Heat pump · Modbus register map

Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus register map

Updated 17 November 2026

Short answer

Daikin Applied EWAK-CZ / EWYK-CZ chiller and heat pump range on a MicroTech 4 controller. With a POL902 module the unit is a Modbus RTU slave and every point is a 16-bit holding register: enable, mode, cool/heat setpoints, capacity and current limits, water temperatures, DHW and collective-housing functions, VFD pump data, master/slave status and packed unit and circuit alarm words.

This page lists 92 Modbus registers for the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) — 29 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Equipment type
Heat pump
Registers
92 (29 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
ICARO control software (version not stated)
Also known as
EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204
Source document
BAS integration guide - Modbus protocol, EWAK-CZ/EWYK-CZ (ICARO) · D-EIGOC00204-26_00EN
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)

Integration in brief

Fit a POL902 module, set its address and serial settings at the keypad, then poll holding registers. Read Unit Status (col 15) and leaving water temperature (col 17); enable with col 9, choose Cool/Heat with col 34 and send setpoints to cols 35/37 in tenths of °C.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Local/Network SourceUINT16Local/Network sourceRead
HR 14Unit StatusUINT16Unit statusRead
HR 16Evaporator Leaving Water TemperatureINT16Leaving water temperatureRead
HR 12Actual CapacityINT16Actual capacityRead
HR 8Unit Enable Setpoint - NetworkUINT16Network enable commandRead/write
HR 33Operation Mode Setpoint - NetworkUINT16Operation mode commandRead/write
HR 34Cool Setpoint - NetworkINT16Cool setpoint commandRead/write
HR 36Heat Setpoint - NetworkINT16Heat setpoint commandRead/write
HR 4Unit General AlarmUINT16Unit general alarmRead

Enable Modbus control & writes

Power off, plug the POL902 module onto the controller's extension bus, power on, check the BUS LED is steady green, then enter the service password and set the Modbus parameters under Main menu > Commissioning > Modbus.

