- EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Heat pump · Modbus register map
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus register map
Updated 17 November 2026
Daikin Applied EWAK-CZ / EWYK-CZ chiller and heat pump range on a MicroTech 4 controller. With a POL902 module the unit is a Modbus RTU slave and every point is a 16-bit holding register: enable, mode, cool/heat setpoints, capacity and current limits, water temperatures, DHW and collective-housing functions, VFD pump data, master/slave status and packed unit and circuit alarm words.
This page lists 92 Modbus registers for the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) — 29 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
- Equipment type
- Heat pump
- Registers
- 92 (29 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- ICARO control software (version not stated)
- Also known as
- EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204
Integration notes: Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Fit a POL902 module, set its address and serial settings at the keypad, then poll holding registers. Read Unit Status (col 15) and leaving water temperature (col 17); enable with col 9, choose Cool/Heat with col 34 and send setpoints to cols 35/37 in tenths of °C.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Local/Network Source | UINT16 | Local/Network source | Read |
| HR 14 | Unit Status | UINT16 | Unit status | Read |
| HR 16 | Evaporator Leaving Water Temperature | INT16 | Leaving water temperature | Read |
| HR 12 | Actual Capacity | INT16 | Actual capacity | Read |
| HR 8 | Unit Enable Setpoint - Network | UINT16 | Network enable command | Read/write |
| HR 33 | Operation Mode Setpoint - Network | UINT16 | Operation mode command | Read/write |
| HR 34 | Cool Setpoint - Network | INT16 | Cool setpoint command | Read/write |
| HR 36 | Heat Setpoint - Network | INT16 | Heat setpoint command | Read/write |
| HR 4 | Unit General Alarm | UINT16 | Unit general alarm | Read |
Enable Modbus control & writes
Power off, plug the POL902 module onto the controller's extension bus, power on, check the BUS LED is steady green, then enter the service password and set the Modbus parameters under Main menu > Commissioning > Modbus.
Byte order & addressing
- Addresses are Modicon-style: subtract 1 from the guide's column value.
- Tenths (0,1) apply to temperatures, percentages and the current limit.
- Unit and circuit alarms are bit-packed words; register 299 is Unit Alarm Word 1 and 295 is Word 5 (descending order).
Network setup
- POL902 defaults per port: address 1, parity None, 2 stop bits, 19200 baud, 5 ms response delay; port T2 is passive by default.
- BSP LED green = module and controller talking; BUS LED green = Modbus traffic, red = communication interrupted.
Watch out for
- Never leave Clear Alarms - Network (col 10) written to Clear; the guide warns that a continuous clear can be hazardous.
- Operation mode values 1, 4 and 5 are marked Not Used on this range; use 2 (Cool) or 3 (Heat).
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Local/Network Source | UINT16 | Read | 0 = Local; 1 = Remote | ||||
| HR | 1doc 2 | Enabled State | UINT16 | Read | 0 = Disabled; 1 = Enabled | ||||
| HR | 3doc 4 | Capacity Limited | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 4doc 5 | Unit General Alarm | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 7doc 8 | Thermoregulation State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Unit Enable Setpoint - Network | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 9doc 10 | Clear Alarms - Network | Do not leave this commanded to Clear; the guide warns a constant clear is hazardous. | UINT16 | Read/write | 0 = Normal; 1 = Clear | |||
| HR | 10doc 11 | Operation Mode | UINT16 | Read | 1 = Not used; 2 = Cool; 3 = Heat; 4 = Not used; 5 = Not used | ||||
| HR | 11doc 12 | Active Setpoint | -15 to 70 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 12doc 13 | Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 13doc 14 | Active Capacity Limit Output | INT16 | × 0.1 | % | Read | |||
| HR | 14doc 15 | Unit Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = Preshutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 16doc 17 | Evaporator Leaving Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 20doc 21 | Master/Slave Leaving Water Temperature | Common leaving water temperature in a master/slave group. | INT16 | × 0.1 | °C | Read | ||
| HR | 23doc 24 | Outdoor Air Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 30doc 31 | Warning Code | INT16 | Read | 0 = No alarm; 1 = External event | ||||
