Air handler (rack-mounted room cooling unit, split DX) · Modbus register map

Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus register map

Updated 19 November 2026

Short answer

The Uniflair ACRMD4K is a rack-mounted split DX cooling unit (indoor unit plus outdoor unit). Its controller is a Modbus RTU / TCP slave. This map covers the unit on/off coil, alarm and output status bits (including outdoor-unit compressor and inverter faults), return and outlet air temperatures, return humidity, pressures, compressor frequency, coil temperatures, operating mode and the writable temperature, humidity, alarm and fan-speed settings.

This page lists 86 Modbus registers for the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
Uniflair Rack Mounted Room Cooling ACRMD4K
Equipment type
Air handler (rack-mounted room cooling unit, split DX)
Registers
86 (14 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Source document
Modbus Register Map: Uniflair Rack Mounted Room Cooling ACRMD4Kxxx · 990-91589 · rev. 2022-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K

Integration in brief

Write coil 00001 (wire 0) to switch the unit on or off and holding 40121 / 40122 for the return / outlet air setpoints in tenths of °C. Poll input registers 30002-30003 for air temperatures, 30176 for operating mode and input status 10002-10003 for the serious / common alarm outputs.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0ON/OFF UNITBITUnit on/offRead/write
IR 1Air return temperatureINT16Air return temperatureRead
IR 2Air outlet temperatureINT16Air outlet temperatureRead
IR 175Operation modeINT16Operation modeRead
DI 1Serious alarm outputBITSerious alarm outputRead
DI 2Common alarm outputBITCommon alarm outputRead
HR 120Air return temperature settingINT16Air return temperature setpointRead/write
HR 121Air outlet temperature settingINT16Air outlet temperature setpointRead/write

Enable Modbus control & writes

Not described in the register map. The unit's Modbus address and baud rate are themselves writable at holding 40216 / 40217.