Byte order & addressing

Network setup

Watch out for

Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

92 of 92 shown
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Local/Network SourceUINT16Read0 = Local; 1 = Remote
HR1doc 2Enabled StateUINT16Read0 = Disabled; 1 = Enabled
HR3doc 4Capacity LimitedUINT16Read0 = No; 1 = Yes
HR4doc 5Unit General AlarmUINT16Read0 = No; 1 = Yes
HR7doc 8Thermoregulation StateUINT16Read0 = Off; 1 = On
HR8doc 9Unit Enable Setpoint - NetworkUINT16Read/write0 = Disable; 1 = Enable
HR9doc 10Clear Alarms - NetworkDo not leave this commanded to Clear; the guide warns a constant clear is hazardous.UINT16Read/write0 = Normal; 1 = Clear
HR10doc 11Operation ModeUINT16Read1 = Not used; 2 = Cool; 3 = Heat; 4 = Not used; 5 = Not used
HR11doc 12Active Setpoint-15 to 70 °C.INT16× 0.1°CRead
HR12doc 13Actual CapacityINT16× 0.1%Read
HR13doc 14Active Capacity Limit OutputINT16× 0.1%Read
HR14doc 15Unit StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Preshutdown; 5 = Service
HR15doc 16Evaporator Entering Water TemperatureINT16× 0.1°CRead
HR16doc 17Evaporator Leaving Water TemperatureINT16× 0.1°CRead
HR20doc 21Master/Slave Leaving Water TemperatureCommon leaving water temperature in a master/slave group.INT16× 0.1°CRead
HR23doc 24Outdoor Air TemperatureINT16× 0.1°CRead
HR30doc 31Warning CodeINT16Read0 = No alarm; 1 = External event
HR31doc 32Problem CodeINT16Read0 = No alarm; 1 = Circuit alarm
HR32doc 33Fault CodeINT16Read0 = No alarm; 1 = Unit alarm or both circuits in alarm
HR33doc 34Operation Mode Setpoint - NetworkUINT16Read/write0 = Null; 1 = Not used; 2 = Cool; 3 = Heat; 4 = Not used
HR34doc 35Cool Setpoint - Network-15 (or 4) to 28 °C depending on unit setup.INT16× 0.1°CRead/write
HR36doc 37Heat Setpoint - Network20 to 70 °C.INT16× 0.1°CRead/write
HR37doc 38Capacity Limit Setpoint - Network0-100 %.INT16× 0.1%Read/write
HR38doc 39Current Limit Setpoint - Network0-2000 A.INT16× 0.1ARead/write
HR46doc 47Unit of MeasureUINT16Read/write0 = Metric; 1 = Imperial
HR47doc 48Noise Reduction Enable SetpointUINT16Read/write0 = Off; 1 = On
HR61doc 62Defrost - Operating StateUINT16Read0 = Off; 1 = On
HR69doc 70Bivalent Operation - Enable SetpointUINT16Read/write0 = Off; 1 = On
HR70doc 71Bivalent Operation - Temperature Cut-Off-7 to 7 °C.INT16× 0.1°CRead/write
HR71doc 72Bivalent Operation - Temperature Bivalent Mode0 to 20 °C.INT16× 0.1°CRead/write
HR72doc 73Bivalent Operation - Boiler Start Delay0 to 60 min.INT16× 0.1minRead/write
HR79doc 80Collective Housing - Enable SetpointUINT16Read/write0 = Off; 1 = On
HR80doc 81Collective Housing - Tank TemperatureINT16× 0.1°CRead
HR81doc 82Collective Housing - Changeover Upper LimitChangeover lower limit to 60 °C.INT16× 0.1°CRead/write
HR82doc 83Collective Housing - Changeover Lower Limit-15 (or 4) to 60 °C.INT16× 0.1°CRead/write
HR83doc 84Collective Housing - Tank Temperature SetpointBetween the changeover lower and upper limits.INT16× 0.1°CRead/write
HR89doc 90DHW Enable SetpointUINT16Read/write0 = Off; 1 = On
HR90doc 91DHW Temperature Setpoint0 to 60 °C.INT16× 0.1°CRead/write
HR91doc 92DHW TemperatureINT16× 0.1°CRead
HR92doc 93DHW Switching Valve StateUINT16Read0 = DHW off; 1 = Switching; 2 = DHW run; 3 = Error
HR93doc 94DHW Anti Legionella CycleUINT16Read0 = Off; 1 = On
HR100doc 101Evaporator Pump 1 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR149doc 150Evaporator VFD Pump - Fixed Speed 1INT16%Read/write
HR150doc 151Evaporator VFD Pump - Fixed Speed 2INT16%Read/write
HR151doc 152Evaporator VFD Pump - Standby SpeedINT16%Read/write
HR152doc 153Evaporator VFD Pump - Actual SpeedINT16%Read
HR153doc 154Evaporator VFD Pump - Building Differential Pressure SetpointINT16kPaRead/write
HR154doc 155Evaporator VFD Pump - Unit Differential Pressure SetpointINT16kPaRead/write
HR155doc 156Evaporator VFD Pump - Building Differential PressureINT16kPaRead
HR156doc 157Evaporator VFD Pump - Unit Differential PressureINT16kPaRead
HR157doc 158Evaporator VFD Pump - Bypass Valve StateUINT16Read0 = Closed; 1 = Opened
HR158doc 159Evaporator VFD Pump - Delta Temperature SetpointWater delta-T setpoint (printed as delta °C).INT16× 0.1°CRead/write
HR159doc 160Evaporator VFD Pump - Delta TemperatureMeasured water delta-T (printed as delta °C).INT16× 0.1°CRead
HR200doc 201Siemens Controller TypeUINT16Read0 = N/A; 1 = POL687; 2 = POL638; 3 = POL687.00; 4 = POL687.70; 5 = POL688.80; 6 = POL688.80UPS; 7 = POL468
HR201doc 202Application SaveUINT16Read/write0 = Off; 1 = On
HR287doc 288External AlarmUINT16Read0 = No alarm; 1 = In alarm
HR288doc 289External EventUINT16Read0 = No event; 1 = Event
HR294doc 295Unit Alarm Word 5BITMAP16Readbit 0 = Compressor box leak detector comm fail; bit 1 = Master electrical panel leak detector comm fail; bit 2 = Slave electrical panel leak detector comm fail; bit 3 = POL925 communication fail
