- Home
- Modbus register maps
- Grundfos
- MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Pump motor protection relay · Modbus register map
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus register map
Updated 19 November 2026
The MP 204 is Grundfos's electronic motor protector for single- and three-phase pump motors. A CIU communication box talks GENIbus to the MP 204 and presents it as a Modbus slave, with blocks for CIU settings, CIU status, one control register, protector status and measured data. The map covers start/stop and trip commands, alarm and warning codes, phase voltages and currents, power factor, power, energy, run hours, start counters and insulation resistance.
This page lists 74 Modbus registers for the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Grundfos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Grundfos
- Model
- MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
- Equipment type
- Pump motor protection relay
- Registers
- 74 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513
Integration notes: Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Set the CIU 200 slave address on the two hex switches, keep 19200 8E1, then poll 00201-00208 for status and alarm, and 00301-00354 for measurements. Start, stop and trip the pump through ControlRegister 00101.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | ControlRegister | BITMAP16 | Start/stop, trip and reset commands | Read/write |
| HR 200 | StatusRegister | BITMAP16 | Running, ready and fault flags | Read |
| HR 201 | OperatingMode | UINT16 | Operating mode | Read |
| HR 203 | AlarmCode | UINT16 | Alarm code | Read |
| HR 204 | WarningBits1 | BITMAP16 | Active warnings | Read |
| HR 311 | LineCurrentMean | UINT16 | Mean line current | Read |
| HR 327 | Power | UINT32 ABCD | Power consumption | Read |
| HR 329 | Energy | UINT32 ABCD | Energy counter | Read |
Enable Modbus control & writes
The MP 204 needs no setting for remote control; configure it with the R100, Grundfos GO or PC Tool first, then connect the CIU. OnOffReq (bit 2 of 00101) starts and stops the motor; the device acts on the last command from Modbus, remote or buttons.
Byte order & addressing
- Reset and trip bits act on a rising edge. With AutoAckControlBits = 1 (default) the CIU clears them itself; with 0 you must clear them and watch 00208.
- Data block values are unsigned unless stated; 0xFFFF means not available.
Network setup
- CIU 200: address on rotary switches SW6/SW7 (hex, high and low nibble), speed on SW4/SW5 (9600, 19200 default, 38400, or software-defined), parity on SW3 (even/1 stop default, or none/2 stop), termination on SW1/SW2.
- CIU 500: Modbus TCP on port 502.
Watch out for
- Changing RegisterOffset (00002) moves every register above 00100; leave it at 0.
- Single-phase motors report different meanings in the L1-L3 voltage and current registers (neutral, main winding, auxiliary winding).
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 00001 | SlaveMinimumReplyDelay | Extra reply delay, 0-10000 ms (default 0). | UINT16 | ms | Read/write | |||
| HR | 1doc 00002 | RegisterOffset | Offset added to every address above 00100; default 0, normally leave it. | UINT16 | Read/write | ||||
| HR | 2doc 00003 | SoftwareDefinedModbusAddress | Slave address used only in software-defined mode (default 231). | UINT16 | Read/write | ||||
| HR | 3doc 00004 | SoftwareDefinedBitRate | Used only when SW4/SW5 select software-defined speed. | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400 | |||
| HR | 4doc 00005 | AutoAckControlBits | UINT16 | Read/write | 0 = Disabled (clear control bits yourself); 1 = Enabled (default) | ||||
| HR | 8doc 00009 | SoftwareDefinedParity | UINT16 | Read/write | 0 = None (default); 1 = Even; 2 = Odd | ||||
| HR | 9doc 00010 | SoftwareDefinedStopBit | UINT16 | Read/write | 0 = No stop bit; 1 = 1 stop bit (default); 2 = 2 stop bits | ||||
| HR | 20doc 00021 | GENIbusCRCErrorCnt | CRC errors on the internal GENIbus link to the MP 204. | UINT16 | Read | ||||
| HR | 21doc 00022 | GENIbusDataErrorCnt | Data errors on the internal GENIbus link. | UINT16 | Read | ||||
