VRF / split AC gateway · Modbus register map
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus register map
Updated 19 November 2026
Aidoo Pro is a small Airzone interface for an air-conditioning unit that can serve Modbus RTU on RS-485 to a BMS. The direct-expansion map gives on/off, mode, setpoint, fan, louvres, room and refrigerant-circuit temperatures, pressures, current, error codes and 32-bit energy counters.
This page lists 52 Modbus registers for the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airzone’s own free documentation (linked below) and checked against it.
- Manufacturer
- Airzone
- Model
- Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
- Equipment type
- VRF / split AC gateway
- Registers
- 52 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus
- Source document
- Integration Manual Aidoo - Modbus · v. 201 · unofficial copy
Integration notes: Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Set the Aidoo output to Modbus and the slave ID in the Airzone Cloud app, connect RS-485 at 19200 8E1, then use registers 0-4 for on/off, setpoint (x10), mode and fan and poll 2, 7-8 and 55 for room temperature and errors.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Unit status on/off | UINT16 | On/off | Read/write |
| HR 3 | Mode | UINT16 | Mode | Read/write |
| HR 1 | Setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 4 | Fan speed (percentage) | UINT16 | Fan speed | Read/write |
| HR 2 | Local (room) temperature | UINT16 | Room temperature (x10) | Read |
| HR 7 | Unit error code part 1 | UINT16 | Error code (ASCII) | Read |
| HR 14 | Available modes | BITMAP16 | Modes the unit supports | Read |
Enable Modbus control & writes
In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.
Byte order & addressing
- Mode codes start at 1 (1 Auto, 2 Cool, 3 Heat, 4 Fan, 5 Dry).
- Fan speed can be set as a percentage (register 4) or a step number (register 54).
- Energy counters are low word first (CDAB).
Network setup
- Factory serial settings 19200 baud, 8 data bits, even parity, 1 stop bit, half duplex.
- Slave address default 1.
Watch out for
- The manual footnotes that the local temperature (register 2) must be greater than 0.
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Unit status on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1 | Setpoint | °C x 10 (230 = 23 °C). Limits depend on the AC unit. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2 | Local (room) temperature | °C x 10 (230 = 23 °C). Must be above 0. | UINT16 | × 0.1 | °C | Read | ||
| HR | 3 | Mode | UINT16 | Read/write | 1 = Auto; 2 = Cool; 3 = Heat; 4 = Fan; 5 = Dry | ||||
| HR | 4 | Fan speed (percentage) | UINT16 | Read/write | 0 = Auto; 25 = Silent; 50 = Low; 75 = Medium; 100 = High | ||||
| HR | 5 | Louver vertical | 4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3. | BITMAP16 | Read/write | bit 0 = Louver 1 position nibble (bits 0-3); bit 4 = Louver 2 position nibble (bits 4-7); bit 8 = Louver 3 position nibble (bits 8-11); bit 12 = Louver 4 position nibble (bits 12-15) | |||
| HR | 6 | Louver horizontal | 4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3. | BITMAP16 | Read/write | bit 0 = Louver 1 position nibble (bits 0-3); bit 4 = Louver 2 position nibble (bits 4-7); bit 8 = Louver 3 position nibble (bits 8-11); bit 12 = Louver 4 position nibble (bits 12-15) | |||
| HR | 7 | Unit error code part 1 | ASCII characters of the indoor unit error code (first part). | UINT16 | Read | ||||
| HR | 8 | Unit error code part 2 | ASCII characters of the indoor unit error code (second part). | UINT16 | Read | ||||
| HR | 14 | Available modes | BITMAP16 | Read | bit 0 = Auto; bit 1 = Cool; bit 2 = Heat; bit 3 = Ventilation; bit 4 = Dry | ||||
| HR | 15 | Available speeds | BITMAP16 | Read | bit 0 = Auto; bit 1 = Super-low; bit 2 = Low; bit 3 = Medium-low; bit 4 = Medium; bit 5 = Medium-high; bit 6 = High; bit 7 = Super-high | ||||
| HR | 16 | Available louvers | Bits 8-11 / 12-15 give the number of vertical / horizontal positions (0-7). | BITMAP16 | Read | bit 0 = Auto up/down; bit 3 = Swing up/down; bit 4 = Swing left/right; bit 5 = Swirl | |||
| HR | 17 | Setpoint limit max air cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 18 | Setpoint limit min air cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 19 | Setpoint limit max air heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 20 | Setpoint limit min air heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 21 | Setpoint limit max air auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 22 | Setpoint limit min air auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 23 | Setpoint limit max air ventilation | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 24 | Setpoint limit min air ventilation | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 25 | Setpoint limit max air dry | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 26 | Setpoint limit min air dry | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 36 | Return temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 37 | Indoor heat exchanger temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 38 | Indoor gas pipe temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 40 | Outdoor compressor discharge temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 41 | Outdoor expansion valve position | UINT16 | pulses | Read | ||||
