Rooftop unit · Modbus register map
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) Modbus register map
Updated 16 October 2026
Packaged rooftop unit whose MicroTech 4 controller speaks Modbus RTU through a plug-on RS-485 module. Everything is a 16-bit holding register: air and refrigerant temperatures, pressures, capacities, setpoints, occupancy and application-mode commands, network enables, status enums and alarm numbers. Values use English or Metric units per a controller setting.
This page lists 112 Modbus registers for the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- Rebel / Rebel Applied rooftop (MicroTech 4 controller)
- Equipment type
- Rooftop unit
- Registers
- 112 (35 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2
Integration notes: Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Set address/baud/parity on the controller HMI (BMS Communication / Modbus Set-Up), apply and cycle power, then read holding registers with function 03. Check register 261 first to know if values are English or Metric, and use 251/252 for occupancy, 249 for application mode and 138-141 for setpoints.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Discharge air temperature | INT16 | Discharge air temperature | Read |
| HR 137 | Occupied cooling setpoint | INT16 | Occupied cooling setpoint | Read/write |
| HR 139 | Occupied heating setpoint | INT16 | Occupied heating setpoint | Read/write |
| HR 244 | Unit status | UINT16 | Unit status | Read |
| HR 248 | Application mode | UINT16 | Application mode | Read/write |
| HR 250 | Occupancy mode (network) | UINT16 | Network occupancy mode | Read/write |
| HR 157 | Alarm value | UINT16 | Highest active alarm | Read |
| HR 263 | Unit local/network control | UINT16 | Local/network control | Read |
| HR 260 | Units of measurement | UINT16 | English/Metric units flag | Read |
Enable Modbus control & writes
A Modbus RTU communication module must be fitted. Network address and baud are set only from the HMI (password 2526, BMS Communication / Modbus Set-Up), then 'Apply Changes' and cycle power. Application mode has no effect unless the HMI Control Mode is Auto. Register 264 (Unit Local/Network Control) must read Network (0), set at the HMI, for most network writes to apply.
Communication loss & watchdog
The module's Com LED Timeout (0-3600 s, default 3 s) only turns the bus LED red when the client stops polling; no control fallback on comms loss is documented. Network temperature/RH inputs fall back to local sensors when the network value is unreliable.
Byte order & addressing
- Printed register numbers are 1-based without the 4xxxx prefix: subtract 1 for the wire address.
- All values follow the English/Metric setting (register 261); the multiplier stays the same.
- Writable registers are shown as 'W' in the document but are readable too.
- Enable registers 162/164/166 use -1 as 'not network-controlled'.
Network setup
- Address 1-247 (default 1), baud 4800/9600/19200/38400 (default 38400), parity Even/Odd/None (default None), two stop bits Yes/No (default Yes).
- Load resistor (termination) is a software setting on the module (default No); set Yes at the ends of the segment.
- Response delay default 5 ms; increase only for slow clients.
- Network parameters revert to defaults after a controller software field upgrade.
Watch out for
- Writing Emergency Override (register 255) = Off stops the unit until it is written back to Normal.
- Current State (252) only acts when Occupancy Mode (251) is Auto.
- Many points exist only with options (power monitoring, refrigerant monitoring, energy recovery, expansion module).