| HR | 22doc 00023 | VersionNumber | Grundfos-specific version number. | UINT16 | Read | ||||
| HR | 23doc 00024 | ActualModbusAddress | Slave address in use (1-247). | UINT16 | Read | ||||
| HR | 24doc 00025 | GENIbusTXcount | Telegrams sent to the MP 204 (HI/LO pair). | UINT32 | ABCD | Read | |||
| HR | 26doc 00027 | GENIbusRXcount | Telegrams received from the MP 204 (HI/LO pair). | UINT32 | ABCD | Read | |||
| HR | 29doc 00030 | UnitFamily | Grundfos product family. | UINT16 | Read | ||||
| HR | 30doc 00031 | UnitType | Grundfos product type. | UINT16 | Read | ||||
| HR | 31doc 00032 | UnitVersion | Grundfos product version. | UINT16 | Read | ||||
| HR | 100doc 00101 | ControlRegister | Command bits; reset bits act on a 0 to 1 edge. | BITMAP16 | Read/write | bit 0 = ResetAlarm; bit 1 = CommandedTrip; bit 2 = OnOffReq (1 = on/start, 0 = off/stop); bit 3 = ProtectionEnabled (1 = enabled); bit 5 = ResetStartCounter; bit 6 = ResetRestartCounter; bit 7 = ResetLogs (min/max logs 00348-00352); bit 8 = ResetHourCounter (operating-time trip counter); bit 9 = ResetEnergyCounter (energy trip counter) | |||
| HR | 200doc 00201 | StatusRegister | BITMAP16 | Read | bit 0 = Rotation (motor consuming power); bit 1 = Protection enabled; bit 2 = Ready; bit 3 = Unacknowledged fault pending; bit 4 = PTC open; bit 5 = Phase sequence left (L3-L2-L1) | ||||
| HR | 201doc 00202 | OperatingMode | UINT16 | Read | 0 = Started (on); 1 = Commanded trip; 2 = Actuator stop (off); 3 = Protection stop (alarm trip) | ||||
| HR | 202doc 00203 | SystemMode | UINT16 | Read | 0 = Power-up; 1 = Operating; 2 = MP 204 fault | ||||
| HR | 203doc 00204 | AlarmCode | Cause of the last motor protection trip. | UINT16 | Read | 2 = Missing phase; 3 = External alarm signal (PTC); 4 = Too many automatic restarts per 24 h; 9 = Phase sequence reversal; 15 = Communication alarm, main system; 18 = Test trip; 20 = Insulation resistance low; 32 = Overvoltage; 40 = Undervoltage; 48 = Overload (current too high); 56 = Underload (current too low); 64 = Overtemperature, Tempcon; 71 = Overtemperature, Pt100; 111 = Current asymmetry; 112 = Cos phi too high; 113 = Cos phi too low; 120 = Auxiliary winding alarm; 123 = Start capacitor low; 124 = Run capacitor low | |||
| HR | 204doc 00205 | WarningBits1 | BITMAP16 | Read | bit 0 = Overvoltage (32); bit 1 = Undervoltage (40); bit 2 = Overload (48); bit 3 = Underload (56); bit 4 = Current asymmetry (111); bit 8 = Insulation resistance low (20); bit 9 = Overtemperature Tempcon (64); bit 10 = Overtemperature Pt100 (71); bit 12 = Cos phi too high (112); bit 13 = Cos phi too low (113); bit 14 = Too many starts per hour (21) | ||||
| HR | 205doc 00206 | WarningBits2 | BITMAP16 | Read | bit 0 = Start capacitor low (123); bit 1 = Run capacitor low (124); bit 3 = Signal fault, Tempcon sensor (91); bit 4 = Signal fault, Pt100 sensor (175); bit 5 = Service warning (12); bit 6 = Load continues with relay R1 off (26) | ||||
| HR | 206doc 00207 | Relays | BITMAP16 | Read | bit 0 = Motor control relay closed; bit 1 = Alarm signal relay closed | ||||
| HR | 207doc 00208 | AcknowledgeRegister | Command acknowledgements; used only when AutoAckControlBits = 0. | BITMAP16 | Read | bit 0 = ResetAlarmAck; bit 1 = TripAck; bit 5 = ResetStartCounterAck; bit 6 = ResetRestartCounterAck; bit 7 = ResetLogsAck; bit 8 = ResetHourCounterAck; bit 9 = ResetEnergyCounterAck | |||
| HR | 300doc 00301 | PhaseVoltageL1 | 3-phase: L1 phase voltage; 1-phase: reference (0). | UINT16 | × 0.1 | V | Read | ||
| HR | 301doc 00302 | PhaseVoltageL2 | 3-phase: L2 phase voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 302doc 00303 | PhaseVoltageL3 | 3-phase: L3 phase voltage; 1-phase: auxiliary winding voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 303doc 00304 | PhaseVoltageMean | UINT16 | × 0.1 | V | Read | |||
| HR | 304doc 00305 | LineVoltageL1L2 | 3-phase only. | UINT16 | × 0.1 | V | Read | ||
| HR | 305doc 00306 | LineVoltageL2L3 | 3-phase only. | UINT16 | × 0.1 | V | Read | ||
| HR | 306doc 00307 | LineVoltageL3L1 | 3-phase only. | UINT16 | × 0.1 | V | Read | ||
| HR | 307doc 00308 | LineVoltageMean | 3-phase only. | UINT16 | × 0.1 | V | Read | ||
