- TeSys T LTMR motor management controller (Modbus RTU)
Motor management and protection relay · Modbus register map
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus register map
Updated 19 November 2026
The TeSys T LTMR protects and controls a motor and talks Modbus RTU on its network port. Registers are grouped by number: monitoring at 450-539 (trips, status, alarms, currents, voltage and power), configuration at 540-699 and commands at 704-705. Most values are 16-bit; phase currents are 32-bit with a selectable word order.
This page lists 50 Modbus registers for the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- TeSys T LTMR motor management controller (Modbus RTU)
- Equipment type
- Motor management and protection relay
- Registers
- 50 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40
Integration notes: Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
Read 450-515 for trips, status, alarms and measurements, and write bits in 704 to run, reverse or reset. Register 455 bit 14 shows whether the controller is in remote (network) control.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 455 | System status register 1 | BITMAP16 | Ready / on / trip / remote status | Read |
| HR 451 | Trip code | UINT16 | Trip code | Read |
| HR 465 | Thermal capacity level | UINT16 | Thermal capacity used | Read |
| HR 500 | Average current | UINT32 ABCD | Average current | Read |
| HR 704 | Control register 1 | BITMAP16 | Run / reverse / reset commands | Read/write |
| HR 460 | Alarm code | UINT16 | Alarm code | Read |
Enable Modbus control & writes
Set the network port address (696), baud (695) and parity (694) via the HMI or SoMove with the TeSys T DTM before communicating. Write run, reverse and reset bits in 704; 455 bit 14 shows whether the controller is in remote control. The guide warns that switching to network control can restart the motor from the last PLC command.
Communication loss & watchdog
Network port comm loss timeout (693, 0.01 s units) with the fallback action set in 682 (hold, run, outputs off/on).
Byte order & addressing
- Printed register numbers are wire addresses (numbering starts at 0).
- Word order of 32-bit currents depends on register 602 bit 10.
- Some bit writes are silently ignored outside configuration mode.
Network setup
- Address 1-247 (1 = undefined at the factory).
- Autodetection tries 19200 baud, even parity first.
- Check the PLC Comm (yellow) and Fallback (red) LEDs.
Watch out for
- Broadcast writes can change configuration; avoid broadcast.
- A reserved register written with a non-zero value returns exception 03.
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 450 | Minimum wait time | Wait before a reset is allowed. | UINT16 | s | Read | |||
| HR | 451 | Trip code | Last trip, or the trip with priority. | UINT16 | Read | 0 = No error; 3 = Ground current; 4 = Thermal overload; 5 = Long start; 6 = Jam; 7 = Current phase imbalance; 8 = Undercurrent; 10 = Test; 11 = HMI port error; 12 = HMI port comm loss; 13 = HMI network port internal error; 16 = External trip; 18 = On-Off diagnostic; 19 = Wiring diagnostic; 20 = Overcurrent; 21 = Current phase loss; 22 = Current phase reversal; 23 = Motor temp sensor; 24 = Voltage phase imbalance; 25 = Voltage phase loss; 26 = Voltage phase reversal; 27 = Undervoltage; 28 = Overvoltage; 29 = Underpower; 30 = Overpower; 31 = Under power factor; 32 = Over power factor; 33 = LTME configuration; 34 = Temperature sensor short-circuit; 35 = Temperature sensor open-circuit; 36 = CT reversal; 37 = Out of boundary CT ratio; 46 = Start check; 47 = Run checkback; 48 = Stop check; 49 = Stop checkback; 51 = Controller internal temperature; 55 = Internal error (stack overflow); 56 = Internal error (RAM); 57 = Internal error (RAM checksum); 58 = Internal error (hardware watchdog); 60 = L2 current in single-phase mode; 64 = Non-volatile memory error; 65 = Expansion module comm error; 66 = Stuck reset button; 67 = Logic function error; 100 = Network port internal error; 101 = Network port internal error; 102 = Network port internal error; 103 = Network port internal error; 104 = Network port internal error; 109 = Network port comm error; 111 = Fast device replacement trip; 555 = Network port configuration error | |||
