VRF / split AC gateway · Modbus register map

Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus register map

Updated 17 November 2026

Short answer

The EKMBPP1(A) connects to the P1P2 remote-controller bus of Daikin Sky Air and VRV indoor units and is a Modbus RTU slave on RS-485. Holding registers set the group's setpoint, fan speed, mode, louvre, on/off, update/lock behaviour, limits, VAM ventilation and Smart Grid mode; input registers give group and per-unit status, errors and temperatures.

This page lists 158 Modbus registers for the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin
Model
EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
Equipment type
VRF / split AC gateway
Registers
158 (19 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
EKMBPP1, EKMBPP1A
Source document
Installation manual EKMBPP1+EKMBPP1A Modbus adapter · 4P720139-1C · rev. 2024-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)

Integration in brief

Read I0020-I0035 for the group state and the unit blocks from I0120 for each indoor unit. Write H0001-H0005 to control the group; choose an update mode (H0010-H0015) so remote controllers are locked or left free as needed.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 5On/offUINT16On/offRead/write
HR 3Operation modeUINT16Operation modeRead/write
HR 1SetpointUINT16SetpointRead/write
IR 20Unit countUINT16Unit countRead
IR 21Group errorUINT16Group errorRead
IR 23Return air averageINT16Average return air temperatureRead
IR 123Unit 1 return air temperatureINT16Unit 1 return air temperatureRead

Enable Modbus control & writes

Set the Modbus address (0-63) on the DIP switch; the protocol is fixed at 9600 baud, no parity, 1 stop bit. DIP switches also select the optional 120 s master timeout. Terminate the RS-485 line with slide switches SS1-SS3 (0, 100 or 120 ohm).

Communication loss & watchdog

Optional (DIP switch): if no holding register is written for 120 seconds all units switch on with their current settings and, depending on the setting, remote controllers are unlocked. A Forced off Smart Grid request is never overruled.

