- Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Chiller (water-cooled, magnetic-bearing centrifugal) · Modbus register map
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus register map
Updated 17 November 2026
The Magnitude WME is Daikin Applied's oil-free magnetic-bearing centrifugal chiller. With the Modbus communication module its MicroTech controller exposes all points as 16-bit holding registers. This map covers chiller status and commands, water temperatures and flows, alarm codes, circuit refrigerant values, per-compressor data and pump run hours.
This page lists 90 Modbus registers for the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
- Equipment type
- Chiller (water-cooled, magnetic-bearing centrifugal)
- Registers
- 90 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME
Integration notes: Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Read printed registers 1-21 and 28-42 (wire 0-20 and 27-41) in two requests for status, temperatures and alarms. To command the chiller, set Control Source = BAS and Remote Enable = Enable at the HMI, then write Chiller Enable (printed 9), Cool Setpoint (35) and Capacity Limit (38).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Chiller On/Off | UINT16 | Chiller on/off | Read |
| HR 14 | Chiller Run Mode | UINT16 | Run mode | Read |
| HR 16 | Evaporator Leaving Fluid Temperature | INT16 | Evaporator leaving water temperature | Read |
| HR 12 | Actual Capacity | UINT16 | Actual capacity | Read |
| HR 32 | Alarm Code - Fault | UINT16 | Active fault alarm code | Read |
| HR 8 | Chiller Enable Setpoint | UINT16 | Chiller enable command | Read/write |
| HR 34 | Cool Setpoint - Network | INT16 | Cool setpoint from network | Read/write |
Enable Modbus control & writes
Install the Modbus communication module, set Control Source to BAS (for the enable command) and Remote Enable to Enable (for setpoint, mode and capacity limit) at the unit HMI.
Byte order & addressing
- Printed numbers are 1-based without the 4 prefix.
- Run hours are two registers, high word first.
- While the chiller is in Local, the network mode, cool and ice setpoints, capacity limit and clear-alarm registers are ignored.
Network setup
- Network parameters are set at the HMI; see Daikin IM 1283 for the Modbus module settings.
Watch out for
- A value of 2 (Null) on the enable or clear-alarm registers releases the point back to its default.
- Some manual-reset alarms (low evaporator pressure, high condenser pressure, freeze) cannot be cleared from the network.
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Chiller Local/Network | UINT16 | Read | 0 = Remote; 1 = Local | ||||
| HR | 1doc 2 | Chiller Enable Output | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| HR | 2doc 3 | Run Enabled | UINT16 | Read | 0 = Off; 1 = Run allowed | ||||
| HR | 3doc 4 | Chiller Capacity Limited | UINT16 | Read | 0 = Not limited; 1 = Limited | ||||
| HR | 4doc 5 | Alarm Digital Output | UINT16 | Read | 0 = No alarm; 1 = Alarm | ||||
| HR | 5doc 6 | Evaporator Flow Switch Status | UINT16 | Read | 0 = No flow; 1 = Flow | ||||
| HR | 6doc 7 | Condenser Flow Switch Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 7doc 8 | Chiller On/Off | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Chiller Enable Setpoint | Used only when Control Source is BAS. | UINT16 | Read/write | 0 = Disable; 1 = Enable; 2 = Null | |||
| HR | 9doc 10 | Clear Alarm - Network | Ignored when the chiller is in Local. | UINT16 | Read/write | 0 = Normal; 1 = Clear alarms; 2 = Null | |||
| HR | 10doc 11 | Chiller Mode Output | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/heat recovery | ||||
| HR | 11doc 12 | Active Setpoint | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 12doc 13 | Actual Capacity | Percent x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 13doc 14 | Active Capacity Limit Output | Percent x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 14doc 15 | Chiller Run Mode | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = Pre-shutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Fluid Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 16doc 17 | Evaporator Leaving Fluid Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 17doc 18 | Evaporator Fluid Flow Rate | Field-supplied flow meter (L/s in metric). | UINT16 | GPM | Read | |||
| HR | 18doc 19 | Condenser Entering Fluid Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 19doc 20 | Condenser Leaving Fluid Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 20doc 21 | Condenser Fluid Flow Rate | Field-supplied flow meter (L/s in metric). | UINT16 | GPM | Read | |||
