Pump protection / monitoring module (Sensor) · Modbus register map

Grundfos IO 113 pump protection module (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The IO 113 supervises a submersible sewage pump: winding and bearing temperatures, insulation resistance, vibration, water in oil, moisture and PTC switches, run hours and starts. With DIP switch 9 on it answers as a Modbus RTU slave. This map covers the measured and peak values, alarm and warning codes and bits, the command registers, the alarm limits and the counters.

This page lists 72 Modbus registers for the Grundfos IO 113 pump protection module (Modbus RTU) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Grundfos’s own free documentation (linked below) and checked against it.

Manufacturer
Grundfos
Model
IO 113 pump protection module (Modbus RTU)
Equipment type
Pump protection / monitoring module (Sensor)
Registers
72 (28 writable)
Transport
Modbus RTU
Default unit ID
231
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
IO113, IO 113 with SM 113, 98288208
Source document
Operating the IO113 via Modbus · 98288208 0115 (Edition 1.7) · rev. 2015-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Grundfos IO 113 pump protection module (Modbus RTU)

Integration in brief

Set DIP switch 9 on for Modbus, choose the address with SW3-SW5 (or 231 default), and poll 1992-2021 with function 03 at 19200 8E1. Read alarm_code/warning_code (2010/2011) when supervise_mode_status is not zero, and write a non-zero value to RESET_ALARM (2033) to clear a pending alarm.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1994t_pt100UINT16Stator temperature (PT100)Read
HR 1998water_in_oilUINT16Water in oilRead
HR 2009supervise_mode_statusBITMAP16Normal / warning / alarm stateRead
HR 2010alarm_codeUINT16Alarm codeRead
HR 2011warning_codeUINT16Warning codeRead
HR 2012alarmsBITMAP16Alarm bitsRead
HR 2022t_runUINT32 ABCDRunning hours (minutes)Read
HR 2033RESET_ALARMUINT16Reset alarm commandWrite

Enable Modbus control & writes

DIP switch 9 = on selects Modbus instead of GENIbus. Commands such as START, STOP, RESET_ALARM and RESET_HIST are executed by writing a non-zero value to their register.

Byte order & addressing

Network setup

Watch out for

Grundfos IO 113 pump protection module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

