Chiller · Modbus register map
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) Modbus register map
Updated 19 November 2026
Water-cooled magnetic-bearing centrifugal chiller (Magnitude WMT) on the MicroTech unit controller. A plug-in BAS module set to Modbus RTU exposes 16-bit holding registers: evaporator and condenser water temperatures, refrigerant pressures and temperatures per compressor, compressor amps/volts/kW, pump status and hours, enable/mode/setpoint commands, status enums and alarm index/module registers. Values follow an English/Metric setting.
This page lists 73 Modbus registers for the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
- Equipment type
- Chiller
- Registers
- 73 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- WMT, Magnitude WMT, Daikin WMT, ED 19131
Integration notes: Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Plug in the BAS module, set BAS Network Protocol = Modbus with address, baud, parity and stop bits on the HMI, cycle power, then set Control Source = BAS. Poll with function 03; use 9 to enable, 35 for the chilled-water setpoint, 38 for capacity limit and 5/28/30 for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Chiller Local/Network | UINT16 | Local/Network state | Read |
| HR 14 | Chiller Status | UINT16 | Chiller status | Read |
| HR 16 | Evaporator Leaving Fluid Temperature | INT16 | Leaving chilled water temperature | Read |
| HR 12 | Actual Capacity | UINT16 | Actual capacity | Read |
| HR 8 | Chiller Enable Setpoint | UINT16 | Network enable command | Read/write |
| HR 34 | Cool Setpoint - Network | INT16 | Cooling setpoint command | Read/write |
| HR 37 | Capacity Limit Setpoint - Network | UINT16 | Capacity limit command | Read/write |
| HR 4 | Alarm Digital Output | UINT16 | Any alarm active | Read |
| HR 315 | Units (English/Metric) | UINT16 | English/Metric flag | Read |
| HR 27 | Warning Alarm Index | UINT16 | Active warning index | Read |
Enable Modbus control & writes
On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.
Byte order & addressing
- Printed register numbers are 1-based without the 4xxxx prefix: subtract 1 for the wire address.
- 32-bit counters are high word first (ABCD).
- Most analog values are x10 and follow the English/Metric setting; the multiplier does not change.
- Each alarm class has four registers: index (28-30) plus module type, module ID and payload (2001-2009).
Network setup
- Address 0-247 (default 1); baud 9600/19200/38400/57600/76800 (default 19200); parity Even/Odd/None (default None); stop bits 1 or 2 (default 1).
- RS-485 lands on the module's 'J3 Disp' 4-pin connector, using only + and -. End-of-line and bias resistors are field-supplied.
- The same module also does BACnet IP and MS/TP; one protocol is active, chosen by BAS Network Protocol (default None/LON).
Watch out for
- Nothing answers until BAS Module Connected = Yes and the panel has been power-cycled.
- Control Source = Local or Remote Switch silently ignores network commands; register 1 shows Local/Remote.
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Chiller Local/Network | Network commands are ignored while Local. | UINT16 | Read | 0 = Remote; 1 = Local | |||
| HR | 1doc 2 | Chiller Enable Output | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| HR | 2doc 3 | Run Enabled | UINT16 | Read | 0 = Off; 1 = Run allowed | ||||
| HR | 3doc 4 | Chiller Capacity Limited | UINT16 | Read | 0 = Not limited; 1 = Limited | ||||
| HR | 4doc 5 | Alarm Digital Output | Poll this for any active alarm. | UINT16 | Read | 0 = No alarm; 1 = Alarm | |||
| HR | 5doc 6 | Evaporator Flow Switch Status | UINT16 | Read | 0 = No flow; 1 = Flow | ||||
| HR | 6doc 7 | Condenser Flow Switch Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 7doc 8 | Chiller On/Off | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Chiller Enable Setpoint | Network enable; used only when Control Source = BAS. | UINT16 | Read/write | 0 = Disable; 1 = Enable; 2 = Null | |||
| HR | 9doc 10 | Clear Alarm - Network | Write 1 to clear; returns to Normal. | UINT16 | Read/write | 0 = Normal; 1 = Clear alarms; 2 = Null | |||
| HR | 10doc 11 | Chiller Mode Output | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery | ||||
| HR | 11doc 12 | Active Setpoint | Leaving water setpoint in use, °F x10. | INT16 | × 0.1 | °F | Read | ||