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Discharge air temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 1doc 2 | Return air temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 2doc 3 | Effective space temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 3doc 4 | Space temperature sensor 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 4doc 5 | Space temperature sensor 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 5doc 6 | Space temperature sensor 3 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 6doc 7 | Entering fan / leaving coil temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 7doc 8 | Effective outdoor air temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 12doc 13 | Space CO2 | ppm x10. | UINT16 | × 0.1 | ppm | Read | ||
| HR | 13doc 14 | Control temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 15doc 16 | Energy recovery leaving wheel temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 16doc 17 | Energy recovery entering wheel temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 18doc 19 | Supply fan duct static pressure | in. w.c. x10 (Pa x10 in Metric). | UINT16 | × 0.1 | in. w.c. | Read | ||
| HR | 19doc 20 | Return fan duct static pressure | Negative range; in. w.c. x10 (Pa x10 in Metric). | INT16 | × 0.1 | in. w.c. | Read | ||
| HR | 25doc 26 | Return air dewpoint | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 27doc 28 | Outdoor air dewpoint | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 38doc 39 | Suction refrigerant temperature circuit 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 39doc 40 | Suction refrigerant pressure circuit 1 | psi x10 (kPa x10 in Metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 40doc 41 | Discharge refrigerant pressure circuit 1 | psi x10 (kPa x10 in Metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 41doc 42 | Liquid line refrigerant temperature circuit 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 42doc 43 | Variable compressor 1 temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 43doc 44 | Fixed compressor temperature circuit 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 46doc 47 | Discharge line refrigerant temperature circuit 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 49doc 50 | Defrost temperature circuit 1 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 50doc 51 | Suction refrigerant temperature circuit 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 51doc 52 | Suction refrigerant pressure circuit 2 | psi x10 (kPa x10 in Metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 52doc 53 | Discharge refrigerant pressure circuit 2 | psi x10 (kPa x10 in Metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 53doc 54 | Liquid line refrigerant temperature circuit 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 54doc 55 | Variable compressor 2 temperature | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 55doc 56 | Fixed compressor temperature circuit 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 58doc 59 | Discharge line refrigerant temperature circuit 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 61doc 62 | Defrost temperature circuit 2 | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 87doc 88 | Voltage L1-L2 | Power monitoring option. | UINT16 | × 0.1 | V | Read | ||
| HR | 88doc 89 | Voltage L2-L3 | Power monitoring option. | UINT16 | × 0.1 | V | Read | ||
| HR | 89doc 90 | Voltage L1-L3 | Power monitoring option. | UINT16 | × 0.1 | V | Read | ||
| HR | 96doc 97 | Current L1 | Power monitoring option. | UINT16 | × 0.1 | A | Read | ||
| HR | 97doc 98 | Current L2 | Power monitoring option. | UINT16 | × 0.1 | A | Read | ||
| HR | 98doc 99 | Current L3 | Power monitoring option. | UINT16 | × 0.1 | A | Read | ||
| HR | 106doc 107 | Power factor | Range -1.0..1.0, x10. | INT16 | × 0.1 | Read | |||
| HR | 115doc 116 | Suction superheat circuit 1 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 116doc 117 | Discharge superheat circuit 1 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 117doc 118 | Subcooling circuit 1 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 118doc 119 | Suction superheat circuit 2 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 119doc 120 | Discharge superheat circuit 2 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 120doc 121 | Subcooling circuit 2 | Temperature difference, °F x10 (°C x10 in Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 126doc 127 | Supply fan operation output | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 128doc 129 | Discharge air temperature economizer setpoint | 40-100 °F, default 55 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 129doc 130 | Supply fan duct static pressure setpoint | 0.2-4 in. w.c. x10, default 1. | UINT16 | × 0.1 | in. w.c. | Read/write | ||
| HR | 130doc 131 | Supply fan building static pressure setpoint | -0.25..0.25 in. x100 (Pa x100 in Metric). | INT16 | × 0.01 | in. w.c. | Read/write | ||
| HR | 137doc 138 | Occupied cooling setpoint | 0-100 °F, default 72 °F; x10. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 138doc 139 | Unoccupied cooling setpoint | 40-100 °F, default 85 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 139doc 140 | Occupied heating setpoint | 0-100 °F, default 68 °F; x10. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 140doc 141 | Unoccupied heating setpoint | 40-100 °F, default 55 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 141doc 142 | Discharge air cooling setpoint | 40-100 °F, default 55 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 142doc 143 | Minimum discharge air cooling setpoint | 40-100 °F, default 55 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 145doc 146 | Discharge air heating setpoint (electric heat) | 40-105 °F, default 85 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 146doc 147 | Discharge air heating setpoint (no electric heat) | 40-140 °F, default 85 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 147doc 148 | Maximum discharge air heating setpoint | 40-130 °F, default 120 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 153doc 154 | Effective discharge air temperature setpoint | °F x10 (°C x10 when register 261 = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 154doc 155 | Warning alarm | Highest-priority active warning alarm number; 0 = none. | UINT16 | Read | ||||
| HR | 155doc 156 | Problem alarm | Highest-priority active problem alarm number; 0 = none. | UINT16 | Read | ||||
| HR | 156doc 157 | Fault alarm | Highest-priority active fault alarm number; 0 = none. | UINT16 | Read | ||||
| HR | 157doc 158 | Alarm value | Highest-priority active alarm of any class; 0 = none. | UINT16 | Read | ||||
| HR | 158doc 159 | Space temperature input | Network space temperature; local sensor used if unreliable. °F x10. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 159doc 160 | Outdoor air temperature input | Network OAT; local sensor used if unreliable. °F x10. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 160doc 161 | Space IAQ (CO2) input | Network CO2, 0-32767 ppm, default 32767. | UINT16 | ppm | Read/write | |||
| HR | 161doc 162 | Economizer enable | Network enable/disable of economizer; -1 = not limited. | INT16 | Read/write | 0 = Off (Disabled); 1 = Enable; -1 = Null (not network-controlled) | |||
| HR | 163doc 164 | Primary cool enable | Network enable/disable of primary cooling; -1 = not controlled. | INT16 | Read/write | 0 = Off (Disabled); 1 = Enable; -1 = Null (not network-controlled) | |||
| HR | 165doc 166 | Primary heat enable | Network enable/disable of primary heating; -1 = not controlled. | INT16 | Read/write | 0 = Off (Disabled); 1 = Enable; -1 = Null (not network-controlled) | |||
| HR | 169doc 170 | Dewpoint setpoint 1 | 0-100 °F, default 50 °F; x10. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 176doc 177 | Minimum leaving coil temperature setpoint | 42-70 °F, default 45 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 178doc 179 | Maximum leaving coil temperature setpoint | 42-70 °F, default 52 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 180doc 181 | Leaving coil temperature setpoint | 45-70 °F, default 52 °F; x10. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 244doc 245 | Unit status | UINT16 | Read | 0 = Enable; 1 = OffMan; 2 = OffManCtrl; 3 = OffNet; 4 = OffAlm; 5 = OffRetry; 6 = OffPassVnt; 7 = OffSnsrCfg; 8 = OffEvac | ||||
| HR | 245doc 246 | Cooling status | UINT16 | Read | 0 = Enabled; 1 = None; 2 = OffAmb; 3 = OffAlm; 4 = OffNet; 5 = OffMan; 6 = NA; 7 = CfgErr | ||||
| HR | 246doc 247 | Economizer status | UINT16 | Read | 0 = Enabled; 1 = None; 2 = OffAmb; 3 = OffAlm; 4 = OffNet; 5 = OffMan; 6 = OffDehum | ||||
| HR | 247doc 248 | Primary heating status | UINT16 | Read | 0 = Enabled; 1 = None; 2 = OffAmb; 3 = OffAlm; 4 = OffNet; 5 = OffMan; 6 = OffDehum; 7 = CfgErr | ||||
| HR | 248doc 249 | Application mode | Limits operation; only acts when HMI Control Mode = Auto. | UINT16 | Read/write | 0 = Off; 1 = HeatOnly; 2 = CoolOnly; 3 = FanOnly; 4 = Auto; 5 = NA | |||
| HR | 249doc 250 | Occupancy status | UINT16 | Read | 0 = Occ; 1 = Unocc; 2 = TntOvrd | ||||
| HR | 250doc 251 | Occupancy mode (network) | Manual occupancy override; default Auto. | UINT16 | Read/write | 0 = Occ; 1 = Unocc; 2 = TntOvrd; 3 = Standby; 4 = Auto | |||
