Easy Modbus
  1. Home
  2. Modbus register maps
  3. Acond
  4. Acond heat pumps (Modbus TCP interface v2.35)

Heat pump · Modbus register map

Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus register map

Updated 19 November 2026

Short answer

Acond heat pumps act as a Modbus TCP slave on port 502 once a service technician has activated the function. Input registers report setpoints, sensor temperatures, a status bit field, the operating and regulation mode, fault codes and compressor speed or capacity. Holding registers let the master set room, hot water, pool and cooling targets, choose the mode, acknowledge faults and feed in its own room, outdoor, solar and pool temperatures.

This page lists 38 Modbus registers for the Acond Acond heat pumps (Modbus TCP interface v2.35) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acond’s own free documentation (linked below) and checked against it.

Manufacturer
Acond
Model
Acond heat pumps (Modbus TCP interface v2.35)
Equipment type
Heat pump
Registers
38 (14 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Acond PRO series, Acond ModbusTCP v2.35
Source document
Acond Modbus TCP INTERFACE DESCRIPTION · Version 2.35 · rev. 2022-12-01 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Acond Acond heat pumps (Modbus TCP interface v2.35)

Integration in brief

Have Acond service enable ModbusTCP, tick ModbusTCP on the heat pump's web page, then poll input registers 30001-30024 with function 4 and write targets and TC_set at 40001-40014 regularly so the heat pump keeps using the master's values.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 6TC_statusBITMAP16Status bits (on, running, alarm, defrost)Read
IR 13rezim_panINT16Operating modeRead
IR 9T_act_airINT16Outdoor temperatureRead
IR 8T_act_water_backINT16Return water temperatureRead
IR 20err_numberINT16Fault codeRead
HR 0T_set_indoor1INT16Room setpoint circuit 1Read/write
HR 4T_set_TUVINT16Hot water setpointRead/write
HR 5TC_setBITMAP16Mode / fault reset bitsRead/write

Enable Modbus control & writes

ModbusTCP is activated by an Acond service technician. Afterwards a ModbusTCP link appears on the heat pump's main web page; tick the ModbusTCP box in the dark blue bar to start communication.

Communication loss & watchdog

If no data is exchanged within MaxCommDataRefresh, the status shows 'ModbusTCP false' and values received from the master are replaced by the heat pump's own sensor readings until communication returns.