Byte order & addressing

Network setup

Watch out for

Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

158 of 158 shown
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR20doc I0020 (30021)Unit countIndoor units found, 0-16.UINT16Read
IR21doc I0021 (30022)Group errorUINT16Read0 = No error; 1 = At least one unit in error
IR22doc I0022 (30023)Group error code255 = no error; else two ASCII characters of the first unit's error code.UINT16Read
IR23doc I0023 (30024)Return air averageINT16× 0.01°CRead
IR24doc I0024 (30025)Group filter alarmUINT16Read0 = No alarm; 1 = At least one unit
IR25doc I0025 (30026)Return air minimumINT16× 0.01°CRead
IR26doc I0026 (30027)Return air maximumINT16× 0.01°CRead
IR30doc I0030 (30031)Group thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling; 3 = Heating and cooling
IR35doc I0035 (30036)DefrostUINT16Read0 = No defrost; 1 = At least one unit in defrost
IR50doc I0050 (30051)Remote controller temperatureSingle indoor unit with Sub remote controller only; else 0.INT16× 0.01°CRead
IR51doc I0051 (30052)Remote controller operation modeUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling; 3 = Heating and cooling
IR120doc I0120 (30121)Unit 1 existsUINT16Read0 = No unit; 1 = Unit found
IR121doc I0121 (30122)Unit 1 errorUINT16Read0 = No error; 1 = In error
IR122doc I0122 (30123)Unit 1 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR123doc I0123 (30124)Unit 1 return air temperatureINT16× 0.01°CRead
IR124doc I0124 (30125)Unit 1 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR130doc I0130 (30131)Unit 1 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR131doc I0131 (30132)Unit 1 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR132doc I0132 (30133)Unit 1 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR220doc I0220 (30221)Unit 2 existsUINT16Read0 = No unit; 1 = Unit found
IR221doc I0221 (30222)Unit 2 errorUINT16Read0 = No error; 1 = In error
IR222doc I0222 (30223)Unit 2 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR223doc I0223 (30224)Unit 2 return air temperatureINT16× 0.01°CRead
IR224doc I0224 (30225)Unit 2 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR230doc I0230 (30231)Unit 2 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR231doc I0231 (30232)Unit 2 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR232doc I0232 (30233)Unit 2 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR320doc I0320 (30321)Unit 3 existsUINT16Read0 = No unit; 1 = Unit found
IR321doc I0321 (30322)Unit 3 errorUINT16Read0 = No error; 1 = In error
IR322doc I0322 (30323)Unit 3 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR323doc I0323 (30324)Unit 3 return air temperatureINT16× 0.01°CRead
IR324doc I0324 (30325)Unit 3 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR330doc I0330 (30331)Unit 3 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR331doc I0331 (30332)Unit 3 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR332doc I0332 (30333)Unit 3 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR420doc I0420 (30421)Unit 4 existsUINT16Read0 = No unit; 1 = Unit found
IR421doc I0421 (30422)Unit 4 errorUINT16Read0 = No error; 1 = In error
IR422doc I0422 (30423)Unit 4 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR423doc I0423 (30424)Unit 4 return air temperatureINT16× 0.01°CRead
IR424doc I0424 (30425)Unit 4 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR430doc I0430 (30431)Unit 4 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR431doc I0431 (30432)Unit 4 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR432doc I0432 (30433)Unit 4 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR520doc I0520 (30521)Unit 5 existsUINT16Read0 = No unit; 1 = Unit found
IR521doc I0521 (30522)Unit 5 errorUINT16Read0 = No error; 1 = In error
IR522doc I0522 (30523)Unit 5 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR523doc I0523 (30524)Unit 5 return air temperatureINT16× 0.01°CRead
IR524doc I0524 (30525)Unit 5 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR530doc I0530 (30531)Unit 5 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR531doc I0531 (30532)Unit 5 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR532doc I0532 (30533)Unit 5 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR620doc I0620 (30621)Unit 6 existsUINT16Read0 = No unit; 1 = Unit found
IR621doc I0621 (30622)Unit 6 errorUINT16Read0 = No error; 1 = In error
IR622doc I0622 (30623)Unit 6 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR623doc I0623 (30624)Unit 6 return air temperatureINT16× 0.01°CRead
IR624doc I0624 (30625)Unit 6 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR630doc I0630 (30631)Unit 6 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR631doc I0631 (30632)Unit 6 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR632doc I0632 (30633)Unit 6 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR720doc I0720 (30721)Unit 7 existsUINT16Read0 = No unit; 1 = Unit found
IR721doc I0721 (30722)Unit 7 errorUINT16Read0 = No error; 1 = In error
IR722doc I0722 (30723)Unit 7 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR723doc I0723 (30724)Unit 7 return air temperatureINT16× 0.01°CRead
IR724doc I0724 (30725)Unit 7 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR730doc I0730 (30731)Unit 7 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR731doc I0731 (30732)Unit 7 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR732doc I0732 (30733)Unit 7 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR820doc I0820 (30821)Unit 8 existsUINT16Read0 = No unit; 1 = Unit found
IR821doc I0821 (30822)Unit 8 errorUINT16Read0 = No error; 1 = In error
IR822doc I0822 (30823)Unit 8 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR823doc I0823 (30824)Unit 8 return air temperatureINT16× 0.01°CRead
IR824doc I0824 (30825)Unit 8 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR830doc I0830 (30831)Unit 8 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR831doc I0831 (30832)Unit 8 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR832doc I0832 (30833)Unit 8 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR920doc I0920 (30921)Unit 9 existsUINT16Read0 = No unit; 1 = Unit found
IR921doc I0921 (30922)Unit 9 errorUINT16Read0 = No error; 1 = In error
IR922doc I0922 (30923)Unit 9 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR923doc I0923 (30924)Unit 9 return air temperatureINT16× 0.01°CRead
IR924doc I0924 (30925)Unit 9 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR930doc I0930 (30931)Unit 9 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR931doc I0931 (30932)Unit 9 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR932doc I0932 (30933)Unit 9 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1020doc I1020 (31021)Unit 10 existsUINT16Read0 = No unit; 1 = Unit found