| HR | 27doc 28 | Alarm Index - Warning | Index of the active warning alarm. | UINT16 | Read | ||||
| HR | 29doc 30 | Alarm Index - Fault | Index of the active fault alarm. | UINT16 | Read | ||||
| HR | 30doc 31 | Alarm Code - Warning | Code of the active warning alarm. | UINT16 | Read | ||||
| HR | 32doc 33 | Alarm Code - Fault | Code of the active fault alarm. | UINT16 | Read | ||||
| HR | 33doc 34 | Chiller Mode Setpoint - Network | Used only when Remote Enable is on; WME-C/D use Cool only. | UINT16 | Read/write | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/heat recovery | |||
| HR | 34doc 35 | Cool Setpoint - Network | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read/write | ||
| HR | 37doc 38 | Capacity Limit Setpoint - Network | Percent x10; used only when Remote Enable is on. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 39 | Condenser Refrigerant Pressure Circuit 1 | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 39doc 40 | Condenser Saturated Refrigerant Temperature Circuit 1 | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 40doc 41 | Evaporator Refrigerant Pressure Circuit 1 | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 41doc 42 | Evaporator Saturated Refrigerant Temperature Circuit 1 | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 62doc 63 | C1 Comp 1 Suction Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 63doc 64 | C1 Comp 1 Suction Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 64doc 65 | C1 Comp 1 Suction Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 65doc 66 | C1 Comp 1 Discharge Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 66doc 67 | C1 Comp 1 Discharge Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 67doc 68 | C1 Comp 1 Discharge Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 68doc 69 | C1 Comp 1 Percent RLA | UINT16 | % | Read | ||||
| HR | 69doc 70 | C1 Comp 1 Current | Average motor current. | UINT16 | A | Read | |||
| HR | 70doc 71 | C1 Comp 1 Voltage | Average motor voltage (VAC). | UINT16 | V | Read | |||
| HR | 71doc 72 | C1 Comp 1 Power | UINT16 | kW | Read | ||||
| HR | 72doc 73 | C1 Comp 1 Starts | UINT16 | Read | |||||
| HR | 73doc 74 | C1 Comp 1 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 75doc 76 | C1 Comp 2 Suction Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 76doc 77 | C1 Comp 2 Suction Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 77doc 78 | C1 Comp 2 Suction Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 78doc 79 | C1 Comp 2 Discharge Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 79doc 80 | C1 Comp 2 Discharge Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 80doc 81 | C1 Comp 2 Discharge Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 81doc 82 | C1 Comp 2 Percent RLA | UINT16 | % | Read | ||||
| HR | 82doc 83 | C1 Comp 2 Current | Average motor current. | UINT16 | A | Read | |||
| HR | 83doc 84 | C1 Comp 2 Voltage | Average motor voltage (VAC). | UINT16 | V | Read | |||
| HR | 84doc 85 | C1 Comp 2 Power | UINT16 | kW | Read | ||||
| HR | 85doc 86 | C1 Comp 2 Starts | UINT16 | Read | |||||
| HR | 86doc 87 | C1 Comp 2 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 101doc 102 | C2 Comp 1 Suction Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 102doc 103 | C2 Comp 1 Suction Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 103doc 104 | C2 Comp 1 Suction Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 104doc 105 | C2 Comp 1 Discharge Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 105doc 106 | C2 Comp 1 Discharge Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 106doc 107 | C2 Comp 1 Discharge Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 107doc 108 | C2 Comp 1 Percent RLA | UINT16 | % | Read | ||||
| HR | 108doc 109 | C2 Comp 1 Current | Average motor current. | UINT16 | A | Read | |||
| HR | 109doc 110 | C2 Comp 1 Voltage | Average motor voltage (VAC). | UINT16 | V | Read | |||
| HR | 110doc 111 | C2 Comp 1 Power | UINT16 | kW | Read | ||||
| HR | 114doc 115 | C2 Comp 2 Suction Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 115doc 116 | C2 Comp 2 Suction Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 116doc 117 | C2 Comp 2 Suction Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 117doc 118 | C2 Comp 2 Discharge Pressure | psi x10 (kPa x10 in metric). | UINT16 | × 0.1 | psi | Read | ||
| HR | 118doc 119 | C2 Comp 2 Discharge Saturated Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 119doc 120 | C2 Comp 2 Discharge Temperature | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 120doc 121 | C2 Comp 2 Percent RLA | UINT16 | % | Read | ||||
