Pump controller (wastewater lift station) · Modbus register map

Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) Modbus register map

Updated 19 November 2026

Short answer

Grundfos Dedicated Controls runs wastewater lift stations with up to six pumps, a mixer, level sensors or float switches. A CIM module in the CU 36X makes it a Modbus slave with blocks for pit control, pit status, pit data and one 50-register block per pump. This map covers pit commands and level setpoints, operating mode and per-pump state bits, pit level, flows, energy and overflow counters, and the main per-pump data (run hours, starts, current, power, frequency).

This page lists 318 Modbus registers for the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Grundfos’s own free documentation (linked below) and checked against it.

Manufacturer
Grundfos
Model
Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Equipment type
Pump controller (wastewater lift station)
Registers
318 (31 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520
Source document
Modbus for Dedicated Controls - CIM 200 Modbus RTU, CIM 260 3G/4G Cellular, CIM 500 Ethernet for Modbus TCP - Functional profile and user manual · 98393520 · rev. 2023-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)

Integration in brief

Poll 00203 (operating mode), 00206/00209 (pumps running / in alarm) and 00301 (pit level) for the station overview, and each pump block for run hours, starts and current. Use PitControl 00101 to reset alarms, interlock the pit or return it to Auto, and 00103-00108 to force pumps on or off.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 202OperatingModeUINT16Pit operating modeRead
HR 205PitPumpsRunningBITMAP16Pumps running bitsRead
HR 208PitPumpsAlarmBITMAP16Pumps in alarm bitsRead
HR 300PitWaterLevelUINT16Pit water levelRead
HR 100PitControlBITMAP16Reset / interlock / auto commandsRead/write
HR 102PitPump1ControlUINT16Pump 1 manual controlRead/write
HR 417Pump1CurrentUINT16Pump 1 motor currentRead
HR 403Pump1OperatingTimeUINT32 ABCDPump 1 operating hoursRead

Enable Modbus control & writes

Fit the CIM module in the CU 36X; set the address and speed on its switches (CIM 200). Remote control needs write access: if SCADA PIN protection is on, write the PIN to 00109 first and check PitStatus bit 5.

