72Event - Device does not support the required functionsBITRead
DI7283doc 0x1C73Event - Bad parameterBITRead
DI7284doc 0x1C74Event - Password wrongBITRead
DI7285doc 0x1C75Event - Password protection activeBITRead
DI7286doc 0x1C76Event - Factory settingsBITRead
DI7287doc 0x1C77Event - Parameterization activeBITRead
DI7296doc 0x1C80Event - DM-FL configuration operationBITRead
DI7297doc 0x1C81Event - DM-FL actual and set configuration are differentBITRead
DI7298doc 0x1C82Event - DM-FL waiting for start-up testBITRead
DI7300doc 0x1C84Event - initialization module write-protected, parameter changes not allowedBITRead
DI7301doc 0x1C85Event - memory module write-protectedBITRead
DI7302doc 0x1C86Event - initialization module write-protectedBITRead
DI7303doc 0x1C87Event - initialization module ident. data write protectedBITRead
DI7304doc 0x1C88Warning - overload operationBITRead
DI7305doc 0x1C89Warning - UnbalanceBITRead
DI7306doc 0x1C8AWarning - OverloadBITRead
DI7307doc 0x1C8BWarning - Overload + phase failureBITRead
DI7308doc 0x1C8CWarning - Internal ground faultBITRead
DI7309doc 0x1C8DWarning - external ground faultBITRead
DI7311doc 0x1C8FWarning - Thermistor overloadBITRead
DI7312doc 0x1C90Warning - Thermistor short circuitBITRead
DI7313doc 0x1C91Warning - Thermistor open circuitBITRead
DI7314doc 0x1C92Warning - TM1 warning T >BITRead
DI7316doc 0x1C94Warning - TM1 sensor faultBITRead
DI7317doc 0x1C95Warning - TM1 out of rangeBITRead
DI7318doc 0x1C96Warning - EM+ open circuitBITRead
DI7319doc 0x1C97Warning - EM+ short circuitBITRead
DI7320doc 0x1C98Warning - Warning I>BITRead
DI7321doc 0x1C99Warning - Warning I<BITRead
DI7322doc 0x1C9AWarning - Warning P>BITRead
DI7323doc 0x1C9BWarning - Warning P<BITRead
DI7324doc 0x1C9CWarning - Warning cos phi<BITRead
DI7325doc 0x1C9DWarning - Warning U<BITRead
DI7326doc 0x1C9EWarning - Warning 0/4 - 20mA>BITRead
DI7327doc 0x1C9FWarning - Warning 0/4 - 20mA<BITRead
DI7328doc 0x1CA0Warning - Stalled rotorBITRead
DI7331doc 0x1CA3Warning - No start possibleBITRead
DI7332doc 0x1CA4Warning - Number of starts >BITRead
DI7333doc 0x1CA5Warning - Just one start possibleBITRead
DI7334doc 0x1CA6Warning - Motor operating hours>BITRead
DI7335doc 0x1CA7Warning - Motor stop time >BITRead
DI7336doc 0x1CA8Warning - External fault 1BITRead
DI7337doc 0x1CA9Warning - External fault 2BITRead
DI7338doc 0x1CAAWarning - External fault 3BITRead
DI7339doc 0x1CABWarning - External fault 4BITRead
DI7340doc 0x1CACWarning - External fault 5BITRead
DI7341doc 0x1CADWarning - External fault 6BITRead
DI7344doc 0x1CB0Warning - AM1 open circuitBITRead
DI7345doc 0x1CB1Warning - DM-F safety-related trippingBITRead
DI7346doc 0x1CB2Warning - DM-F test requirementBITRead
DI7350doc 0x1CB6Warning - DM-F feedback circuitBITRead
DI7351doc 0x1CB7Warning - DM-FL simultaneityBITRead
DI7352doc 0x1CB8Fault - hardware fault basic unitBITRead
DI7353doc 0x1CB9Fault - Module faultBITRead
DI7354doc 0x1CBAFault - Temporary componentsBITRead
DI7355doc 0x1CBBFault - configuration errorBITRead
DI7356doc 0x1CBCFault - ParameterizationBITRead
DI7357doc 0x1CBDFault - busBITRead
DI7358doc 0x1CBEFault - PLC/PCSBITRead
DI7360doc 0x1CC0Fault - execution ON commandBITRead
DI7361doc 0x1CC1Fault - execution STOP commandBITRead
DI7362doc 0x1CC2Fault - feedback (FB) ONBITRead
DI7363doc 0x1CC3Fault - feedback (FB) OFFBITRead
DI7364doc 0x1CC4Fault - stalled positionerBITRead
DI7365doc 0x1CC5Fault - double 0BITRead
DI7366doc 0x1CC6Fault - double 1BITRead
DI7367doc 0x1CC7Fault - end positionBITRead
DI7368doc 0x1CC8Fault - antivalenceBITRead
DI7369doc 0x1CC9Fault - Cold run (TPF) errorBITRead
DI7370doc 0x1CCAFault - power failure (UVO)BITRead
DI7371doc 0x1CCBFault - Operational Protection Off (OPO)BITRead
DI7377doc 0x1CD1Fault - unbalanceBITRead
DI7378doc 0x1CD2Fault - overloadBITRead
DI7379doc 0x1CD3Fault - overload + phase failureBITRead
DI7380doc 0x1CD4Fault - int. ground faultBITRead
DI7381doc 0x1CD5Fault - ext. ground faultBITRead
