- Aidoo Pro Modbus control for air-to-water heat pumps
Heat pump Modbus interface · Modbus register map
Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus register map
Updated 19 November 2026
Modbus RTU map that an Airzone Aidoo Pro serves when it is connected to an air-to-water heat pump: on/off and mode, water, air and DHW setpoints for one or two circuits, setpoint limits, water and refrigerant temperatures, flow, pressure, error codes and 32-bit energy counters.
This page lists 80 Modbus registers for the Airzone Aidoo Pro Modbus control for air-to-water heat pumps — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airzone’s own free documentation (linked below) and checked against it.
- Manufacturer
- Airzone
- Model
- Aidoo Pro Modbus control for air-to-water heat pumps
- Equipment type
- Heat pump Modbus interface
- Registers
- 80 (13 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal
- Source document
- Integration Manual Aidoo - Modbus · v. 201 · unofficial copy
Integration notes: Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Set the Aidoo output to Modbus and the slave ID in the Airzone Cloud app, connect RS-485 at 19200 8E1, then use registers 0, 3, 9, 11 and 12 for on/off, mode, DHW and setpoints, and poll 46-48 and 7-8 for water temperatures and errors.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Unit status on/off | UINT16 | On/off | Read/write |
| HR 3 | Mode | UINT16 | Mode | Read/write |
| HR 11 | Water setpoint circuit 1 | UINT16 | Water setpoint circuit 1 (x10) | Read/write |
| HR 9 | DHW (ACS) unit on/off | UINT16 | DHW on/off | Read/write |
| HR 12 | DHW (ACS) setpoint | UINT16 | DHW setpoint (x10) | Read/write |
| HR 46 | Water out temperature | UINT16 | Water out temperature (x10) | Read |
| HR 48 | DHW tank temperature | UINT16 | DHW tank temperature (x10) | Read |
| HR 7 | Unit error code part 1 | UINT16 | Error code (ASCII) | Read |
Enable Modbus control & writes
In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.
Byte order & addressing
- Mode codes start at 1 (1 Auto, 2 Cool, 3 Heat, 4 Fan, 5 Dry).
- Energy counters are low word first (CDAB).
Network setup
- Factory serial settings 19200 baud, 8 data bits, even parity, 1 stop bit.
- Slave address default 1.
Watch out for
- Register 13 bit 0 tells whether a DHW tank is configured.
Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Unit status on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2 | Local (room) temperature | °C x 10 (230 = 23 °C). Must be above 0. | UINT16 | × 0.1 | °C | Read | ||
| HR | 3 | Mode | UINT16 | Read/write | 1 = Auto; 2 = Cool; 3 = Heat; 4 = Fan; 5 = Dry | ||||
| HR | 7 | Unit error code part 1 | ASCII characters of the unit error code (first part). | UINT16 | Read | ||||
| HR | 8 | Unit error code part 2 | ASCII characters of the unit error code (second part). | UINT16 | Read | ||||
| HR | 9 | DHW (ACS) unit on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 10 | DHW (ACS) power mode on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 11 | Water setpoint circuit 1 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 12 | DHW (ACS) setpoint | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 13 | Water unit general function | Bit 1 clear = TAI mode; bit 2 clear = valve on heating/cooling. | BITMAP16 | Read | bit 0 = DHW available; bit 1 = TH mode (0 = TAI mode); bit 2 = Diverter valve in DHW position | |||
| HR | 14 | Available modes | BITMAP16 | Read | bit 0 = Auto; bit 1 = Cool; bit 2 = Heat; bit 3 = Ventilation; bit 4 = Dry | ||||
| HR | 17 | Setpoint limit max air cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 18 | Setpoint limit min air cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 19 | Setpoint limit max air heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 20 | Setpoint limit min air heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 21 | Setpoint limit max air auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 22 | Setpoint limit min air auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 23 | Setpoint limit max air ventilation | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 24 | Setpoint limit min air ventilation | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 25 | Setpoint limit max air dry | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 26 | Setpoint limit min air dry | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 27 | Setpoint limit max water cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 28 | Setpoint limit min water cool | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 29 | Setpoint limit max water heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 30 | Setpoint limit min water heat | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 31 | Setpoint limit max water auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 32 | Setpoint limit min water auto | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 33 | Setpoint limit max DHW | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 34 | Setpoint limit min DHW | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 36 | Return temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 37 | Indoor heat exchanger temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 38 | Indoor gas pipe temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 40 | Outdoor compressor discharge temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 41 | Outdoor expansion valve position | UINT16 | pulses | Read | ||||
| HR | 42 | Indoor expansion valve position | UINT16 | pulses | Read | ||||
| HR | 43 | Evaporation pressure | MPa x 100. | UINT16 | × 0.01 | MPa | Read | ||
| HR | 44 | Condensation pressure | MPa x 100. | UINT16 | × 0.01 | MPa | Read | ||
| HR | 45 | Current consumption | A x 10. | UINT16 | × 0.1 | A | Read | ||
| HR | 46 | Water out temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 47 | Water in temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 48 | DHW tank temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 49 | Water out temperature ICP | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 50 | Refrigerant temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 51 | Water flow | l/min x 10 (72 = 7.2 l/min). | UINT16 | × 0.1 | l/min | Read | ||
| HR | 52 | Water pressure | bar x 10 (13 = 1.3 bar). | UINT16 | × 0.1 | bar | Read | ||