Byte order & addressing

Network setup

Watch out for

Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

318 of 318 shown
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 00001SlaveMinimumReplyDelayExtra reply delay 0-10000 ms (default 0).UINT16msRead/write
HR1doc 00002RegisterOffsetOffset added to addresses above 00100; default 0.UINT16Read/write
HR4doc 00005AutoAckControlBitsUINT16Read/write0 = Disabled; 1 = Enabled (default)
HR23doc 00024ActualModbusAddressSlave address in use.UINT16Read
HR29doc 00030UnitFamily26 = Dedicated Controls.UINT16Read
HR30doc 00031UnitTypeUINT16Read
HR31doc 00032UnitVersionUINT16Read
HR100doc 00101PitControlCommand bits, act on a 0 to 1 edge.BITMAP16Read/writebit 0 = ResetAlarm; bit 2 = ResetEventLog; bit 3 = InterlockPit (stop all pumps for InterlockTimeout); bit 4 = AutoPit (back to Auto mode); bit 5 = CallBackAck; bit 6 = ResetUserDefCounter1; bit 7 = ResetUserDefCounter2; bit 8 = ResetUserDefCounter3; bit 9 = CallBackTest
HR101doc 00102CustomRelayControlBITMAP16Read/writebit 0 = SetCustomRelay; bit 1 = PulseCustomRelay
HR102doc 00103PitPump1ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR103doc 00104PitPump2ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR104doc 00105PitPump3ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR105doc 00106PitPump4ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR106doc 00107PitPump5ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR107doc 00108PitPump6ControlUINT16Read/write0 = Auto (controlled by CU 36X); 1 = Forced start; 2 = Forced stop
HR108doc 00109ScadaPinCodePIN for remote control when SCADA PIN protection is on.UINT16Read/write
HR110doc 00111SetInterlockTimeoutInterlock duration for the InterlockPit command.UINT16minRead/write
HR111doc 00112SetRealTimeClockUNIX time; write HI then LO.UINT32ABCDsRead/write
HR120doc 00121SetOverflowLevelUINT16× 0.01mRead/write
HR121doc 00122SetHighLevelUINT16× 0.01mRead/write
HR122doc 00123SetAlarmLevelUINT16× 0.01mRead/write
HR123doc 00124SetDryRunningLevelUINT16× 0.01mRead/write
HR124doc 00125SetFoamDrainingLevelUINT16× 0.01mRead/write
HR125doc 00126SetStartLevelPump1UINT16× 0.01mRead/write
HR126doc 00127SetStopLevelPump1UINT16× 0.01mRead/write
HR127doc 00128SetStartLevelPump2UINT16× 0.01mRead/write
HR128doc 00129SetStopLevelPump2UINT16× 0.01mRead/write
HR129doc 00130SetStartLevelPump3UINT16× 0.01mRead/write
HR130doc 00131SetStopLevelPump3UINT16× 0.01mRead/write
HR131doc 00132SetStartLevelPump4UINT16× 0.01mRead/write
HR132doc 00133SetStopLevelPump4UINT16× 0.01mRead/write
HR133doc 00134SetStartLevelPump5UINT16× 0.01mRead/write
HR134doc 00135SetStopLevelPump5UINT16× 0.01mRead/write
HR135doc 00136SetStartLevelPump6UINT16× 0.01mRead/write
HR136doc 00137SetStopLevelPump6UINT16× 0.01mRead/write
HR200doc 00201AcknowledgeRegisterCommand acknowledgements when AutoAckControlBits = 0.BITMAP16Readbit 0 = AckResetAlarm; bit 1 = AckSetRtc; bit 2 = AckResetEventLog; bit 3 = AckInterlockPit; bit 4 = AckAutoPit; bit 5 = AckCallBack; bit 6 = ResetUserDefCounter1; bit 7 = ResetUserDefCounter2; bit 8 = ResetUserDefCounter3; bit 9 = CallBackTest; bit 10 = RelayPulse
HR201doc 00202PitStatusBITMAP16Readbit 1 = AlarmActive; bit 2 = WarningActive; bit 3 = ManualControl; bit 4 = ScadaPinCodeEnabled; bit 5 = WriteAccess
HR202doc 00203OperatingModeUINT16Read0 = Standby (stopped by level control); 1 = Startup delay; 2 = Pumping; 3 = Stop delay; 4 = Pumping max.; 5 = Stopped; 6 = Foam draining; 7 = Daily emptying; 8 = Pump anti-seizing; 9 = Manual control; 10 = Interlock control; 11 = Mains supply fault; 12 = Level sensor fault; 13 = All enabled pumps in alarm; 14 = All pumps out of operation; 15 = CU 36X in service mode