HR295doc 296Unit Alarm Word 4BITMAP16Readbit 0 = ACS communication fail; bit 1 = Pump communication fail; bit 2 = Domestic hot water alarm; bit 3 = Controller time not valid; bit 4 = Outdoor communication error; bit 5 = Outdoor mismatch alarm; bit 6 = Software mismatch alarm; bit 7 = Gas leakage alarm; bit 8 = Gas sensor fault; bit 9 = Tank water temperature sensor fault (TankWtSenf); bit 10 = Water overheat alarm; bit 11 = DHW anti-legionella alarm/event; bit 12 = pCOe Modbus communication error; bit 13 = Extraction fan fault; bit 14 = Ground fault relay alarm; bit 15 = Inverter DAE communication fail
HR296doc 297Unit Alarm Word 3BITMAP16Readbit 0 = Outside ambient temperature sensor fault; bit 1 = Option extension fault; bit 15 = Unit power restore
HR297doc 298Unit Alarm Word 2BITMAP16Readbit 1 = External alarm; bit 2 = External event; bit 14 = Low outside ambient temperature lockout; bit 15 = Leaving water temperature reset fault
HR298doc 299Unit Alarm Word 1BITMAP16Readbit 7 = Demand limit fault; bit 10 = Evaporator entering water temperature sensor fault; bit 11 = Evaporator flow loss; bit 12 = Evaporator freeze (unit); bit 14 = Evaporator leaving water temperature sensor fault; bit 15 = Evaporator pump 1 fault
HR299doc 300Circuit 1 StateUINT16Read0 = Off; 1 = Preopen; 2 = Run; 3 = Pumpdown
HR320doc 321Circuit 1 Compressor 1 StatusUINT16Read0 = Off; 1 = On
HR321doc 322Circuit 1 Compressor 1 StartsStart counter (printed range 0-9,999,999 although the register is one word).UINT16Read/write
HR324doc 325Circuit 1 Compressor 1 Actual CapacityINT16× 0.1%Read
HR325doc 326Circuit 1 Compressor 1 Percent RLA0-110 %.INT16× 0.1%Read
HR329doc 330Master/Slave Disconnect SetpointUINT16Read/write0 = No; 1 = Yes
HR395doc 396Circuit 1 Alarm Word 4BITMAP16Readbit 2 = Fan communication alarm; bit 3 = General inverter DAE alarm
HR396doc 397Circuit 1 Alarm Word 3BITMAP16Readbit 5 = Suction temperature sensor fault; bit 7 = VFD communication fail; bit 8 = VFD fault
HR397doc 398Circuit 1 Alarm Word 2BITMAP16Readbit 0 = High motor temperature; bit 2 = High VFD amperes; bit 6 = Low discharge superheat; bit 7 = Low evaporating pressure; bit 8 = Low pressure ratio; bit 10 = Mechanical high pressure switch; bit 11 = No pressure at start; bit 12 = No pressure change at start; bit 15 = Pumpdown fail
HR398doc 399Circuit 1 Alarm Word 1BITMAP16Readbit 0 = Condensing pressure sensor fault; bit 1 = Discharge temperature sensor fault; bit 4 = Economizer pressure sensor fault; bit 5 = Economizer temperature sensor fault; bit 6 = Evaporating pressure sensor fault; bit 10 = Fan fault; bit 11 = Gas leakage; bit 13 = High condensing pressure; bit 14 = High discharge temperature
HR399doc 400Circuit 2 StateUINT16Read0 = Off; 1 = Preopen; 2 = Run; 3 = Pumpdown
HR420doc 421Circuit 2 Compressor 1 StatusUINT16Read0 = Off; 1 = On
HR421doc 422Circuit 2 Compressor 1 StartsStart counter (printed range 0-9,999,999 although the register is one word).UINT16Read/write
HR424doc 425Circuit 2 Compressor 1 Actual CapacityINT16× 0.1%Read
HR425doc 426Circuit 2 Compressor 1 Percent RLA0-110 %.INT16× 0.1%Read
HR495doc 496Circuit 2 Alarm Word 4BITMAP16Readbit 2 = Fan communication alarm; bit 3 = General inverter DAE alarm
HR496doc 497Circuit 2 Alarm Word 3BITMAP16Readbit 5 = Suction temperature sensor fault; bit 7 = VFD communication fail; bit 8 = VFD fault
HR497doc 498Circuit 2 Alarm Word 2BITMAP16Readbit 0 = High motor temperature; bit 2 = High VFD amperes; bit 6 = Low discharge superheat; bit 7 = Low evaporating pressure; bit 8 = Low pressure ratio; bit 10 = Mechanical high pressure switch; bit 11 = No pressure at start; bit 12 = No pressure change at start; bit 15 = Pumpdown fail
HR498doc 499Circuit 2 Alarm Word 1BITMAP16Readbit 0 = Condensing pressure sensor fault; bit 1 = Discharge temperature sensor fault; bit 4 = Economizer pressure sensor fault; bit 5 = Economizer temperature sensor fault; bit 6 = Evaporating pressure sensor fault; bit 10 = Fan fault; bit 11 = Gas leakage; bit 13 = High condensing pressure; bit 14 = High discharge temperature
HR594doc 595Master/Slave LWT Sensor FaultUINT16Read0 = No alarm; 1 = In alarm
HR889doc 890Master Comm ErrorUINT16Read0 = No alarm; 1 = In alarm
HR890doc 891Slave 1 Comm ErrorUINT16Read0 = No alarm; 1 = In alarm
HR891doc 892Slave 2 Comm ErrorUINT16Read0 = No alarm; 1 = In alarm
HR892doc 893Slave 3 Comm ErrorUINT16Read0 = No alarm; 1 = In alarm
HR1149doc 1150Slave 1 LoadINT16× 0.1%Read
HR1153doc 1154Slave 1 StateUINT16Read0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error
HR1167doc 1168Slave 2 LoadINT16× 0.1%Read
HR1171doc 1172Slave 2 StateUINT16Read0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error
HR1185doc 1186Slave 3 LoadINT16× 0.1%Read
HR1189doc 1190Slave 3 StateUINT16Read0 = Stop; 1 = Run; 2 = Alarm; 3 = Communication error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)

