Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus register map

Updated 19 November 2026

Short answer

Modbus RTU map that an Airzone Aidoo Pro serves when it is connected to an air-to-water heat pump: on/off and mode, water, air and DHW setpoints for one or two circuits, setpoint limits, water and refrigerant temperatures, flow, pressure, error codes and 32-bit energy counters.

This page lists 80 Modbus registers for the Airzone Aidoo Pro Modbus control for air-to-water heat pumps — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airzone’s own free documentation (linked below) and checked against it.

Manufacturer
Airzone
Model
Aidoo Pro Modbus control for air-to-water heat pumps
Equipment type
Heat pump Modbus interface
Registers
80 (13 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal
Source document
Integration Manual Aidoo - Modbus · v. 201 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Airzone Aidoo Pro Modbus control for air-to-water heat pumps

Integration in brief

Set the Aidoo output to Modbus and the slave ID in the Airzone Cloud app, connect RS-485 at 19200 8E1, then use registers 0, 3, 9, 11 and 12 for on/off, mode, DHW and setpoints, and poll 46-48 and 7-8 for water temperatures and errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Unit status on/offUINT16On/offRead/write
HR 3ModeUINT16ModeRead/write
HR 11Water setpoint circuit 1UINT16Water setpoint circuit 1 (x10)Read/write
HR 9DHW (ACS) unit on/offUINT16DHW on/offRead/write
HR 12DHW (ACS) setpointUINT16DHW setpoint (x10)Read/write
HR 46Water out temperatureUINT16Water out temperature (x10)Read
HR 48DHW tank temperatureUINT16DHW tank temperature (x10)Read
HR 7Unit error code part 1UINT16Error code (ASCII)Read

Enable Modbus control & writes

In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.