DI7383doc 0x1CD7Fault - thermistor overloadBITRead
DI7384doc 0x1CD8Fault - thermistor short circuitBITRead
DI7385doc 0x1CD9Fault - thermistor open circuitBITRead
DI7387doc 0x1CDBTrip - TM1 trip T>BITRead
DI7388doc 0x1CDCTrip - TM1 sensor faultBITRead
DI7389doc 0x1CDDTrip - TM1 out of rangeBITRead
DI7390doc 0x1CDEFault - EM+ open circuitBITRead
DI7391doc 0x1CDFFault - EM+ short circuitBITRead
DI7392doc 0x1CE0Fault - trip I>BITRead
DI7393doc 0x1CE1Fault - trip I<BITRead
DI7394doc 0x1CE2Fault - trip P>BITRead
DI7395doc 0x1CE3Fault - trip P<BITRead
DI7396doc 0x1CE4Fault - trip cos phi<BITRead
DI7397doc 0x1CE5Fault - trip U<BITRead
DI7398doc 0x1CE6Fault - Trip 0/4 - 20mA>BITRead
DI7399doc 0x1CE7Fault - Trip 0/4 - 20mA<BITRead
DI7400doc 0x1CE8Fault - stalled rotorBITRead
DI7404doc 0x1CECFault - Number of starts >BITRead
DI7408doc 0x1CF0Fault - External fault 1BITRead
DI7409doc 0x1CF1Fault - External fault 2BITRead
DI7410doc 0x1CF2Fault - External fault 3BITRead
DI7411doc 0x1CF3Fault - External fault 4BITRead
DI7412doc 0x1CF4Fault - External fault 5BITRead
DI7413doc 0x1CF5Fault - External fault 6BITRead
DI7416doc 0x1CF8Fault - AM1 open circuitBITRead
DI7417doc 0x1CF9Fault - test tripBITRead
DI7418doc 0x1CFAFault - DM-F safety-related trippingBITRead
DI7419doc 0x1CFBFault - DM-F wiringBITRead
DI7420doc 0x1CFCFault - DM-FL cross circuitBITRead
HR1doc 0x0001Cyclic receive - analog valueUnassigned by default.UINT16Read/write
HR1025doc 0x0401PLC/PCS analog input 1Default: maximum current I_max.UINT16Read
HR1026doc 0x0402PLC/PCS analog input 2Unassigned by default.UINT16Read
HR1027doc 0x0403PLC/PCS analog input 3Unassigned by default.UINT16Read
HR1028doc 0x0404PLC/PCS analog input 4Unassigned by default.UINT16Read
HR2054doc 0x0806Max. current I_maxPercent of set current Is.UINT16%Read
HR2055doc 0x0807Current I_L1Percent of set current Is.UINT16%Read
HR2056doc 0x0808Current I_L2Percent of set current Is.UINT16%Read
HR2057doc 0x0809Current I_L3Percent of set current Is.UINT16%Read
HR2058doc 0x080ALast trip currentPercent of set current Is.UINT16%Read
HR2059doc 0x080BTime to tripPrinted unit 100 ms.UINT16× 0.1sRead
HR2060doc 0x080CCooling down periodPrinted unit 100 ms.UINT16× 0.1sRead
HR2061doc 0x080DVoltage U_L1UINT16VRead
HR2062doc 0x080EVoltage U_L2UINT16VRead
HR2063doc 0x080FVoltage U_L3UINT16VRead
HR2064doc 0x0810AM1 - outputS7 format: 0/4 mA = 0, 20 mA = 27648.UINT16Read
HR2068doc 0x0814TM1 - temperatureTemperature module 1, in kelvin.UINT16KRead
HR2074doc 0x081AActive power PUINT32ABCDWRead
HR2076doc 0x081CApparent power SUINT32ABCDVARead
HR3076doc 0x0C04Number of parameterizationsUINT16Read
HR3077doc 0x0C05Number of overload tripsUINT16Read/write
HR3078doc 0x0C06Number of internal overload tripsUINT16Read
HR3079doc 0x0C07Stop timeUINT16hRead/write
HR3080doc 0x0C08Timer 1 actual valuePrinted unit 100 ms.UINT16× 0.1sRead
HR3081doc 0x0C09Timer 2 actual valuePrinted unit 100 ms.UINT16× 0.1sRead
HR3082doc 0x0C0ATimer 3 actual valuePrinted unit 100 ms.UINT16× 0.1sRead
HR3083doc 0x0C0BTimer 4 actual valuePrinted unit 100 ms.UINT16× 0.1sRead
HR3084doc 0x0C0CCounter 1 actual valueUINT16Read
HR3085doc 0x0C0DCounter 2 actual valueUINT16Read
HR3086doc 0x0C0ECounter 3 actual valueUINT16Read
HR3087doc 0x0C0FCounter 4 actual valueUINT16Read
HR3088doc 0x0C10Calculator 1 outputUINT16Read
HR3089doc 0x0C11Calculator 2 outputUINT16Read
HR3092doc 0x0C14Motor operating hoursCounted in seconds despite the name.UINT32ABCDsRead/write
HR3094doc 0x0C16Internal motor operating hoursCounted in seconds despite the name.UINT32ABCDsRead
HR3096doc 0x0C18Device operating hoursCounted in seconds despite the name.UINT32ABCDsRead
HR3098doc 0x0C1ANumber of startsUINT32ABCDRead/write
HR3100doc 0x0C1CNumber of internal starts CWUINT32ABCDRead
HR3102doc 0x0C1ENumber of internal starts CCWUINT32ABCDRead
HR3104doc 0x0C20Energy WUINT32ABCDkWhRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens SIMOCODE pro V Modbus RTU basic unit