IR1021doc I1021 (31022)Unit 10 errorUINT16Read0 = No error; 1 = In error
IR1022doc I1022 (31023)Unit 10 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1023doc I1023 (31024)Unit 10 return air temperatureINT16× 0.01°CRead
IR1024doc I1024 (31025)Unit 10 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1030doc I1030 (31031)Unit 10 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1031doc I1031 (31032)Unit 10 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1032doc I1032 (31033)Unit 10 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1120doc I1120 (31121)Unit 11 existsUINT16Read0 = No unit; 1 = Unit found
IR1121doc I1121 (31122)Unit 11 errorUINT16Read0 = No error; 1 = In error
IR1122doc I1122 (31123)Unit 11 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1123doc I1123 (31124)Unit 11 return air temperatureINT16× 0.01°CRead
IR1124doc I1124 (31125)Unit 11 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1130doc I1130 (31131)Unit 11 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1131doc I1131 (31132)Unit 11 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1132doc I1132 (31133)Unit 11 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1220doc I1220 (31221)Unit 12 existsUINT16Read0 = No unit; 1 = Unit found
IR1221doc I1221 (31222)Unit 12 errorUINT16Read0 = No error; 1 = In error
IR1222doc I1222 (31223)Unit 12 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1223doc I1223 (31224)Unit 12 return air temperatureINT16× 0.01°CRead
IR1224doc I1224 (31225)Unit 12 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1230doc I1230 (31231)Unit 12 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1231doc I1231 (31232)Unit 12 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1232doc I1232 (31233)Unit 12 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1320doc I1320 (31321)Unit 13 existsUINT16Read0 = No unit; 1 = Unit found
IR1321doc I1321 (31322)Unit 13 errorUINT16Read0 = No error; 1 = In error
IR1322doc I1322 (31323)Unit 13 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1323doc I1323 (31324)Unit 13 return air temperatureINT16× 0.01°CRead
IR1324doc I1324 (31325)Unit 13 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1330doc I1330 (31331)Unit 13 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1331doc I1331 (31332)Unit 13 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1332doc I1332 (31333)Unit 13 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1420doc I1420 (31421)Unit 14 existsUINT16Read0 = No unit; 1 = Unit found
IR1421doc I1421 (31422)Unit 14 errorUINT16Read0 = No error; 1 = In error
IR1422doc I1422 (31423)Unit 14 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1423doc I1423 (31424)Unit 14 return air temperatureINT16× 0.01°CRead
IR1424doc I1424 (31425)Unit 14 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1430doc I1430 (31431)Unit 14 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1431doc I1431 (31432)Unit 14 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1432doc I1432 (31433)Unit 14 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1520doc I1520 (31521)Unit 15 existsUINT16Read0 = No unit; 1 = Unit found
IR1521doc I1521 (31522)Unit 15 errorUINT16Read0 = No error; 1 = In error
IR1522doc I1522 (31523)Unit 15 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1523doc I1523 (31524)Unit 15 return air temperatureINT16× 0.01°CRead
IR1524doc I1524 (31525)Unit 15 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1530doc I1530 (31531)Unit 15 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1531doc I1531 (31532)Unit 15 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1532doc I1532 (31533)Unit 15 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1620doc I1620 (31621)Unit 16 existsUINT16Read0 = No unit; 1 = Unit found
IR1621doc I1621 (31622)Unit 16 errorUINT16Read0 = No error; 1 = In error
IR1622doc I1622 (31623)Unit 16 error code255 = no error; else two ASCII characters (high/low byte).UINT16Read
IR1623doc I1623 (31624)Unit 16 return air temperatureINT16× 0.01°CRead
IR1624doc I1624 (31625)Unit 16 filter alarmUINT16Read0 = No alarm; 1 = Filter alarm
IR1630doc I1630 (31631)Unit 16 thermo onUINT16Read0 = Idle / fan; 1 = Heating; 2 = Cooling
IR1631doc I1631 (31632)Unit 16 coil in temperatureP1P2 Main mode only.INT16× 0.01°CRead
IR1632doc I1632 (31633)Unit 16 coil out temperatureP1P2 Main mode only.INT16× 0.01°CRead
HR1doc H0001 (40002)SetpointRange 16-32; out-of-range values are clamped.UINT16Read/write
HR2doc H0002 (40003)Fan speedUnits with 3 speeds use 1, 3, 5; Auto reads 5.UINT16Read/write1 = Low; 2 = Medium low; 3 = Medium; 4 = Medium high; 5 = High
HR3doc H0003 (40004)Operation modeUINT16Read/write0 = Auto; 1 = Heating; 2 = Fan / ventilation; 3 = Cooling; 4 = Dry
HR4doc H0004 (40005)Airflow directionUINT16Read/write1 = Swing; 2 = 0 degrees; 3 = 20 degrees; 4 = 45 degrees; 5 = 70 degrees; 6 = 90 degrees
HR5doc H0005 (40006)On/offUINT16Read/write0 = Off; 1 = On
HR10doc H0010 (40011)Global update modeWrites all update registers at once.UINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR11doc H0011 (40012)Setpoint update modeUINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR12doc H0012 (40013)Fan speed update modeUINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR13doc H0013 (40014)Mode update modeUINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR14doc H0014 (40015)Airflow direction update modeUINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR15doc H0015 (40016)On/off update modeUINT16Read/write0 = LastTouch; 1 = Central (remote locked); 2 = Local; 3 = OnChange
HR20doc H0020 (40021)Setpoint minimum limit16-32; 0 = no limit.UINT16Read/write
HR21doc H0021 (40022)Setpoint maximum limit16-32; 0 = no limit.UINT16Read/write
HR22doc H0022 (40023)Fan speed inhibitSum of inhibited speeds; 0 = no limit.BITMAP16Read/writebit 1 = Inhibit low; bit 2 = Inhibit medium low; bit 3 = Inhibit medium; bit 4 = Inhibit medium high; bit 5 = Inhibit high
HR23doc H0023 (40024)Mode inhibitSum of inhibited modes; 0 = no limit.BITMAP16Read/writebit 0 = Inhibit auto; bit 1 = Inhibit heating; bit 2 = Inhibit fan; bit 3 = Inhibit cooling; bit 4 = Inhibit dry
HR24doc H0024 (40025)Airflow direction inhibitSum of inhibited directions; 0 = no limit.BITMAP16Read/writebit 1 = Inhibit swing; bit 2 = Inhibit 0 degrees; bit 3 = Inhibit 20 degrees; bit 4 = Inhibit 45 degrees; bit 5 = Inhibit 70 degrees; bit 6 = Inhibit 90 degrees
HR30doc H0030 (40031)Ventilation mode (VAM/VKM)UINT16Read/write0 = Auto; 1 = Heat recovery; 2 = Bypass
HR31doc H0031 (40032)Ventilation rate (VAM/VKM)UINT16Read/write1 = Low; 2 = High
HR55doc H0055 (40056)Smart Grid operation modeUINT16Read/write0 = Free running; 1 = Forced off; 2 = Recommended on; 3 = Forced on