Byte order & addressing

Network setup

Watch out for

Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

86 of 86 shown
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001ON/OFF UNITBITRead/write0 = Off; 1 = On
DI1doc 10002Serious alarm outputBITRead0 = Without output; 1 = With output
DI2doc 10003Common alarm outputBITRead0 = Without output; 1 = With output
DI3doc 10004Condensation pump outputBITRead0 = Without output; 1 = With output
DI6doc 10007PTC heater outputBITRead0 = Without output; 1 = With output
DI9doc 10010IDU fan outputBITRead0 = Without output; 1 = With output
DI10doc 10011SV for low temp kit outputBITRead0 = Without output; 1 = With output
DI48doc 10049AL49 Fire/smoke alarm (serious)BITRead0 = No alarm; 1 = Alarm
DI49doc 10050AL50 High air return temperature (common)BITRead0 = No alarm; 1 = Alarm
DI50doc 10051AL51 High air outlet temperature (common)BITRead0 = No alarm; 1 = Alarm
DI51doc 10052AL52 Low air outlet temperature (common)BITRead0 = No alarm; 1 = Alarm
DI52doc 10053AL53 Condensation pump failureBITRead0 = No alarm; 1 = Alarm
DI53doc 10054AL54 EEPROM failureBITRead0 = No alarm; 1 = Alarm
DI54doc 10055AL55 Water on floorBITRead0 = No alarm; 1 = Alarm
DI55doc 10056AL56 Maintenance alarm for IDU fanBITRead0 = No alarm; 1 = Alarm
DI67doc 10068AL68 Air return humidity probe failureBITRead0 = No alarm; 1 = Alarm
DI68doc 10069AL69 Air return temperature probe failureBITRead0 = No alarm; 1 = Alarm
DI73doc 10074AL74 Air outlet temperature probe failureBITRead0 = No alarm; 1 = Alarm
DI85doc 10086AL86 High air return humidity (common)BITRead0 = No alarm; 1 = Alarm
DI86doc 10087AL87 Low air return humidity (common)BITRead0 = No alarm; 1 = Alarm
DI100doc 10101AL101 IDU & ODU communication failureBITRead0 = No alarm; 1 = Alarm
DI112doc 10113AL113 Coil inlet temperature probe failureBITRead0 = No alarm; 1 = Alarm
DI114doc 10115AL115 Coil outlet temperature probe failureBITRead0 = No alarm; 1 = Alarm
DI122doc 10123C123 High discharge pressureBITRead0 = No alarm; 1 = Alarm
DI123doc 10124C124 High pressure switch protectionBITRead0 = No alarm; 1 = Alarm
DI125doc 10126C126 Low suction pressureBITRead0 = No alarm; 1 = Alarm
DI127doc 10128C128 High discharge temperatureBITRead0 = No alarm; 1 = Alarm
DI130doc 10131C131 Memory storage failure (ODU)BITRead0 = No alarm; 1 = Alarm
DI131doc 10132C132 Refrigerant leakBITRead0 = No alarm; 1 = Alarm
DI132doc 10133C133 Low exhaust pressureBITRead0 = No alarm; 1 = Alarm
DI133doc 10134C134 Environment temperature out of rangeBITRead0 = No alarm; 1 = Alarm
DI134doc 10135C135 High-pressure sensor failureBITRead0 = No alarm; 1 = Alarm
DI135doc 10136C136 Low-pressure sensor failureBITRead0 = No alarm; 1 = Alarm
DI136doc 10137C137 TH1 open/short circuit (discharge temperature 1)BITRead0 = No alarm; 1 = Alarm
DI137doc 10138C138 TH2 open/short circuit (discharge temperature 2)BITRead0 = No alarm; 1 = Alarm
DI138doc 10139C139 TH3 open/short circuit (suction temperature 1)BITRead0 = No alarm; 1 = Alarm
DI139doc 10140C140 TH4 open/short circuit (suction temperature 2)BITRead0 = No alarm; 1 = Alarm
DI140doc 10141C141 TH5 open/short circuit (subcool inlet)BITRead0 = No alarm; 1 = Alarm
DI143doc 10144C144 TH8 open/short circuit (environment temperature)BITRead0 = No alarm; 1 = Alarm
DI148doc 10149C149 Suction temperature sensor abnormalityBITRead0 = No alarm; 1 = Alarm
DI149doc 10150C150 Discharge temperature sensor abnormalityBITRead0 = No alarm; 1 = Alarm
DI150doc 10151C151 Low superheat protectionBITRead0 = No alarm; 1 = Alarm
DI152doc 10153C153 Compressor current protectionBITRead0 = No alarm; 1 = Alarm
DI153doc 10154C154 IPM module protectionBITRead0 = No alarm; 1 = Alarm
DI156doc 10157C157 PFC module protectionBITRead0 = No alarm; 1 = Alarm
DI157doc 10158C158 PFC module temperature sensor internal circuit exceptionBITRead0 = No alarm; 1 = Alarm
DI158doc 10159C159 PFC module high temperature protectionBITRead0 = No alarm; 1 = Alarm
DI159doc 10160C160 Input power exception failureBITRead0 = No alarm; 1 = Alarm
DI160doc 10161C161 Excessive input current protectionBITRead0 = No alarm; 1 = Alarm
DI161doc 10162C162 VDC high voltage protectionBITRead0 = No alarm; 1 = Alarm
DI162doc 10163C163 VDC low voltage protectionBITRead0 = No alarm; 1 = Alarm
DI163doc 10164C164 Drive and module communication failureBITRead0 = No alarm; 1 = Alarm
DI164doc 10165C165 Compressor out-of-step during runningBITRead0 = No alarm; 1 = Alarm
DI165doc 10166C166 Current detection circuit failureBITRead0 = No alarm; 1 = Alarm
DI166doc 10167C167 Startup failedBITRead0 = No alarm; 1 = Alarm
DI167doc 10168C168 Compressor out-of-phase failureBITRead0 = No alarm; 1 = Alarm
DI170doc 10171C171 IPM module temperature sensor internal circuit abnormalityBITRead0 = No alarm; 1 = Alarm
DI171doc 10172C172 IPM module high temperature protectionBITRead0 = No alarm; 1 = Alarm
IR1doc 30002Air return temperatureINT16× 0.1°CRead
IR2doc 30003Air outlet temperatureINT16× 0.1°CRead
IR13doc 30014Air return humidityTenths; the map prints the unit column as 0.1 °C (see notes).INT16× 0.1Read
IR34doc 30035IDU DC fan voltageINT16× 0.1VRead
IR36doc 30037Discharge pressureTenths; the map gives no pressure unit (see notes).INT16× 0.1Read
IR37doc 30038Suction pressureTenths; the map gives no pressure unit (see notes).INT16× 0.1Read
IR38doc 30039Target frequencyINT16HzRead
IR39doc 30040Running frequencyINT16HzRead
IR40doc 30041Target evaporation temperatureINT16× 0.1°CRead
IR41doc 30042Discharge temperatureINT16× 0.1°CRead
IR42doc 30043Evaporation temperatureINT16× 0.1°CRead
IR43doc 30044In-coil temperatureINT16× 0.1°CRead
IR44doc 30045Out-coil temperatureINT16× 0.1°CRead
IR46doc 30047IDU valve stepsINT16stepsRead
IR175doc 30176Operation modeINT16Read0 = Refrigeration/Cooling; 1 = Dehumidification; 2 = BMS shutdown; 3 = HMI shutdown; 4 = Fault shutdown
HR100doc 40101Condensation pump alarm modeINT16Read/write0 = Unit off; 1 = Alarm only
HR120doc 40121Air return temperature settingRaw 160-420 (16.0-42.0 °C).INT16× 0.1°CRead/write
HR121doc 40122Air outlet temperature settingRaw 130-270 (13.0-27.0 °C).INT16× 0.1°CRead/write
HR122doc 40123Min. humidify settingRaw 0-950 (0-95 %).INT16× 0.1%Read/write
HR123doc 40124Max. humidify settingRaw 0-1000 (0-100 %).INT16× 0.1%Read/write
HR182doc 40183PTC heater / condensation pump functionBITMAP16Read/writebit 10 = PTC heater function (0 = yes, 1 = no); bit 11 = Condensation pump function (0 = yes, 1 = no)
HR200doc 40201High air return temperature alarm value settingINT16× 0.1°CRead/write
HR203doc 40204Low outlet air temperature alarm value settingINT16× 0.1°CRead/write
HR204doc 40205High outlet air temperature alarm value settingINT16× 0.1°CRead/write
HR215doc 40216Modbus addressINT16Read/write
HR216doc 40217Comm. speedINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200
HR218doc 40219Max. speed of EC/DC fanINT16%Read/write
HR219doc 40220Min. speed of EC/DC fanINT16%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K