| HR | 308doc 00309 | LineCurrentL1 | 1-phase: neutral current. | UINT16 | × 0.1 | A | Read | ||
| HR | 309doc 00310 | LineCurrentL2 | 1-phase: mains winding current. | UINT16 | × 0.1 | A | Read | ||
| HR | 310doc 00311 | LineCurrentL3 | 1-phase: auxiliary winding current. | UINT16 | × 0.1 | A | Read | ||
| HR | 311doc 00312 | LineCurrentMean | UINT16 | × 0.1 | A | Read | |||
| HR | 312doc 00313 | LineCurrentStart | Peak line current at the latest motor start. | UINT16 | × 0.1 | A | Read | ||
| HR | 313doc 00314 | MotorTemp1 | Motor temperature from Tempcon, in 0.01 K. | UINT16 | × 0.01 | K | Read | ||
| HR | 314doc 00315 | MotorTemp2 | Motor temperature from the Pt sensor, in 0.01 K. | UINT16 | × 0.01 | K | Read | ||
| HR | 315doc 00316 | LineCurrentAsym | 3-phase only. | UINT16 | × 0.1 | % | Read | ||
| HR | 316doc 00317 | CapacitorStart | 1-phase only. | UINT16 | µF | Read | |||
| HR | 317doc 00318 | CapacitorRun | 1-phase only. | UINT16 | µF | Read | |||
| HR | 318doc 00319 | CapacitorStartRef | 1-phase only. | UINT16 | µF | Read | |||
| HR | 319doc 00320 | CapacitorRunRef | 1-phase only. | UINT16 | µF | Read | |||
| HR | 320doc 00321 | LineFrequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 321doc 00322 | VoltageAngleL1L2 | 3-phase only. | UINT16 | ° | Read | |||
| HR | 322doc 00323 | VoltageAngleL1L3 | 3-phase only. | UINT16 | ° | Read | |||
| HR | 323doc 00324 | CosPhiL1 | 3-phase only. | UINT16 | × 0.01 | Read | |||
| HR | 324doc 00325 | CosPhiL2 | 3-phase only. | UINT16 | × 0.01 | Read | |||
| HR | 325doc 00326 | CosPhiL3 | 3-phase only. | UINT16 | × 0.01 | Read | |||
| HR | 326doc 00327 | CosPhi | Mean power factor. | UINT16 | × 0.01 | Read | |||
| HR | 327doc 00328 | Power | Power consumption (HI/LO pair). | UINT32 | ABCD | W | Read | ||
| HR | 329doc 00330 | Energy | Energy consumption (HI/LO pair). | UINT32 | ABCD | kWh | Read | ||
| HR | 331doc 00332 | EnergyTripCounter | Resettable with ControlRegister bit 9. | UINT32 | ABCD | kWh | Read | ||
| HR | 333doc 00334 | OperationTime | UINT32 | ABCD | h | Read | |||
| HR | 335doc 00336 | TotalPoweredTime | UINT32 | ABCD | h | Read | |||
| HR | 337doc 00338 | OperationTimeTripCounter | Resettable with ControlRegister bit 8. | UINT32 | ABCD | h | Read | ||
| HR | 339doc 00340 | NumberOfStarts | UINT32 | ABCD | Read | ||||
| HR | 341doc 00342 | NumberOfStartsTripCounter | Resettable with ControlRegister bit 5. | UINT32 | ABCD | Read | |||
| HR | 343doc 00344 | AutoRestartsTripCounter | Resettable with ControlRegister bit 6. | UINT32 | ABCD | Read | |||
| HR | 345doc 00346 | InsulationResistance | 3-phase only. | UINT16 | × 10 | kΩ | Read | ||
| HR | 346doc 00347 | PhaseVoltageDistortion | UINT16 | × 0.01 | % | Read | |||
| HR | 347doc 00348 | VoltageMaxLog | Logged maximum line voltage; reset with bit 7. | UINT16 | × 0.1 | V | Read | ||
| HR | 348doc 00349 | VoltageMinLog | Logged minimum line voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 349doc 00350 | CurrentLineMaxLog | Logged maximum line current. | UINT16 | × 0.1 | A | Read | ||
| HR | 350doc 00351 | CurrentLineMinLog | Logged minimum line current. | UINT16 | × 0.1 | A | Read | ||
| HR | 351doc 00352 | StartsHourMaxLog | Logged maximum starts per hour. | UINT16 | Read | ||||
| HR | 352doc 00353 | StartsPerHour | Moving average. | UINT16 | Read | ||||
| HR | 353doc 00354 | AutoRestartsPer24h | Moving average. | UINT16 | Read | ||||
| HR | 700doc 00701 | SimulationWarningBits1 | Simulated warnings/alarms, bits as in 00205/00206. | BITMAP16 | Read/write | ||||
| HR | 701doc 00702 | SimulationWarningBits2 | Simulated warnings/alarms, bits as in 00205/00206. | BITMAP16 | Read/write | ||||
| HR | 702doc 00703 | SimulationAlarmBits1 | Simulated warnings/alarms, bits as in 00205/00206. | BITMAP16 | Read/write | ||||
| HR | 703doc 00704 | SimulationAlarmBits2 | Simulated warnings/alarms, bits as in 00205/00206. | BITMAP16 | Read/write |
Notes on this map
- All registers can be read with function 03 or 04 (the same data is in both tables); they are listed here as holding registers. Control and configuration registers are written with 06 or 16.