| HR | 452 | Trip register 1 | BITMAP16 | Read | bit 2 = Ground current trip; bit 3 = Thermal overload trip; bit 4 = Long start trip; bit 5 = Jam trip; bit 6 = Current phase imbalance trip; bit 7 = Undercurrent trip; bit 9 = Test trip; bit 10 = HMI port trip; bit 11 = Controller internal trip; bit 12 = Internal port trip; bit 14 = Network port config trip; bit 15 = Network port trip | ||||
| HR | 453 | Trip register 2 | Bits 6-15 need the LTMEV40 module. | BITMAP16 | Read | bit 0 = External system trip; bit 1 = Diagnostic trip; bit 2 = Wiring trip; bit 3 = Overcurrent trip; bit 4 = Current phase loss trip; bit 5 = Current phase reversal trip; bit 6 = Motor temperature sensor trip; bit 7 = Voltage phase imbalance trip; bit 8 = Voltage phase loss trip; bit 9 = Voltage phase reversal trip; bit 10 = Undervoltage trip; bit 11 = Overvoltage trip; bit 12 = Underpower trip; bit 13 = Overpower trip; bit 14 = Under power factor trip; bit 15 = Over power factor trip | |||
| HR | 455 | System status register 1 | Bits 8-13 hold the average current ratio (32 = 100 % FLC, 63 = 200 % FLC). | BITMAP16 | Read | bit 0 = System ready; bit 1 = System on; bit 2 = System trip; bit 3 = System alarm; bit 4 = System tripped; bit 5 = Trip reset authorized; bit 6 = Controller power; bit 7 = Motor running (current above 10 % FLC); bit 14 = In remote; bit 15 = Motor starting; bit 8-13 = Motor average current ratio | |||
| HR | 456 | System status register 2 | BITMAP16 | Read | bit 0 = Auto-reset active; bit 2 = Trip power cycle requested; bit 3 = Motor restart time undefined; bit 4 = Rapid cycle lockout; bit 5 = Load shedding; bit 6 = Motor speed: 0 = FLC1, 1 = FLC2; bit 7 = HMI port comm loss; bit 8 = Network port comm loss; bit 9 = Motor transition lockout | ||||
| HR | 457 | Logic inputs status | Bit n-1 = logic input n; inputs 7-16 need the LTMEV40. | BITMAP16 | Read | bit 0 = Logic input 1; bit 1 = Logic input 2; bit 2 = Logic input 3; bit 3 = Logic input 4; bit 4 = Logic input 5; bit 5 = Logic input 6; bit 6 = Logic input 7; bit 7 = Logic input 8; bit 8 = Logic input 9; bit 9 = Logic input 10; bit 10 = Logic input 11; bit 11 = Logic input 12; bit 12 = Logic input 13; bit 13 = Logic input 14; bit 14 = Logic input 15; bit 15 = Logic input 16 | |||
| HR | 458 | Logic outputs status | Bit n-1 = logic output n; outputs 5-8 need the LTMEV40. | BITMAP16 | Read | bit 0 = Logic output 1; bit 1 = Logic output 2; bit 2 = Logic output 3; bit 3 = Logic output 4; bit 4 = Logic output 5; bit 5 = Logic output 6; bit 6 = Logic output 7; bit 7 = Logic output 8 | |||
| HR | 460 | Alarm code | Code of the active alarm; 0 = none. | UINT16 | Read | ||||
| HR | 461 | Alarm register 1 | BITMAP16 | Read | bit 2 = Ground current alarm; bit 3 = Thermal overload alarm; bit 5 = Jam alarm; bit 6 = Current phase imbalance alarm; bit 7 = Undercurrent alarm; bit 10 = HMI port alarm; bit 11 = Controller internal temperature alarm; bit 15 = Network port alarm | ||||
| HR | 462 | Alarm register 2 | Bits 7-15 need the LTMEV40 module. | BITMAP16 | Read | bit 1 = Diagnostic alarm; bit 3 = Overcurrent alarm; bit 4 = Current phase loss alarm; bit 5 = Current phase reversal alarm; bit 6 = Motor temperature sensor alarm; bit 7 = Voltage phase imbalance alarm; bit 8 = Voltage phase loss alarm; bit 10 = Undervoltage alarm; bit 11 = Overvoltage alarm; bit 12 = Underpower alarm; bit 13 = Overpower alarm; bit 14 = Under power factor alarm; bit 15 = Over power factor alarm | |||