| HR | 42 | Indoor expansion valve position | UINT16 | pulses | Read | ||||
| HR | 43 | Evaporation pressure | MPa x 100 (127 = 1.27 MPa). | UINT16 | × 0.01 | MPa | Read | ||
| HR | 44 | Condensation pressure | MPa x 100 (127 = 1.27 MPa). | UINT16 | × 0.01 | MPa | Read | ||
| HR | 45 | Current consumption | A x 10 (70 = 7 A). | UINT16 | × 0.1 | A | Read | ||
| HR | 53 | Work temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 54 | Fan speed (numeric) | UINT16 | Read/write | 0 = Auto; 1 = Silent; 2 = Low; 3 = Medium; 4 = High | ||||
| HR | 55 | Error value | Numeric indoor unit error value. | UINT16 | Read | ||||
| HR | 56 | Modbus slave address | Default 1. | UINT16 | Read/write | ||||
| HR | 57 | Port baud rate | UINT16 | Read/write | 0 = 100; 1 = 300; 2 = 500; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 7800; 7 = 9600; 8 = 19200; 9 = 57600; 10 = 115200 | ||||
| HR | 58 | Port parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 59 | Emergency heat status | UINT16 | Read | 0 = Deactivated; 1 = Activated | ||||
| HR | 60 | Input T1T2 status | UINT16 | Read | 0 = Deactivated; 1 = Activated | ||||
| HR | 73doc 73 / 74 | Total energy generated in heating | Low word at 73, high word at 74 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 75 | Actual power generated in heating | Example 0x1CAC = 7340 W. | UINT16 | W | Read | |||
| HR | 76doc 76 / 77 | Total energy generated in cooling | Low word at 76, high word at 77 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 78 | Actual power generated in cooling | Example 0x1CAC = 7340 W. | UINT16 | W | Read | |||
| HR | 82 | Actual power generated by photovoltaic | Example 0x1CAC = 7340 W. | UINT16 | W | Read | |||
| HR | 83doc 83 / 84 | Total energy produced | Low word at 83, high word at 84 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 85doc 85 / 86 | Total energy consumed by heat pump | Low word at 85, high word at 86 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 87 | Actual power consumed by heat pump | Example 0x1CAC = 7340 W. | UINT16 | W | Read | |||
| HR | 88 | Actual power consumed by whole building | Example 0x1CAC = 7340 W. | UINT16 | W | Read | |||
| HR | 89doc 89 / 90 | Electric resistor consumption in heating | Low word at 89, high word at 90 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 93doc 93 / 94 | Compressor consumption in heating | Low word at 93, high word at 94 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 95doc 95 / 96 | Compressor consumption in cooling | Low word at 95, high word at 96 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read | ||
| HR | 99doc 99 / 100 | Total consumption | Low word at 99, high word at 100 (manual example 0x1215 + 0x0001 = 70165). | UINT32 | CDAB | kWh | Read |
Notes on this map
- Distributor copy: airzonecontrol.com answers automated requests with a bot check (not bypassed) and no other Airzone-hosted copy was found; this multilingual PDF carries Airzone's own layout and address.
- 32-bit energy counters span two registers with the low word first: the manual's worked example reads (1) 0x1215 and (2) 0x0001 as 0x00011215 = 70165 kWh, so CDAB.
- The manual does not state signed or unsigned for 16-bit values; the remaining registers are listed as UINT16 because their normal values are not negative.
- The Modbus slave address is set in the Airzone Cloud app (Airtools > Integration > Modbus) or via register 56.
- Function codes 03, 04, 06 and 16 are supported.
- External (outdoor) temperature (35) and outdoor heat exchanger temperature (39) are left out: these routinely go below 0 °C and the manual gives no sign convention for 16-bit values.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
What Modbus registers does the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners have?
This map lists 52 registers: 52 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 0 (unit on/off is register 0) and the command description puts this number in the 'register address' field, so the printed number is the wire address.
What byte order does the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners?
Start with HR 0 Unit status on/off (On/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint (x10)); HR 4 Fan speed (percentage) (Fan speed); HR 2 Local (room) temperature (Room temperature (x10)); HR 7 Unit error code part 1 (Error code (ASCII)); HR 14 Available modes (Modes the unit supports).
How do I enable Modbus control of the Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners?
In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.
Where is the official Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners Modbus documentation?
The source is Integration Manual Aidoo - Modbus (v. 201). Airzone doesn't publish it on its own website, so this map was re-typed from a free copy at https://thermosilesia.pl/assets/default/system_object_files/4bc5a150b45a2a7401add97664eff2aa.pdf. It may be an older revision, so check it against the live unit.
More Airzone Modbus register maps
Other ac & vrf gateways register maps
- VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus
All ac & vrf gateways Modbus register maps →
Source: Integration Manual Aidoo - Modbus · v. 201 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.