Chiller · Modbus register map

Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's Ascend ACR is an air-cooled chiller with variable-speed compressors and an optional free-cooling package. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, compressor currents and speeds, power monitor values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 765 Modbus registers for the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Ascend ACR Series C air-cooled chiller (Symbio 800)
Equipment type
Chiller
Registers
765 (14 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 2024-11-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Ascend ACR Series C air-cooled chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Chilled Water SetpointFLOAT32 ABCDActive chilled water setpointRead
IR 2010Running ModeUINT16Running modeRead
IR 3010Run EnableUINT16Run enableRead
IR 3026Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 12Demand Limit SetpointFLOAT32 ABCDDemand limit setpoint (BAS)Read/write
HR 3018Chiller Auto Stop Command BASUINT16Chiller auto/stop commandRead/write
HR 3010Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

765 of 765 shown
Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Active Demand Limit SetpointNeeds: Ice Building not InstalledFLOAT32ABCD%Read
IR16doc 30017Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR18doc 30019Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR22doc 30023Unit Power ConsumptionElectrical power. Needs: Power MonitorFLOAT32ABCDRead
IR24doc 30025Outdoor Air TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Differential Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR36doc 30037Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR38doc 30039Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR40doc 30041Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR42doc 30043Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR44doc 30045Differential Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR46doc 30047Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR48doc 30049Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR50doc 30051Refrigerant Discharge Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR52doc 30053High Side Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR54doc 30055Refrigerant Discharge Temperature - Compressor 2ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR56doc 30057High Side Oil Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR58doc 30059Air Flow Percentage Circuit 1FLOAT32ABCD%Read
IR60doc 30061Air Flow Percentage Circuit 2FLOAT32ABCD%Read
IR62doc 30063Drive Motor Average Voltage Circuit 1Voltage. Needs: PF755 TR200FLOAT32ABCDRead
IR64doc 30065Drive Motor Current U Circuit 1Current. Needs: PF755 TR200FLOAT32ABCDRead
IR66doc 30067Drive Motor Current V Circuit 1Current. Needs: PF755 TR200FLOAT32ABCDRead
IR68doc 30069Drive Motor Current W Circuit 1Current. Needs: PF755 TR200FLOAT32ABCDRead
IR70doc 30071Drive Motor Current U RLA Circuit 1Needs: PF755 TR200FLOAT32ABCD%Read
IR72doc 30073Drive Motor Current V RLA Circuit 1Needs: PF755 TR200FLOAT32ABCD%Read
IR74doc 30075Drive Motor Current W RLA Circuit 1Needs: PF755 TR200FLOAT32ABCD%Read
IR76doc 30077Drive Motor Average Current RLA Circuit 1Needs: PF755 TR200FLOAT32ABCD%Read
IR78doc 30079Drive DC Bus Voltage Circuit 1Voltage. Needs: PF755 TR200FLOAT32ABCDRead
IR80doc 30081Drive Output Power Circuit 1Electrical power. Needs: PF755 TR200FLOAT32ABCDRead
IR82doc 30083AFD Transistor Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: PF755 TR200FLOAT32ABCDRead
IR84doc 30085Motor Winding Temperature 1 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR86doc 30087Motor Winding Temperature 2 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR88doc 30089Drive Motor Average Voltage Circuit 2Voltage. Needs: PF755 TR200FLOAT32ABCDRead
IR90doc 30091Drive Motor Current U Circuit 2Current. Needs: PF755 TR200FLOAT32ABCDRead
IR92doc 30093Drive Motor Current V Circuit 2Current. Needs: PF755 TR200FLOAT32ABCDRead
IR94doc 30095Drive Motor Current W Circuit 2Current. Needs: PF755 TR200FLOAT32ABCDRead
IR96doc 30097Drive Motor Current U RLA Circuit 2Needs: PF755 TR200FLOAT32ABCD%Read
IR98doc 30099Drive Motor Current V RLA Circuit 2Needs: PF755 TR200FLOAT32ABCD%Read