| HR | 251doc 252 | Current state | Scheduler occupancy command; active only when register 251 = Auto. | UINT16 | Read/write | 0 = Occ; 1 = Unocc; 2 = TntOvrd; 3 = Standby; 4 = NA | |||
| HR | 252doc 253 | Next state | Used for optimal start. | UINT16 | Read/write | 0 = Occ; 1 = Unocc; 2 = TntOvrd; 3 = Standby; 4 = NA | |||
| HR | 253doc 254 | Time to next state | Used for optimal start; default 65535. | UINT16 | Read/write | ||||
| HR | 254doc 255 | Emergency override | Off shuts the unit down until set back to Normal. | UINT16 | Read/write | 0 = Normal; 1 = Off | |||
| HR | 255doc 256 | Supply fan control | UINT16 | Read/write | 0 = DSP; 1 = Speed; 2 = 1ZnVAV; 3 = BSP; 4 = CO2; 5 = Flow; 6 = CAV | ||||
| HR | 256doc 257 | Return fan capacity control | UINT16 | Read/write | 0 = CAV; 1 = BSP; 2 = Tracking; 3 = DSP; 4 = Speed; 5 = Flow; 6 = OAD; 7 = FlowDiff | ||||
| HR | 258doc 259 | VAV box output status | UINT16 | Read | 0 = Heat; 1 = Cool | ||||
| HR | 259doc 260 | Unit state | UINT16 | Read | 0 = Off; 1 = Start; 2 = Recirc; 3 = FanOnly; 4 = MinDAT (printed 'Min x 10DAT'); 5 = Htg; 6 = Econo; 7 = Clg | ||||
| HR | 260doc 261 | Units of measurement | Unit system used for all Modbus values. | UINT16 | Read | 0 = Metric; 1 = English | |||
| HR | 261doc 262 | Passive ventilation | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 262doc 263 | Energy recovery wheel status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 263doc 264 | Unit local/network control | UINT16 | Read | 0 = Network; 1 = Local | ||||
| HR | 264doc 265 | Control temp source | UINT16 | Read/write | 0 = RAT; 1 = Space; 2 = OAT; 3 = None | ||||
| HR | 265doc 266 | Dehumidification status | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 266doc 267 | Network demand shed enable | UINT16 | Read/write | 0 = Inactive; 1 = Auto; 2 = Manual | ||||
| HR | 267doc 268 | Morning warmup status | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 268doc 269 | Free cooling status | UINT16 | Read | 0 = Unavail; 1 = Avail | ||||
| HR | 272doc 273 | Secondary heating status | UINT16 | Read | 0 = Enabled; 1 = None; 2 = OffAmb; 3 = OffAlm; 4 = OffNet; 5 = OffMan; 6 = NA; 7 = NA | ||||
| HR | 273doc 274 | Supply air fan 1 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 274doc 275 | Supply air fan 2 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 275doc 276 | Supply air fan 3 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 276doc 277 | Supply air fan 4 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 277doc 278 | Supply air fan 5 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 278doc 279 | Supply air fan 6 status | UINT16 | Read | 0 = OK; 1 = HLL; 2 = TFEI; 3 = TFM; 4 = TFE; 5 = LK; 6 = SKF; 7 = PHA; 8 = UzLo; 9 = UzHi; 10 = UeLo; 11 = UeHi; 12 = NoCm; 13 = OC; 14 = OT; 15 = RRP; 16 = EE; 17 = POC; 18 = AOV; 19 = AUV | ||||
| HR | 287doc 288 | Minimum outdoor air reset | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 292doc 293 | Occupancy source | UINT16 | Read | 0 = None; 1 = NetSchd; 2 = IntSchd; 3 = OneEvnt; 4 = RemoteSw; 5 = NetManCmd; 6 = OccMode; 7 = TstatTO; 8 = ManTO; 9 = UnitDsbld | ||||
| HR | 349doc 350 | Control type | UINT16 | Read | 0 = Zone; 1 = DAT; 2 = 1ZnVAV; 3 = RO_FC; 4 = RO_FCGE; 5 = RO_DCSA | ||||
| HR | 350doc 351 | Fixed compressors | Number configured, 0-8. | UINT16 | Read | ||||
| HR | 351doc 352 | Variable compressors | Number configured, 0-4. | UINT16 | Read | ||||
| HR | 370doc 371 | Refrigerant type | UINT16 | Read | 0 = None; 1 = R410A; 2 = R32; 3 = R32HP; 4 = R32HP75; 5 = R32HP50; 6 = R32HP25; 7 = R32HP0 | ||||
| HR | 371doc 372 | Unit voltage | UINT16 | Read | 0 = 208_60Hz; 1 = 230_60Hz; 2 = 460_60Hz; 3 = 575_60Hz | ||||
| HR | 399doc 400 | Clear alarms | UINT16 | Read/write | 0 = No; 1 = ClrFlts; 2 = ClrPrblms; 3 = ClrWrngs; 4 = ClrAllAlms |
Notes on this map
- Network settings (defaults 38400 bps, no parity, 2 stop bits, address 1) come from the companion manual IM 1374-1-1, Modbus RTU Communication Module for MicroTech 4 Rebel and Rebel Applied (Feb 2026): https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/IM%201374-1%20MicroTech%20Rebel%20Applied%20Modbus%20Comm%20Manual%200219.pdf
- The document marks writable registers 'W' and defines that as read-write; they are listed as RW.
- The document never defines 'x 10' / 'x 100' / 'x 1000'. The only reading consistent with its decimal ranges and defaults (for example '72°F x 10', '-45.6-121.1°C x 10') is raw = value x factor, so scales are 0.1 / 0.01 / 0.001.
- Units follow register 261 / the module's 'Unit Support' setting (default English). Units shown here are the English ones (°F, psi, in. w.c.); in Metric the same registers carry °C, kPa and Pa with the same multiplier.