72 of 72 shown
Grundfos IO 113 pump protection module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1992t_support_bearSupport bearing temperature (PT100); SM113 power-line units only.UINT16°CRead
HR1993t_main_bearMain bearing temperature (PT100); SM113 units only.UINT16°CRead
HR1994t_pt100Motor stator temperature (PT100).UINT16°CRead
HR1995t_pt1000Motor stator temperature (PT1000).UINT16°CRead
HR1996r_insulateInsulation resistance; SM113 units only.UINT16× 100kΩRead
HR1997vibrationVibration, x direction; 1 count = 20/254 mm/s. SM113 units only.UINT16× 0.0787401575mm/sRead
HR1998water_in_oilUINT16× 0.1%Read
HR1999aux_sensorAuxiliary sensor at SM113 (unscaled).UINT16Read
HR2000t_support_bear_peakUINT16°CRead
HR2001t_main_bear_peakUINT16°CRead
HR2002t_pt100_peakUINT16°CRead
HR2003t_pt1000_peakUINT16°CRead
HR2004r_insulate_peakUINT16× 100kΩRead
HR2005vibration_peakUINT16× 0.0787401575mm/sRead
HR2006water_in_oil_peakUINT16× 0.1%Read
HR2007aux_sensor_peakUnscaled.UINT16Read
HR2008command_mode_statusBITMAP16Readbit 0 = Operation mode (0 = start, 1 = stop); bit 1 = Test mode (internal use); bit 2 = Automatic sensor learning armed
HR2009supervise_mode_statusBits 1-0: 00 normal, 01 warning mode, 10 alarm mode.BITMAP16Readbit 2 = Unacknowledged (pending) alarm
HR2010alarm_codeEvent code of the pending alarm.UINT16Read10 = Power line communication fault; 11 = Leakage (water in oil high / water in air); 12 = Time for service; 20 = Insulation resistance low; 22 = Moisture switch activated; 24 = Vibration high; 25 = Setup conflict; 64 = Motor stator temperature high (PT100/PT1000); 69 = Thermal switch (PTC) activated; 83 = IO113 EEPROM parameter verification error; 85 = Sensor board EEPROM parameter error; 145 = Support bearing temperature high; 146 = Main bearing temperature high; 170 = Water-in-oil sensor signal fault; 179 = Support bearing sensor signal fault; 180 = Main bearing sensor signal fault; 181 = Thermal switch (PTC) signal fault
HR2011warning_codeEvent code of the pending warning.UINT16Read10 = Power line communication fault; 11 = Leakage (water in oil high / water in air); 12 = Time for service; 20 = Insulation resistance low; 22 = Moisture switch activated; 24 = Vibration high; 25 = Setup conflict; 64 = Motor stator temperature high (PT100/PT1000); 69 = Thermal switch (PTC) activated; 83 = IO113 EEPROM parameter verification error; 85 = Sensor board EEPROM parameter error; 145 = Support bearing temperature high; 146 = Main bearing temperature high; 170 = Water-in-oil sensor signal fault; 179 = Support bearing sensor signal fault; 180 = Main bearing sensor signal fault; 181 = Thermal switch (PTC) signal fault
HR2012alarmsBITMAP16Readbit 0 = Moisture switch (22); bit 1 = PTC activated (69); bit 2 = PTC signal fault (181); bit 3 = PT100 stator temperature high (64); bit 4 = PT1000 stator temperature high (64); bit 5 = Power line communication fault (10); bit 6 = Setup conflict (25); bit 8 = Support bearing temperature high (145); bit 9 = Main bearing temperature high (146); bit 10 = Support bearing sensor fault (179); bit 11 = Main bearing sensor fault (180); bit 12 = Insulation resistance low (20); bit 13 = Leakage (11); bit 14 = Water-in-oil sensor fault (170); bit 15 = Vibration high (24)
HR2013warnings1Same bit layout as alarms (bits 0-2 never set as warnings).BITMAP16Readbit 0 = Moisture switch (22); bit 1 = PTC activated (69); bit 2 = PTC signal fault (181); bit 3 = PT100 stator temperature high (64); bit 4 = PT1000 stator temperature high (64); bit 5 = Power line communication fault (10); bit 6 = Setup conflict (25); bit 8 = Support bearing temperature high (145); bit 9 = Main bearing temperature high (146); bit 10 = Support bearing sensor fault (179); bit 11 = Main bearing sensor fault (180); bit 12 = Insulation resistance low (20); bit 13 = Leakage (11); bit 14 = Water-in-oil sensor fault (170); bit 15 = Vibration high (24)
HR2014warnings2BITMAP16Readbit 0 = IO113 EEPROM parameter error (83); bit 1 = Sensor board EEPROM parameter error (85); bit 2 = Time for service (12)
HR2015sensors_presentResult of sensor learning or preset.BITMAP16Read
HR2016dip_switchHardware DIP switch setup.BITMAP16Readbit 0 = SW6 (0 to 1 needed to arm sensor learning); bit 1 = SW10 explosion protection; bit 13 = SW7 motor temp output: 1 = PT1000 emulation; bit 14 = SW8 WIO output: 1 = pulse; bit 15 = SW9 interface: 1 = Modbus
HR2017dig_outputsBITMAP16Readbit 0 = Alarm relay; bit 1 = General warning; bit 2 = Temperature alarm; bit 3 = Moisture alarm; bit 4 = Insulation alarm
HR2018dig_inputsBITMAP16Readbit 0 = Contactor feedback (1 = motor switched in); bit 1 = Reset button enabled; bit 2 = Alarm reset active
HR2019unit_family22 for IO113.UINT16Read
HR2020unit_typeUINT16Read4 = Pump type C, SM 113 integrated (reserved); 5 = Pump type A, sensors wired to IO 113; 6 = Pump type B, SM 113 integrated; 7 = Pump type D, sensors wired to IO 113
HR2021unit_versionUINT16Read
HR2022t_runRunning time (hi/lo pair).UINT32ABCDminRead
HR2024t_onPower-on time (hi/lo pair).UINT32ABCDminRead
HR2026t_run_trip_cntRunning time trip counter; cleared by RESET_HIST.UINT32ABCDminRead
HR2028start_cntNumber of starts.UINT32ABCDRead
HR2030start_trip_cntStarts trip counter; cleared by RESET_HIST.UINT32ABCDRead
HR2032RESETCommand: write a non-zero value. Hardware reset of the module.UINT16Write
HR2033RESET_ALARMCommand: write a non-zero value. Resets pending alarms and tries a restart.UINT16Write
HR2034FACT_BOOTCommand: write a non-zero value. Rebuild factory EEPROM area (needs RESET or power cycle).UINT16Write
HR2035USER_BOOTCommand: write a non-zero value. Rebuild user EEPROM area (needs RESET or power cycle).UINT16Write
HR2036STOPCommand: write a non-zero value. Records the pump as stopped.UINT16Write
HR2037STARTCommand: write a non-zero value. Records the pump as started.UINT16Write
HR2038RESET_HISTCommand: write a non-zero value. Resets historical values.UINT16Write
HR2040ARM_LEARNINGCommand: write a non-zero value. Arms automatic sensor learning; follow with RESET.UINT16Write
HR2041t_support_bear_alarmFactory 140.UINT16°CRead/write
HR2042t_support_bear_warnFactory 120.UINT16°CRead/write
HR2043t_main_bear_alarmFactory 140.UINT16°CRead/write
HR2044t_main_bear_warnFactory 120.UINT16°CRead/write
HR2045t_pt1000_alarmStator alarm limit, factory 150.UINT16°CRead/write
HR2046t_pt1000_warnStator warning limit, factory 130.UINT16°CRead/write
HR2047t_pt100_alarmExtra temperature alarm limit, factory 150.UINT16°CRead/write
HR2048t_pt100_warnExtra temperature warning limit, factory 130.UINT16°CRead/write
HR2049t_run_trip_cnt_warnService warning limit; factory 255.UINT16× 100hRead/write
HR2050unit_addrModbus address 32-231; factory 231.UINT16Read/write
HR2051vibration_alarmFactory 255.UINT16× 0.0787401575mm/sRead/write
HR2052vibration_warnFactory 255.UINT16× 0.0787401575mm/sRead/write
HR2053water_in_oil_warnFactory 195.UINT16× 0.1%Read/write
HR2054wio_meas_delayFactory 20 s.UINT16sRead/write
HR2055wio_meas_filterFactory 120.UINT16Read/write
HR2059alarms_enableEnable bits, layout as alarms (2012).BITMAP16Read/write
HR2060warnings1_enableEnable bits, layout as warnings1 (2013).BITMAP16Read/write
HR2061warnings2_enableEnable bits, layout as warnings2 (2014).BITMAP16Read/write
HR2063r_insulate_peak_servPeak since last service.UINT16× 100kΩRead
HR2064speedPump speed.UINT16rpmRead
HR2065vibration_peak_servPeak since last service.UINT16× 0.0787401575mm/sRead
HR2066water_in_oil_peak_servPeak since last service.UINT16× 0.1%Read
HR2067water_in_airBoolean: water-in-air detection.UINT16Read
HR2068aux_sensor_peak_servUnscaled; since last service.UINT16Read
HR2069front_leds1Front-plate LED states, part 1.BITMAP16Read
HR2070front_leds2Front-plate LED states, part 2.BITMAP16Read
HR2071digital_sensorsBITMAP16Readbit 0 = Moisture switch; bit 1 = PTC thermal switch
HR2072vib_meas_delayFactory 20.UINT16sRead/write
HR2073vibmeas_filterFactory 0.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Grundfos IO 113 pump protection module (Modbus RTU)