| HR | 12doc 13 | Actual Capacity | Percent of maximum capacity, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 13doc 14 | Active Capacity Limit Output | Lowest of all active capacity limits, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 14doc 15 | Chiller Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 16doc 17 | Evaporator Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 18doc 19 | Condenser Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 19doc 20 | Condenser Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 27doc 28 | Warning Alarm Index | Highest active warning index; 0 = none. | UINT16 | Read | ||||
| HR | 29doc 30 | Fault Alarm Index | Highest active fault index; 0 = none. | UINT16 | Read | ||||
| HR | 33doc 34 | Chiller Mode Setpoint - Network | Default Cool. Used only when Control Source = BAS. | UINT16 | Read/write | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery | |||
| HR | 34doc 35 | Cool Setpoint - Network | WMT 36.0-80.0 °F x10; default 44.0 °F. Used only when Control Source = BAS. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 37doc 38 | Capacity Limit Setpoint - Network | 0-100 % x10; default 100 %. Used only when Control Source = BAS. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 39 | Circuit 1 Condenser Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 39doc 40 | Circuit 1 Condenser Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 40doc 41 | Circuit 1 Evaporator Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 41doc 42 | Circuit 1 Evaporator Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 42doc 43 | Circuit 2 Condenser Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 43doc 44 | Circuit 2 Condenser Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 44doc 45 | Circuit 2 Evaporator Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 45doc 46 | Circuit 2 Evaporator Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 62doc 63 | Circuit 1 Compressor 1 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 63doc 64 | Circuit 1 Compressor 1 Suction Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 64doc 65 | Circuit 1 Compressor 1 Suction Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 65doc 66 | Circuit 1 Compressor 1 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 66doc 67 | Circuit 1 Compressor 1 Discharge Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 67doc 68 | Circuit 1 Compressor 1 Discharge Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 68doc 69 | Circuit 1 Compressor 1 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 69doc 70 | Circuit 1 Compressor 1 Current | Average motor current, 0-10000 A. | UINT16 | A | Read | |||
| HR | 70doc 71 | Circuit 1 Compressor 1 Voltage | Average motor voltage, 0-15000 VAC. | UINT16 | V | Read | |||
| HR | 71doc 72 | Circuit 1 Compressor 1 Power | Motor power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 72doc 73 | Circuit 1 Compressor 1 Starts | 0-65535. | UINT16 | Read | ||||
| HR | 73doc 74-75 | Circuit 1 Compressor 1 Run Hours | 0-999,999 h; high word in 74. | UINT32 | ABCD | h | Read | ||
| HR | 75doc 76 | Circuit 1 Compressor 2 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 76doc 77 | Circuit 1 Compressor 2 Suction Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 77doc 78 | Circuit 1 Compressor 2 Suction Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 78doc 79 | Circuit 1 Compressor 2 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 79doc 80 | Circuit 1 Compressor 2 Discharge Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 80doc 81 | Circuit 1 Compressor 2 Discharge Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 81doc 82 | Circuit 1 Compressor 2 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 82doc 83 | Circuit 1 Compressor 2 Current | Average motor current, 0-10000 A. | UINT16 | A | Read | |||
| HR | 83doc 84 | Circuit 1 Compressor 2 Voltage | Average motor voltage, 0-15000 VAC. | UINT16 | V | Read | |||
| HR | 84doc 85 | Circuit 1 Compressor 2 Power | Motor power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 85doc 86 | Circuit 1 Compressor 2 Starts | 0-65535. | UINT16 | Read | ||||
| HR | 86doc 87-88 | Circuit 1 Compressor 2 Run Hours | 0-999,999 h; high word in 87. | UINT32 | ABCD | h | Read | ||
| HR | 296doc 297-298 | Condenser Pump 1 Run Hours | 0-999,999 h; high word in 297. | UINT32 | ABCD | h | Read | ||
| HR | 298doc 299 | Condenser Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 299doc 300-301 | Condenser Pump 2 Run Hours | 0-999,999 h; high word in 300. | UINT32 | ABCD | h | Read | ||
| HR | 301doc 302 | Condenser Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 302doc 303-304 | Evaporator Pump 1 Run Hours | 0-999,999 h; high word in 303. | UINT32 | ABCD | h | Read | ||
| HR | 304doc 305 | Evaporator Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 305doc 306-307 | Evaporator Pump 2 Run Hours | 0-999,999 h; high word in 306. | UINT32 | ABCD | h | Read | ||