What Modbus registers does the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) have?

This map lists 92 registers: 92 holding registers. 29 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says all variables are holding registers 'addressed 4xxxx' with the number in its Address column (1 = 40001), the same rule as Daikin Applied's other MicroTech 4 Modbus guides. Wire address = column value - 1.

What are the minimum Modbus registers to integrate the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)?

Start with HR 0 Local/Network Source (Local/Network source); HR 14 Unit Status (Unit status); HR 16 Evaporator Leaving Water Temperature (Leaving water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Unit Enable Setpoint - Network (Network enable command); HR 33 Operation Mode Setpoint - Network (Operation mode command); HR 34 Cool Setpoint - Network (Cool setpoint command); HR 36 Heat Setpoint - Network (Heat setpoint command); HR 4 Unit General Alarm (Unit general alarm).

How do I enable Modbus control of the Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)?

Power off, plug the POL902 module onto the controller's extension bus, power on, check the BUS LED is steady green, then enter the service password and set the Modbus parameters under Main menu > Commissioning > Modbus.

Where is the official Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software) Modbus documentation?

The source is BAS integration guide - Modbus protocol, EWAK-CZ/EWYK-CZ (ICARO) (D-EIGOC00204-26_00EN), published free by Daikin Applied at https://www.daikinapplied.uk/hubfs/portale-documentale/D_EIGOC00204_26_00EN_EWA_Y_K_CZ.pdf.

More Daikin Applied Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: BAS integration guide - Modbus protocol, EWAK-CZ/EWYK-CZ (ICARO) · D-EIGOC00204-26_00EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.