HR203doc 00204PitPumpsPresenceBITMAP16Readbit 0 = Pump 1 present; bit 1 = Pump 2 present; bit 2 = Pump 3 present; bit 3 = Pump 4 present; bit 4 = Pump 5 present; bit 5 = Pump 6 present; bit 6 = Mixer present
HR204doc 00205PitPumpsDisabledBITMAP16Readbit 0 = Pump 1 disabled; bit 1 = Pump 2 disabled; bit 2 = Pump 3 disabled; bit 3 = Pump 4 disabled; bit 4 = Pump 5 disabled; bit 5 = Pump 6 disabled; bit 6 = Mixer disabled
HR205doc 00206PitPumpsRunningBITMAP16Readbit 0 = Pump 1 running; bit 1 = Pump 2 running; bit 2 = Pump 3 running; bit 3 = Pump 4 running; bit 4 = Pump 5 running; bit 5 = Pump 6 running; bit 6 = Mixer running
HR206doc 00207PitPumpsMonitoringFaultBITMAP16Readbit 0 = Pump 1 monitoring fault; bit 1 = Pump 2 monitoring fault; bit 2 = Pump 3 monitoring fault; bit 3 = Pump 4 monitoring fault; bit 4 = Pump 5 monitoring fault; bit 5 = Pump 6 monitoring fault; bit 6 = Mixer monitoring fault
HR207doc 00208PitPumpsWarningBITMAP16Readbit 0 = Pump 1 warning; bit 1 = Pump 2 warning; bit 2 = Pump 3 warning; bit 3 = Pump 4 warning; bit 4 = Pump 5 warning; bit 5 = Pump 6 warning; bit 6 = Mixer warning
HR208doc 00209PitPumpsAlarmBITMAP16Readbit 0 = Pump 1 alarm; bit 1 = Pump 2 alarm; bit 2 = Pump 3 alarm; bit 3 = Pump 4 alarm; bit 4 = Pump 5 alarm; bit 5 = Pump 6 alarm; bit 6 = Mixer alarm
HR209doc 00210PitAlarms1Pit alarm events, word 1 (see the manual's alarm list).BITMAP16Read
HR210doc 00211PitAlarms2Pit alarm events, word 2 (see the manual's alarm list).BITMAP16Read
HR211doc 00212PitAlarms3Pit alarm events, word 3 (see the manual's alarm list).BITMAP16Read
HR212doc 00213PitWarnings1Pit warning events, word 1.BITMAP16Read
HR213doc 00214PitWarnings2Pit warning events, word 2.BITMAP16Read
HR214doc 00215PitWarnings3Pit warning events, word 3.BITMAP16Read
HR215doc 00216EventLogLatestIDID of the newest event log entry.UINT16Read
HR216doc 00217NumberOfFloatSwitchesInstalled float switches (0-5).UINT16Read
HR217doc 00218FloatSwitchesStatusBITMAP16Readbit 0 = Float switch 1 on; bit 1 = Float switch 2 on; bit 2 = Float switch 3 on; bit 3 = Float switch 4 on; bit 4 = Float switch 5 on; bit 5 = Extra overflow switch on
HR218doc 00219FloatSwitch1FunctionUINT16Read0 = Not used; 1 = Dry running; 3 = Stop of all pumps; 4 = Stop; 5 = Stop of first pump; 6 = Stop of second pump; 11 = Start/stop; 12 = Start of first pump/stop; 13 = Start; 14 = Start of first pump; 15 = Start of second pump; 20 = Start of all pumps; 21 = Alarm level; 23 = High level
HR219doc 00220FloatSwitch2FunctionUINT16Read0 = Not used; 1 = Dry running; 3 = Stop of all pumps; 4 = Stop; 5 = Stop of first pump; 6 = Stop of second pump; 11 = Start/stop; 12 = Start of first pump/stop; 13 = Start; 14 = Start of first pump; 15 = Start of second pump; 20 = Start of all pumps; 21 = Alarm level; 23 = High level
HR220doc 00221FloatSwitch3FunctionUINT16Read0 = Not used; 1 = Dry running; 3 = Stop of all pumps; 4 = Stop; 5 = Stop of first pump; 6 = Stop of second pump; 11 = Start/stop; 12 = Start of first pump/stop; 13 = Start; 14 = Start of first pump; 15 = Start of second pump; 20 = Start of all pumps; 21 = Alarm level; 23 = High level
HR221doc 00222FloatSwitch4FunctionUINT16Read0 = Not used; 1 = Dry running; 3 = Stop of all pumps; 4 = Stop; 5 = Stop of first pump; 6 = Stop of second pump; 11 = Start/stop; 12 = Start of first pump/stop; 13 = Start; 14 = Start of first pump; 15 = Start of second pump; 20 = Start of all pumps; 21 = Alarm level; 23 = High level
