- EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
VRF / split AC gateway · Modbus register map
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus register map
Updated 17 November 2026
The EKMBPP1(A) connects to the P1P2 remote-controller bus of Daikin Sky Air and VRV indoor units and is a Modbus RTU slave on RS-485. Holding registers set the group's setpoint, fan speed, mode, louvre, on/off, update/lock behaviour, limits, VAM ventilation and Smart Grid mode; input registers give group and per-unit status, errors and temperatures.
This page lists 158 Modbus registers for the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin
- Model
- EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
- Equipment type
- VRF / split AC gateway
- Registers
- 158 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- EKMBPP1, EKMBPP1A
Integration notes: Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
Read I0020-I0035 for the group state and the unit blocks from I0120 for each indoor unit. Write H0001-H0005 to control the group; choose an update mode (H0010-H0015) so remote controllers are locked or left free as needed.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 5 | On/off | UINT16 | On/off | Read/write |
| HR 3 | Operation mode | UINT16 | Operation mode | Read/write |
| HR 1 | Setpoint | UINT16 | Setpoint | Read/write |
| IR 20 | Unit count | UINT16 | Unit count | Read |
| IR 21 | Group error | UINT16 | Group error | Read |
| IR 23 | Return air average | INT16 | Average return air temperature | Read |
| IR 123 | Unit 1 return air temperature | INT16 | Unit 1 return air temperature | Read |
Enable Modbus control & writes
Set the Modbus address (0-63) on the DIP switch; the protocol is fixed at 9600 baud, no parity, 1 stop bit. DIP switches also select the optional 120 s master timeout. Terminate the RS-485 line with slide switches SS1-SS3 (0, 100 or 120 ohm).
Communication loss & watchdog
Optional (DIP switch): if no holding register is written for 120 seconds all units switch on with their current settings and, depending on the setting, remote controllers are unlocked. A Forced off Smart Grid request is never overruled.
Byte order & addressing
- Up to 10 registers per read or write.
- In update mode Central the value is written to the unit repeatedly and the remote buttons are locked; LastTouch requires writing only on change.
- Smart Grid does not work with update mode Local.
Network setup
- 3-wire RS-485, Modbus RTU slave, 9600 baud, no parity, 1 stop bit.
Watch out for
- Only one Modbus master is allowed; a Smart Grid controller and a BMS cannot share the adapter.
- Coil temperatures are only available when the adapter is in P1P2 Main mode.
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 20doc I0020 (30021) | Unit count | Indoor units found, 0-16. | UINT16 | Read | ||||
| IR | 21doc I0021 (30022) | Group error | UINT16 | Read | 0 = No error; 1 = At least one unit in error | ||||
| IR | 22doc I0022 (30023) | Group error code | 255 = no error; else two ASCII characters of the first unit's error code. | UINT16 | Read | ||||
| IR | 23doc I0023 (30024) | Return air average | INT16 | × 0.01 | °C | Read | |||
| IR | 24doc I0024 (30025) | Group filter alarm | UINT16 | Read | 0 = No alarm; 1 = At least one unit | ||||
| IR | 25doc I0025 (30026) | Return air minimum | INT16 | × 0.01 | °C | Read | |||
| IR | 26doc I0026 (30027) | Return air maximum | INT16 | × 0.01 | °C | Read | |||
| IR | 30doc I0030 (30031) | Group thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling; 3 = Heating and cooling | ||||
| IR | 35doc I0035 (30036) | Defrost | UINT16 | Read | 0 = No defrost; 1 = At least one unit in defrost | ||||
| IR | 50doc I0050 (30051) | Remote controller temperature | Single indoor unit with Sub remote controller only; else 0. | INT16 | × 0.01 | °C | Read | ||
| IR | 51doc I0051 (30052) | Remote controller operation mode | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling; 3 = Heating and cooling | ||||
| IR | 120doc I0120 (30121) | Unit 1 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 121doc I0121 (30122) | Unit 1 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 122doc I0122 (30123) | Unit 1 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 123doc I0123 (30124) | Unit 1 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 124doc I0124 (30125) | Unit 1 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 130doc I0130 (30131) | Unit 1 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 131doc I0131 (30132) | Unit 1 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 132doc I0132 (30133) | Unit 1 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 220doc I0220 (30221) | Unit 2 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 221doc I0221 (30222) | Unit 2 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 222doc I0222 (30223) | Unit 2 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 223doc I0223 (30224) | Unit 2 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 224doc I0224 (30225) | Unit 2 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 230doc I0230 (30231) | Unit 2 