| HR | 31doc 32 | Problem Code | INT16 | Read | 0 = No alarm; 1 = Circuit alarm | ||||
| HR | 32doc 33 | Fault Code | INT16 | Read | 0 = No alarm; 1 = Unit alarm or both circuits in alarm | ||||
| HR | 33doc 34 | Operation Mode Setpoint - Network | UINT16 | Read/write | 0 = Null; 1 = Not used; 2 = Cool; 3 = Heat; 4 = Not used | ||||
| HR | 34doc 35 | Cool Setpoint - Network | -15 (or 4) to 28 °C depending on unit setup. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 36doc 37 | Heat Setpoint - Network | 20 to 70 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 37doc 38 | Capacity Limit Setpoint - Network | 0-100 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 39 | Current Limit Setpoint - Network | 0-2000 A. | INT16 | × 0.1 | A | Read/write | ||
| HR | 46doc 47 | Unit of Measure | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 47doc 48 | Noise Reduction Enable Setpoint | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 61doc 62 | Defrost - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 69doc 70 | Bivalent Operation - Enable Setpoint | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 70doc 71 | Bivalent Operation - Temperature Cut-Off | -7 to 7 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 71doc 72 | Bivalent Operation - Temperature Bivalent Mode | 0 to 20 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 72doc 73 | Bivalent Operation - Boiler Start Delay | 0 to 60 min. | INT16 | × 0.1 | min | Read/write | ||
| HR | 79doc 80 | Collective Housing - Enable Setpoint | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 80doc 81 | Collective Housing - Tank Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 81doc 82 | Collective Housing - Changeover Upper Limit | Changeover lower limit to 60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 82doc 83 | Collective Housing - Changeover Lower Limit | -15 (or 4) to 60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 83doc 84 | Collective Housing - Tank Temperature Setpoint | Between the changeover lower and upper limits. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 89doc 90 | DHW Enable Setpoint | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 90doc 91 | DHW Temperature Setpoint | 0 to 60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 91doc 92 | DHW Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 92doc 93 | DHW Switching Valve State | UINT16 | Read | 0 = DHW off; 1 = Switching; 2 = DHW run; 3 = Error | ||||
| HR | 93doc 94 | DHW Anti Legionella Cycle | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 100doc 101 | Evaporator Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 149doc 150 | Evaporator VFD Pump - Fixed Speed 1 | INT16 | % | Read/write | ||||
| HR | 150doc 151 | Evaporator VFD Pump - Fixed Speed 2 | INT16 | % | Read/write | ||||
| HR | 151doc 152 | Evaporator VFD Pump - Standby Speed | INT16 | % | Read/write | ||||
| HR | 152doc 153 | Evaporator VFD Pump - Actual Speed | INT16 | % | Read | ||||
| HR | 153doc 154 | Evaporator VFD Pump - Building Differential Pressure Setpoint | INT16 | kPa | Read/write | ||||
| HR | 154doc 155 | Evaporator VFD Pump - Unit Differential Pressure Setpoint | INT16 | kPa | Read/write | ||||
| HR | 155doc 156 | Evaporator VFD Pump - Building Differential Pressure | INT16 | kPa | Read | ||||
| HR | 156doc 157 | Evaporator VFD Pump - Unit Differential Pressure | INT16 | kPa | Read | ||||
| HR | 157doc 158 | Evaporator VFD Pump - Bypass Valve State | UINT16 | Read | 0 = Closed; 1 = Opened | ||||
| HR | 158doc 159 | Evaporator VFD Pump - Delta Temperature Setpoint | Water delta-T setpoint (printed as delta °C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 159doc 160 | Evaporator VFD Pump - Delta Temperature | Measured water delta-T (printed as delta °C). | INT16 | × 0.1 | °C | Read | ||
| HR | 200doc 201 | Siemens Controller Type | UINT16 | Read | 0 = N/A; 1 = POL687; 2 = POL638; 3 = POL687.00; 4 = POL687.70; 5 = POL688.80; 6 = POL688.80UPS; 7 = POL468 | ||||
| HR | 201doc 202 | Application Save | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 287doc 288 | External Alarm | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 288doc 289 | External Event | UINT16 | Read | 0 = No event; 1 = Event | ||||
| HR | 294doc 295 | Unit Alarm Word 5 | BITMAP16 | Read | bit 0 = Compressor box leak detector comm fail; bit 1 = Master electrical panel leak detector comm fail; bit 2 = Slave electrical panel leak detector comm fail; bit 3 = POL925 communication fail | ||||
