Heat pump · Modbus register map
Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus register map
Updated 19 November 2026
Acond heat pumps act as a Modbus TCP slave on port 502 once a service technician has activated the function. Input registers report setpoints, sensor temperatures, a status bit field, the operating and regulation mode, fault codes and compressor speed or capacity. Holding registers let the master set room, hot water, pool and cooling targets, choose the mode, acknowledge faults and feed in its own room, outdoor, solar and pool temperatures.
This page lists 38 Modbus registers for the Acond Acond heat pumps (Modbus TCP interface v2.35) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acond’s own free documentation (linked below) and checked against it.
- Manufacturer
- Acond
- Model
- Acond heat pumps (Modbus TCP interface v2.35)
- Equipment type
- Heat pump
- Registers
- 38 (14 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Acond PRO series, Acond ModbusTCP v2.35
Integration notes: Acond Acond heat pumps (Modbus TCP interface v2.35)
Have Acond service enable ModbusTCP, tick ModbusTCP on the heat pump's web page, then poll input registers 30001-30024 with function 4 and write targets and TC_set at 40001-40014 regularly so the heat pump keeps using the master's values.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 6 | TC_status | BITMAP16 | Status bits (on, running, alarm, defrost) | Read |
| IR 13 | rezim_pan | INT16 | Operating mode | Read |
| IR 9 | T_act_air | INT16 | Outdoor temperature | Read |
| IR 8 | T_act_water_back | INT16 | Return water temperature | Read |
| IR 20 | err_number | INT16 | Fault code | Read |
| HR 0 | T_set_indoor1 | INT16 | Room setpoint circuit 1 | Read/write |
| HR 4 | T_set_TUV | INT16 | Hot water setpoint | Read/write |
| HR 5 | TC_set | BITMAP16 | Mode / fault reset bits | Read/write |
Enable Modbus control & writes
ModbusTCP is activated by an Acond service technician. Afterwards a ModbusTCP link appears on the heat pump's main web page; tick the ModbusTCP box in the dark blue bar to start communication.
Communication loss & watchdog
If no data is exchanged within MaxCommDataRefresh, the status shows 'ModbusTCP false' and values received from the master are replaced by the heat pump's own sensor readings until communication returns.
Byte order & addressing
- Only one Modbus master may talk to the heat pump at a time.
- Unit ID 2 is reserved for the heat pump cascade; the slave answers as ID 1.
- A temperature written outside its range makes the heat pump use its own sensor value; an out-of-range setpoint is ignored.
Network setup
- Modbus TCP on port 502; supported functions 3 and 4 for reading, 6 and 16 for writing.
Watch out for
- The last communication error stays on the status page only until the next successful exchange.
Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | T_set_indoor1 | Desired room temperature, circuit 1 (10.0-30.0). | INT16 | × 0.1 | °C | Read | ||
| IR | 1doc 30002 | T_act_indoor1 | Room temperature sensor, circuit 1. | INT16 | × 0.1 | °C | Read | ||
| IR | 2doc 30003 | T_set_indoor2 | Desired room temperature, circuit 2. | INT16 | × 0.1 | °C | Read | ||
| IR | 3doc 30004 | T_act_indoor2 | Room temperature sensor, circuit 2. | INT16 | × 0.1 | °C | Read | ||
| IR | 4doc 30005 | T_set_TUV | Desired hot water (DHW) temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 5doc 30006 | T_act_TUV | Hot water (DHW) temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 6doc 30007 | TC_status | Heat pump status flags. | BITMAP16 | Read | bit 0 = Heat pump switched on; bit 1 = Heat pump running; bit 2 = Alarm; bit 3 = DHW being heated; bit 4 = Heating circuit 1 circulation pump running; bit 5 = Heating circuit circulation pump running (printed as circuit 1 again); bit 6 = Solar circulation pump running; bit 7 = Swimming pool circulation pump running; bit 8 = Defrosting; bit 9 = Auxiliary heater operating; bit 10 = Summer operation; bit 12 = Cooling operation | |||
| IR | 7doc 30008 | T_set_water_back | Desired return water temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 8doc 30009 | T_act_water_back | Return water temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 9doc 30010 | T_act_air | Outdoor temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 10doc 30011 | T_act_solar | Solar panel temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 11doc 30012 | T_act_pool | Swimming pool temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 12doc 30013 | T_set_pool | Desired swimming pool temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 13doc 30014 | rezim_pan | Current operating mode. | INT16 | Read | 0 = Automatic mode; 1 = Heat pump only; 2 = Not used; 3 = Auxiliary heating only; 4 = Off mode; 5 = Manual mode; 6 = Cooling mode | |||
| IR | 14doc 30015 | typ_reg_pan | How the return water target is calculated. | INT16 | Read | 0 = AcondTherm; 1 = Equitherm; 2 = Manual | |||
| IR | 15doc 30016 | T_solanka | Brine temperature at the collector outlet (ground-source units). | INT16 | × 0.1 | °C | Read | ||
| IR | 16doc 30017 | HeartBeat | Counter 0-255 that changes on each exchange; use it to check the link. | INT16 | Read | ||||
| IR | 17doc 30018 | T_act_water_outlet | Outlet water temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 18doc 30019 | T_set_water_outlet | Desired outlet water temperature in cooling. | INT16 | × 0.1 | °C | Read | ||
| IR | 19doc 30020 | Comp_rpm_max / Comp_capacity_max | Max compressor speed (rpm), or max output in W on PRO series. | INT16 | Read | ||||
| IR | 20doc 30021 | err_number | Basic fault code (0-62). | INT16 | Read | ||||
| IR | 21doc 30022 | err_number_SECMono | SECMono fault code (0-42). | INT16 | Read | ||||