- 32-bit values are split into HI and LO registers with the HI (high-order) part at the lower address, so they are ABCD.
- A raw value of 65535 (0xFFFF) means 'not available'. Several values exist only for 1-phase or only for 3-phase motors, or need the optional sensors (Tempcon, Pt100).
- Motor temperatures are given in 0.01 K as printed; the manual does not say whether an offset of 273.15 applies, so no offset is set here.
- Left out: CIU 250-only registers (GSM real-time clock 00080-00097, GeneralStatus/PIN bits 00029, GSM battery 00033, NoDataActivityTimeout 00008, GSM signal and IP address 00236-00239) and the free user registers 00751-00800.
- Software-defined parity and stop-bit defaults (none / 1 stop bit) apply only in software-defined mode; the DIP-switch default is even parity, 1 stop bit.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
What Modbus registers does the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) have?
This map lists 74 registers: 74 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 5-digit register numbers; the telegram examples address register X as X-1 (ControlRegister 00101 is written at address 0x0064). The RegisterOffset register 00002 shifts every address above 00100 if it is changed from its default 0.
What byte order does the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)?
Start with HR 100 ControlRegister (Start/stop, trip and reset commands); HR 200 StatusRegister (Running, ready and fault flags); HR 201 OperatingMode (Operating mode); HR 203 AlarmCode (Alarm code); HR 204 WarningBits1 (Active warnings); HR 311 LineCurrentMean (Mean line current); HR 327 Power (Power consumption); HR 329 Energy (Energy counter).
How do I enable Modbus control of the Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)?
The MP 204 needs no setting for remote control; configure it with the R100, Grundfos GO or PC Tool first, then connect the CIU. OnOffReq (bit 2 of 00101) starts and stops the motor; the device acts on the last command from Modbus, remote or buttons.
Where is the official Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus) Modbus documentation?
The source is Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual (98393513 1114), revision 2014-11, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012935.pdf.
More Grundfos Modbus register maps
- Pump (booster system / multi-pump controller)
Grundfos Booster systems (Hydro MPC, Hydro Multi-E, Multi-B) via CIM 200 / CIM 500
Grundfos booster systems: Hydro MPC / Control MPC (CU 352), GENIECON MPC, Hydro Multi-B (CU 323), DDD (CU 354), Hydro Multi-E, TPED and MAGNA3-D twin pumps, with CIM/CIU 200, CIM/CIU 500 or SoftCIM.
Also known as: Hydro MPC, Control MPC, CU 352, GENIECON MPC, Hydro Multi-E, Hydro Multi-B, CU 323, DDD, CU 354, TPED, MAGNA3-D, CIM 200, CIM 500, SoftCIM Modbus TCP - Pump controller (wastewater lift station)
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Grundfos Dedicated Controls wastewater pit controller (CU 361 / CU 362, up to six pumps and a mixer) with a CIM 200 Modbus RTU, CIM 260 cellular or CIM 500 Modbus TCP module; functional profile 98393520 (2023-03).
Also known as: Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU - Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341 - Pump (chemical dosing pump)
Grundfos SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500)
Grundfos SMART Digital DDA dosing pumps: DDA model C with built-in SoftCIM Modbus RTU/TCP, and DDA XL (or others) through a CIM 200 Modbus RTU or CIM 500 Modbus TCP module in a CIU 900, per functional profile 98473491 (09.2026).
Also known as: DDA, DDA S, DDA XL, DDA-C, DDA model C, SMART Digital S, SMART Digital XL, CIM 200, CIM 500, 98473491
Other pumps register maps
- Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Heat pump
Acond Acond heat pumps (Modbus TCP interface v2.35)
Acond air-to-water and brine heat pumps with the ModbusTCP function activated, interface description version 2.35 dated 01.12.2022.
Also known as: Acond PRO series, Acond ModbusTCP v2.35 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP
All pumps Modbus register maps →
Source: Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual · 98393513 1114 · rev. 2014-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.