Motor management and protection relay · Modbus register map

Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The TeSys T LTMR protects and controls a motor and talks Modbus RTU on its network port. Registers are grouped by number: monitoring at 450-539 (trips, status, alarms, currents, voltage and power), configuration at 540-699 and commands at 704-705. Most values are 16-bit; phase currents are 32-bit with a selectable word order.

This page lists 50 Modbus registers for the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
TeSys T LTMR motor management controller (Modbus RTU)
Equipment type
Motor management and protection relay
Registers
50 (8 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40
Source document
TeSys T LTMR Motor Management Controller Modbus Communication Guide · DOCA0130EN-03 · rev. 2024-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)

Integration in brief

Read 450-515 for trips, status, alarms and measurements, and write bits in 704 to run, reverse or reset. Register 455 bit 14 shows whether the controller is in remote (network) control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 455System status register 1BITMAP16Ready / on / trip / remote statusRead
HR 451Trip codeUINT16Trip codeRead
HR 465Thermal capacity levelUINT16Thermal capacity usedRead
HR 500Average currentUINT32 ABCDAverage currentRead
HR 704Control register 1BITMAP16Run / reverse / reset commandsRead/write
HR 460Alarm codeUINT16Alarm codeRead

Enable Modbus control & writes

Set the network port address (696), baud (695) and parity (694) via the HMI or SoMove with the TeSys T DTM before communicating. Write run, reverse and reset bits in 704; 455 bit 14 shows whether the controller is in remote control. The guide warns that switching to network control can restart the motor from the last PLC command.

Communication loss & watchdog

Network port comm loss timeout (693, 0.01 s units) with the fallback action set in 682 (hold, run, outputs off/on).