- Signedness is not stated. A register is INT16 only when its published English or Metric range includes negative values (or an enum uses -1); every other register is UINT16. Each kept register's range was checked to fit its type after scaling in both unit systems.
- The network 'invalid' value for space/outdoor temperature inputs is printed as 621.8 °F / 327.7 °C x10; the raw number is not stated.
- Left out: every two-register value (energy and power totals 80-115, airflow setpoints 175-176 and 187-190, run-hour counters 191-236) because the document never states the word order for multi-register numbers.
- Left out: single-register airflows 29, 30 and 172 ('0-60000 cfm x 10' cannot fit in 16 bits), building static pressure 9 (x10 on a ±0.249 in. range is unclear), return fan DSP setpoint 134, exhaust plenum setpoint 135 and OAT 128 (no multiplier printed), and duplicate/unnamed rows (133, 169, 171, 178, 180, 182, 183, 258, 283-287, 292).
- Left out: air-quality sensors 31-38, circuit 3 points 63-73, generic I/O 300-349 (expansion module) and most configuration enums 353-376. Alarm number meanings (pp. 25-37) are not reproduced.
- Left out because the '% x 10' multiplier cannot be trusted: this revision shows a mechanical '%' -> '% x 10' edit (register 15 reads '0-100% x 10 x 10', notes read '100% x 10 outdoor air' and 'held at 0% x 10', an alarm text reads '5% x 10' and the ASCII appendix lists '% x 10' for character 37). Every percent register is therefore ambiguous between raw 0-100 and 0-1000: 10, 11, 15, 18, 25, 27, 125, 126, 144, 145, 149-153, 163, 165, 167, 168, 174 and 186.
- Left out: maximum purge time 184 ('0-300 Min x 10'), because the same edit also produced 'Min x 10' text (Unit State value 4 reads 'Min x 10DAT').
- Left out: filter pressure 21 (the table cell spans registers 21-23, and '0-1250 Pa x 100' cannot fit 16 bits in Metric) and building static pressure setpoint 137 ('-62.2-62.2 Pa x 1000' cannot fit a signed 16-bit register in Metric). Also not mapped: exhaust air plenum static pressure 24 and Remote Setpoint Source 270/271, power monitor reset 272.
- Unit State (260) value 4 is printed 'Min x 10DAT', an artefact of the same edit; it is listed with the printed text.
- The data-bits setting is not stated in ED 19133-2 or IM 1374-1, so it is left null.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
What Modbus registers does the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) have?
This map lists 112 registers: 112 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol document prints holding registers without the 4xxxx prefix (register 8 = 40008) and states that register number 1 is sent as index 0 in the PDU. Wire address = printed number - 1.
What are the minimum Modbus registers to integrate the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)?
Start with HR 0 Discharge air temperature (Discharge air temperature); HR 137 Occupied cooling setpoint (Occupied cooling setpoint); HR 139 Occupied heating setpoint (Occupied heating setpoint); HR 244 Unit status (Unit status); HR 248 Application mode (Application mode); HR 250 Occupancy mode (network) (Network occupancy mode); HR 157 Alarm value (Highest active alarm); HR 263 Unit local/network control (Local/network control); HR 260 Units of measurement (English/Metric units flag).
How do I enable Modbus control of the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)?
A Modbus RTU communication module must be fitted. Network address and baud are set only from the HMI (password 2526, BMS Communication / Modbus Set-Up), then 'Apply Changes' and cycle power. Application mode has no effect unless the HMI Control Mode is Auto. Register 264 (Unit Local/Network Control) must read Network (0), set at the HMI, for most network writes to apply.
What happens when the Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) loses Modbus communication?
The module's Com LED Timeout (0-3600 s, default 3 s) only turns the bus LED red when the client stops polling; no control fallback on comms loss is documented. Network temperature/RH inputs fall back to local sensors when the network value is unreliable.
Where is the official Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller) Modbus documentation?
The source is MicroTech Applied Rooftop Unit Controller Modbus Network Integration (ED 19133-2) (ED 19133-2), revision 2025-10, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019133-2%20MicroTech%20Applied%20Rooftop%20Modbus%20Unit%20Controller%20Protocol%20Document.pdf.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131
Source: MicroTech Applied Rooftop Unit Controller Modbus Network Integration (ED 19133-2) · ED 19133-2 · rev. 2025-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.