| HR | 307doc 308 | Evaporator Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 315doc 316 | Units (English/Metric) | Unit system for network values; default English. Set at the HMI. | UINT16 | Read | 0 = English; 1 = Metric | |||
| HR | 1605doc 1606 | Refrigerant Type | UINT16 | Read | 1 = R22; 2 = R134a; 3 = R407c; 4 = R410a; 5 = R32; 6 = R454C; 7 = R513A; 8 = R515B; 9 = R1233zd(E); 10 = R1234ze(E) | ||||
| HR | 1983doc 1984 | Circuit 1 Liquid Line Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 2000doc 2001 | Warning Alarm Module Type | Module type behind the active warning. | UINT16 | Read | 0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC | |||
| HR | 2001doc 2002 | Warning Alarm Module ID | Which module (compressor, fan, VFD number) is in warning. | UINT16 | Read | ||||
| HR | 2002doc 2003 | Warning Alarm Module Payload | Hardware-specific code (VFD, fan) for the warning, where used. | UINT16 | Read | ||||
| HR | 2006doc 2007 | Fault Alarm Module Type | Module type behind the active fault. | UINT16 | Read | 0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC | |||
| HR | 2007doc 2008 | Fault Alarm Module ID | Which module is in fault. | UINT16 | Read | ||||
| HR | 2008doc 2009 | Fault Alarm Module Payload | Hardware-specific code for the fault, where used. | UINT16 | Read |
Notes on this map
- Network setup and parameter ranges come from the companion manual IM 1283-1, BACnet and Modbus Chiller Unit Controller (Mar 2024), pp. 36-39: https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/IM1283-1.pdf/
- Two-register counters: the document's worked example (99900 = 0x0001863C stored as 74 = 0x0001, 75 = 0x863C) puts the high word first, so they are ABCD.
- The document never defines 'x 10'. Its ranges and defaults ('Default: 100% x 10', '-40-230°F x 10') only make sense as raw = value x 10, so those registers use scale 0.1.
- Signedness is not stated. Temperatures and refrigerant pressures are INT16 because their published ranges go negative (the pressure rows include sub-atmospheric R-1233zd(E) ranges); counters, percentages and enums are UINT16.
- Units follow the HMI 'BAS Measurement Units' setting, readable at register 316 (English default). Units shown are English (°F, psi); Metric uses °C and kPa with the same multiplier.
- Units (316) shows 'RW Holding Register' in the data-type column but 'R' in the access column; it is listed read-only (change it at the HMI).
- Compressor points are listed for the Circuit 1 Compressor 1 and Compressor 2 slots that Table 12 gives for current, %RLA, power, voltage and pressures; run hours and starts use the same two slots.
- Left out: evaporator and condenser flow rates (18, 21). They are printed as 0-65,535 GPM / 0-4134.6 L/S with no multiplier, so the Metric scaling is not settled.
- Alarm index meanings (pp. 32-33) are not reproduced; the module-type value list is the same for all classes.
- ED 19131 is shared with AGZ-F and WMC-E chillers. Only points that Table 5 marks in the WMT column are listed.
- Left out: points Table 5 does not mark for WMT (problem-class alarm registers 29 and 2004-2006, heat recovery temperatures, heat setpoint, ice setpoint, outdoor air temperature).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
What Modbus registers does the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) have?
This map lists 73 registers: 73 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 19131 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: 40002 is sent as 0001. Wire address = printed number - 1.
What byte order does the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)?
Start with HR 0 Chiller Local/Network (Local/Network state); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 34 Cool Setpoint - Network (Cooling setpoint command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 315 Units (English/Metric) (English/Metric flag); HR 27 Warning Alarm Index (Active warning index).
How do I enable Modbus control of the Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)?
On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.
Where is the official Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller) Modbus documentation?
The source is MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) (ED 19131-1), revision 2026-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019131-1.pdf/.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001 - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM
All chillers & heat pumps Modbus register maps →
Source: MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) · ED 19131-1 · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.