Byte order & addressing

Network setup

Watch out for

Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR450Minimum wait timeWait before a reset is allowed.UINT16sRead
HR451Trip codeLast trip, or the trip with priority.UINT16Read0 = No error; 3 = Ground current; 4 = Thermal overload; 5 = Long start; 6 = Jam; 7 = Current phase imbalance; 8 = Undercurrent; 10 = Test; 11 = HMI port error; 12 = HMI port comm loss; 13 = HMI network port internal error; 16 = External trip; 18 = On-Off diagnostic; 19 = Wiring diagnostic; 20 = Overcurrent; 21 = Current phase loss; 22 = Current phase reversal; 23 = Motor temp sensor; 24 = Voltage phase imbalance; 25 = Voltage phase loss; 26 = Voltage phase reversal; 27 = Undervoltage; 28 = Overvoltage; 29 = Underpower; 30 = Overpower; 31 = Under power factor; 32 = Over power factor; 33 = LTME configuration; 34 = Temperature sensor short-circuit; 35 = Temperature sensor open-circuit; 36 = CT reversal; 37 = Out of boundary CT ratio; 46 = Start check; 47 = Run checkback; 48 = Stop check; 49 = Stop checkback; 51 = Controller internal temperature; 55 = Internal error (stack overflow); 56 = Internal error (RAM); 57 = Internal error (RAM checksum); 58 = Internal error (hardware watchdog); 60 = L2 current in single-phase mode; 64 = Non-volatile memory error; 65 = Expansion module comm error; 66 = Stuck reset button; 67 = Logic function error; 100 = Network port internal error; 101 = Network port internal error; 102 = Network port internal error; 103 = Network port internal error; 104 = Network port internal error; 109 = Network port comm error; 111 = Fast device replacement trip; 555 = Network port configuration error
HR452Trip register 1BITMAP16Readbit 2 = Ground current trip; bit 3 = Thermal overload trip; bit 4 = Long start trip; bit 5 = Jam trip; bit 6 = Current phase imbalance trip; bit 7 = Undercurrent trip; bit 9 = Test trip; bit 10 = HMI port trip; bit 11 = Controller internal trip; bit 12 = Internal port trip; bit 14 = Network port config trip; bit 15 = Network port trip
HR453Trip register 2Bits 6-15 need the LTMEV40 module.BITMAP16Readbit 0 = External system trip; bit 1 = Diagnostic trip; bit 2 = Wiring trip; bit 3 = Overcurrent trip; bit 4 = Current phase loss trip; bit 5 = Current phase reversal trip; bit 6 = Motor temperature sensor trip; bit 7 = Voltage phase imbalance trip; bit 8 = Voltage phase loss trip; bit 9 = Voltage phase reversal trip; bit 10 = Undervoltage trip; bit 11 = Overvoltage trip; bit 12 = Underpower trip; bit 13 = Overpower trip; bit 14 = Under power factor trip; bit 15 = Over power factor trip
HR455System status register 1Bits 8-13 hold the average current ratio (32 = 100 % FLC, 63 = 200 % FLC).BITMAP16Readbit 0 = System ready; bit 1 = System on; bit 2 = System trip; bit 3 = System alarm; bit 4 = System tripped; bit 5 = Trip reset authorized; bit 6 = Controller power; bit 7 = Motor running (current above 10 % FLC); bit 14 = In remote; bit 15 = Motor starting; bit 8-13 = Motor average current ratio
HR456System status register 2BITMAP16Readbit 0 = Auto-reset active; bit 2 = Trip power cycle requested; bit 3 = Motor restart time undefined; bit 4 = Rapid cycle lockout; bit 5 = Load shedding; bit 6 = Motor speed: 0 = FLC1, 1 = FLC2; bit 7 = HMI port comm loss; bit 8 = Network port comm loss; bit 9 = Motor transition lockout
HR457Logic inputs statusBit n-1 = logic input n; inputs 7-16 need the LTMEV40.BITMAP16Readbit 0 = Logic input 1; bit 1 = Logic input 2; bit 2 = Logic input 3; bit 3 = Logic input 4; bit 4 = Logic input 5; bit 5 = Logic input 6; bit 6 = Logic input 7; bit 7 = Logic input 8; bit 8 = Logic input 9; bit 9 = Logic input 10; bit 10 = Logic input 11; bit 11 = Logic input 12; bit 12 = Logic input 13; bit 13 = Logic input 14; bit 14 = Logic input 15; bit 15 = Logic input 16
HR458Logic outputs statusBit n-1 = logic output n; outputs 5-8 need the LTMEV40.BITMAP16Readbit 0 = Logic output 1; bit 1 = Logic output 2; bit 2 = Logic output 3; bit 3 = Logic output 4; bit 4 = Logic output 5; bit 5 = Logic output 6; bit 6 = Logic output 7; bit 7 = Logic output 8
HR460Alarm codeCode of the active alarm; 0 = none.UINT16Read
HR461Alarm register 1BITMAP16Readbit 2 = Ground current alarm; bit 3 = Thermal overload alarm; bit 5 = Jam alarm; bit 6 = Current phase imbalance alarm; bit 7 = Undercurrent alarm; bit 10 = HMI port alarm; bit 11 = Controller internal temperature alarm; bit 15 = Network port alarm
HR462Alarm register 2Bits 7-15 need the LTMEV40 module.BITMAP16Readbit 1 = Diagnostic alarm; bit 3 = Overcurrent alarm; bit 4 = Current phase loss alarm; bit 5 = Current phase reversal alarm; bit 6 = Motor temperature sensor alarm; bit 7 = Voltage phase imbalance alarm; bit 8 = Voltage phase loss alarm; bit 10 = Undervoltage alarm; bit 11 = Overvoltage alarm; bit 12 = Underpower alarm; bit 13 = Overpower alarm; bit 14 = Under power factor alarm; bit 15 = Over power factor alarm
HR464Motor temperature sensor degreeUINT16°CRead
HR465Thermal capacity levelPercent of the trip level.UINT16%Read