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 231doc I0231 (30232) | Unit 2 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 232doc I0232 (30233) | Unit 2 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 320doc I0320 (30321) | Unit 3 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 321doc I0321 (30322) | Unit 3 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 322doc I0322 (30323) | Unit 3 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 323doc I0323 (30324) | Unit 3 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 324doc I0324 (30325) | Unit 3 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 330doc I0330 (30331) | Unit 3 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 331doc I0331 (30332) | Unit 3 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 332doc I0332 (30333) | Unit 3 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 420doc I0420 (30421) | Unit 4 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 421doc I0421 (30422) | Unit 4 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 422doc I0422 (30423) | Unit 4 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 423doc I0423 (30424) | Unit 4 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 424doc I0424 (30425) | Unit 4 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 430doc I0430 (30431) | Unit 4 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 431doc I0431 (30432) | Unit 4 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 432doc I0432 (30433) | Unit 4 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 520doc I0520 (30521) | Unit 5 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 521doc I0521 (30522) | Unit 5 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 522doc I0522 (30523) | Unit 5 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 523doc I0523 (30524) | Unit 5 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 524doc I0524 (30525) | Unit 5 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 530doc I0530 (30531) | Unit 5 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 531doc I0531 (30532) | Unit 5 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 532doc I0532 (30533) | Unit 5 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 620doc I0620 (30621) | Unit 6 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 621doc I0621 (30622) | Unit 6 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 622doc I0622 (30623) | Unit 6 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 623doc I0623 (30624) | Unit 6 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 624doc I0624 (30625) | Unit 6 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 630doc I0630 (30631) | Unit 6 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 631doc I0631 (30632) | Unit 6 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 632doc I0632 (30633) | Unit 6 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 720doc I0720 (30721) | Unit 7 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 721doc I0721 (30722) | Unit 7 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 722doc I0722 (30723) | Unit 7 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 723doc I0723 (30724) | Unit 7 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 724doc I0724 (30725) | Unit 7 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 730doc I0730 (30731) | Unit 7 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 731doc I0731 (30732) | Unit 7 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 732doc I0732 (30733) | Unit 7 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 820doc I0820 (30821) | Unit 8 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 821doc I0821 (30822) | Unit 8 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 822doc I0822 (30823) | Unit 8 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 823doc I0823 (30824) | Unit 8 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 824doc I0824 (30825) | Unit 8 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 830doc I0830 (30831) | Unit 8 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 831doc I0831 (30832) | Unit 8 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 832doc I0832 (30833) | Unit 8 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 920doc I0920 (30921) | Unit 9 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 921doc I0921 (30922) | Unit 9 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 922doc I0922 (30923) | Unit 9 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 923doc I0923 (30924) | Unit 9 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 924doc I0924 (30925) | Unit 9 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 930doc I0930 (30931) | Unit 9 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 931doc I0931 (30932) | Unit 9 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 932doc I0932 (30933) | Unit 9 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1020doc I1020 (31021) | Unit 10 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1021doc I1021 (31022) | Unit 10 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1022doc I1022 (31023) | Unit 10 