VRF / split AC gateway · Modbus register map

Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus register map

Updated 19 November 2026

Short answer

Aidoo Pro is a small Airzone interface for an air-conditioning unit that can serve Modbus RTU on RS-485 to a BMS. The direct-expansion map gives on/off, mode, setpoint, fan, louvres, room and refrigerant-circuit temperatures, pressures, current, error codes and 32-bit energy counters.

This page lists 52 Modbus registers for the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airzone’s own free documentation (linked below) and checked against it.

Manufacturer
Airzone
Model
Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Equipment type
VRF / split AC gateway
Registers
52 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus
Source document
Integration Manual Aidoo - Modbus · v. 201 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners

Integration in brief

Set the Aidoo output to Modbus and the slave ID in the Airzone Cloud app, connect RS-485 at 19200 8E1, then use registers 0-4 for on/off, setpoint (x10), mode and fan and poll 2, 7-8 and 55 for room temperature and errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Unit status on/offUINT16On/offRead/write
HR 3ModeUINT16ModeRead/write
HR 1SetpointUINT16Setpoint (x10)Read/write
HR 4Fan speed (percentage)UINT16Fan speedRead/write
HR 2Local (room) temperatureUINT16Room temperature (x10)Read
HR 7Unit error code part 1UINT16Error code (ASCII)Read
HR 14Available modesBITMAP16Modes the unit supportsRead

Enable Modbus control & writes

In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.

Byte order & addressing

Network setup

Watch out for

Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

52 of 52 shown
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Unit status on/offUINT16Read/write0 = Off; 1 = On
HR1Setpoint°C x 10 (230 = 23 °C). Limits depend on the AC unit.UINT16× 0.1°CRead/write
HR2Local (room) temperature°C x 10 (230 = 23 °C). Must be above 0.UINT16× 0.1°CRead
HR3ModeUINT16Read/write1 = Auto; 2 = Cool; 3 = Heat; 4 = Fan; 5 = Dry
HR4Fan speed (percentage)UINT16Read/write0 = Auto; 25 = Silent; 50 = Low; 75 = Medium; 100 = High
HR5Louver vertical4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3.BITMAP16Read/writebit 0 = Louver 1 position nibble (bits 0-3); bit 4 = Louver 2 position nibble (bits 4-7); bit 8 = Louver 3 position nibble (bits 8-11); bit 12 = Louver 4 position nibble (bits 12-15)
HR6Louver horizontal4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3.BITMAP16Read/writebit 0 = Louver 1 position nibble (bits 0-3); bit 4 = Louver 2 position nibble (bits 4-7); bit 8 = Louver 3 position nibble (bits 8-11); bit 12 = Louver 4 position nibble (bits 12-15)
HR7Unit error code part 1ASCII characters of the indoor unit error code (first part).UINT16Read
HR8Unit error code part 2ASCII characters of the indoor unit error code (second part).UINT16Read
HR14Available modesBITMAP16Readbit 0 = Auto; bit 1 = Cool; bit 2 = Heat; bit 3 = Ventilation; bit 4 = Dry
HR15Available speedsBITMAP16Readbit 0 = Auto; bit 1 = Super-low; bit 2 = Low; bit 3 = Medium-low; bit 4 = Medium; bit 5 = Medium-high; bit 6 = High; bit 7 = Super-high
HR16Available louversBits 8-11 / 12-15 give the number of vertical / horizontal positions (0-7).BITMAP16Readbit 0 = Auto up/down; bit 3 = Swing up/down; bit 4 = Swing left/right; bit 5 = Swirl
HR17Setpoint limit max air cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR18Setpoint limit min air cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR19Setpoint limit max air heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR20Setpoint limit min air heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR21Setpoint limit max air auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR22Setpoint limit min air auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR23Setpoint limit max air ventilation°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR24Setpoint limit min air ventilation°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR25Setpoint limit max air dry°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR26Setpoint limit min air dry°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR36Return temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR37Indoor heat exchanger temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR38Indoor gas pipe temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR40Outdoor compressor discharge temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR41Outdoor expansion valve positionUINT16pulsesRead
HR42Indoor expansion valve positionUINT16pulsesRead
HR43Evaporation pressureMPa x 100 (127 = 1.27 MPa).UINT16× 0.01MPaRead
HR44Condensation pressureMPa x 100 (127 = 1.27 MPa).UINT16× 0.01MPaRead
HR45Current consumptionA x 10 (70 = 7 A).UINT16× 0.1ARead
HR53Work temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR54Fan speed (numeric)UINT16Read/write0 = Auto; 1 = Silent; 2 = Low; 3 = Medium; 4 = High
HR55Error valueNumeric indoor unit error value.UINT16Read
HR56Modbus slave addressDefault 1.UINT16Read/write
HR57Port baud rateUINT16Read/write0 = 100; 1 = 300; 2 = 500; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 7800; 7 = 9600; 8 = 19200; 9 = 57600; 10 = 115200
HR58Port parityUINT16Read/write0 = None; 1 = Odd; 2 = Even
HR59Emergency heat statusUINT16Read0 = Deactivated; 1 = Activated
HR60Input T1T2 statusUINT16Read0 = Deactivated; 1 = Activated
HR73doc 73 / 74Total energy generated in heatingLow word at 73, high word at 74 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR75Actual power generated in heatingExample 0x1CAC = 7340 W.UINT16WRead
HR76doc 76 / 77Total energy generated in coolingLow word at 76, high word at 77 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR78Actual power generated in coolingExample 0x1CAC = 7340 W.UINT16WRead
HR82Actual power generated by photovoltaicExample 0x1CAC = 7340 W.UINT16WRead
HR83doc 83 / 84Total energy producedLow word at 83, high word at 84 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR85doc 85 / 86Total energy consumed by heat pumpLow word at 85, high word at 86 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR87Actual power consumed by heat pumpExample 0x1CAC = 7340 W.UINT16WRead
HR88Actual power consumed by whole buildingExample 0x1CAC = 7340 W.UINT16WRead
HR89doc 89 / 90Electric resistor consumption in heatingLow word at 89, high word at 90 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR93doc 93 / 94Compressor consumption in heatingLow word at 93, high word at 94 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR95doc 95 / 96Compressor consumption in coolingLow word at 95, high word at 96 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead
HR99doc 99 / 100Total consumptionLow word at 99, high word at 100 (manual example 0x1215 + 0x0001 = 70165).UINT32CDABkWhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners

What Modbus registers does the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners have?

This map lists 52 registers: 52 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 0 (unit on/off is register 0) and the command description puts this number in the 'register address' field, so the printed number is the wire address.

What byte order does the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners?

Start with HR 0 Unit status on/off (On/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint (x10)); HR 4 Fan speed (percentage) (Fan speed); HR 2 Local (room) temperature (Room temperature (x10)); HR 7 Unit error code part 1 (Error code (ASCII)); HR 14 Available modes (Modes the unit supports).

How do I enable Modbus control of the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners?

In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.

Where is the official Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus documentation?

The source is Integration Manual Aidoo - Modbus (v. 201). Airzone doesn't publish it on its own website, so this map was re-typed from a free copy at https://thermosilesia.pl/assets/default/system_object_files/4bc5a150b45a2a7401add97664eff2aa.pdf. It may be an older revision, so check it against the live unit.

More Airzone Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Integration Manual Aidoo - Modbus · v. 201 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.