HR466Average current ratioPercent of FLC.UINT16%Read
HR467L1 current ratioPercent of FLC.UINT16%Read
HR468L2 current ratioPercent of FLC.UINT16%Read
HR469L3 current ratioPercent of FLC.UINT16%Read
HR470Ground current ratioUnits of 0.1 % of FLC min.UINT16× 0.1%Read
HR471Current phase imbalanceUINT16%Read
HR472Controller internal temperatureINT16°CRead
HR474FrequencyAlways present; 0 without the LTMEV40.UINT16× 0.01HzRead
HR475Motor temperature sensor resistanceUINT16× 0.1ΩRead
HR476Average voltageNeeds the LTMEV40 voltage expansion module.UINT16VRead
HR477L3-L1 voltageNeeds the LTMEV40 voltage expansion module.UINT16VRead
HR478L1-L2 voltageNeeds the LTMEV40 voltage expansion module.UINT16VRead
HR479L2-L3 voltageNeeds the LTMEV40 voltage expansion module.UINT16VRead
HR480Voltage phase imbalanceNeeds the LTMEV40 voltage expansion module.UINT16%Read
HR481Power factorNeeds the LTMEV40 voltage expansion module.UINT16× 0.01Read
HR482Active powerNeeds the LTMEV40 voltage expansion module.UINT16× 0.1kWRead
HR483Reactive powerNeeds the LTMEV40 voltage expansion module.UINT16× 0.1kVARRead
HR490Network port monitoringBITMAP16Readbit 0 = Network port monitoring; bit 1 = Network port connected; bit 2 = Network port self-testing; bit 3 = Network port self-detecting; bit 4 = Network port bad config
HR491Network port baud rateActual baud rate in use.UINT16Read1200 = 1200; 2400 = 2400; 4800 = 4800; 9600 = 9600; 19200 = 19200; 65535 = Autodetection
HR493Network port parityActual parity in use.UINT16Read0 = None; 1 = Even; 2 = Odd
HR500doc 500-501Average currentUINT32ABCD× 0.01ARead
HR502doc 502-503L1 currentUINT32ABCD× 0.01ARead
HR504doc 504-505L2 currentUINT32ABCD× 0.01ARead
HR506doc 506-507L3 currentUINT32ABCD× 0.01ARead
HR508doc 508-509Ground currentUINT32ABCDmARead
HR511Time to tripUINT16sRead
HR512Motor last start current ratioPercent of FLC.UINT16%Read
HR513Motor last start durationUINT16sRead
HR514Motor starts per hour countUINT16Read
HR540Motor operating modeWritable only in configuration mode; 256-511 = custom logic program 0-255.UINT16Read/write2 = 2-wire overload; 3 = 3-wire overload; 4 = 2-wire independent; 5 = 3-wire independent; 6 = 2-wire reverser; 7 = 3-wire reverser; 8 = 2-wire 2-step; 9 = 3-wire 2-step; 10 = 2-wire 2-speed; 11 = 3-wire 2-speed
HR682Network port fallback settingOutput state on loss of communication.UINT16Read/write0 = Hold LO1 LO2; 1 = Run (2-step mode only); 2 = LO1, LO2 off; 3 = LO1, LO2 on; 4 = LO1 on; 5 = LO2 on
HR693Network port comm loss timeoutModbus only.UINT16× 0.01sRead/write
HR694Network port parity settingModbus only.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR695Network port baud rate settingUINT16Read/write1200 = 1200; 2400 = 2400; 4800 = 4800; 9600 = 9600; 19200 = 19200; 65535 = Autodetection (factory setting)
HR696Network port address setting1-247.UINT16Read/write
HR704Control register 1Run commands from the network.BITMAP16Read/writebit 0 = Motor run forward command; bit 1 = Motor run reverse command; bit 3 = Trip reset command; bit 5 = Self test command; bit 6 = Motor low speed command
HR705Control register 2Clear commands.BITMAP16Read/writebit 0 = Clear all; bit 1 = Clear statistics; bit 2 = Clear thermal capacity level; bit 3 = Clear controller settings; bit 4 = Clear network port settings

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)

What Modbus registers does the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) have?

This map lists 50 registers: 50 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 0 (identification block 0-99), calls each number an 'address', and its PLC examples read 'address 455' and write 'address 704' directly, so the printed number is the wire address.

What byte order does the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)?

Start with HR 455 System status register 1 (Ready / on / trip / remote status); HR 451 Trip code (Trip code); HR 465 Thermal capacity level (Thermal capacity used); HR 500 Average current (Average current); HR 704 Control register 1 (Run / reverse / reset commands); HR 460 Alarm code (Alarm code).

How do I enable Modbus control of the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)?

Set the network port address (696), baud (695) and parity (694) via the HMI or SoMove with the TeSys T DTM before communicating. Write run, reverse and reset bits in 704; 455 bit 14 shows whether the controller is in remote control. The guide warns that switching to network control can restart the motor from the last PLC command.

What happens when the Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) loses Modbus communication?

Network port comm loss timeout (693, 0.01 s units) with the fallback action set in 682 (hold, run, outputs off/on).

Where is the official Schneider Electric TeSys T LTMR motor management controller (Modbus RTU) Modbus documentation?

The source is TeSys T LTMR Motor Management Controller Modbus Communication Guide (DOCA0130EN-03), revision 2024-02, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0130EN.