What Modbus registers does the Grundfos IO 113 pump protection module (Modbus RTU) have?

This map lists 72 registers: 72 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Grundfos IO 113 pump protection module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed in decimal and used directly as the telegram address: the read example requests 0x07C8 (1992, t_support_bear) and the START example writes 0x07F5 (2037).

What byte order does the Grundfos IO 113 pump protection module (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Grundfos IO 113 pump protection module (Modbus RTU)?

Start with HR 1994 t_pt100 (Stator temperature (PT100)); HR 1998 water_in_oil (Water in oil); HR 2009 supervise_mode_status (Normal / warning / alarm state); HR 2010 alarm_code (Alarm code); HR 2011 warning_code (Warning code); HR 2012 alarms (Alarm bits); HR 2022 t_run (Running hours (minutes)); HR 2033 RESET_ALARM (Reset alarm command).

How do I enable Modbus control of the Grundfos IO 113 pump protection module (Modbus RTU)?

DIP switch 9 = on selects Modbus instead of GENIbus. Commands such as START, STOP, RESET_ALARM and RESET_HIST are executed by writing a non-zero value to their register.

Where is the official Grundfos IO 113 pump protection module (Modbus RTU) Modbus documentation?

The source is Operating the IO113 via Modbus (98288208 0115 (Edition 1.7)), revision 2015-01, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-4363039.pdf.

More Grundfos Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Operating the IO113 via Modbus · 98288208 0115 (Edition 1.7) · rev. 2015-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.