HR240doc 00241HighLevelUINT16× 0.01mRead
HR241doc 00242AlarmLevelUINT16× 0.01mRead
HR242doc 00243DryRunningLevelUINT16× 0.01mRead
HR243doc 00244FoamDrainingLevelUINT16× 0.01mRead
HR244doc 00245StartLevelPump1UINT16× 0.01mRead
HR245doc 00246StopLevelPump1UINT16× 0.01mRead
HR246doc 00247StartLevelPump2UINT16× 0.01mRead
HR247doc 00248StopLevelPump2UINT16× 0.01mRead
HR248doc 00249StartLevelPump3UINT16× 0.01mRead
HR249doc 00250StopLevelPump3UINT16× 0.01mRead
HR250doc 00251StartLevelPump4UINT16× 0.01mRead
HR251doc 00252StopLevelPump4UINT16× 0.01mRead
HR252doc 00253StartLevelPump5UINT16× 0.01mRead
HR253doc 00254StopLevelPump5UINT16× 0.01mRead
HR254doc 00255StartLevelPump6UINT16× 0.01mRead
HR255doc 00256StopLevelPump6UINT16× 0.01mRead
HR257doc 00258BatteryVoltageUINT16× 0.1VRead
HR300doc 00301PitWaterLevelNeeds a level sensor.UINT16× 0.01mRead
HR301doc 00302PitSwitchWaterLevelLevel from float switches, 0-5.UINT16Read
HR302doc 00303PitDepthUINT16× 0.01mRead
HR303doc 00304PitFlowInUINT16× 0.1l/sRead
HR304doc 00305PitAverageFlowInUINT16× 0.1l/sRead
HR305doc 00306PitFlowOutUINT16× 0.1l/sRead
HR306doc 00307PitAverageFlowOutUINT16× 0.1l/sRead
HR307doc 00308PitPowerUINT32ABCDWRead
HR309doc 00310PitEnergyUINT32ABCD× 0.1kWhRead
HR311doc 00312PitEnergyYesterdayUINT16× 0.1kWhRead
HR312doc 00313PitEnergyTodayUINT16× 0.1kWhRead
HR313doc 00314PitSpecificEnergyUINT16Wh/m³Read
HR314doc 00315PitPumpedVolumeUINT32ABCD× 0.1m³Read
HR316doc 00317PitPumpedVolumeYesterdayUINT16× 0.1m³Read
HR317doc 00318PitPumpedVolumeTodayUINT16× 0.1m³Read
HR318doc 00319PitMixerStartsPerHourUINT16Read
HR319doc 00320PitOverflowVolumeUINT16× 0.1m³Read
HR320doc 00321PitOverflowVolumeYesterdayUINT16× 0.1m³Read
HR321doc 00322PitOverflowVolumeTodayUINT16× 0.1m³Read
HR322doc 00323PitOverflowTimeUINT16minRead
HR323doc 00324PitOverflowTimeYesterdayUINT16minRead
HR324doc 00325PitOverflowTimeTodayUINT16minRead
HR325doc 00326PitOverflowCounterUINT16Read
HR326doc 00327PitOverflowCounterYesterdayUINT16Read
HR327doc 00328PitOverflowCounterTodayUINT16Read
HR328doc 00329PitOperatingTimeTotal power-on time.UINT32ABCDminRead
HR330doc 00331Pit2PumpsOprTimeTotal time with 2 pumps running together.UINT32ABCDminRead
HR332doc 00333Pit2PumpsOprTimeYesterdayUINT16minRead
HR333doc 00334Pit2PumpsOprTimeTodayUINT16minRead
HR334doc 00335Pit3PumpsOprTimeTotal time with 3 pumps running together.UINT32ABCDminRead
HR336doc 00337Pit3PumpsOprTimeYesterdayUINT16minRead
HR337doc 00338Pit3PumpsOprTimeTodayUINT16minRead
HR338doc 00339Pit4PumpsOprTimeTotal time with 4 pumps running together.UINT32ABCDminRead
HR340doc 00341Pit4PumpsOprTimeYesterdayUINT16minRead
HR341doc 00342Pit4PumpsOprTimeTodayUINT16minRead
HR342doc 00343Pit5PumpsOprTimeTotal time with 5 pumps running together.UINT32ABCDminRead
HR344doc 00345Pit5PumpsOprTimeYesterdayUINT16minRead
HR345doc 00346Pit5PumpsOprTimeTodayUINT16minRead
HR346doc 00347Pit6PumpsOprTimeTotal time with 6 pumps running together.UINT32ABCDminRead
HR348doc 00349Pit6PumpsOprTimeYesterdayUINT16minRead
HR349doc 00350Pit6PumpsOprTimeTodayUINT16minRead
HR350doc 00351UserAnalogInput1UINT16× 0.1%Read
HR351doc 00352UserAnalogInput2UINT16× 0.1%Read
HR352doc 00353UserAnalogInput3UINT16× 0.1%Read
HR353doc 00354Pit0PumpsOprTimeTotal time with no pump running.UINT32ABCDminRead
HR355doc 00356Pit0PumpsOprTimeYesterdayUINT16minRead
HR356doc 00357Pit0PumpsOprTimeTodayUINT16minRead
HR357doc 00358Pit1PumpsOprTimeTotal time with one pump running.UINT32ABCDminRead
