Chiller (water-cooled, magnetic-bearing centrifugal) · Modbus register map

Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus register map

Updated 17 November 2026

Short answer

The Magnitude WME is Daikin Applied's oil-free magnetic-bearing centrifugal chiller. With the Modbus communication module its MicroTech controller exposes all points as 16-bit holding registers. This map covers chiller status and commands, water temperatures and flows, alarm codes, circuit refrigerant values, per-compressor data and pump run hours.

This page lists 90 Modbus registers for the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Equipment type
Chiller (water-cooled, magnetic-bearing centrifugal)
Registers
90 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME
Source document
MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (BACnet / Modbus) · ED 19111-4 · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)

Integration in brief

Read printed registers 1-21 and 28-42 (wire 0-20 and 27-41) in two requests for status, temperatures and alarms. To command the chiller, set Control Source = BAS and Remote Enable = Enable at the HMI, then write Chiller Enable (printed 9), Cool Setpoint (35) and Capacity Limit (38).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7Chiller On/OffUINT16Chiller on/offRead
HR 14Chiller Run ModeUINT16Run modeRead
HR 16Evaporator Leaving Fluid TemperatureINT16Evaporator leaving water temperatureRead
HR 12Actual CapacityUINT16Actual capacityRead
HR 32Alarm Code - FaultUINT16Active fault alarm codeRead
HR 8Chiller Enable SetpointUINT16Chiller enable commandRead/write
HR 34Cool Setpoint - NetworkINT16Cool setpoint from networkRead/write

Enable Modbus control & writes

Install the Modbus communication module, set Control Source to BAS (for the enable command) and Remote Enable to Enable (for setpoint, mode and capacity limit) at the unit HMI.