IR100doc 30101Drive Motor Current W RLA Circuit 2Needs: PF755 TR200FLOAT32ABCD%Read
IR102doc 30103Drive Motor Average Current RLA Circuit 2Needs: PF755 TR200FLOAT32ABCD%Read
IR104doc 30105Drive DC Bus Voltage Circuit 2Voltage. Needs: PF755 TR200FLOAT32ABCDRead
IR106doc 30107Drive Output Power Circuit 2Electrical power. Needs: PF755 TR200FLOAT32ABCDRead
IR108doc 30109AFD Transistor Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: PF755FLOAT32ABCDRead
IR110doc 30111Motor Winding Temperature 1 Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR112doc 30113Motor Winding Temperature 2 Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR114doc 30115Sub Cooled Liquid Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR116doc 30117Sub Cooled Liquid Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR118doc 30119Evaporator Differential Water PressureDifferential water pressure; the list prints the unit as Temperature. Needs: Variable Primary FlowFLOAT32ABCDRead
IR120doc 30121System Chilled Water Differential PressurePressure in the factory unit system (I-P or SI). Needs: Variable Primary FlowFLOAT32ABCDRead
IR126doc 30127Phase AB Voltage - Compressor 1BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR128doc 30129Line 1 Current - Compressor 1BCurrent.FLOAT32ABCDRead
IR130doc 30131Line 2 Current - Compressor 1BCurrent.FLOAT32ABCDRead
IR132doc 30133Line 3 Current - Compressor 1BCurrent.FLOAT32ABCDRead
IR134doc 30135Line 1 Current RLA - Compressor 1BFLOAT32ABCD%Read
IR136doc 30137Line 2 Current RLA - Compressor 1BFLOAT32ABCD%Read
IR138doc 30139Line 3 Current RLA - Compressor 1BFLOAT32ABCD%Read
IR140doc 30141Phase AB Voltage - Compressor 2BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR142doc 30143Line 1 Current - Compressor 2BCurrent.FLOAT32ABCDRead
IR144doc 30145Line 2 Current - Compressor 2BCurrent.FLOAT32ABCDRead
IR146doc 30147Line 3 Current - Compressor 2BCurrent.FLOAT32ABCDRead
IR148doc 30149Line 1 Current RLA - Compressor 2BFLOAT32ABCD%Read
IR150doc 30151Line 2 Current RLA - Compressor 2BFLOAT32ABCD%Read
IR152doc 30153Line 3 Current RLA - Compressor 2BFLOAT32ABCD%Read
IR156doc 30157Refrigerant Discharge Temperature - Compressor 1BTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR158doc 30159High Side Oil Pressure - Compressor 1BPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR160doc 30161Refrigerant Discharge Temperature - Compressor 2BTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR162doc 30163High Side Oil Pressure - Compressor 2BPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR164doc 30165Number of CircuitsFLOAT32ABCDRead
IR166doc 30167Number of Compressors Circuit 1FLOAT32ABCDRead
IR168doc 30169Number of Compressors Circuit 2FLOAT32ABCDRead
IR170doc 30171Actual Running CapacityFLOAT32ABCD%Read
IR172doc 30173Free Cooling Capacity StatusNeeds: Free CoolingFLOAT32ABCD%Read
IR174doc 30175Free Cooling Entering Water Temperature ActiveTemperature in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR180doc 30181Evaporator Differential Water Pressure Setpoint StatusPressure in the factory unit system (I-P or SI). Needs: Variable Primary FlowFLOAT32ABCDRead
IR182doc 30183Energy Consumption LifetimeElectrical energy. Needs: Power MonitorFLOAT32ABCDRead
IR184doc 30185Energy ConsumptionElectrical energy. Needs: Power MonitorFLOAT32ABCDRead
IR186doc 30187Starts - Compressor 1AFLOAT32ABCDRead
IR188doc 30189Run Time - Compressor 1AFLOAT32ABCDRead
IR190doc 30191Starts - Compressor 2AFLOAT32ABCDRead
IR192doc 30193Run Time - Compressor 2AFLOAT32ABCDRead
IR194doc 30195Starts - Compressor 1BFLOAT32ABCDRead
IR196doc 30197Run Time - Compressor 1BFLOAT32ABCDRead
IR198doc 30199Starts - Compressor 2BFLOAT32ABCDRead
IR200doc 30201Run Time - Compressor 2BFLOAT32ABCDRead
IR202doc 30203Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR206doc 30207Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR208doc 30209Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR210doc 30211Unit Source IDFLOAT32ABCDRead
IR212doc 30213Drive Input Voltage Calculated 1AVoltage. Needs: PF755 TR200FLOAT32ABCDRead
IR214doc 30215Drive Input Voltage Calculated 2AVoltage. Needs: PF755 TR200FLOAT32ABCDRead
