  4. Pathfinder AWV air-cooled screw chiller (MicroTech controller)

Chiller · Modbus register map

Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) Modbus register map

Updated 25 October 2026

Short answer

Air-cooled screw chiller with two refrigerant circuits, each with a variable-speed screw compressor. The MicroTech controller speaks Modbus RTU through a plug-on RS-485 module, and every point is a 16-bit holding register: water and refrigerant temperatures, pressures, compressor amps/volts/kW, enable and setpoint commands, status enums, alarm indexes and run-hour counters. Values follow an English/Metric setting.

This page lists 96 Modbus registers for the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Equipment type
Chiller
Registers
96 (17 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
AWV application software 263220504 (document baseline); individual points need 263220112 / 263220502 / 263220504 / 263220505 or newer as marked.
Also known as
AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121
Source document
MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) · ED 15121-13 · rev. 2026-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)

Integration in brief

Fit the Modbus module, set address and baud at the keypad (Modbus Setup), apply so the controller reboots, then poll holding registers with function 03. Read 1 (Local/Remote) and 316 (Units) first; use 9 to enable, 35 for the chilled-water setpoint, 38 for capacity limit, and 5 plus 28-33 for alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Chiller Local/RemoteUINT16Local/Remote - network commands only work in RemoteRead
HR 14Chiller StatusUINT16Chiller statusRead
HR 16Evaporator Leaving Fluid TemperatureINT16Leaving chilled water temperatureRead
HR 12Actual CapacityUINT16Actual capacityRead
HR 8Chiller Enable SetpointUINT16Network enable commandRead/write
HR 34Cool Setpoint - NetworkINT16Cooling setpoint commandRead/write
HR 37Capacity Limit Setpoint - NetworkUINT16Capacity limit commandRead/write
HR 4Alarm Digital OutputUINT16Any alarm activeRead
HR 29Fault Alarm IndexUINT16Active fault indexRead
HR 315Units (English/Metric)UINT16English/Metric flagRead/write

Enable Modbus control & writes

A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.

Communication loss & watchdog

The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.