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)

What Modbus registers does the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) have?

This map lists 158 registers: 139 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes registers as H0001 / I0020 with the matching Modicon number beside them (H0001 = 40002, I0020 = 30021). The H/I number is the wire address.

What are the minimum Modbus registers to integrate the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)?

Start with HR 5 On/off (On/off); HR 3 Operation mode (Operation mode); HR 1 Setpoint (Setpoint); IR 20 Unit count (Unit count); IR 21 Group error (Group error); IR 23 Return air average (Average return air temperature); IR 123 Unit 1 return air temperature (Unit 1 return air temperature).

How do I enable Modbus control of the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)?

Set the Modbus address (0-63) on the DIP switch; the protocol is fixed at 9600 baud, no parity, 1 stop bit. DIP switches also select the optional 120 s master timeout. Terminate the RS-485 line with slide switches SS1-SS3 (0, 100 or 120 ohm).

What happens when the Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) loses Modbus communication?

Optional (DIP switch): if no holding register is written for 120 seconds all units switch on with their current settings and, depending on the setting, remote controllers are unlocked. A Forced off Smart Grid request is never overruled.

Where is the official Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2) Modbus documentation?

The source is Installation manual EKMBPP1+EKMBPP1A Modbus adapter (4P720139-1C), revision 2024-11, published free by Daikin at https://www.daikin.eu/content/dam/document-library/installation-manuals/opt-and-acc/for-outdoor-units/ekmbpp1/EKMBPP1.EKMBPP1A_Installation%20manual_4PEN720139-1C_English.pdf.

More Daikin Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Installation manual EKMBPP1+EKMBPP1A Modbus adapter · 4P720139-1C · rev. 2024-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.