What Modbus registers does the Siemens SIMOCODE pro V Modbus RTU basic unit have?

This map lists 258 registers: 8 coils, 210 discrete inputs, 40 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens SIMOCODE pro V Modbus RTU basic unit Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as hex offsets and sent unchanged as the start address. The manual's examples read device status bits with start address 0x1C08 (FC 01) and write the cooling-down period at 0x419A (FC 06). In a 1-based tool add 1 (0x0807 = 2055 -> 42056).

What byte order does the Siemens SIMOCODE pro V Modbus RTU basic unit use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens SIMOCODE pro V Modbus RTU basic unit?

Start with HR 2055 Current I_L1 (Current L1 (% of Is)); HR 2054 Max. current I_max (Max. phase current); HR 2074 Active power P (Active power); DI 7176 Status - group fault (Group fault); DI 7186 Status - Off (Status Off); CO 2 Cyclic receive bit 0.2 (Command ON> (default)); CO 1 Cyclic receive bit 0.1 (Command OFF (default)).

How do I enable Modbus control of the Siemens SIMOCODE pro V Modbus RTU basic unit?

Set the Modbus address with the addressing plug (DIP switches 1-247, press TEST/RESET) or in SIMOCODE ES (Parameter > Modbus), together with baud rate, port configuration (8E1/8O1/8N2/8N1) and wait time. Remote control over the bus needs the operating mode Remote (mode selector S1 = 1 and S2 = 1).

What happens when the Siemens SIMOCODE pro V Modbus RTU basic unit loses Modbus communication?

Watchdog / watchdog time in the Modbus parameters: if no valid read or write arrives within the time, the unit restarts its baud search (auto baud) and, with Bus monitoring enabled, raises 'Fault - bus'. 'PLC/PCS monitoring' raises 'Fault - PLC/PCS' when its input (normally cyclic receive bit 0.7) drops in Remote mode.

Where is the official Siemens SIMOCODE pro V Modbus RTU basic unit Modbus documentation?