HR359doc 00360Pit1PumpsOprTimeYesterdayUINT16minRead
HR360doc 00361Pit1PumpsOprTimeTodayUINT16minRead
HR361doc 00362MixerRuntimeUINT16minRead
HR362doc 00363MixerStartCounterUINT16Read
HR366doc 00367PitOutletPressureUINT16× 0.001barRead
HR367doc 00368PitOverflowVolume32bitUINT32ABCD× 0.1m³Read
HR369doc 00370PitOverflowTime32bitUINT32ABCDminRead
HR377doc 00378H2SLevelActualUINT16ppmRead
HR378doc 00379H2SLevelTodayAverage today.UINT16ppmRead
HR379doc 00380H2SLevelYesterdayAverage yesterday.UINT16ppmRead
HR380doc 00381DosingFeedTankLevelUINT16× 0.01mRead
HR381doc 00382DosingVolumeTotalUINT32ABCD× 0.001m³Read
HR383doc 00384DosingVolumeTodayUINT16× 0.001m³Read
HR384doc 00385DosingVolumeYesterdayUINT16× 0.001m³Read
HR385doc 00386DosingRefActualUINT16× 0.1l/hRead
HR386doc 00387GrinderOperatingTimeUINT32ABCDminRead
HR400doc 00401Pump1StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR401doc 00402Pump1ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR403doc 00404Pump1OperatingTimeUINT32ABCDminRead
HR405doc 00406Pump1TimeToServiceUINT32ABCDminRead
HR407doc 00408Pump1OperatingTimeYesterdayUINT16minRead
HR408doc 00409Pump1OperatingTimeTodayUINT16minRead
HR409doc 00410Pump1LatestOperatingTimeLength of the last run.UINT16sRead
HR410doc 00411Pump1StartCounterUINT32ABCDRead
HR412doc 00413Pump1StartCounterYesterdayUINT16Read
HR413doc 00414Pump1StartCounterTodayUINT16Read
HR414doc 00415Pump1StartsPerHourUINT16Read
HR415doc 00416Pump1FlowUINT16× 0.1l/sRead
HR416doc 00417Pump1LatestFlowUINT16× 0.1l/sRead
HR417doc 00418Pump1CurrentUINT16× 0.1ARead
HR418doc 00419Pump1LatestCurrentUINT16× 0.1ARead
HR419doc 00420Pump1VoltageUINT16× 0.1VRead
HR420doc 00421Pump1InsulationUINT16× 10kΩRead
HR421doc 00422Pump1WaterInOilUINT16× 0.1%Read
HR428doc 00429Pump1MotorTemperature1UINT16°CRead
HR429doc 00430Pump1MotorTemperature2UINT16°CRead
HR430doc 00431Pump1PowerUINT32ABCDWRead
HR432doc 00433Pump1EnergyUINT32ABCD× 0.1kWhRead
HR434doc 00435Pump1CosPhiUINT16× 0.01Read
HR435doc 00436Pump1FrequencyUINT16× 0.1HzRead
HR436doc 00437Pump1VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR437doc 00438Pump1TorqueUINT16× 0.1NmRead
HR438doc 00439Pump1iAsymLine current asymmetry.UINT16× 0.1%Read
HR446doc 00447Pump1ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR447doc 00448Pump1ActualSetpointUINT16%Read
HR448doc 00449Pump1FixedFrequencyUINT16× 0.01HzRead
HR450doc 00451Pump2StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR451doc 00452Pump2ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR453doc 00454Pump2OperatingTimeUINT32ABCDminRead
HR455doc 00456Pump2TimeToServiceUINT32ABCDminRead
HR457doc 00458Pump2OperatingTimeYesterdayUINT16minRead
HR458doc 00459Pump2OperatingTimeTodayUINT16minRead
HR459doc 00460Pump2LatestOperatingTimeLength of the last run.UINT16sRead
HR460doc 00461Pump2StartCounterUINT32ABCDRead
HR462doc 00463Pump2StartCounterYesterdayUINT16Read
HR463doc 00464Pump2StartCounterTodayUINT16Read
HR464doc 00465Pump2StartsPerHourUINT16Read
HR465doc 00466Pump2FlowUINT16× 0.1l/sRead
HR466doc 00467Pump2LatestFlowUINT16× 0.1l/sRead
HR467doc 00468Pump2CurrentUINT16× 0.1ARead
HR468doc 00469Pump2LatestCurrentUINT16× 0.1ARead
HR469doc 00470Pump2VoltageUINT16× 0.1VRead
HR470doc 00471Pump2InsulationUINT16× 10kΩRead
HR471doc 00472Pump2WaterInOilUINT16× 0.1%Read
HR478doc 00479Pump2MotorTemperature1UINT16°CRead
HR479doc 00480Pump2MotorTemperature2UINT16°CRead
HR480doc 00481Pump2PowerUINT32ABCDWRead
HR482doc 00483Pump2EnergyUINT32ABCD× 0.1kWhRead