Byte order & addressing

Network setup

Watch out for

Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

90 of 90 shown
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Chiller Local/NetworkUINT16Read0 = Remote; 1 = Local
HR1doc 2Chiller Enable OutputUINT16Read0 = Disable; 1 = Enable
HR2doc 3Run EnabledUINT16Read0 = Off; 1 = Run allowed
HR3doc 4Chiller Capacity LimitedUINT16Read0 = Not limited; 1 = Limited
HR4doc 5Alarm Digital OutputUINT16Read0 = No alarm; 1 = Alarm
HR5doc 6Evaporator Flow Switch StatusUINT16Read0 = No flow; 1 = Flow
HR6doc 7Condenser Flow Switch StatusUINT16Read0 = Off; 1 = On
HR7doc 8Chiller On/OffUINT16Read0 = Off; 1 = On
HR8doc 9Chiller Enable SetpointUsed only when Control Source is BAS.UINT16Read/write0 = Disable; 1 = Enable; 2 = Null
HR9doc 10Clear Alarm - NetworkIgnored when the chiller is in Local.UINT16Read/write0 = Normal; 1 = Clear alarms; 2 = Null
HR10doc 11Chiller Mode OutputUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/heat recovery
HR11doc 12Active Setpoint°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR12doc 13Actual CapacityPercent x10.UINT16× 0.1%Read
HR13doc 14Active Capacity Limit OutputPercent x10.UINT16× 0.1%Read
HR14doc 15Chiller Run ModeUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Pre-shutdown; 5 = Service
HR15doc 16Evaporator Entering Fluid Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR16doc 17Evaporator Leaving Fluid Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR17doc 18Evaporator Fluid Flow RateField-supplied flow meter (L/s in metric).UINT16GPMRead
HR18doc 19Condenser Entering Fluid Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR19doc 20Condenser Leaving Fluid Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR20doc 21Condenser Fluid Flow RateField-supplied flow meter (L/s in metric).UINT16GPMRead
HR27doc 28Alarm Index - WarningIndex of the active warning alarm.UINT16Read
HR29doc 30Alarm Index - FaultIndex of the active fault alarm.UINT16Read
HR30doc 31Alarm Code - WarningCode of the active warning alarm.UINT16Read
HR32doc 33Alarm Code - FaultCode of the active fault alarm.UINT16Read
HR33doc 34Chiller Mode Setpoint - NetworkUsed only when Remote Enable is on; WME-C/D use Cool only.UINT16Read/write1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/heat recovery
HR34doc 35Cool Setpoint - Network°F x10 (°C x10 in metric).INT16× 0.1°FRead/write
HR37doc 38Capacity Limit Setpoint - NetworkPercent x10; used only when Remote Enable is on.UINT16× 0.1%Read/write
HR38doc 39Condenser Refrigerant Pressure Circuit 1psi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR39doc 40Condenser Saturated Refrigerant Temperature Circuit 1°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR40doc 41Evaporator Refrigerant Pressure Circuit 1psi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR41doc 42Evaporator Saturated Refrigerant Temperature Circuit 1°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR62doc 63C1 Comp 1 Suction Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR63doc 64C1 Comp 1 Suction Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR64doc 65C1 Comp 1 Suction Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR65doc 66C1 Comp 1 Discharge Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR66doc 67C1 Comp 1 Discharge Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR67doc 68C1 Comp 1 Discharge Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR68doc 69C1 Comp 1 Percent RLAUINT16%Read
HR69doc 70C1 Comp 1 CurrentAverage motor current.UINT16ARead
HR70doc 71C1 Comp 1 VoltageAverage motor voltage (VAC).UINT16VRead
HR71doc 72C1 Comp 1 PowerUINT16kWRead
HR72doc 73C1 Comp 1 StartsUINT16Read
HR73doc 74C1 Comp 1 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR75doc 76C1 Comp 2 Suction Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR76doc 77C1 Comp 2 Suction Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR77doc 78C1 Comp 2 Suction Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR78doc 79C1 Comp 2 Discharge Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR79doc 80C1 Comp 2 Discharge Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR80doc 81C1 Comp 2 Discharge Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR81doc 82C1 Comp 2 Percent RLAUINT16%Read
HR82doc 83C1 Comp 2 CurrentAverage motor current.UINT16ARead
HR83doc 84C1 Comp 2 VoltageAverage motor voltage (VAC).UINT16VRead
HR84doc 85C1 Comp 2 PowerUINT16kWRead
HR85doc 86C1 Comp 2 StartsUINT16Read
HR86doc 87C1 Comp 2 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR101doc 102C2 Comp 1 Suction Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR102doc 103C2 Comp 1 Suction Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR103doc 104C2 Comp 1 Suction Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR104doc 105C2 Comp 1 Discharge Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR105doc 106C2 Comp 1 Discharge Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR106doc 107C2 Comp 1 Discharge Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR107doc 108C2 Comp 1 Percent RLAUINT16%Read
HR108doc 109C2 Comp 1 CurrentAverage motor current.UINT16ARead
HR109doc 110C2 Comp 1 VoltageAverage motor voltage (VAC).UINT16VRead
HR110doc 111C2 Comp 1 PowerUINT16kWRead
HR114doc 115C2 Comp 2 Suction Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR115doc 116C2 Comp 2 Suction Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR116doc 117C2 Comp 2 Suction Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR117doc 118C2 Comp 2 Discharge Pressurepsi x10 (kPa x10 in metric).UINT16× 0.1psiRead
HR118doc 119C2 Comp 2 Discharge Saturated Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR119doc 120C2 Comp 2 Discharge Temperature°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR120doc 121C2 Comp 2 Percent RLAUINT16%Read
HR121doc 122C2 Comp 2 CurrentAverage motor current.UINT16ARead
HR122doc 123C2 Comp 2 VoltageAverage motor voltage (VAC).UINT16VRead
HR123doc 124C2 Comp 2 PowerUINT16kWRead
HR296doc 297Condenser Pump 1 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR298doc 299Condenser Pump 1 StatusUINT16Read0 = Off request; 1 = On request
HR299doc 300Condenser Pump 2 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR301doc 302Condenser Pump 2 StatusUINT16Read0 = Off request; 1 = On request
HR302doc 303Evaporator Pump 1 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR304doc 305Evaporator Pump 1 StatusUINT16Read0 = Off request; 1 = On request
HR305doc 306Evaporator Pump 2 Run HoursHigh word in the lower register.UINT32ABCDhRead
HR307doc 308Evaporator Pump 2 StatusUINT16Read0 = Off request; 1 = On request
HR1787doc 1788C2 Comp 2 Off/AutoNetwork enable for the compressor; returns to Auto after a power cycle.UINT16Read0 = Off; 1 = Auto
HR1800doc 1801C2 Comp 1 Off/AutoNetwork enable for the compressor; returns to Auto after a power cycle.UINT16Read0 = Off; 1 = Auto
HR1826doc 1827C1 Comp 2 Off/AutoNetwork enable for the compressor; returns to Auto after a power cycle.UINT16Read0 = Off; 1 = Auto
HR1840doc 1841C1 Comp 1 Off/AutoNetwork enable for the compressor; returns to Auto after a power cycle.UINT16Read0 = Off; 1 = Auto
HR1967doc 1968Liquid Line Refrigerant Temperature Circuit 2°F x10 (°C x10 in metric).INT16× 0.1°FRead
HR1983doc 1984Liquid Line Refrigerant Temperature Circuit 1°F x10 (°C x10 in metric).INT16× 0.1°FRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)

What Modbus registers does the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) have?

This map lists 90 registers: 90 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register tables drop the 4xxxx prefix (register 1 = 40001) and the document says the module is zero-based: 40002 is sent as 0001. Wire address = printed number - 1.

What byte order does the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)?

Start with HR 7 Chiller On/Off (Chiller on/off); HR 14 Chiller Run Mode (Run mode); HR 16 Evaporator Leaving Fluid Temperature (Evaporator leaving water temperature); HR 12 Actual Capacity (Actual capacity); HR 32 Alarm Code - Fault (Active fault alarm code); HR 8 Chiller Enable Setpoint (Chiller enable command); HR 34 Cool Setpoint - Network (Cool setpoint from network).

How do I enable Modbus control of the Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)?

Install the Modbus communication module, set Control Source to BAS (for the enable command) and Remote Enable to Enable (for setpoint, mode and capacity limit) at the unit HMI.

Where is the official Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus) Modbus documentation?

The source is MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (BACnet / Modbus) (ED 19111-4), revision 2026-03, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/19111-4.pdf.

More Daikin Applied Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (BACnet / Modbus) · ED 19111-4 · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.