| HR | 295doc 296 | Unit Alarm Word 4 | BITMAP16 | Read | bit 0 = ACS communication fail; bit 1 = Pump communication fail; bit 2 = Domestic hot water alarm; bit 3 = Controller time not valid; bit 4 = Outdoor communication error; bit 5 = Outdoor mismatch alarm; bit 6 = Software mismatch alarm; bit 7 = Gas leakage alarm; bit 8 = Gas sensor fault; bit 9 = Tank water temperature sensor fault (TankWtSenf); bit 10 = Water overheat alarm; bit 11 = DHW anti-legionella alarm/event; bit 12 = pCOe Modbus communication error; bit 13 = Extraction fan fault; bit 14 = Ground fault relay alarm; bit 15 = Inverter DAE communication fail | ||||
| HR | 296doc 297 | Unit Alarm Word 3 | BITMAP16 | Read | bit 0 = Outside ambient temperature sensor fault; bit 1 = Option extension fault; bit 15 = Unit power restore | ||||
| HR | 297doc 298 | Unit Alarm Word 2 | BITMAP16 | Read | bit 1 = External alarm; bit 2 = External event; bit 14 = Low outside ambient temperature lockout; bit 15 = Leaving water temperature reset fault | ||||
| HR | 298doc 299 | Unit Alarm Word 1 | BITMAP16 | Read | bit 7 = Demand limit fault; bit 10 = Evaporator entering water temperature sensor fault; bit 11 = Evaporator flow loss; bit 12 = Evaporator freeze (unit); bit 14 = Evaporator leaving water temperature sensor fault; bit 15 = Evaporator pump 1 fault | ||||
| HR | 299doc 300 | Circuit 1 State | UINT16 | Read | 0 = Off; 1 = Preopen; 2 = Run; 3 = Pumpdown | ||||
| HR | 320doc 321 | Circuit 1 Compressor 1 Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 321doc 322 | Circuit 1 Compressor 1 Starts | Start counter (printed range 0-9,999,999 although the register is one word). | UINT16 | Read/write | ||||
| HR | 324doc 325 | Circuit 1 Compressor 1 Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 325doc 326 | Circuit 1 Compressor 1 Percent RLA | 0-110 %. | INT16 | × 0.1 | % | Read | ||
| HR | 329doc 330 | Master/Slave Disconnect Setpoint | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 395doc 396 | Circuit 1 Alarm Word 4 | BITMAP16 | Read | bit 2 = Fan communication alarm; bit 3 = General inverter DAE alarm | ||||
| HR | 396doc 397 | Circuit 1 Alarm Word 3 | BITMAP16 | Read | bit 5 = Suction temperature sensor fault; bit 7 = VFD communication fail; bit 8 = VFD fault | ||||
| HR | 397doc 398 | Circuit 1 Alarm Word 2 | BITMAP16 | Read | bit 0 = High motor temperature; bit 2 = High VFD amperes; bit 6 = Low discharge superheat; bit 7 = Low evaporating pressure; bit 8 = Low pressure ratio; bit 10 = Mechanical high pressure switch; bit 11 = No pressure at start; bit 12 = No pressure change at start; bit 15 = Pumpdown fail | ||||
| HR | 398doc 399 | Circuit 1 Alarm Word 1 | BITMAP16 | Read | bit 0 = Condensing pressure sensor fault; bit 1 = Discharge temperature sensor fault; bit 4 = Economizer pressure sensor fault; bit 5 = Economizer temperature sensor fault; bit 6 = Evaporating pressure sensor fault; bit 10 = Fan fault; bit 11 = Gas leakage; bit 13 = High condensing pressure; bit 14 = High discharge temperature | ||||
| HR | 399doc 400 | Circuit 2 State | UINT16 | Read | 0 = Off; 1 = Preopen; 2 = Run; 3 = Pumpdown | ||||
| HR | 420doc 421 | Circuit 2 Compressor 1 Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 421doc 422 | Circuit 2 Compressor 1 Starts | Start counter (printed range 0-9,999,999 although the register is one word). | UINT16 | Read/write | ||||
| HR | 424doc 425 | Circuit 2 Compressor 1 Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 425doc 426 | Circuit 2 Compressor 1 Percent RLA | 0-110 %. | INT16 | × 0.1 | % | Read | ||
| HR | 495doc 496 | Circuit 2 Alarm Word 4 | BITMAP16 | Read | bit 2 = Fan communication alarm; bit 3 = General inverter DAE alarm | ||||
| HR | 496doc 497 | Circuit 2 Alarm Word 3 | BITMAP16 | Read | bit 5 = Suction temperature sensor fault; bit 7 = VFD communication fail; bit 8 = VFD fault | ||||
| HR | 497doc 498 | Circuit 2 Alarm Word 2 | BITMAP16 | Read | bit 0 = High motor temperature; bit 2 = High VFD amperes; bit 6 = Low discharge superheat; bit 7 = Low evaporating pressure; bit 8 = Low pressure ratio; bit 10 = Mechanical high pressure switch; bit 11 = No pressure at start; bit 12 = No pressure change at start; bit 15 = Pumpdown fail | ||||
| HR | 498doc 499 | Circuit 2 Alarm Word 1 | BITMAP16 | Read | bit 0 = Condensing pressure sensor fault; bit 1 = Discharge temperature sensor fault; bit 4 = Economizer pressure sensor fault; bit 5 = Economizer temperature sensor fault; bit 6 = Evaporating pressure sensor fault; bit 10 = Fan fault; bit 11 = Gas leakage; bit 13 = High condensing pressure; bit 14 = High discharge temperature | ||||