| IR | 22doc 30023 | err_number_driver | Compressor driver fault code (0-39). | INT16 | Read | ||||
| IR | 23doc 30024 | comp_rpm_actual / comp_capacity_actual | Actual compressor speed (rpm), or current output in W on PRO series. | INT16 | Read | ||||
| HR | 0doc 40001 | T_set_indoor1 | Desired room temperature, circuit 1 (10.0-30.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1doc 40002 | T_act_indoor1 | Room temperature sent by the master for circuit 1 (0.0-50.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2doc 40003 | T_set_indoor2 | Desired room temperature, circuit 2 (10.0-30.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3doc 40004 | T_act_indoor2 | Room temperature sent by the master for circuit 2 (0.0-50.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4doc 40005 | T_set_TUV | Desired hot water temperature (10.0-46.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | TC_set | Mode selection and fault confirmation bits. | BITMAP16 | Read/write | bit 0 = Automatic mode; bit 1 = Heat pump mode; bit 2 = Auxiliary heating mode; bit 3 = Off mode; bit 4 = Cooling mode; bit 5 = Fault confirmation; bit 6 = Solar on; bit 7 = Swimming pool on; bit 8 = Summer/winter switchover | |||
| HR | 6doc 40007 | TC_set_reg | Regulation method (0-2). | INT16 | Read/write | 0 = AcondTherm; 1 = Equitherm; 2 = Manual | |||
| HR | 7doc 40008 | T_set_water_back | Desired return temperature in manual mode (10.0-65.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 8doc 40009 | T_air | Outdoor temperature sent by the master (-50.0 to 50.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 9doc 40010 | T_act_solar | Solar system temperature sent by the master (-50.0 to 300.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 10doc 40011 | T_act_pool | Pool temperature sent by the master (0.0-50.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 11doc 40012 | T_set_pool | Desired swimming pool temperature (10.0-50.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 12doc 40013 | T_set_water_cool | Desired heat pump outlet temperature in cooling (15.0-30.0). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 13doc 40014 | Comp_rpm_max / Comp_capacity_max | Speed limit 1800-6000 rpm, or capacity limit 2000-20000 W on PRO series. | INT16 | Read/write |
Notes on this map
- Acond's own site does not serve this description publicly (its older v2.34 link returns an HTML page); the link is an unaltered copy of Acond's PDF posted on the OpenEnergyMonitor forum.
- Every value is a single 16-bit register: 'Int' rows are INT16 (several have negative minimums printed) and 'Word' rows are bit fields. x10 rows are tenths of a degree.
- 30020, 30024 and 40014 carry compressor speed in rpm on most series but heat pump power in W on the PRO series; the units field is left blank for that reason.
- Bit 5 of 30007 is printed with the same text as bit 4 (circuit 1 pump); it is reproduced as printed. Bits 11 and 13-15 are reserved.
- The fault code books referenced by 30021-30023 are not part of this document.
- 30019 is printed with a x10 modifier but a min/max of 10/25; the x10 scale is kept as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Acond Acond heat pumps (Modbus TCP interface v2.35)
What Modbus registers does the Acond Acond heat pumps (Modbus TCP interface v2.35) have?
This map lists 38 registers: 24 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 30001- (input registers, read with function 4) and 40001- (holding registers, function 3/6/16). Drop the leading 3 or 4 and subtract one: 30007 is input register 6, 40006 is holding register 5.
What are the minimum Modbus registers to integrate the Acond Acond heat pumps (Modbus TCP interface v2.35)?
Start with IR 6 TC_status (Status bits (on, running, alarm, defrost)); IR 13 rezim_pan (Operating mode); IR 9 T_act_air (Outdoor temperature); IR 8 T_act_water_back (Return water temperature); IR 20 err_number (Fault code); HR 0 T_set_indoor1 (Room setpoint circuit 1); HR 4 T_set_TUV (Hot water setpoint); HR 5 TC_set (Mode / fault reset bits).
How do I enable Modbus control of the Acond Acond heat pumps (Modbus TCP interface v2.35)?
ModbusTCP is activated by an Acond service technician. Afterwards a ModbusTCP link appears on the heat pump's main web page; tick the ModbusTCP box in the dark blue bar to start communication.
What happens when the Acond Acond heat pumps (Modbus TCP interface v2.35) loses Modbus communication?
If no data is exchanged within MaxCommDataRefresh, the status shows 'ModbusTCP false' and values received from the master are replaced by the heat pump's own sensor readings until communication returns.
Where is the official Acond Acond heat pumps (Modbus TCP interface v2.35) Modbus documentation?
The source is Acond Modbus TCP INTERFACE DESCRIPTION (Version 2.35), revision 2022-12-01. Acond doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.openenergymonitor.org/uploads/short-url/bJsxkmQiygrj9DNip0f8rSOgVU.pdf. It may be an older revision, so check it against the live unit.
Other pumps register maps
- Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Pump controller (wastewater lift station)
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Grundfos Dedicated Controls wastewater pit controller (CU 361 / CU 362, up to six pumps and a mixer) with a CIM 200 Modbus RTU, CIM 260 cellular or CIM 500 Modbus TCP module; functional profile 98393520 (2023-03).
Also known as: Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520 - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus - Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP
All pumps Modbus register maps →
Source: Acond Modbus TCP INTERFACE DESCRIPTION · Version 2.35 · rev. 2022-12-01 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.