What Modbus registers does the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K have?

This map lists 86 registers: 1 coil, 57 discrete inputs, 15 input registers, 13 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row shows a Modicon number (00001 / 10002 / 30002 / 40101 style), a hex and a decimal absolute register. The notes say absolute register 0 is Modicon 40001 and address zero on the wire, so the decimal column is the wire address; e.g. holding 40121 is wire 120 and input status 10002 is wire 1.

What are the minimum Modbus registers to integrate the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K?

Start with CO 0 ON/OFF UNIT (Unit on/off); IR 1 Air return temperature (Air return temperature); IR 2 Air outlet temperature (Air outlet temperature); IR 175 Operation mode (Operation mode); DI 1 Serious alarm output (Serious alarm output); DI 2 Common alarm output (Common alarm output); HR 120 Air return temperature setting (Air return temperature setpoint); HR 121 Air outlet temperature setting (Air outlet temperature setpoint).

How do I enable Modbus control of the Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K?

Not described in the register map. The unit's Modbus address and baud rate are themselves writable at holding 40216 / 40217.

Where is the official Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K Modbus documentation?

The source is Modbus Register Map: Uniflair Rack Mounted Room Cooling ACRMD4Kxxx (990-91589), revision 2022-02, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=Modbus_Register_Map_990-91589.

More Schneider Electric Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Modbus Register Map: Uniflair Rack Mounted Room Cooling ACRMD4Kxxx · 990-91589 · rev. 2022-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.