| HR | 594doc 595 | Master/Slave LWT Sensor Fault | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 889doc 890 | Master Comm Error | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 890doc 891 | Slave 1 Comm Error | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 891doc 892 | Slave 2 Comm Error | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 892doc 893 | Slave 3 Comm Error | UINT16 | Read | 0 = No alarm; 1 = In alarm | ||||
| HR | 1149doc 1150 | Slave 1 Load | INT16 | × 0.1 | % | Read | |||
| HR | 1153doc 1154 | Slave 1 State | UINT16 | Read | 0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error | ||||
| HR | 1167doc 1168 | Slave 2 Load | INT16 | × 0.1 | % | Read | |||
| HR | 1171doc 1172 | Slave 2 State | UINT16 | Read | 0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error | ||||
| HR | 1185doc 1186 | Slave 3 Load | INT16 | × 0.1 | % | Read | |||
| HR | 1189doc 1190 | Slave 3 State | UINT16 | Read | 0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error |
Notes on this map
- The integration list's 'Offset' column holds 1 for enums and 0,1 for temperatures, percentages and the current limit; it is a multiplier (0,1 = tenths), so it is used as scale here.
- Temperatures are shown in °C; register 47 switches the unit system between Metric and Imperial.
- The W access letter is taken as read/write.
- Left out: the three 'UNSIGNED DOUBLE WORD' run-hour counters (102 evaporator pump 1, 323 and 423 compressor run hours) because the guide does not say which word is high.
- Left out: DHW Standby Mode (95), whose type and offset columns are not filled in properly (MV_red / DHWStandbyMode), and the Reserved registers 279, 290, 291.
- Alarm words are single 16-bit registers (the printed 0...4294967295 range is not meaningful for one word). Only bits with a named alarm are listed; the annex marks which bits apply to the SIC, SPLIT, R454C and R290 variants.
- Compressor starts registers are single words although the printed range is 0-9,999,999.
- Bit numbering in the alarm words is confirmed by the guide's worked example: Unit Alarm Word #1 = 17,408 (0100 0100 0000 0000) means bits 10 and 14 are active.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
What Modbus registers does the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) have?
This map lists 92 registers: 92 holding registers. 29 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says all variables are holding registers 'addressed 4xxxx' with the number in its Address column (1 = 40001), the same rule as Daikin Applied's other MicroTech 4 Modbus guides. Wire address = column value - 1.
What are the minimum Modbus registers to integrate the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)?
Start with HR 0 Local/Network Source (Local/Network source); HR 14 Unit Status (Unit status); HR 16 Evaporator Leaving Water Temperature (Leaving water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Unit Enable Setpoint - Network (Network enable command); HR 33 Operation Mode Setpoint - Network (Operation mode command); HR 34 Cool Setpoint - Network (Cool setpoint command); HR 36 Heat Setpoint - Network (Heat setpoint command); HR 4 Unit General Alarm (Unit general alarm).
How do I enable Modbus control of the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)?
Power off, plug the POL902 module onto the controller's extension bus, power on, check the BUS LED is steady green, then enter the service password and set the Modbus parameters under Main menu > Commissioning > Modbus.
Where is the official Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus documentation?
The source is BAS integration guide - Modbus protocol, EWAK-CZ/EWYK-CZ (ICARO) (D-EIGOC00204-26_00EN), published free by Daikin Applied at https://www.daikinapplied.uk/hubfs/portale-documentale/D_EIGOC00204_26_00EN_EWA_Y_K_CZ.pdf.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other pumps register maps
- Pump controller (wastewater lift station)
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Grundfos Dedicated Controls wastewater pit controller (CU 361 / CU 362, up to six pumps and a mixer) with a CIM 200 Modbus RTU, CIM 260 cellular or CIM 500 Modbus TCP module; functional profile 98393520 (2023-03).
Also known as: Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520 - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus - Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface
All pumps Modbus register maps →
Source: BAS integration guide - Modbus protocol, EWAK-CZ/EWYK-CZ (ICARO) · D-EIGOC00204-26_00EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.