| HR | 464 | Motor temperature sensor degree | UINT16 | °C | Read | ||||
| HR | 465 | Thermal capacity level | Percent of the trip level. | UINT16 | % | Read | |||
| HR | 466 | Average current ratio | Percent of FLC. | UINT16 | % | Read | |||
| HR | 467 | L1 current ratio | Percent of FLC. | UINT16 | % | Read | |||
| HR | 468 | L2 current ratio | Percent of FLC. | UINT16 | % | Read | |||
| HR | 469 | L3 current ratio | Percent of FLC. | UINT16 | % | Read | |||
| HR | 470 | Ground current ratio | Units of 0.1 % of FLC min. | UINT16 | × 0.1 | % | Read | ||
| HR | 471 | Current phase imbalance | UINT16 | % | Read | ||||
| HR | 472 | Controller internal temperature | INT16 | °C | Read | ||||
| HR | 474 | Frequency | Always present; 0 without the LTMEV40. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 475 | Motor temperature sensor resistance | UINT16 | × 0.1 | Ω | Read | |||
| HR | 476 | Average voltage | Needs the LTMEV40 voltage expansion module. | UINT16 | V | Read | |||
| HR | 477 | L3-L1 voltage | Needs the LTMEV40 voltage expansion module. | UINT16 | V | Read | |||
| HR | 478 | L1-L2 voltage | Needs the LTMEV40 voltage expansion module. | UINT16 | V | Read | |||
| HR | 479 | L2-L3 voltage | Needs the LTMEV40 voltage expansion module. | UINT16 | V | Read | |||
| HR | 480 | Voltage phase imbalance | Needs the LTMEV40 voltage expansion module. | UINT16 | % | Read | |||
| HR | 481 | Power factor | Needs the LTMEV40 voltage expansion module. | UINT16 | × 0.01 | Read | |||
| HR | 482 | Active power | Needs the LTMEV40 voltage expansion module. | UINT16 | × 0.1 | kW | Read | ||
| HR | 483 | Reactive power | Needs the LTMEV40 voltage expansion module. | UINT16 | × 0.1 | kVAR | Read | ||
| HR | 490 | Network port monitoring | BITMAP16 | Read | bit 0 = Network port monitoring; bit 1 = Network port connected; bit 2 = Network port self-testing; bit 3 = Network port self-detecting; bit 4 = Network port bad config | ||||
| HR | 491 | Network port baud rate | Actual baud rate in use. | UINT16 | Read | 1200 = 1200; 2400 = 2400; 4800 = 4800; 9600 = 9600; 19200 = 19200; 65535 = Autodetection | |||
| HR | 493 | Network port parity | Actual parity in use. | UINT16 | Read | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 500doc 500-501 | Average current | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 502doc 502-503 | L1 current | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 504doc 504-505 | L2 current | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 506doc 506-507 | L3 current | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 508doc 508-509 | Ground current | UINT32 | ABCD | mA | Read | |||
| HR | 511 | Time to trip | UINT16 | s | Read | ||||
| HR | 512 | Motor last start current ratio | Percent of FLC. | UINT16 | % | Read | |||
| HR | 513 | Motor last start duration | UINT16 | s | Read | ||||
| HR | 514 | Motor starts per hour count | UINT16 | Read | |||||
| HR | 540 | Motor operating mode | Writable only in configuration mode; 256-511 = custom logic program 0-255. | UINT16 | Read/write | 2 = 2-wire overload; 3 = 3-wire overload; 4 = 2-wire independent; 5 = 3-wire independent; 6 = 2-wire reverser; 7 = 3-wire reverser; 8 = 2-wire 2-step; 9 = 3-wire 2-step; 10 = 2-wire 2-speed; 11 = 3-wire 2-speed | |||
| HR | 682 | Network port fallback setting | Output state on loss of communication. | UINT16 | Read/write | 0 = Hold LO1 LO2; 1 = Run (2-step mode only); 2 = LO1, LO2 off; 3 = LO1, LO2 on; 4 = LO1 on; 5 = LO2 on | |||
