Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) Modbus register map

Updated 25 October 2026

Short answer

Current-generation air-cooled scroll chiller with two circuits and up to three scroll compressors per circuit. Its BAS module (BACnet IP, BACnet MS/TP or Modbus RTU) exposes everything as 16-bit holding registers: water and refrigerant temperatures and pressures, enable/mode/setpoint/capacity-limit commands, status enums, alarm index and module registers, and run-hour/start counters.

This page lists 63 Modbus registers for the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Equipment type
Chiller
Registers
63 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Firmware
Chiller application 1.2.0, HMI 1.12.0 (document baseline)
Also known as
AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131
Source document
MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) · ED 19131-1 · rev. 2026-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)

Integration in brief

Plug in the BAS module, set BAS Network Protocol = Modbus with address, baud, parity and stop bits on the HMI, cycle power, then set Control Source = BAS. Poll with function 03; use 9 to enable, 35 for the chilled-water setpoint, 38 for capacity limit and 5/28-30 for alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Chiller Local/NetworkUINT16Local/Network stateRead
HR 14Chiller StatusUINT16Chiller statusRead
HR 16Evaporator Leaving Fluid TemperatureINT16Leaving chilled water temperatureRead
HR 12Actual CapacityUINT16Actual capacityRead
HR 8Chiller Enable SetpointUINT16Network enable commandRead/write
HR 34Cool Setpoint - NetworkINT16Cooling setpoint commandRead/write
HR 37Capacity Limit Setpoint - NetworkUINT16Capacity limit commandRead/write
HR 4Alarm Digital OutputUINT16Any alarm activeRead
HR 29Fault Alarm IndexUINT16Active fault indexRead
HR 315Units (English/Metric)UINT16English/Metric flagRead

Enable Modbus control & writes

On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.