Byte order & addressing

Network setup

Watch out for

Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

80 of 80 shown
Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Unit status on/offUINT16Read/write0 = Off; 1 = On
HR2Local (room) temperature°C x 10 (230 = 23 °C). Must be above 0.UINT16× 0.1°CRead
HR3ModeUINT16Read/write1 = Auto; 2 = Cool; 3 = Heat; 4 = Fan; 5 = Dry
HR7Unit error code part 1ASCII characters of the unit error code (first part).UINT16Read
HR8Unit error code part 2ASCII characters of the unit error code (second part).UINT16Read
HR9DHW (ACS) unit on/offUINT16Read/write0 = Off; 1 = On
HR10DHW (ACS) power mode on/offUINT16Read/write0 = Off; 1 = On
HR11Water setpoint circuit 1°C x 10 (230 = 23 °C).UINT16× 0.1°CRead/write
HR12DHW (ACS) setpoint°C x 10 (230 = 23 °C).UINT16× 0.1°CRead/write
HR13Water unit general functionBit 1 clear = TAI mode; bit 2 clear = valve on heating/cooling.BITMAP16Readbit 0 = DHW available; bit 1 = TH mode (0 = TAI mode); bit 2 = Diverter valve in DHW position
HR14Available modesBITMAP16Readbit 0 = Auto; bit 1 = Cool; bit 2 = Heat; bit 3 = Ventilation; bit 4 = Dry
HR17Setpoint limit max air cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR18Setpoint limit min air cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR19Setpoint limit max air heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR20Setpoint limit min air heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR21Setpoint limit max air auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR22Setpoint limit min air auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR23Setpoint limit max air ventilation°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR24Setpoint limit min air ventilation°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR25Setpoint limit max air dry°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR26Setpoint limit min air dry°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR27Setpoint limit max water cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR28Setpoint limit min water cool°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR29Setpoint limit max water heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR30Setpoint limit min water heat°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR31Setpoint limit max water auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR32Setpoint limit min water auto°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR33Setpoint limit max DHW°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR34Setpoint limit min DHW°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR36Return temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR37Indoor heat exchanger temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR38Indoor gas pipe temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR40Outdoor compressor discharge temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR41Outdoor expansion valve positionUINT16pulsesRead
HR42Indoor expansion valve positionUINT16pulsesRead
HR43Evaporation pressureMPa x 100.UINT16× 0.01MPaRead
HR44Condensation pressureMPa x 100.UINT16× 0.01MPaRead
HR45Current consumptionA x 10.UINT16× 0.1ARead
HR46Water out temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR47Water in temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR48DHW tank temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR49Water out temperature ICP°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR50Refrigerant temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR51Water flowl/min x 10 (72 = 7.2 l/min).UINT16× 0.1l/minRead
HR52Water pressurebar x 10 (13 = 1.3 bar).UINT16× 0.1barRead
HR53Work temperature°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR55Error valueUINT16Read
HR56Modbus slave addressDefault 1.UINT16Read/write
HR57Port baud rateUINT16Read/write0 = 100; 1 = 300; 2 = 500; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 7800; 7 = 9600; 8 = 19200; 9 = 57600; 10 = 115200
HR58Port parityUINT16Read/write0 = None; 1 = Odd; 2 = Even
HR60Input T1T2 statusUINT16Read0 = Deactivated; 1 = Activated
HR61Circuit 2 on/offUINT16Read/write0 = Off; 1 = On
HR62Water setpoint circuit 2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead/write
HR63Air setpoint circuit 1°C x 10 (230 = 23 °C).UINT16× 0.1°CRead/write
HR64Air setpoint circuit 2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead/write
HR65Setpoint limit max water cool C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR66Setpoint limit min water cool C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR67Setpoint limit max water heat C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR68Setpoint limit min water heat C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR69Setpoint limit max water auto C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR70Setpoint limit min water auto C2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR71Water out temperature circuit 2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR72Local temperature circuit 2°C x 10 (230 = 23 °C).UINT16× 0.1°CRead
HR73doc 73 / 74Total energy generated in heatingLow word at 73, high word at 74.UINT32CDABkWhRead
HR75Actual power generated in heatingUINT16WRead
HR76doc 76 / 77Total energy generated in coolingLow word at 76, high word at 77.UINT32CDABkWhRead
HR78Actual power generated in coolingUINT16WRead
HR79doc 79 / 80Total energy generated in DHWLow word at 79, high word at 80.UINT32CDABkWhRead
HR81Actual power generated in DHWUINT16WRead
HR82Actual power generated by photovoltaicUINT16WRead
HR83doc 83 / 84Total energy producedLow word at 83, high word at 84.UINT32CDABkWhRead
HR85doc 85 / 86Total energy consumed by heat pumpLow word at 85, high word at 86.UINT32CDABkWhRead
HR87Actual power consumed by heat pumpUINT16WRead
HR88Actual power consumed by whole buildingUINT16WRead
HR89doc 89 / 90Electric resistor consumption in heatingLow word at 89, high word at 90.UINT32CDABkWhRead
HR91doc 91 / 92Electric resistor consumption in DHWLow word at 91, high word at 92.UINT32CDABkWhRead
HR93doc 93 / 94Compressor consumption in heatingLow word at 93, high word at 94.UINT32CDABkWhRead
HR95doc 95 / 96Compressor consumption in coolingLow word at 95, high word at 96.UINT32CDABkWhRead
HR97doc 97 / 98Compressor consumption in DHWLow word at 97, high word at 98.UINT32CDABkWhRead
HR99doc 99 / 100Total consumptionLow word at 99, high word at 100.UINT32CDABkWhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Airzone Aidoo Pro Modbus control for air-to-water heat pumps

What Modbus registers does the Airzone Aidoo Pro Modbus control for air-to-water heat pumps have?

This map lists 80 registers: 80 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 0 (unit on/off is register 0) and the command description puts this number in the 'register address' field, so the printed number is the wire address.

What byte order does the Airzone Aidoo Pro Modbus control for air-to-water heat pumps use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Airzone Aidoo Pro Modbus control for air-to-water heat pumps?

Start with HR 0 Unit status on/off (On/off); HR 3 Mode (Mode); HR 11 Water setpoint circuit 1 (Water setpoint circuit 1 (x10)); HR 9 DHW (ACS) unit on/off (DHW on/off); HR 12 DHW (ACS) setpoint (DHW setpoint (x10)); HR 46 Water out temperature (Water out temperature (x10)); HR 48 DHW tank temperature (DHW tank temperature (x10)); HR 7 Unit error code part 1 (Error code (ASCII)).

How do I enable Modbus control of the Airzone Aidoo Pro Modbus control for air-to-water heat pumps?

In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.

Where is the official Airzone Aidoo Pro Modbus control for air-to-water heat pumps Modbus documentation?

The source is Integration Manual Aidoo - Modbus (v. 201). Airzone doesn't publish it on its own website, so this map was re-typed from a free copy at https://thermosilesia.pl/assets/default/system_object_files/4bc5a150b45a2a7401add97664eff2aa.pdf. It may be an older revision, so check it against the live unit.