Air handler DX kit (VRF / split AC gateway built in) · Modbus register map

LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus register map

Updated 19 November 2026

Short answer

The PAHCMS000 kit connects a third-party air handler to LG Multi V or single-split outdoor units and controls discharge air temperature; a DDC can drive it over Modbus RTU on RS485 CH4. A coil switches the unit, holding registers set mode, capacity request and the cooling and heating discharge targets, and discrete inputs and input registers report unit and per-outdoor-unit (up to 4) run, compressor, defrost and error status, the error code and return/supply air temperatures.

This page lists 27 Modbus registers for the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.

Manufacturer
LG
Model
PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
Equipment type
Air handler DX kit (VRF / split AC gateway built in)
Registers
27 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus
Source document
Installation Manual for LG Air Handler Unit (AHU) Communications Kit - PAHCMS000 · IM_AHU_Comm_Kit_PAHCMS000_11_23 · rev. 2023-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)

Integration in brief

With DIP SW1-1 ON (communication), write coil 00001 for on/off and holding registers 40001, 40003 and 40004 for mode and discharge targets; read 30011/30013 for air temperatures and 10001-10026 for unit and outdoor-unit status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Operating On/OffBITOn/offRead/write
HR 0Operation modeUINT16Operation modeRead/write
HR 2Cooling target temperatureINT16Cooling discharge targetRead/write
HR 3Heating target temperatureINT16Heating discharge targetRead/write
IR 12Supply air temperatureINT16Supply air temperatureRead
IR 0Error codeUINT16Error codeRead
DI 0Error statusBITError statusRead
DI 2Defrost statusBITDefrost statusRead

Enable Modbus control & writes

DIP SW1-1 ON = controlled by DDC through Modbus or an LG central controller (OFF = contact signal, where Modbus control functions are unavailable). SW1-4 ON selects LG central communication over Modbus.

Byte order & addressing

Network setup

Watch out for

LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Operating On/OffBITRead/write0 = Off; 1 = On
DI0doc 10001Error statusBITRead0 = Normal; 1 = Error
DI1doc 10002Operation statusBITRead0 = Off; 1 = On
DI2doc 10003Defrost statusBITRead0 = Normal; 1 = Defrost
DI10doc 10011ODU#1 operation statusBITRead0 = Off; 1 = On
DI11doc 10012ODU#1 compressor statusBITRead0 = Off; 1 = On
DI12doc 10013ODU#1 defrost statusBITRead0 = Normal; 1 = Defrost
DI13doc 10014ODU#1 error statusBITRead0 = Normal; 1 = Error
DI14doc 10015ODU#2 operation statusBITRead0 = Off; 1 = On
DI15doc 10016ODU#2 compressor statusBITRead0 = Off; 1 = On
DI16doc 10017ODU#2 defrost statusBITRead0 = Normal; 1 = Defrost
DI17doc 10018ODU#2 error statusBITRead0 = Normal; 1 = Error
DI18doc 10019ODU#3 operation statusBITRead0 = Off; 1 = On
DI19doc 10020ODU#3 compressor statusBITRead0 = Off; 1 = On
DI20doc 10021ODU#3 defrost statusBITRead0 = Normal; 1 = Defrost
DI21doc 10022ODU#3 error statusBITRead0 = Normal; 1 = Error
DI22doc 10023ODU#4 operation statusBITRead0 = Off; 1 = On
DI23doc 10024ODU#4 compressor statusBITRead0 = Off; 1 = On
DI24doc 10025ODU#4 defrost statusBITRead0 = Normal; 1 = Defrost
DI25doc 10026ODU#4 error statusBITRead0 = Normal; 1 = Error
IR0doc 30001Error codeFormat 1xxxx: second digit = module number, last three digits = error code.UINT16Read
IR10doc 30011Return air temperatureRange -50 to 100 °C, sent x10.INT16× 0.1°CRead
IR12doc 30013Supply air temperatureRange -50 to 100 °C, sent x10.INT16× 0.1°CRead
HR0doc 40001Operation modeUINT16Read/write0 = Cooling; 2 = Fan; 4 = Heating
HR1doc 40002CapacityCapacity request as a UI7 0-10 V equivalent: 0 or 2.0-10 V, x10, 0.5 V steps.UINT16× 0.1VRead/write
HR2doc 40003Cooling target temperature15.6-30 °C, sent x10, 1.0 °C steps.INT16× 0.1°CRead/write
HR3doc 40004Heating target temperature15.6-30 °C, sent x10, 1.0 °C steps.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)

What Modbus registers does the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) have?

This map lists 27 registers: 1 coil, 19 discrete inputs, 3 input registers, 4 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as 00001/10001/30001/40001-style registers, with a function-code table per block (01/05 coils 00001-00008, 02 inputs 10001-10030, 04 input registers 30001-30016, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 30011 is input register 10.

What are the minimum Modbus registers to integrate the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)?

Start with CO 0 Operating On/Off (On/off); HR 0 Operation mode (Operation mode); HR 2 Cooling target temperature (Cooling discharge target); HR 3 Heating target temperature (Heating discharge target); IR 12 Supply air temperature (Supply air temperature); IR 0 Error code (Error code); DI 0 Error status (Error status); DI 2 Defrost status (Defrost status).

How do I enable Modbus control of the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)?

DIP SW1-1 ON = controlled by DDC through Modbus or an LG central controller (OFF = contact signal, where Modbus control functions are unavailable). SW1-4 ON selects LG central communication over Modbus.

Where is the official LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus documentation?

The source is Installation Manual for LG Air Handler Unit (AHU) Communications Kit - PAHCMS000 (IM_AHU_Comm_Kit_PAHCMS000_11_23), revision 2023-11, published free by LG at https://media.us.lg.com/m/11adf83da67f6527/original/IM_AHU_Comm_Kit_PAHCMS000-pdf.pdf.

More LG Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →