Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus register map

Updated 19 November 2026

Short answer

The MP 204 is Grundfos's electronic motor protector for single- and three-phase pump motors. A CIU communication box talks GENIbus to the MP 204 and presents it as a Modbus slave, with blocks for CIU settings, CIU status, one control register, protector status and measured data. The map covers start/stop and trip commands, alarm and warning codes, phase voltages and currents, power factor, power, energy, run hours, start counters and insulation resistance.

This page lists 74 Modbus registers for the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Grundfos’s own free documentation (linked below) and checked against it.

Manufacturer
Grundfos
Model
MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Equipment type
Pump motor protection relay
Registers
74 (12 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513
Source document
Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual · 98393513 1114 · rev. 2014-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)

Integration in brief

Set the CIU 200 slave address on the two hex switches, keep 19200 8E1, then poll 00201-00208 for status and alarm, and 00301-00354 for measurements. Start, stop and trip the pump through ControlRegister 00101.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100ControlRegisterBITMAP16Start/stop, trip and reset commandsRead/write
HR 200StatusRegisterBITMAP16Running, ready and fault flagsRead
HR 201OperatingModeUINT16Operating modeRead
HR 203AlarmCodeUINT16Alarm codeRead
HR 204WarningBits1BITMAP16Active warningsRead
HR 311LineCurrentMeanUINT16Mean line currentRead
HR 327PowerUINT32 ABCDPower consumptionRead
HR 329EnergyUINT32 ABCDEnergy counterRead

Enable Modbus control & writes

The MP 204 needs no setting for remote control; configure it with the R100, Grundfos GO or PC Tool first, then connect the CIU. OnOffReq (bit 2 of 00101) starts and stops the motor; the device acts on the last command from Modbus, remote or buttons.

Byte order & addressing

Network setup

Watch out for

Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

74 of 74 shown
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 00001SlaveMinimumReplyDelayExtra reply delay, 0-10000 ms (default 0).UINT16msRead/write
HR1doc 00002RegisterOffsetOffset added to every address above 00100; default 0, normally leave it.UINT16Read/write
HR2doc 00003SoftwareDefinedModbusAddressSlave address used only in software-defined mode (default 231).UINT16Read/write
HR3doc 00004SoftwareDefinedBitRateUsed only when SW4/SW5 select software-defined speed.UINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400
HR4doc 00005AutoAckControlBitsUINT16Read/write0 = Disabled (clear control bits yourself); 1 = Enabled (default)
HR8doc 00009SoftwareDefinedParityUINT16Read/write0 = None (default); 1 = Even; 2 = Odd
HR9doc 00010SoftwareDefinedStopBitUINT16Read/write0 = No stop bit; 1 = 1 stop bit (default); 2 = 2 stop bits
HR20doc 00021GENIbusCRCErrorCntCRC errors on the internal GENIbus link to the MP 204.UINT16Read
HR21doc 00022GENIbusDataErrorCntData errors on the internal GENIbus link.UINT16Read
HR22doc 00023VersionNumberGrundfos-specific version number.UINT16Read
HR23doc 00024ActualModbusAddressSlave address in use (1-247).UINT16Read
HR24doc 00025GENIbusTXcountTelegrams sent to the MP 204 (HI/LO pair).UINT32ABCDRead
HR26doc 00027GENIbusRXcountTelegrams received from the MP 204 (HI/LO pair).UINT32ABCDRead
HR29doc 00030UnitFamilyGrundfos product family.UINT16Read
HR30doc 00031UnitTypeGrundfos product type.UINT16Read
HR31doc 00032UnitVersionGrundfos product version.UINT16Read
HR100doc 00101ControlRegisterCommand bits; reset bits act on a 0 to 1 edge.BITMAP16Read/writebit 0 = ResetAlarm; bit 1 = CommandedTrip; bit 2 = OnOffReq (1 = on/start, 0 = off/stop); bit 3 = ProtectionEnabled (1 = enabled); bit 5 = ResetStartCounter; bit 6 = ResetRestartCounter; bit 7 = ResetLogs (min/max logs 00348-00352); bit 8 = ResetHourCounter (operating-time trip counter); bit 9 = ResetEnergyCounter (energy trip counter)
HR200doc 00201StatusRegisterBITMAP16Readbit 0 = Rotation (motor consuming power); bit 1 = Protection enabled; bit 2 = Ready; bit 3 = Unacknowledged fault pending; bit 4 = PTC open; bit 5 = Phase sequence left (L3-L2-L1)
HR201doc 00202OperatingModeUINT16Read0 = Started (on); 1 = Commanded trip; 2 = Actuator stop (off); 3 = Protection stop (alarm trip)
HR202doc 00203SystemModeUINT16Read0 = Power-up; 1 = Operating; 2 = MP 204 fault
HR203doc 00204AlarmCodeCause of the last motor protection trip.UINT16Read2 = Missing phase; 3 = External alarm signal (PTC); 4 = Too many automatic restarts per 24 h; 9 = Phase sequence reversal; 15 = Communication alarm, main system; 18 = Test trip; 20 = Insulation resistance low; 32 = Overvoltage; 40 = Undervoltage; 48 = Overload (current too high); 56 = Underload (current too low); 64 = Overtemperature, Tempcon; 71 = Overtemperature, Pt100; 111 = Current asymmetry; 112 = Cos phi too high; 113 = Cos phi too low; 120 = Auxiliary winding alarm; 123 = Start capacitor low; 124 = Run capacitor low
HR204doc 00205WarningBits1BITMAP16Readbit 0 = Overvoltage (32); bit 1 = Undervoltage (40); bit 2 = Overload (48); bit 3 = Underload (56); bit 4 = Current asymmetry (111); bit 8 = Insulation resistance low (20); bit 9 = Overtemperature Tempcon (64); bit 10 = Overtemperature Pt100 (71); bit 12 = Cos phi too high (112); bit 13 = Cos phi too low (113); bit 14 = Too many starts per hour (21)
HR205doc 00206WarningBits2BITMAP16Readbit 0 = Start capacitor low (123); bit 1 = Run capacitor low (124); bit 3 = Signal fault, Tempcon sensor (91); bit 4 = Signal fault, Pt100 sensor (175); bit 5 = Service warning (12); bit 6 = Load continues with relay R1 off (26)
HR206doc 00207RelaysBITMAP16Readbit 0 = Motor control relay closed; bit 1 = Alarm signal relay closed
HR207doc 00208AcknowledgeRegisterCommand acknowledgements; used only when AutoAckControlBits = 0.BITMAP16Readbit 0 = ResetAlarmAck; bit 1 = TripAck; bit 5 = ResetStartCounterAck; bit 6 = ResetRestartCounterAck; bit 7 = ResetLogsAck; bit 8 = ResetHourCounterAck; bit 9 = ResetEnergyCounterAck
HR300doc 00301PhaseVoltageL13-phase: L1 phase voltage; 1-phase: reference (0).UINT16× 0.1VRead
HR301doc 00302PhaseVoltageL23-phase: L2 phase voltage.UINT16× 0.1VRead
HR302doc 00303PhaseVoltageL33-phase: L3 phase voltage; 1-phase: auxiliary winding voltage.UINT16× 0.1VRead
HR303doc 00304PhaseVoltageMeanUINT16× 0.1VRead
HR304doc 00305LineVoltageL1L23-phase only.UINT16× 0.1VRead
HR305doc 00306LineVoltageL2L33-phase only.UINT16× 0.1VRead
HR306doc 00307LineVoltageL3L13-phase only.UINT16× 0.1VRead
HR307doc 00308LineVoltageMean3-phase only.UINT16× 0.1VRead
HR308doc 00309LineCurrentL11-phase: neutral current.UINT16× 0.1ARead
HR309doc 00310LineCurrentL21-phase: mains winding current.UINT16× 0.1ARead
HR310doc 00311LineCurrentL31-phase: auxiliary winding current.UINT16× 0.1ARead
HR311doc 00312LineCurrentMeanUINT16× 0.1ARead
HR312doc 00313LineCurrentStartPeak line current at the latest motor start.UINT16× 0.1ARead
HR313doc 00314MotorTemp1Motor temperature from Tempcon, in 0.01 K.UINT16× 0.01KRead
HR314doc 00315MotorTemp2Motor temperature from the Pt sensor, in 0.01 K.UINT16× 0.01KRead
HR315doc 00316LineCurrentAsym3-phase only.UINT16× 0.1%Read
HR316doc 00317CapacitorStart1-phase only.UINT16µFRead
HR317doc 00318CapacitorRun1-phase only.UINT16µFRead
HR318doc 00319CapacitorStartRef1-phase only.UINT16µFRead
HR319doc 00320CapacitorRunRef1-phase only.UINT16µFRead
HR320doc 00321LineFrequencyUINT16× 0.1HzRead
HR321doc 00322VoltageAngleL1L23-phase only.UINT16°Read
HR322doc 00323VoltageAngleL1L33-phase only.UINT16°Read
HR323doc 00324CosPhiL13-phase only.UINT16× 0.01Read
HR324doc 00325CosPhiL23-phase only.UINT16× 0.01Read
HR325doc 00326CosPhiL33-phase only.UINT16× 0.01Read
HR326doc 00327CosPhiMean power factor.UINT16× 0.01Read
HR327doc 00328PowerPower consumption (HI/LO pair).UINT32ABCDWRead
HR329doc 00330EnergyEnergy consumption (HI/LO pair).UINT32ABCDkWhRead
HR331doc 00332EnergyTripCounterResettable with ControlRegister bit 9.UINT32ABCDkWhRead
HR333doc 00334OperationTimeUINT32ABCDhRead
HR335doc 00336TotalPoweredTimeUINT32ABCDhRead
HR337doc 00338OperationTimeTripCounterResettable with ControlRegister bit 8.UINT32ABCDhRead
HR339doc 00340NumberOfStartsUINT32ABCDRead
HR341doc 00342NumberOfStartsTripCounterResettable with ControlRegister bit 5.UINT32ABCDRead
HR343doc 00344AutoRestartsTripCounterResettable with ControlRegister bit 6.UINT32ABCDRead
HR345doc 00346InsulationResistance3-phase only.UINT16× 10kΩRead
HR346doc 00347PhaseVoltageDistortionUINT16× 0.01%Read
HR347doc 00348VoltageMaxLogLogged maximum line voltage; reset with bit 7.UINT16× 0.1VRead
HR348doc 00349VoltageMinLogLogged minimum line voltage.UINT16× 0.1VRead
HR349doc 00350CurrentLineMaxLogLogged maximum line current.UINT16× 0.1ARead
HR350doc 00351CurrentLineMinLogLogged minimum line current.UINT16× 0.1ARead
HR351doc 00352StartsHourMaxLogLogged maximum starts per hour.UINT16Read
HR352doc 00353StartsPerHourMoving average.UINT16Read
HR353doc 00354AutoRestartsPer24hMoving average.UINT16Read
HR700doc 00701SimulationWarningBits1Simulated warnings/alarms, bits as in 00205/00206.BITMAP16Read/write
HR701doc 00702SimulationWarningBits2Simulated warnings/alarms, bits as in 00205/00206.BITMAP16Read/write
HR702doc 00703SimulationAlarmBits1Simulated warnings/alarms, bits as in 00205/00206.BITMAP16Read/write
HR703doc 00704SimulationAlarmBits2Simulated warnings/alarms, bits as in 00205/00206.BITMAP16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)

What Modbus registers does the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) have?

This map lists 74 registers: 74 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 5-digit register numbers; the telegram examples address register X as X-1 (ControlRegister 00101 is written at address 0x0064). The RegisterOffset register 00002 shifts every address above 00100 if it is changed from its default 0.

What byte order does the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)?

Start with HR 100 ControlRegister (Start/stop, trip and reset commands); HR 200 StatusRegister (Running, ready and fault flags); HR 201 OperatingMode (Operating mode); HR 203 AlarmCode (Alarm code); HR 204 WarningBits1 (Active warnings); HR 311 LineCurrentMean (Mean line current); HR 327 Power (Power consumption); HR 329 Energy (Energy counter).

How do I enable Modbus control of the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)?

The MP 204 needs no setting for remote control; configure it with the R100, Grundfos GO or PC Tool first, then connect the CIU. OnOffReq (bit 2 of 00101) starts and stops the motor; the device acts on the last command from Modbus, remote or buttons.

Where is the official Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus documentation?

The source is Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual (98393513 1114), revision 2014-11, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012935.pdf.

More Grundfos Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual · 98393513 1114 · rev. 2014-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.