| HR | 693 | Network port comm loss timeout | Modbus only. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 694 | Network port parity setting | Modbus only. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 695 | Network port baud rate setting | UINT16 | Read/write | 1200 = 1200; 2400 = 2400; 4800 = 4800; 9600 = 9600; 19200 = 19200; 65535 = Autodetection (factory setting) | ||||
| HR | 696 | Network port address setting | 1-247. | UINT16 | Read/write | ||||
| HR | 704 | Control register 1 | Run commands from the network. | BITMAP16 | Read/write | bit 0 = Motor run forward command; bit 1 = Motor run reverse command; bit 3 = Trip reset command; bit 5 = Self test command; bit 6 = Motor low speed command | |||
| HR | 705 | Control register 2 | Clear commands. | BITMAP16 | Read/write | bit 0 = Clear all; bit 1 = Clear statistics; bit 2 = Clear thermal capacity level; bit 3 = Clear controller settings; bit 4 = Clear network port settings |
Notes on this map
- 32-bit values (UDInt) follow the 'Network port endian setting' (bit 10 of register 602): 1 = most significant word first (factory setting), 0 = least significant word first. The map assumes the factory setting.
- Registers marked note 1 (voltage, power, power factor, voltage trip/alarm bits, extra I/O) exist only with the LTMEV40 expansion module. Frequency (474) is always present but reads 0 without it.
- Factory network settings: address 1 (treated as undefined), baud and parity on autodetection (19200 and even tried first). Parity none uses 2 stop bits, even/odd use 1.
- Left out: identification and statistics blocks (0-449), trip history, the full configuration area, user map 800-999 and custom logic registers.
- At most 100 registers per request; functions 03, 06, 16 and 43 are supported.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
What Modbus registers does the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) have?
This map lists 50 registers: 50 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 0 (identification block 0-99), calls each number an 'address', and its PLC examples read 'address 455' and write 'address 704' directly, so the printed number is the wire address.
What byte order does the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)?
Start with HR 455 System status register 1 (Ready / on / trip / remote status); HR 451 Trip code (Trip code); HR 465 Thermal capacity level (Thermal capacity used); HR 500 Average current (Average current); HR 704 Control register 1 (Run / reverse / reset commands); HR 460 Alarm code (Alarm code).
How do I enable Modbus control of the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)?
Set the network port address (696), baud (695) and parity (694) via the HMI or SoMove with the TeSys T DTM before communicating. Write run, reverse and reset bits in 704; 455 bit 14 shows whether the controller is in remote control. The guide warns that switching to network control can restart the motor from the last PLC command.
What happens when the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) loses Modbus communication?
Network port comm loss timeout (693, 0.01 s units) with the fallback action set in 682 (hold, run, outputs off/on).
Where is the official Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus documentation?
The source is TeSys T LTMR Motor Management Controller Modbus Communication Guide (DOCA0130EN-03), revision 2024-02, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0130EN.
More Schneider Electric Modbus register maps
- Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Other soft starters & protection relays register maps
- Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V
All soft starters & protection relays Modbus register maps →
Source: TeSys T LTMR Motor Management Controller Modbus Communication Guide · DOCA0130EN-03 · rev. 2024-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.