HR484doc 00485Pump2CosPhiUINT16× 0.01Read
HR485doc 00486Pump2FrequencyUINT16× 0.1HzRead
HR486doc 00487Pump2VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR487doc 00488Pump2TorqueUINT16× 0.1NmRead
HR488doc 00489Pump2AsymLine current asymmetry.UINT16× 0.1%Read
HR496doc 00497Pump2ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR497doc 00498Pump2ActualSetpointUINT16%Read
HR498doc 00499Pump2FixedFrequencyUINT16× 0.01HzRead
HR500doc 00501Pump3StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR501doc 00502Pump3ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR503doc 00504Pump3OperatingTimeUINT32ABCDminRead
HR505doc 00506Pump3TimeToServiceUINT32ABCDminRead
HR507doc 00508Pump3OperatingTimeYesterdayUINT16minRead
HR508doc 00509Pump3OperatingTimeTodayUINT16minRead
HR509doc 00510Pump3LatestOperatingTimeLength of the last run.UINT16sRead
HR510doc 00511Pump3StartCounterUINT32ABCDRead
HR512doc 00513Pump3StartCounterYesterdayUINT16Read
HR513doc 00514Pump3StartCounterTodayUINT16Read
HR514doc 00515Pump3StartsPerHourUINT16Read
HR515doc 00516Pump3FlowUINT16× 0.1l/sRead
HR516doc 00517Pump3LatestFlowUINT16× 0.1l/sRead
HR517doc 00518Pump3CurrentUINT16× 0.1ARead
HR518doc 00519Pump3LatestCurrentUINT16× 0.1ARead
HR519doc 00520Pump3VoltageUINT16× 0.1VRead
HR520doc 00521Pump3InsulationUINT16× 10kΩRead
HR521doc 00522Pump3WaterInOilUINT16× 0.1%Read
HR528doc 00529Pump3MotorTemperature1UINT16°CRead
HR529doc 00530Pump3MotorTemperature2UINT16°CRead
HR530doc 00531Pump3PowerUINT32ABCDWRead
HR532doc 00533Pump3EnergyUINT32ABCD× 0.1kWhRead
HR534doc 00535Pump3CosPhiUINT16× 0.01Read
HR535doc 00536Pump3FrequencyUINT16× 0.1HzRead
HR536doc 00537Pump3VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR537doc 00538Pump3TorqueUINT16× 0.1NmRead
HR538doc 00539Pump3AsymLine current asymmetry.UINT16× 0.1%Read
HR546doc 00547Pump3ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR547doc 00548Pump3ActualSetpointUINT16%Read
HR548doc 00549Pump3FixedFrequencyUINT16× 0.01HzRead
HR550doc 00551Pump4StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR551doc 00552Pump4ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR553doc 00554Pump4OperatingTimeUINT32ABCDminRead
HR555doc 00556Pump4TimeToServiceUINT32ABCDminRead
HR557doc 00558Pump4OperatingTimeYesterdayUINT16minRead
HR558doc 00559Pump4OperatingTimeTodayUINT16minRead
HR559doc 00560Pump4LatestOperatingTimeLength of the last run.UINT16sRead
HR560doc 00561Pump4StartCounterUINT32ABCDRead
HR562doc 00563Pump4StartCounterYesterdayUINT16Read
HR563doc 00564Pump4StartCounterTodayUINT16Read
HR564doc 00565Pump4StartsPerHourUINT16Read
HR565doc 00566Pump4FlowUINT16× 0.1l/sRead
HR566doc 00567Pump4LatestFlowUINT16× 0.1l/sRead
HR567doc 00568Pump4CurrentUINT16× 0.1ARead
HR568doc 00569Pump4LatestCurrentUINT16× 0.1ARead
HR569doc 00570Pump4VoltageUINT16× 0.1VRead
HR570doc 00571Pump4InsulationUINT16× 10kΩRead
HR571doc 00572Pump4WaterInOilUINT16× 0.1%Read
HR578doc 00579Pump4MotorTemperature1UINT16°CRead
HR579doc 00580Pump4MotorTemperature2UINT16°CRead
HR580doc 00581Pump4PowerUINT32ABCDWRead
HR582doc 00583Pump4EnergyUINT32ABCD× 0.1kWhRead
HR584doc 00585Pump4CosPhiUINT16× 0.01Read
HR585doc 00586Pump4FrequencyUINT16× 0.1HzRead
HR586doc 00587Pump4VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR587doc 00588Pump4TorqueUINT16× 0.1NmRead
HR588doc 00589Pump4AsymLine current asymmetry.UINT16× 0.1%Read
HR596doc 00597Pump4ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR597doc 00598Pump4ActualSetpointUINT16%Read
HR598doc 00599Pump4FixedFrequencyUINT16× 0.01HzRead
