- PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
Air handler DX kit (VRF / split AC gateway built in) · Modbus register map
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus register map
Updated 19 November 2026
The PAHCMS000 kit connects a third-party air handler to LG Multi V or single-split outdoor units and controls discharge air temperature; a DDC can drive it over Modbus RTU on RS485 CH4. A coil switches the unit, holding registers set mode, capacity request and the cooling and heating discharge targets, and discrete inputs and input registers report unit and per-outdoor-unit (up to 4) run, compressor, defrost and error status, the error code and return/supply air temperatures.
This page lists 27 Modbus registers for the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.
- Manufacturer
- LG
- Model
- PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
- Equipment type
- Air handler DX kit (VRF / split AC gateway built in)
- Registers
- 27 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus
Integration notes: LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
With DIP SW1-1 ON (communication), write coil 00001 for on/off and holding registers 40001, 40003 and 40004 for mode and discharge targets; read 30011/30013 for air temperatures and 10001-10026 for unit and outdoor-unit status.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Operating On/Off | BIT | On/off | Read/write |
| HR 0 | Operation mode | UINT16 | Operation mode | Read/write |
| HR 2 | Cooling target temperature | INT16 | Cooling discharge target | Read/write |
| HR 3 | Heating target temperature | INT16 | Heating discharge target | Read/write |
| IR 12 | Supply air temperature | INT16 | Supply air temperature | Read |
| IR 0 | Error code | UINT16 | Error code | Read |
| DI 0 | Error status | BIT | Error status | Read |
| DI 2 | Defrost status | BIT | Defrost status | Read |
Enable Modbus control & writes
DIP SW1-1 ON = controlled by DDC through Modbus or an LG central controller (OFF = contact signal, where Modbus control functions are unavailable). SW1-4 ON selects LG central communication over Modbus.
Byte order & addressing
- Operation mode uses 0 = cooling, 2 = fan, 4 = heating.
- The error code is a decimal number whose second digit is the module number.
Network setup
- DDC central communication on RS485 CH4, 2-core 18-16 AWG, up to 1640 ft.
- The main module address (1-247, needed with an LG central controller) is set with the Set/ESC buttons and the 7-segment display; the manual does not say whether it is also the Modbus slave ID for a DDC.
Watch out for
- Control functions are not available when contact-signal control is selected (SW1-1 OFF).
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Operating On/Off | BIT | Read/write | 0 = Off; 1 = On | ||||
| DI | 0doc 10001 | Error status | BIT | Read | 0 = Normal; 1 = Error | ||||
| DI | 1doc 10002 | Operation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 10doc 10011 | ODU#1 operation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 11doc 10012 | ODU#1 compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 12doc 10013 | ODU#1 defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 13doc 10014 | ODU#1 error status | BIT | Read | 0 = Normal; 1 = Error | ||||
| DI | 14doc 10015 | ODU#2 operation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 15doc 10016 | ODU#2 compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 16doc 10017 | ODU#2 defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 17doc 10018 | ODU#2 error status | BIT | Read | 0 = Normal; 1 = Error | ||||
| DI | 18doc 10019 | ODU#3 operation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 19doc 10020 | ODU#3 compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 20doc 10021 | ODU#3 defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 21doc 10022 | ODU#3 error status | BIT | Read | 0 = Normal; 1 = Error | ||||
| DI | 22doc 10023 | ODU#4 operation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 23doc 10024 | ODU#4 compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 24doc 10025 | ODU#4 defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 25doc 10026 | ODU#4 error status | BIT | Read | 0 = Normal; 1 = Error | ||||
| IR | 0doc 30001 | Error code | Format 1xxxx: second digit = module number, last three digits = error code. | UINT16 | Read | ||||
| IR | 10doc 30011 | Return air temperature | Range -50 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 12doc 30013 | Supply air temperature | Range -50 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read | ||
| HR | 0doc 40001 | Operation mode | UINT16 | Read/write | 0 = Cooling; 2 = Fan; 4 = Heating | ||||
| HR | 1doc 40002 | Capacity | Capacity request as a UI7 0-10 V equivalent: 0 or 2.0-10 V, x10, 0.5 V steps. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 2doc 40003 | Cooling target temperature | 15.6-30 °C, sent x10, 1.0 °C steps. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3doc 40004 | Heating target temperature | 15.6-30 °C, sent x10, 1.0 °C steps. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Access follows the function-code dots in the memory map: coil 00001 takes 01 and 05, discrete inputs 02 only, input registers 04 only, holding registers 03 and 06.
- Reserved points are left out.
- The manual does not print the RS485 serial settings for the DDC port; set them to match the kit (the R32 sister kit PAHCMR000 states 9600 bps, no parity, 1 stop bit, but that is a different manual).
- Temperatures are sent multiplied by 10; the return/supply air range includes negative values, so they are listed as signed 16-bit.
- For the capacity ratio behind register 40002 see the UI7 (0-10 V) capacity table in the manual.
- An older revision of this manual (IM_AHU_Comm_Kit_PAHCMS000_5_18) is also hosted by LG.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
What Modbus registers does the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) have?
This map lists 27 registers: 1 coil, 19 discrete inputs, 3 input registers, 4 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as 00001/10001/30001/40001-style registers, with a function-code table per block (01/05 coils 00001-00008, 02 inputs 10001-10030, 04 input registers 30001-30016, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 30011 is input register 10.
What are the minimum Modbus registers to integrate the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)?
Start with CO 0 Operating On/Off (On/off); HR 0 Operation mode (Operation mode); HR 2 Cooling target temperature (Cooling discharge target); HR 3 Heating target temperature (Heating discharge target); IR 12 Supply air temperature (Supply air temperature); IR 0 Error code (Error code); DI 0 Error status (Error status); DI 2 Defrost status (Defrost status).
How do I enable Modbus control of the LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)?
DIP SW1-1 ON = controlled by DDC through Modbus or an LG central controller (OFF = contact signal, where Modbus control functions are unavailable). SW1-4 ON selects LG central communication over Modbus.
Where is the official LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC) Modbus documentation?
The source is Installation Manual for LG Air Handler Unit (AHU) Communications Kit - PAHCMS000 (IM_AHU_Comm_Kit_PAHCMS000_11_23), revision 2023-11, published free by LG at https://media.us.lg.com/m/11adf83da67f6527/original/IM_AHU_Comm_Kit_PAHCMS000-pdf.pdf.
More LG Modbus register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615
Other ac & vrf gateways register maps
- VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - Heat pump (via ISG Modbus TCP gateway)
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
Stiebel Eltron heat pumps run by a WPMsystem, WPM 3 or WPM 3i manager, reached through an ISG web (229336) or ISG plus (233493) with the Modbus TCP/IP software extension.
Also known as: ISG web Modbus TCP/IP, ISG plus Modbus TCP/IP, WPMsystem, WPM 3, WPM 3i - VRF / split AC gateway
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.
Also known as: Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus - VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus
All ac & vrf gateways Modbus register maps →
Source: Installation Manual for LG Air Handler Unit (AHU) Communications Kit - PAHCMS000 · IM_AHU_Comm_Kit_PAHCMS000_11_23 · rev. 2023-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.