Byte order & addressing

Network setup

Watch out for

Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

96 of 96 shown
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Chiller Local/RemoteSet at the keypad only; Local makes the controller ignore network commands.UINT16Read0 = Remote; 1 = Local
HR1doc 2Chiller Enable OutputUINT16Read0 = Disable; 1 = Enable
HR2doc 3Run EnabledChiller may start if operating conditions allow.UINT16Read0 = Off; 1 = Run allowed
HR3doc 4Chiller Capacity LimitedUINT16Read0 = Not limited; 1 = Limited
HR4doc 5Alarm Digital OutputPoll this for any active alarm.UINT16Read0 = No alarm; 1 = Alarm
HR5doc 6Evaporator Flow Switch StatusUINT16Read0 = No flow; 1 = Flow
HR7doc 8Chiller On/OffUINT16Read0 = Off; 1 = On
HR8doc 9Chiller Enable SetpointNetwork enable; Null behaves as Disable.UINT16Read/write0 = Disable; 1 = Enable; 2 = Null
HR9doc 10Clear Alarms - NetworkSome lockout alarms cannot be cleared from the network.UINT16Read/write0 = Normal; 1 = Clear alarms; 2 = Null
HR10doc 11Chiller Mode OutputUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery; 5 = Defrost
HR11doc 12Active SetpointLeaving water setpoint in use (Cool or Ice), °F x10.INT16× 0.1°FRead
HR12doc 13Actual CapacityPercent of maximum capacity, x10.UINT16× 0.1%Read
HR13doc 14Active Capacity Limit OutputLowest of all active capacity limits, x10.UINT16× 0.1%Read
HR14doc 15Chiller StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service
HR15doc 16Evaporator Entering Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR16doc 17Evaporator Leaving Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR23doc 24Outdoor Air Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR26doc 27Total KilowattsTotal chiller power, 0-3500 kW.UINT16kWRead
HR27doc 28Warning Alarm IndexIndex of the active warning (highest index); 0 = none.UINT16Read
HR28doc 29Problem Alarm IndexIndex of the active problem alarm (highest index); 0 = none.UINT16Read
HR29doc 30Fault Alarm IndexIndex of the active fault (highest index); 0 = none.UINT16Read
HR30doc 31Warning Alarm CodeEncoded code of the active warning; 0 = none.UINT16Read
HR31doc 32Problem Alarm CodeEncoded code of the active problem alarm; 0 = none.UINT16Read
HR32doc 33Fault Alarm CodeEncoded code of the active fault; 0 = none.UINT16Read
HR33doc 34Chiller Mode Setpoint - NetworkNull runs Cool. Needs Available Modes other than Cool Only.UINT16Read/write0 = Null; 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery
HR34doc 35Cool Setpoint - NetworkChilled fluid setpoint 24.98-60.08 °F x10; default 43.88 °F.INT16× 0.1°FRead/write
HR35doc 36Ice Setpoint - NetworkAWV range 17.6-39.2 °F x10; default 24.98 °F.INT16× 0.1°FRead/write
HR37doc 38Capacity Limit Setpoint - NetworkNetwork capacity limit 0-100 % x10; default 100 %.UINT16× 0.1%Read/write
HR38doc 39Circuit 1 Condenser Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR39doc 40Circuit 1 Condenser Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR40doc 41Circuit 1 Evaporator Refrigerant Pressurepsi x10 (kPa x10 in Metric); signed range.INT16× 0.1psiRead
HR42doc 43Circuit 2 Condenser Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR43doc 44Circuit 2 Condenser Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR44doc 45Circuit 2 Evaporator Refrigerant Pressurepsi x10 (kPa x10 in Metric); signed range.INT16× 0.1psiRead
HR45doc 46Circuit 2 Evaporator Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR64doc 65Circuit 1 Compressor 1 Suction Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR67doc 68Circuit 1 Compressor 1 Discharge Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR68doc 69Circuit 1 Compressor 1 Percent RLAMotor load as percent of rated load amps, 0-100 %.UINT16%Read
HR69doc 70Circuit 1 Compressor 1 CurrentAverage motor current, 0-10000 A.UINT16ARead
HR70doc 71Circuit 1 Compressor 1 VoltageAverage motor voltage, 0-15000 VAC. Not on Turboscrew compressors.UINT16VRead
HR71doc 72Circuit 1 Compressor 1 PowerMotor power, 0-3500 kW.UINT16kWRead
HR72doc 73Circuit 1 Compressor 1 StartsStart counter, 0-65535.UINT16Read
HR73doc 74-75Circuit 1 Compressor 1 Run Hours0-999,999 h; low word in 74.UINT32CDABhRead/write
HR103doc 104Circuit 2 Compressor 1 Suction Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR106doc 107Circuit 2 Compressor 1 Discharge Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR107doc 108Circuit 2 Compressor 1 Percent RLAMotor load as percent of rated load amps.UINT16%Read
HR108doc 109Circuit 2 Compressor 1 CurrentAverage motor current, 0-10000 A.UINT16ARead
HR109doc 110Circuit 2 Compressor 1 VoltageAverage motor voltage, 0-15000 VAC. Not on Turboscrew compressors.UINT16VRead
HR110doc 111Circuit 2 Compressor 1 PowerMotor power, 0-3500 kW.UINT16kWRead
HR111doc 112Circuit 2 Compressor 1 StartsStart counter, 0-65535.UINT16Read
HR112doc 113-114Circuit 2 Compressor 1 Run Hours0-999,999 h; low word in 113.UINT32CDABhRead/write
HR169doc 170Circuit 1 Compressor VFD TemperatureVFD heat-sink temperature, °F x10. AWV app 263220502+.INT16× 0.1°FRead
HR170doc 171Circuit 2 Compressor VFD TemperatureVFD heat-sink temperature, °F x10. AWV app 263220502+.INT16× 0.1°FRead
HR302doc 303-304Evaporator Pump 1 Run Hours0-999,999 h; low word in 303.UINT32CDABhRead
HR304doc 305Evaporator Pump 1 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR305doc 306-307Evaporator Pump 2 Run Hours0-999,999 h; low word in 306.UINT32CDABhRead
