Air handler (rack-mounted room cooling unit, split DX) · Modbus register map
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus register map
Updated 19 November 2026
The Uniflair ACRMD4K is a rack-mounted split DX cooling unit (indoor unit plus outdoor unit). Its controller is a Modbus RTU / TCP slave. This map covers the unit on/off coil, alarm and output status bits (including outdoor-unit compressor and inverter faults), return and outlet air temperatures, return humidity, pressures, compressor frequency, coil temperatures, operating mode and the writable temperature, humidity, alarm and fan-speed settings.
This page lists 86 Modbus registers for the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- Uniflair Rack Mounted Room Cooling ACRMD4K
- Equipment type
- Air handler (rack-mounted room cooling unit, split DX)
- Registers
- 86 (14 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Integration notes: Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Write coil 00001 (wire 0) to switch the unit on or off and holding 40121 / 40122 for the return / outlet air setpoints in tenths of °C. Poll input registers 30002-30003 for air temperatures, 30176 for operating mode and input status 10002-10003 for the serious / common alarm outputs.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | ON/OFF UNIT | BIT | Unit on/off | Read/write |
| IR 1 | Air return temperature | INT16 | Air return temperature | Read |
| IR 2 | Air outlet temperature | INT16 | Air outlet temperature | Read |
| IR 175 | Operation mode | INT16 | Operation mode | Read |
| DI 1 | Serious alarm output | BIT | Serious alarm output | Read |
| DI 2 | Common alarm output | BIT | Common alarm output | Read |
| HR 120 | Air return temperature setting | INT16 | Air return temperature setpoint | Read/write |
| HR 121 | Air outlet temperature setting | INT16 | Air outlet temperature setpoint | Read/write |
Enable Modbus control & writes
Not described in the register map. The unit's Modbus address and baud rate are themselves writable at holding 40216 / 40217.
Byte order & addressing
- Use the decimal absolute register as the wire address (Modicon number minus the 0/1/3/4 prefix and minus 1).
- Two separate settings share holding 40183 as bits 10 and 11.
Network setup
- Baud rate choices per holding 40217: 2400, 4800, 9600 or 19200. Parity, stop bits and the default address are not stated in the map.
Watch out for
- The humidity and pressure input registers are printed with a temperature unit in the map; check them against the unit display.
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | ON/OFF UNIT | BIT | Read/write | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Serious alarm output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 2doc 10003 | Common alarm output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 3doc 10004 | Condensation pump output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 6doc 10007 | PTC heater output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 9doc 10010 | IDU fan output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 10doc 10011 | SV for low temp kit output | BIT | Read | 0 = Without output; 1 = With output | ||||
| DI | 48doc 10049 | AL49 Fire/smoke alarm (serious) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 49doc 10050 | AL50 High air return temperature (common) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 50doc 10051 | AL51 High air outlet temperature (common) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 51doc 10052 | AL52 Low air outlet temperature (common) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 52doc 10053 | AL53 Condensation pump failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 53doc 10054 | AL54 EEPROM failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 54doc 10055 | AL55 Water on floor | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 55doc 10056 | AL56 Maintenance alarm for IDU fan | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 67doc 10068 | AL68 Air return humidity probe failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 68doc 10069 | AL69 Air return temperature probe failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 73doc 10074 | AL74 Air outlet temperature probe failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 85doc 10086 | AL86 High air return humidity (common) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 86doc 10087 | AL87 Low air return humidity (common) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 100doc 10101 | AL101 IDU & ODU communication failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 112doc 10113 | AL113 Coil inlet temperature probe failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 114doc 10115 | AL115 Coil outlet temperature probe failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 122doc 10123 | C123 High discharge pressure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 123doc 10124 | C124 High pressure switch protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 125doc 10126 | C126 Low suction pressure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 127doc 10128 | C128 High discharge temperature | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 130doc 10131 | C131 Memory storage failure (ODU) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 131doc 10132 | C132 Refrigerant leak | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 132doc 10133 | C133 Low exhaust pressure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 133doc 10134 | C134 Environment temperature out of range | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 134doc 10135 | C135 High-pressure sensor failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 135doc 10136 | C136 Low-pressure sensor failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 136doc 10137 | C137 TH1 open/short circuit (discharge temperature 1) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 137doc 10138 | C138 TH2 open/short circuit (discharge temperature 2) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 138doc 10139 | C139 TH3 open/short circuit (suction temperature 1) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 139doc 10140 | C140 TH4 open/short circuit (suction temperature 2) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 140doc 10141 | C141 TH5 open/short circuit (subcool inlet) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 143doc 10144 | C144 TH8 open/short circuit (environment temperature) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 148doc 10149 | C149 Suction temperature sensor abnormality | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 149doc 10150 | C150 Discharge temperature sensor abnormality | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 150doc 10151 | C151 Low superheat protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 152doc 10153 | C153 Compressor current protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 153doc 10154 | C154 IPM module protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 156doc 10157 | C157 PFC module protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 157doc 10158 | C158 PFC module temperature sensor internal circuit exception | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 158doc 10159 | C159 PFC module high temperature protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 159doc 10160 | C160 Input power exception failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 160doc 10161 | C161 Excessive input current protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 161doc 10162 | C162 VDC high voltage protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 162doc 10163 | C163 VDC low voltage protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 163doc 10164 | C164 Drive and module communication failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 164doc 10165 | C165 Compressor out-of-step during running | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 165doc 10166 | C166 Current detection circuit failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 166doc 10167 | C167 Startup failed | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 167doc 10168 | C168 Compressor out-of-phase failure | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 170doc 10171 | C171 IPM module temperature sensor internal circuit abnormality | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 171doc 10172 | C172 IPM module high temperature protection | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| IR | 1doc 30002 | Air return temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2doc 30003 | Air outlet temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 13doc 30014 | Air return humidity | Tenths; the map prints the unit column as 0.1 °C (see notes). | INT16 | × 0.1 | Read | |||
| IR | 34doc 30035 | IDU DC fan voltage | INT16 | × 0.1 | V | Read | |||
| IR | 36doc 30037 | Discharge pressure | Tenths; the map gives no pressure unit (see notes). | INT16 | × 0.1 | Read | |||
| IR | 37doc 30038 | Suction pressure | Tenths; the map gives no pressure unit (see notes). | INT16 | × 0.1 | Read | |||
| IR | 38doc 30039 | Target frequency | INT16 | Hz | Read | ||||
| IR | 39doc 30040 | Running frequency | INT16 | Hz | Read | ||||
| IR | 40doc 30041 | Target evaporation temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 41doc 30042 | Discharge temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 42doc 30043 | Evaporation temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 43doc 30044 | In-coil temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 44doc 30045 | Out-coil temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 46doc 30047 | IDU valve steps | INT16 | steps | Read | ||||
| IR | 175doc 30176 | Operation mode | INT16 | Read | 0 = Refrigeration/Cooling; 1 = Dehumidification; 2 = BMS shutdown; 3 = HMI shutdown; 4 = Fault shutdown | ||||
| HR | 100doc 40101 | Condensation pump alarm mode | INT16 | Read/write | 0 = Unit off; 1 = Alarm only | ||||
| HR | 120doc 40121 | Air return temperature setting | Raw 160-420 (16.0-42.0 °C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 121doc 40122 | Air outlet temperature setting | Raw 130-270 (13.0-27.0 °C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 122doc 40123 | Min. humidify setting | Raw 0-950 (0-95 %). | INT16 | × 0.1 | % | Read/write | ||
| HR | 123doc 40124 | Max. humidify setting | Raw 0-1000 (0-100 %). | INT16 | × 0.1 | % | Read/write | ||
| HR | 182doc 40183 | PTC heater / condensation pump function | BITMAP16 | Read/write | bit 10 = PTC heater function (0 = yes, 1 = no); bit 11 = Condensation pump function (0 = yes, 1 = no) | ||||
| HR | 200doc 40201 | High air return temperature alarm value setting | INT16 | × 0.1 | °C | Read/write | |||
| HR | 203doc 40204 | Low outlet air temperature alarm value setting | INT16 | × 0.1 | °C | Read/write | |||
| HR | 204doc 40205 | High outlet air temperature alarm value setting | INT16 | × 0.1 | °C | Read/write | |||
| HR | 215doc 40216 | Modbus address | INT16 | Read/write | |||||
| HR | 216doc 40217 | Comm. speed | INT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200 | ||||
| HR | 218doc 40219 | Max. speed of EC/DC fan | INT16 | % | Read/write | ||||
| HR | 219doc 40220 | Min. speed of EC/DC fan | INT16 | % | Read/write |
Notes on this map
- Per the map's notes, 16-bit values are big-endian and signed values are two's complement; all points here are single registers or bits.