| HR | 53 | Work temperature | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 55 | Error value | UINT16 | Read | |||||
| HR | 56 | Modbus slave address | Default 1. | UINT16 | Read/write | ||||
| HR | 57 | Port baud rate | UINT16 | Read/write | 0 = 100; 1 = 300; 2 = 500; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 7800; 7 = 9600; 8 = 19200; 9 = 57600; 10 = 115200 | ||||
| HR | 58 | Port parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 60 | Input T1T2 status | UINT16 | Read | 0 = Deactivated; 1 = Activated | ||||
| HR | 61 | Circuit 2 on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 62 | Water setpoint circuit 2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 63 | Air setpoint circuit 1 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 64 | Air setpoint circuit 2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 65 | Setpoint limit max water cool C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 66 | Setpoint limit min water cool C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 67 | Setpoint limit max water heat C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 68 | Setpoint limit min water heat C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 69 | Setpoint limit max water auto C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 70 | Setpoint limit min water auto C2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 71 | Water out temperature circuit 2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 72 | Local temperature circuit 2 | °C x 10 (230 = 23 °C). | UINT16 | × 0.1 | °C | Read | ||
| HR | 73doc 73 / 74 | Total energy generated in heating | Low word at 73, high word at 74. | UINT32 | CDAB | kWh | Read | ||
| HR | 75 | Actual power generated in heating | UINT16 | W | Read | ||||
| HR | 76doc 76 / 77 | Total energy generated in cooling | Low word at 76, high word at 77. | UINT32 | CDAB | kWh | Read | ||
| HR | 78 | Actual power generated in cooling | UINT16 | W | Read | ||||
| HR | 79doc 79 / 80 | Total energy generated in DHW | Low word at 79, high word at 80. | UINT32 | CDAB | kWh | Read | ||
| HR | 81 | Actual power generated in DHW | UINT16 | W | Read | ||||
| HR | 82 | Actual power generated by photovoltaic | UINT16 | W | Read | ||||
| HR | 83doc 83 / 84 | Total energy produced | Low word at 83, high word at 84. | UINT32 | CDAB | kWh | Read | ||
| HR | 85doc 85 / 86 | Total energy consumed by heat pump | Low word at 85, high word at 86. | UINT32 | CDAB | kWh | Read | ||
| HR | 87 | Actual power consumed by heat pump | UINT16 | W | Read | ||||
| HR | 88 | Actual power consumed by whole building | UINT16 | W | Read | ||||
| HR | 89doc 89 / 90 | Electric resistor consumption in heating | Low word at 89, high word at 90. | UINT32 | CDAB | kWh | Read | ||
| HR | 91doc 91 / 92 | Electric resistor consumption in DHW | Low word at 91, high word at 92. | UINT32 | CDAB | kWh | Read | ||
| HR | 93doc 93 / 94 | Compressor consumption in heating | Low word at 93, high word at 94. | UINT32 | CDAB | kWh | Read | ||
| HR | 95doc 95 / 96 | Compressor consumption in cooling | Low word at 95, high word at 96. | UINT32 | CDAB | kWh | Read | ||
| HR | 97doc 97 / 98 | Compressor consumption in DHW | Low word at 97, high word at 98. | UINT32 | CDAB | kWh | Read | ||
| HR | 99doc 99 / 100 | Total consumption | Low word at 99, high word at 100. | UINT32 | CDAB | kWh | Read |
Notes on this map
- Distributor copy: airzonecontrol.com answers automated requests with a bot check (not bypassed) and no other Airzone-hosted copy was found; this multilingual PDF carries Airzone's own layout and address.
- 32-bit energy counters are low word first: the manual's example (1) 0x1215, (2) 0x0001 = 0x00011215 = 70165 kWh, so CDAB.
- ACS in the manual means domestic hot water (DHW). C1 / C2 are water circuits 1 and 2.
- The manual does not state signed or unsigned for 16-bit values; the remaining registers are listed as UINT16 because their normal values are not negative.
- External (outdoor) temperature (35) and outdoor heat exchanger temperature (39) are left out: these routinely go below 0 °C and the manual gives no sign convention for 16-bit values.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Airzone Aidoo Pro Modbus control for air-to-water heat pumps
What Modbus registers does the Airzone Aidoo Pro Modbus control for air-to-water heat pumps have?
This map lists 80 registers: 80 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 0 (unit on/off is register 0) and the command description puts this number in the 'register address' field, so the printed number is the wire address.
What byte order does the Airzone Aidoo Pro Modbus control for air-to-water heat pumps use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Airzone Aidoo Pro Modbus control for air-to-water heat pumps?
Start with HR 0 Unit status on/off (On/off); HR 3 Mode (Mode); HR 11 Water setpoint circuit 1 (Water setpoint circuit 1 (x10)); HR 9 DHW (ACS) unit on/off (DHW on/off); HR 12 DHW (ACS) setpoint (DHW setpoint (x10)); HR 46 Water out temperature (Water out temperature (x10)); HR 48 DHW tank temperature (DHW tank temperature (x10)); HR 7 Unit error code part 1 (Error code (ASCII)).
How do I enable Modbus control of the Airzone Aidoo Pro Modbus control for air-to-water heat pumps?
In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.
Where is the official Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus documentation?
The source is Integration Manual Aidoo - Modbus (v. 201). Airzone doesn't publish it on its own website, so this map was re-typed from a free copy at https://thermosilesia.pl/assets/default/system_object_files/4bc5a150b45a2a7401add97664eff2aa.pdf. It may be an older revision, so check it against the live unit.
More Airzone Modbus register maps
Other pumps register maps
- Heat pump
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Ecoforest ecoGEO, ecoGEO HP and ecoAIR heat pumps on software AWD24, WWD24, WWC24 or later, register list API HP24_V01.02 (heat pump list only; supervisor and source-manager lists not included).
Also known as: ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02 - Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH - Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0
All pumps Modbus register maps →
Source: Integration Manual Aidoo - Modbus · v. 201 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.