HR600doc 00601Pump5StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR601doc 00602Pump5ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR603doc 00604Pump5OperatingTimeUINT32ABCDminRead
HR605doc 00606Pump5TimeToServiceUINT32ABCDminRead
HR607doc 00608Pump5OperatingTimeYesterdayUINT16minRead
HR608doc 00609Pump5OperatingTimeTodayUINT16minRead
HR609doc 00610Pump5LatestOperatingTimeLength of the last run.UINT16sRead
HR610doc 00611Pump5StartCounterUINT32ABCDRead
HR612doc 00613Pump5StartCounterYesterdayUINT16Read
HR613doc 00614Pump5StartCounterTodayUINT16Read
HR614doc 00615Pump5StartsPerHourUINT16Read
HR615doc 00616Pump5FlowUINT16× 0.1l/sRead
HR616doc 00617Pump5LatestFlowUINT16× 0.1l/sRead
HR617doc 00618Pump5CurrentUINT16× 0.1ARead
HR618doc 00619Pump5LatestCurrentUINT16× 0.1ARead
HR619doc 00620Pump5VoltageUINT16× 0.1VRead
HR620doc 00621Pump5InsulationUINT16× 10kΩRead
HR621doc 00622Pump5WaterInOilUINT16× 0.1%Read
HR628doc 00629Pump5MotorTemperature1UINT16°CRead
HR629doc 00630Pump5MotorTemperature2UINT16°CRead
HR630doc 00631Pump5PowerUINT32ABCDWRead
HR632doc 00633Pump5EnergyUINT32ABCD× 0.1kWhRead
HR634doc 00635Pump5CosPhiUINT16× 0.01Read
HR635doc 00636Pump5FrequencyUINT16× 0.1HzRead
HR636doc 00637Pump5VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR637doc 00638Pump5TorqueUINT16× 0.1NmRead
HR638doc 00639Pump5AsymLine current asymmetry.UINT16× 0.1%Read
HR646doc 00647Pump5ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR647doc 00648Pump5ActualSetpointUINT16%Read
HR648doc 00649Pump5FixedFrequencyUINT16× 0.01HzRead
HR650doc 00651Pump6StatusBITMAP16Readbit 0 = Present; bit 1 = Running; bit 2 = Monitoring fault; bit 3 = Warning; bit 4 = Alarm; bit 5 = IO 111 present; bit 6 = IO 111 fault; bit 7 = MP 204 present; bit 8 = MP 204 fault; bit 9 = CUE present; bit 10 = CUE fault; bit 11 = Pump disabled
HR651doc 00652Pump6ControlSourceUINT16Read0 = Auto; 1 = Switch; 2 = Display; 3 = Remote (bus)
HR653doc 00654Pump6OperatingTimeUINT32ABCDminRead
HR655doc 00656Pump6TimeToServiceUINT32ABCDminRead
HR657doc 00658Pump6OperatingTimeYesterdayUINT16minRead
HR658doc 00659Pump6OperatingTimeTodayUINT16minRead
HR659doc 00660Pump6LatestOperatingTimeLength of the last run.UINT16sRead
HR660doc 00661Pump6StartCounterUINT32ABCDRead
HR662doc 00663Pump6StartCounterYesterdayUINT16Read
HR663doc 00664Pump6StartCounterTodayUINT16Read
HR664doc 00665Pump6StartsPerHourUINT16Read
HR665doc 00666Pump6FlowUINT16× 0.1l/sRead
HR666doc 00667Pump6LatestFlowUINT16× 0.1l/sRead
HR667doc 00668Pump6CurrentUINT16× 0.1ARead
HR668doc 00669Pump6LatestCurrentUINT16× 0.1ARead
HR669doc 00670Pump6VoltageUINT16× 0.1VRead
HR670doc 00671Pump6InsulationUINT16× 10kΩRead
HR671doc 00672Pump6WaterInOilUINT16× 0.1%Read
HR678doc 00679Pump6MotorTemperature1UINT16°CRead
HR679doc 00680Pump6MotorTemperature2UINT16°CRead
HR680doc 00681Pump6PowerUINT32ABCDWRead
HR682doc 00683Pump6EnergyUINT32ABCD× 0.1kWhRead
HR684doc 00685Pump6CosPhiUINT16× 0.01Read
HR685doc 00686Pump6FrequencyUINT16× 0.1HzRead
HR686doc 00687Pump6VFDmodeUINT16Read0 = VFD not controlled; 2 = Stopped; 3 = Reverse start; 4 = Start flushing; 5 = Normal; 6 = Run flushing; 7 = Stop flushing; 8 = Specific-energy test
HR687doc 00688Pump6TorqueUINT16× 0.1NmRead
HR688doc 00689Pump6AsymLine current asymmetry.UINT16× 0.1%Read
HR696doc 00697Pump6ControlModeUINT16Read0 = Fixed frequency; 1 = Linear control; 2 = Minimum control; 3 = PID control
HR697doc 00698Pump6ActualSetpointUINT16%Read
HR698doc 00699Pump6FixedFrequencyUINT16× 0.01HzRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)

What Modbus registers does the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) have?

This map lists 318 registers: 318 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 5-digit register numbers; this manual states that register X is addressed as X - 1 in the telegram (e.g. 00301 PitWaterLevel is wire address 300). Pump n's block starts at 00401 + 50 x (n-1).

What byte order does the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)?

Start with HR 202 OperatingMode (Pit operating mode); HR 205 PitPumpsRunning (Pumps running bits); HR 208 PitPumpsAlarm (Pumps in alarm bits); HR 300 PitWaterLevel (Pit water level); HR 100 PitControl (Reset / interlock / auto commands); HR 102 PitPump1Control (Pump 1 manual control); HR 417 Pump1Current (Pump 1 motor current); HR 403 Pump1OperatingTime (Pump 1 operating hours).

How do I enable Modbus control of the Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)?

Fit the CIM module in the CU 36X; set the address and speed on its switches (CIM 200). Remote control needs write access: if SCADA PIN protection is on, write the PIN to 00109 first and check PitStatus bit 5.

Where is the official Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus) Modbus documentation?

The source is Modbus for Dedicated Controls - CIM 200 Modbus RTU, CIM 260 3G/4G Cellular, CIM 500 Ethernet for Modbus TCP - Functional profile and user manual (98393520), revision 2023-03, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012936.pdf.

More Grundfos Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Modbus for Dedicated Controls - CIM 200 Modbus RTU, CIM 260 3G/4G Cellular, CIM 500 Ethernet for Modbus TCP - Functional profile and user manual · 98393520 · rev. 2023-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.