- Scale: the map's 'Units' column holds the resolution (e.g. 0.1 °C, 0.1 %) and the row text says values are 'magnified 10 times' (219 = 21.9). The map's 'Scale' column actually holds the raw setting range; ranges are given in the descriptions.
- Air return humidity (30014) and the discharge/suction pressures (30037, 30038) are printed with the unit '0.1 °C', which looks copied from the temperature rows. We keep the 0.1 scale but leave the unit blank because the map does not give the real unit.
- Holding register 40183 (wire 182) carries two settings as bits: bit 10 = PTC heater function, bit 11 = condensation pump function (0 = yes, 1 = no).
- Reads use function code 3 or 4; writes use function code 16, or 6 for single registers. The general notes name only these function codes, but the tables also list one coil and input-status points.
- The map prints no revision or date; 2022-02 is the PDF's own creation date (2022-02-10).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
What Modbus registers does the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K have?
This map lists 86 registers: 1 coil, 57 discrete inputs, 15 input registers, 13 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row shows a Modicon number (00001 / 10002 / 30002 / 40101 style), a hex and a decimal absolute register. The notes say absolute register 0 is Modicon 40001 and address zero on the wire, so the decimal column is the wire address; e.g. holding 40121 is wire 120 and input status 10002 is wire 1.
What are the minimum Modbus registers to integrate the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K?
Start with CO 0 ON/OFF UNIT (Unit on/off); IR 1 Air return temperature (Air return temperature); IR 2 Air outlet temperature (Air outlet temperature); IR 175 Operation mode (Operation mode); DI 1 Serious alarm output (Serious alarm output); DI 2 Common alarm output (Common alarm output); HR 120 Air return temperature setting (Air return temperature setpoint); HR 121 Air outlet temperature setting (Air outlet temperature setpoint).
How do I enable Modbus control of the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K?
Not described in the register map. The unit's Modbus address and baud rate are themselves writable at holding 40216 / 40217.
Where is the official Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus documentation?
The source is Modbus Register Map: Uniflair Rack Mounted Room Cooling ACRMD4Kxxx (990-91589), revision 2022-02, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=Modbus_Register_Map_990-91589.
More Schneider Electric Modbus register maps
- Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40
Other ac & vrf gateways register maps
- Split AC unit (VRF / split AC gateway built in)
Aermec LCG series DC inverter air conditioners (built-in Modbus)
Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).
Also known as: LCG - VRF / split AC gateway
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
EKMBPP1 and EKMBPP1A adapters on the P1P2 bus of Sky Air / VRV indoor units (up to 16), installation manual 4P720139-1C (2024.11).
Also known as: EKMBPP1, EKMBPP1A - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink
All ac & vrf gateways Modbus register maps →
Source: Modbus Register Map: Uniflair Rack Mounted Room Cooling ACRMD4Kxxx · 990-91589 · rev. 2022-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.