Byte order & addressing

Network setup

Watch out for

Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

38 of 38 shown
Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001T_set_indoor1Desired room temperature, circuit 1 (10.0-30.0).INT16× 0.1°CRead
IR1doc 30002T_act_indoor1Room temperature sensor, circuit 1.INT16× 0.1°CRead
IR2doc 30003T_set_indoor2Desired room temperature, circuit 2.INT16× 0.1°CRead
IR3doc 30004T_act_indoor2Room temperature sensor, circuit 2.INT16× 0.1°CRead
IR4doc 30005T_set_TUVDesired hot water (DHW) temperature.INT16× 0.1°CRead
IR5doc 30006T_act_TUVHot water (DHW) temperature sensor.INT16× 0.1°CRead
IR6doc 30007TC_statusHeat pump status flags.BITMAP16Readbit 0 = Heat pump switched on; bit 1 = Heat pump running; bit 2 = Alarm; bit 3 = DHW being heated; bit 4 = Heating circuit 1 circulation pump running; bit 5 = Heating circuit circulation pump running (printed as circuit 1 again); bit 6 = Solar circulation pump running; bit 7 = Swimming pool circulation pump running; bit 8 = Defrosting; bit 9 = Auxiliary heater operating; bit 10 = Summer operation; bit 12 = Cooling operation
IR7doc 30008T_set_water_backDesired return water temperature.INT16× 0.1°CRead
IR8doc 30009T_act_water_backReturn water temperature sensor.INT16× 0.1°CRead
IR9doc 30010T_act_airOutdoor temperature sensor.INT16× 0.1°CRead
IR10doc 30011T_act_solarSolar panel temperature sensor.INT16× 0.1°CRead
IR11doc 30012T_act_poolSwimming pool temperature sensor.INT16× 0.1°CRead
IR12doc 30013T_set_poolDesired swimming pool temperature.INT16× 0.1°CRead
IR13doc 30014rezim_panCurrent operating mode.INT16Read0 = Automatic mode; 1 = Heat pump only; 2 = Not used; 3 = Auxiliary heating only; 4 = Off mode; 5 = Manual mode; 6 = Cooling mode
IR14doc 30015typ_reg_panHow the return water target is calculated.INT16Read0 = AcondTherm; 1 = Equitherm; 2 = Manual
IR15doc 30016T_solankaBrine temperature at the collector outlet (ground-source units).INT16× 0.1°CRead
IR16doc 30017HeartBeatCounter 0-255 that changes on each exchange; use it to check the link.INT16Read
IR17doc 30018T_act_water_outletOutlet water temperature sensor.INT16× 0.1°CRead
IR18doc 30019T_set_water_outletDesired outlet water temperature in cooling.INT16× 0.1°CRead
IR19doc 30020Comp_rpm_max / Comp_capacity_maxMax compressor speed (rpm), or max output in W on PRO series.INT16Read
IR20doc 30021err_numberBasic fault code (0-62).INT16Read
IR21doc 30022err_number_SECMonoSECMono fault code (0-42).INT16Read
IR22doc 30023err_number_driverCompressor driver fault code (0-39).INT16Read
IR23doc 30024comp_rpm_actual / comp_capacity_actualActual compressor speed (rpm), or current output in W on PRO series.INT16Read
HR0doc 40001T_set_indoor1Desired room temperature, circuit 1 (10.0-30.0).INT16× 0.1°CRead/write
HR1doc 40002T_act_indoor1Room temperature sent by the master for circuit 1 (0.0-50.0).INT16× 0.1°CRead/write
HR2doc 40003T_set_indoor2Desired room temperature, circuit 2 (10.0-30.0).INT16× 0.1°CRead/write
HR3doc 40004T_act_indoor2Room temperature sent by the master for circuit 2 (0.0-50.0).INT16× 0.1°CRead/write
HR4doc 40005T_set_TUVDesired hot water temperature (10.0-46.0).INT16× 0.1°CRead/write
HR5doc 40006TC_setMode selection and fault confirmation bits.BITMAP16Read/writebit 0 = Automatic mode; bit 1 = Heat pump mode; bit 2 = Auxiliary heating mode; bit 3 = Off mode; bit 4 = Cooling mode; bit 5 = Fault confirmation; bit 6 = Solar on; bit 7 = Swimming pool on; bit 8 = Summer/winter switchover
HR6doc 40007TC_set_regRegulation method (0-2).INT16Read/write0 = AcondTherm; 1 = Equitherm; 2 = Manual
HR7doc 40008T_set_water_backDesired return temperature in manual mode (10.0-65.0).INT16× 0.1°CRead/write
HR8doc 40009T_airOutdoor temperature sent by the master (-50.0 to 50.0).INT16× 0.1°CRead/write
HR9doc 40010T_act_solarSolar system temperature sent by the master (-50.0 to 300.0).INT16× 0.1°CRead/write
HR10doc 40011T_act_poolPool temperature sent by the master (0.0-50.0).INT16× 0.1°CRead/write
HR11doc 40012T_set_poolDesired swimming pool temperature (10.0-50.0).INT16× 0.1°CRead/write
HR12doc 40013T_set_water_coolDesired heat pump outlet temperature in cooling (15.0-30.0).INT16× 0.1°CRead/write
HR13doc 40014Comp_rpm_max / Comp_capacity_maxSpeed limit 1800-6000 rpm, or capacity limit 2000-20000 W on PRO series.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Acond Acond heat pumps (Modbus TCP interface v2.35)

What Modbus registers does the Acond Acond heat pumps (Modbus TCP interface v2.35) have?

This map lists 38 registers: 24 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 30001- (input registers, read with function 4) and 40001- (holding registers, function 3/6/16). Drop the leading 3 or 4 and subtract one: 30007 is input register 6, 40006 is holding register 5.

What are the minimum Modbus registers to integrate the Acond Acond heat pumps (Modbus TCP interface v2.35)?

Start with IR 6 TC_status (Status bits (on, running, alarm, defrost)); IR 13 rezim_pan (Operating mode); IR 9 T_act_air (Outdoor temperature); IR 8 T_act_water_back (Return water temperature); IR 20 err_number (Fault code); HR 0 T_set_indoor1 (Room setpoint circuit 1); HR 4 T_set_TUV (Hot water setpoint); HR 5 TC_set (Mode / fault reset bits).

How do I enable Modbus control of the Acond Acond heat pumps (Modbus TCP interface v2.35)?

ModbusTCP is activated by an Acond service technician. Afterwards a ModbusTCP link appears on the heat pump's main web page; tick the ModbusTCP box in the dark blue bar to start communication.

What happens when the Acond Acond heat pumps (Modbus TCP interface v2.35) loses Modbus communication?

If no data is exchanged within MaxCommDataRefresh, the status shows 'ModbusTCP false' and values received from the master are replaced by the heat pump's own sensor readings until communication returns.

Where is the official Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus documentation?

The source is Acond Modbus TCP INTERFACE DESCRIPTION (Version 2.35), revision 2022-12-01. Acond doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.openenergymonitor.org/uploads/short-url/bJsxkmQiygrj9DNip0f8rSOgVU.pdf. It may be an older revision, so check it against the live unit.

Other pumps register maps

All pumps Modbus register maps →

Source: Acond Modbus TCP INTERFACE DESCRIPTION · Version 2.35 · rev. 2022-12-01 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.