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1023doc I1023 (31024) | Unit 10 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1024doc I1024 (31025) | Unit 10 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1030doc I1030 (31031) | Unit 10 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1031doc I1031 (31032) | Unit 10 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1032doc I1032 (31033) | Unit 10 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1120doc I1120 (31121) | Unit 11 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1121doc I1121 (31122) | Unit 11 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1122doc I1122 (31123) | Unit 11 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1123doc I1123 (31124) | Unit 11 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1124doc I1124 (31125) | Unit 11 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1130doc I1130 (31131) | Unit 11 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1131doc I1131 (31132) | Unit 11 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1132doc I1132 (31133) | Unit 11 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1220doc I1220 (31221) | Unit 12 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1221doc I1221 (31222) | Unit 12 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1222doc I1222 (31223) | Unit 12 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1223doc I1223 (31224) | Unit 12 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1224doc I1224 (31225) | Unit 12 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1230doc I1230 (31231) | Unit 12 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1231doc I1231 (31232) | Unit 12 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1232doc I1232 (31233) | Unit 12 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1320doc I1320 (31321) | Unit 13 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1321doc I1321 (31322) | Unit 13 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1322doc I1322 (31323) | Unit 13 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1323doc I1323 (31324) | Unit 13 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1324doc I1324 (31325) | Unit 13 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1330doc I1330 (31331) | Unit 13 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1331doc I1331 (31332) | Unit 13 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1332doc I1332 (31333) | Unit 13 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1420doc I1420 (31421) | Unit 14 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1421doc I1421 (31422) | Unit 14 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1422doc I1422 (31423) | Unit 14 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1423doc I1423 (31424) | Unit 14 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1424doc I1424 (31425) | Unit 14 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1430doc I1430 (31431) | Unit 14 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1431doc I1431 (31432) | Unit 14 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1432doc I1432 (31433) | Unit 14 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1520doc I1520 (31521) | Unit 15 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1521doc I1521 (31522) | Unit 15 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1522doc I1522 (31523) | Unit 15 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1523doc I1523 (31524) | Unit 15 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1524doc I1524 (31525) | Unit 15 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1530doc I1530 (31531) | Unit 15 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1531doc I1531 (31532) | Unit 15 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1532doc I1532 (31533) | Unit 15 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1620doc I1620 (31621) | Unit 16 exists | UINT16 | Read | 0 = No unit; 1 = Unit found | ||||
| IR | 1621doc I1621 (31622) | Unit 16 error | UINT16 | Read | 0 = No error; 1 = In error | ||||
| IR | 1622doc I1622 (31623) | Unit 16 error code | 255 = no error; else two ASCII characters (high/low byte). | UINT16 | Read | ||||
| IR | 1623doc I1623 (31624) | Unit 16 return air temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 1624doc I1624 (31625) | Unit 16 filter alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 1630doc I1630 (31631) | Unit 16 thermo on | UINT16 | Read | 0 = Idle / fan; 1 = Heating; 2 = Cooling | ||||
| IR | 1631doc I1631 (31632) | Unit 16 coil in temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| IR | 1632doc I1632 (31633) | Unit 16 coil out temperature | P1P2 Main mode only. | INT16 | × 0.01 | °C | Read | ||
| HR | 1doc H0001 (40002) | Setpoint | Range 16-32; out-of-range values are clamped. | UINT16 | Read/write | ||||
| HR | 2doc H0002 (40003) | Fan speed | Units with 3 speeds use 1, 3, 5; Auto reads 5. | UINT16 | Read/write | 1 = Low; 2 = Medium low; 3 = Medium; 4 = Medium high; 5 = High | |||
| HR | 3doc H0003 (40004) | Operation mode | UINT16 | Read/write | 0 = Auto; 1 = Heating; 2 = Fan / ventilation; 3 = Cooling; 4 = Dry | ||||
