Manufacturer

Daikin Applied Modbus register maps

Updated 25 October 2026

3 Daikin Applied models, 271 registers in all, each re-typed from Daikin Applied’s own free documentation and checked against it.

3 of 3 shown

Daikin Applied: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
Pathfinder AWV air-cooled screw chiller (MicroTech controller)RTU138400 baud, 8N2CDAB1-based96
Rebel / Rebel Applied rooftop (MicroTech 4 controller)RTU138400 baud, 8N216-bit only1-based112
Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)RTU119200 baud, 8N1ABCD1-based63