Byte order & addressing

Network setup

Watch out for

Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

63 of 63 shown
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Chiller Local/NetworkNetwork commands are ignored while Local.UINT16Read0 = Remote; 1 = Local
HR1doc 2Chiller Enable OutputUINT16Read0 = Disable; 1 = Enable
HR2doc 3Run EnabledUINT16Read0 = Off; 1 = Run allowed
HR3doc 4Chiller Capacity LimitedUINT16Read0 = Not limited; 1 = Limited
HR4doc 5Alarm Digital OutputPoll this for any active alarm.UINT16Read0 = No alarm; 1 = Alarm
HR5doc 6Evaporator Flow Switch StatusUINT16Read0 = No flow; 1 = Flow
HR7doc 8Chiller On/OffUINT16Read0 = Off; 1 = On
HR8doc 9Chiller Enable SetpointNetwork enable; used only when Control Source = BAS.UINT16Read/write0 = Disable; 1 = Enable; 2 = Null
HR9doc 10Clear Alarm - NetworkWrite 1 to clear; returns to Normal.UINT16Read/write0 = Normal; 1 = Clear alarms; 2 = Null
HR10doc 11Chiller Mode OutputUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery
HR11doc 12Active SetpointLeaving water setpoint in use, °F x10.INT16× 0.1°FRead
HR12doc 13Actual CapacityPercent of maximum capacity, x10.UINT16× 0.1%Read
HR13doc 14Active Capacity Limit OutputLowest of all active capacity limits, x10.UINT16× 0.1%Read
HR14doc 15Chiller StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service
HR15doc 16Evaporator Entering Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR16doc 17Evaporator Leaving Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR23doc 24Outdoor Air Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR27doc 28Warning Alarm IndexHighest active warning index; 0 = none.UINT16Read
HR28doc 29Problem Alarm IndexHighest active problem index; 0 = none.UINT16Read
HR29doc 30Fault Alarm IndexHighest active fault index; 0 = none.UINT16Read
HR33doc 34Chiller Mode Setpoint - NetworkDefault Cool. Used only when Control Source = BAS.UINT16Read/write1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery
HR34doc 35Cool Setpoint - NetworkAGZ-F 14.9-70.0 °F x10 (39.9 °F min without glycol); default 44.0 °F.INT16× 0.1°FRead/write
HR35doc 36Ice Setpoint - NetworkAGZ-F 14.9-39.9 °F x10; default 24.98 °F.INT16× 0.1°FRead/write
HR37doc 38Capacity Limit Setpoint - Network0-100 % x10; default 100 %. Used only when Control Source = BAS.UINT16× 0.1%Read/write
HR38doc 39Circuit 1 Condenser Refrigerant Pressurepsi x10 (kPa x10 in Metric); R-32 range 0-700 psi. Prefer English units (see notes).INT16× 0.1psiRead
HR39doc 40Circuit 1 Condenser Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR40doc 41Circuit 1 Evaporator Refrigerant Pressurepsi x10 (kPa x10 in Metric); R-32 range 0-350 psi.INT16× 0.1psiRead
HR41doc 42Circuit 1 Evaporator Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR42doc 43Circuit 2 Condenser Refrigerant Pressurepsi x10 (kPa x10 in Metric); R-32 range 0-700 psi. Prefer English units (see notes).INT16× 0.1psiRead
HR43doc 44Circuit 2 Condenser Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR44doc 45Circuit 2 Evaporator Refrigerant Pressurepsi x10 (kPa x10 in Metric); R-32 range 0-350 psi.INT16× 0.1psiRead
HR45doc 46Circuit 2 Evaporator Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR67doc 68Circuit 1 Discharge Refrigerant TemperatureListed as Circuit 1 Compressor 1; AGZ-F has one sensor per circuit. °F x10.INT16× 0.1°FRead
HR72doc 73Circuit 1 Compressor 1 Starts0-65535.UINT16Read
HR73doc 74-75Circuit 1 Compressor 1 Run Hours0-999,999 h; high word in 74.UINT32ABCDhRead
HR85doc 86Circuit 1 Compressor 2 Starts0-65535.UINT16Read
HR86doc 87-88Circuit 1 Compressor 2 Run Hours0-999,999 h; high word in 87.UINT32ABCDhRead
HR98doc 99Circuit 1 Compressor 3 Starts0-65535.UINT16Read
HR99doc 100-101Circuit 1 Compressor 3 Run Hours0-999,999 h; high word in 100.UINT32ABCDhRead
HR106doc 107Circuit 2 Discharge Refrigerant TemperatureListed as Circuit 2 Compressor 1; AGZ-F has one sensor per circuit. °F x10.INT16× 0.1°FRead
HR111doc 112Circuit 2 Compressor 1 Starts0-65535.UINT16Read
HR112doc 113-114Circuit 2 Compressor 1 Run Hours0-999,999 h; high word in 113.UINT32ABCDhRead
HR124doc 125Circuit 2 Compressor 2 Starts0-65535.UINT16Read
HR125doc 126-127Circuit 2 Compressor 2 Run Hours0-999,999 h; high word in 126.UINT32ABCDhRead
HR137doc 138Circuit 2 Compressor 3 Starts0-65535.UINT16Read
HR138doc 139-140Circuit 2 Compressor 3 Run Hours0-999,999 h; high word in 139.UINT32ABCDhRead
HR302doc 303-304Evaporator Pump 1 Run Hours0-999,999 h; high word in 303.UINT32ABCDhRead
HR304doc 305Evaporator Pump 1 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR305doc 306-307Evaporator Pump 2 Run Hours0-999,999 h; high word in 306.UINT32ABCDhRead
HR307doc 308Evaporator Pump 2 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR315doc 316Units (English/Metric)Unit system for network values; default English. Set at the HMI.UINT16Read0 = English; 1 = Metric
HR1605doc 1606Refrigerant TypeUINT16Read1 = R22; 2 = R134a; 3 = R407c; 4 = R410a; 5 = R32; 6 = R454C; 7 = R513A; 8 = R515B; 9 = R1233zd(E); 10 = R1234ze(E)
HR1973doc 1974Circuit 2 Suction Refrigerant TemperaturePer-circuit suction sensor, °F x10.INT16× 0.1°FRead
HR1989doc 1990Circuit 1 Suction Refrigerant TemperaturePer-circuit suction sensor, °F x10.INT16× 0.1°FRead
HR2000doc 2001Warning Alarm Module TypeModule type behind the active warning.UINT16Read0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC
HR2001doc 2002Warning Alarm Module IDWhich module (compressor, fan, VFD number) is in warning.UINT16Read
HR2002doc 2003Warning Alarm Module PayloadHardware-specific code (VFD, fan) for the warning, where used.UINT16Read
HR2003doc 2004Problem Alarm Module TypeModule type behind the active problem alarm.UINT16Read0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC
HR2004doc 2005Problem Alarm Module IDWhich module is in problem alarm.UINT16Read
HR2005doc 2006Problem Alarm Module PayloadHardware-specific code for the problem alarm, where used.UINT16Read
HR2006doc 2007Fault Alarm Module TypeModule type behind the active fault.UINT16Read0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC
HR2007doc 2008Fault Alarm Module IDWhich module is in fault.UINT16Read
HR2008doc 2009Fault Alarm Module PayloadHardware-specific code for the fault, where used.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)

What Modbus registers does the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) have?

This map lists 63 registers: 63 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 19131 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: 40002 is sent as 0001. Wire address = printed number - 1.

What byte order does the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)?

Start with HR 0 Chiller Local/Network (Local/Network state); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 34 Cool Setpoint - Network (Cooling setpoint command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 29 Fault Alarm Index (Active fault index); HR 315 Units (English/Metric) (English/Metric flag).

How do I enable Modbus control of the Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)?

On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.

Where is the official Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller) Modbus documentation?

The source is MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) (ED 19131-1), revision 2026-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019131-1.pdf/.

More Daikin Applied Modbus register maps

Source: MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) · ED 19131-1 · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.