| HR | 4doc H0004 (40005) | Airflow direction | UINT16 | Read/write | 1 = Swing; 2 = 0 degrees; 3 = 20 degrees; 4 = 45 degrees; 5 = 70 degrees; 6 = 90 degrees | ||||
| HR | 5doc H0005 (40006) | On/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 10doc H0010 (40011) | Global update mode | Writes all update registers at once. | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | |||
| HR | 11doc H0011 (40012) | Setpoint update mode | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | ||||
| HR | 12doc H0012 (40013) | Fan speed update mode | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | ||||
| HR | 13doc H0013 (40014) | Mode update mode | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | ||||
| HR | 14doc H0014 (40015) | Airflow direction update mode | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | ||||
| HR | 15doc H0015 (40016) | On/off update mode | UINT16 | Read/write | 0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange | ||||
| HR | 20doc H0020 (40021) | Setpoint minimum limit | 16-32; 0 = no limit. | UINT16 | Read/write | ||||
| HR | 21doc H0021 (40022) | Setpoint maximum limit | 16-32; 0 = no limit. | UINT16 | Read/write | ||||
| HR | 22doc H0022 (40023) | Fan speed inhibit | Sum of inhibited speeds; 0 = no limit. | BITMAP16 | Read/write | bit 1 = Inhibit low; bit 2 = Inhibit medium low; bit 3 = Inhibit medium; bit 4 = Inhibit medium high; bit 5 = Inhibit high | |||
| HR | 23doc H0023 (40024) | Mode inhibit | Sum of inhibited modes; 0 = no limit. | BITMAP16 | Read/write | bit 0 = Inhibit auto; bit 1 = Inhibit heating; bit 2 = Inhibit fan; bit 3 = Inhibit cooling; bit 4 = Inhibit dry | |||
| HR | 24doc H0024 (40025) | Airflow direction inhibit | Sum of inhibited directions; 0 = no limit. | BITMAP16 | Read/write | bit 1 = Inhibit swing; bit 2 = Inhibit 0 degrees; bit 3 = Inhibit 20 degrees; bit 4 = Inhibit 45 degrees; bit 5 = Inhibit 70 degrees; bit 6 = Inhibit 90 degrees | |||
| HR | 30doc H0030 (40031) | Ventilation mode (VAM/VKM) | UINT16 | Read/write | 0 = Auto; 1 = Heat recovery; 2 = Bypass | ||||
| HR | 31doc H0031 (40032) | Ventilation rate (VAM/VKM) | UINT16 | Read/write | 1 = Low; 2 = High | ||||
| HR | 55doc H0055 (40056) | Smart Grid operation mode | UINT16 | Read/write | 0 = Free running; 1 = Forced off; 2 = Recommended on; 3 = Forced on |
Notes on this map
- All registers are 16-bit. Temperatures are degrees C x 100 as signed values (above 32767 is negative).
- Per-unit input registers: unit n uses n x 100 + 20 to n x 100 + 32 (unit 1 = I0120-I0132, unit 16 = I1620-I1632).
- Error codes hold two ASCII characters (high and low byte) forming the Daikin error code; 0 = waiting for data, 255 = no error, 14384 = group timeout (80), 14388 = unit missing (84).
- Inhibit registers are sums of the listed inhibit values (1, 2, 4, 8 ...), shown here as bits.
- The setpoint registers print a range of 16-32 with no unit.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
What Modbus registers does the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) have?
This map lists 158 registers: 139 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes registers as H0001 / I0020 with the matching Modicon number beside them (H0001 = 40002, I0020 = 30021). The H/I number is the wire address.
What are the minimum Modbus registers to integrate the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)?
Start with HR 5 On/off (On/off); HR 3 Operation mode (Operation mode); HR 1 Setpoint (Setpoint); IR 20 Unit count (Unit count); IR 21 Group error (Group error); IR 23 Return air average (Average return air temperature); IR 123 Unit 1 return air temperature (Unit 1 return air temperature).
How do I enable Modbus control of the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)?
Set the Modbus address (0-63) on the DIP switch; the protocol is fixed at 9600 baud, no parity, 1 stop bit. DIP switches also select the optional 120 s master timeout. Terminate the RS-485 line with slide switches SS1-SS3 (0, 100 or 120 ohm).
What happens when the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) loses Modbus communication?
Optional (DIP switch): if no holding register is written for 120 seconds all units switch on with their current settings and, depending on the setting, remote controllers are unlocked. A Forced off Smart Grid request is never overruled.
Where is the official Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus documentation?
The source is Installation manual EKMBPP1+EKMBPP1A Modbus adapter (4P720139-1C), revision 2024-11, published free by Daikin at https://www.daikin.eu/content/dam/document-library/installation-manuals/opt-and-acc/for-outdoor-units/ekmbpp1/EKMBPP1.EKMBPP1A_Installation%20manual_4PEN720139-1C_English.pdf.
More Daikin Modbus register maps
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
Other ac & vrf gateways register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus
All ac & vrf gateways Modbus register maps →
Source: Installation manual EKMBPP1+EKMBPP1A Modbus adapter · 4P720139-1C · rev. 2024-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.