HR307doc 308Evaporator Pump 2 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR308doc 309Clock YearController clock; write to sync with the BAS.UINT16Read/write
HR309doc 310Clock Month1-12.UINT16Read/write
HR310doc 311Clock DateDay of month, 1-31.UINT16Read/write
HR311doc 312Clock Day of WeekCalculated by the controller.UINT16Read0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday
HR312doc 313Clock Hour0-23.UINT16Read/write
HR313doc 314Clock Minute0-59.UINT16Read/write
HR314doc 315Clock Second0-59.UINT16Read/write
HR315doc 316Units (English/Metric)Unit system for all network values; default English.UINT16Read/write0 = English; 1 = Metric
HR316doc 317Chiller ModelUINT16Read0 = Centrifugal; 1 = Water cooled; 2 = Air cooled; 3 = Heat pump; 9 = Other
HR317doc 318-327Chiller LocationUp to 20 ASCII characters, two per register, first character in the high byte.STRING[20]Read/write
HR333doc 334-338Application Software VersionUp to 10 ASCII characters, two per register, first character in the high byte.STRING[10]Read
HR399doc 400Waterside Economizer Entering Water Temperature°F x10. Waterside economizer option; AWV app 263220502+.INT16× 0.1°FRead
HR839doc 840Control Panel Internal Temperature°F x10. AWV app 263220504+.INT16× 0.1°FRead
HR840doc 841Power Panel Internal Temperature°F x10. AWV app 263220504+.INT16× 0.1°FRead
HR841doc 842Harmonic Filter Internal Temperature°F x10. AWV app 263220504+.INT16× 0.1°FRead
HR842doc 843Circuit 1 Liquid Line Approach Temperature0-50 °F x10. AWV app 263220504+.UINT16× 0.1°FRead
HR843doc 844Circuit 2 Liquid Line Approach Temperature0-50 °F x10. AWV app 263220504+.UINT16× 0.1°FRead
HR844doc 845Main Power LossAWV app 263220505+.UINT16Read0 = Normal; 1 = Power loss
HR845doc 846Circuit 1 Subcooling Temperature°F x10. AWV app 263220505+.INT16× 0.1°FRead
HR846doc 847Circuit 2 Subcooling Temperature°F x10. AWV app 263220505+.INT16× 0.1°FRead
HR969doc 970Circuit 1 Compressor 1 UnavailableAWV app 263220112+.UINT16Read0 = Available; 1 = Unavailable
HR971doc 972Circuit 2 Compressor 1 UnavailableAWV app 263220112+.UINT16Read0 = Available; 1 = Unavailable
HR1099doc 1100Evaporator Recirculate Time Remaining0-300 s. AWV app 263220502+.UINT16sRead
HR1100doc 1101Circuit 1 Cycle Time Remaining0-3600 s. AWV app 263220502+.UINT16sRead
HR1101doc 1102Circuit 2 Cycle Time Remaining0-3600 s. AWV app 263220502+.UINT16sRead
HR1808doc 1809Circuit 2 Compressor 1 Oil Feed Pressurepsi x10 (kPa x10 in Metric); signed range.INT16× 0.1psiRead
HR1848doc 1849Circuit 1 Compressor 1 Oil Feed Pressurepsi x10 (kPa x10 in Metric); signed range.INT16× 0.1psiRead
HR1853doc 1854Waterside Economizer StateCurrent cooling mode. Waterside economizer option only.UINT16Read0 = Off; 1 = Mech; 2 = Hybrid; 3 = WsEcon
HR1854doc 1855Waterside Economizer Enable SetpointUsed only when Local/Remote = Remote. Option only.UINT16Read/write0 = Disable; 1 = Enable
HR1898doc 1899Circuit 1 Evaporator Superheat Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1899doc 1900Circuit 2 Evaporator Superheat Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1910doc 1911Circuit 1 Discharge Superheat Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1911doc 1912Circuit 2 Discharge Superheat Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1967doc 1968Circuit 2 Liquid Line Refrigerant Temperature°F x10. AWV app 263220502+.INT16× 0.1°FRead
HR1970doc 1971Circuit 2 Condenser Approach Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1971doc 1972Circuit 2 Evaporator Approach Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1983doc 1984Circuit 1 Liquid Line Refrigerant Temperature°F x10. AWV app 263220502+.INT16× 0.1°FRead
HR1986doc 1987Circuit 1 Condenser Approach Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead
HR1987doc 1988Circuit 1 Evaporator Approach Temperature0-50 °F x10. AWV app 263220502+.UINT16× 0.1°FRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)

What Modbus registers does the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) have?

This map lists 96 registers: 96 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 15121 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: register 40003 goes out as 0002 in the PDU. Wire address = printed number - 1.

What byte order does the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)?

Start with HR 0 Chiller Local/Remote (Local/Remote - network commands only work in Remote); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 34 Cool Setpoint - Network (Cooling setpoint command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 29 Fault Alarm Index (Active fault index); HR 315 Units (English/Metric) (English/Metric flag).

How do I enable Modbus control of the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)?

A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.

What happens when the Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) loses Modbus communication?

The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.

Where is the official Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller) Modbus documentation?

The source is MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) (ED 15121-13), revision 2026-09, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15121-13.pdf/.

More Daikin Applied Modbus register maps

Source: MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) · ED 15121-13 · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.