| HR | 121doc 122 | C2 Comp 2 Current | Average motor current. | UINT16 | A | Read | |||
| HR | 122doc 123 | C2 Comp 2 Voltage | Average motor voltage (VAC). | UINT16 | V | Read | |||
| HR | 123doc 124 | C2 Comp 2 Power | UINT16 | kW | Read | ||||
| HR | 296doc 297 | Condenser Pump 1 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 298doc 299 | Condenser Pump 1 Status | UINT16 | Read | 0 = Off request; 1 = On request | ||||
| HR | 299doc 300 | Condenser Pump 2 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 301doc 302 | Condenser Pump 2 Status | UINT16 | Read | 0 = Off request; 1 = On request | ||||
| HR | 302doc 303 | Evaporator Pump 1 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 304doc 305 | Evaporator Pump 1 Status | UINT16 | Read | 0 = Off request; 1 = On request | ||||
| HR | 305doc 306 | Evaporator Pump 2 Run Hours | High word in the lower register. | UINT32 | ABCD | h | Read | ||
| HR | 307doc 308 | Evaporator Pump 2 Status | UINT16 | Read | 0 = Off request; 1 = On request | ||||
| HR | 1787doc 1788 | C2 Comp 2 Off/Auto | Network enable for the compressor; returns to Auto after a power cycle. | UINT16 | Read | 0 = Off; 1 = Auto | |||
| HR | 1800doc 1801 | C2 Comp 1 Off/Auto | Network enable for the compressor; returns to Auto after a power cycle. | UINT16 | Read | 0 = Off; 1 = Auto | |||
| HR | 1826doc 1827 | C1 Comp 2 Off/Auto | Network enable for the compressor; returns to Auto after a power cycle. | UINT16 | Read | 0 = Off; 1 = Auto | |||
| HR | 1840doc 1841 | C1 Comp 1 Off/Auto | Network enable for the compressor; returns to Auto after a power cycle. | UINT16 | Read | 0 = Off; 1 = Auto | |||
| HR | 1967doc 1968 | Liquid Line Refrigerant Temperature Circuit 2 | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 1983doc 1984 | Liquid Line Refrigerant Temperature Circuit 1 | °F x10 (°C x10 in metric). | INT16 | × 0.1 | °F | Read |
Notes on this map
- Word order: the document's example puts compressor run hours 99900 (0x0001863C) at 74 = 0x0001 and 75 = 0x863C, so two-register values are high word first (ABCD).
- 'x 10' in a range means the register holds the value times ten, so those registers use scale 0.1. Temperatures and pressures are printed with both English (°F, psi) and metric (°C, kPa) ranges; the English units are shown here. The document's units selector is described for BACnet only, so check which unit system the Modbus values use on site.
- Signedness is not stated: a register is typed INT16 when its published range goes below zero, otherwise UINT16.
- Compressor Off/Auto (1841, 1827, 1801, 1788) is typed RW in the data-type column but R in the access column; it is listed read-only. The WME-C needs chiller application code 1.2.4 or newer for these registers.
- Left out: the alarm module ID/type/payload registers (2001-2009), which are explained only in the BACnet alarm sections; communication defaults, because the Table 1 Modbus column is misaligned in the source (see Daikin IM 1283 for network setup).
- For Ice and Heat modes only Cool applies on WME-C and WME-D.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
What Modbus registers does the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) have?
This map lists 90 registers: 90 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register tables drop the 4xxxx prefix (register 1 = 40001) and the document says the module is zero-based: 40002 is sent as 0001. Wire address = printed number - 1.
What byte order does the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)?
Start with HR 7 Chiller On/Off (Chiller on/off); HR 14 Chiller Run Mode (Run mode); HR 16 Evaporator Leaving Fluid Temperature (Evaporator leaving water temperature); HR 12 Actual Capacity (Actual capacity); HR 32 Alarm Code - Fault (Active fault alarm code); HR 8 Chiller Enable Setpoint (Chiller enable command); HR 34 Cool Setpoint - Network (Cool setpoint from network).
How do I enable Modbus control of the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)?
Install the Modbus communication module, set Control Source to BAS (for the enable command) and Remote Enable to Enable (for setpoint, mode and capacity limit) at the unit HMI.
Where is the official Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus documentation?
The source is MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (BACnet / Modbus) (ED 19111-4), revision 2026-03, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/19111-4.pdf.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex
All chillers & heat pumps Modbus register maps →
Source: MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (BACnet / Modbus) · ED 19111-4 · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.