Equipment type

Soft starters & protection relays Modbus register maps

Updated 19 November 2026

12 soft starters & protection relays register maps from 5 manufacturers: ABB, Eaton, Lovato Electric, Schneider Electric, Siemens.

12 of 12 shown

Soft starters & protection relays: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
PSE softstarter (internal Modbus RTU)RTU25519200 baud, 8E116-bit onlyhex 0-based67
PSTX softstarter (built-in Modbus RTU)RTUNot stated-16-bit onlyhex 0-based60
C440 electronic overload relay (via C441 Ethernet module)TCPNot stated-16-bit only1-based37
C441 Motor Insight motor protection relay (via C441 Ethernet module)TCP/RTU/ASCII119200 baud, 8E116-bit only1-based89
S611 soft starter (via C441 Ethernet module)TCP/RTU/ASCII119200 baud, 8E116-bit only1-based90
S811+ soft starter (via C441 Ethernet module)TCPNot stated-16-bit only1-based88
ADXL soft starters (Modbus RTU / ASCII / TCP)RTU/ASCII/TCP19600 baud, 8N1ABCD1-based32
ADXNP soft starters with CX04 RS-485 module (Modbus RTU)RTU19600 baud, 8N1ABCD1-based19
TeSys T LTMR motor management controller (Modbus RTU)RTUNot stated-ABCD0-based50
Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)RTUNot stated19200 baud, 8E1ABCDModicon426
Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)RTUNot stated19200 baud, 8E1ABCDModicon370
SIMOCODE pro V Modbus RTU basic unitRTU12619200 baudABCDhex 0-based258