IR216doc 30217Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR218doc 30219Phase BC Voltage - Compressor 1BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR220doc 30221Phase CA Voltage - Compressor 1BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR222doc 30223Phase BC Voltage - Compressor 2BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR224doc 30225Phase CA Voltage - Compressor 2BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR226doc 30227Average Line Current Circuit 1Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR228doc 30229Average Line Current Circuit 2Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR230doc 30231Average Line Voltage Circuit 1Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR232doc 30233Average Line Voltage Circuit 2Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR234doc 30235Line Current L1 Circuit 1Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR236doc 30237Line Current L2 Circuit 1Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR238doc 30239Line Current L3 Circuit 1Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR240doc 30241Line Current L1 Circuit 2Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR242doc 30243Line Current L2 Circuit 2Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR244doc 30245Line Current L3 Circuit 2Current. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR246doc 30247Voltage L1-L2 Circuit 1Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR248doc 30249Voltage L2-L3 Circuit 1Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR250doc 30251Voltage L1-L3 Circuit 1Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR252doc 30253Voltage L1-L2 Circuit 2Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR254doc 30255Voltage L2-L1 Circuit 2Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR256doc 30257Voltage L1-L3 Circuit 2Voltage. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR258doc 30259Total Real PowerElectrical power. Needs: Power MonitorFLOAT32ABCDRead
IR260doc 30261Line Frequency Circuit 1Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR262doc 30263Line Frequency Circuit 2Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR264doc 30265Power Factor Circuit 1Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR266doc 30267Power Factor Circuit 2Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR268doc 30269Power Demand Circuit 1Electrical power. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR270doc 30271Power Demand Circuit 2Electrical power. Needs: Two Energy Meters InstalledFLOAT32ABCDRead
IR272doc 30273Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR284doc 30285Evaporator Water Flow RateFlow in the factory unit system (I-P or SI). Needs: Evap Water Flow MeasurementFLOAT32ABCDRead
IR286doc 30287Evaporator Differential Water PressureNeeds: Evap Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR288doc 30289Entering Evaporator Water PressureNeeds: Evap Water Flow Measurement Dual Pressure SensorsFLOAT32ABCDRead
IR290doc 30291Leaving Evaporator Water PressureNeeds: Evap Water Flow Measurement Dual Pressure SensorsFLOAT32ABCDRead
IR292doc 30293Power FactorNeeds: One Energy Meter InstalledFLOAT32ABCDRead
IR294doc 30295Current L1Current. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR296doc 30297Current L2Current. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR298doc 30299Current L3Current. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR300doc 30301Average CurrentCurrent. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR302doc 30303Voltage L1-L2Voltage. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR304doc 30305Voltage L2-L3Voltage. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR306doc 30307Voltage L1-L3Voltage. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR310doc 30311Average Voltage L-LVoltage. Needs: One Energy Meter InstalledFLOAT32ABCDRead
IR312doc 30313Line FrequencyNeeds: One Energy Meter InstalledFLOAT32ABCDRead
IR314doc 30315AFD Coolant Supply Temperature CompressorTemperature in the factory unit system (I-P or SI). Needs: PF755FLOAT32ABCDRead
IR316doc 30317AFD Coolant Supply Temperature CompressorTemperature in the factory unit system (I-P or SI). Needs: PF755FLOAT32ABCDRead
IR318doc 30319Evaporator Water Pump Speed CommandNeeds: Evap Pump Control - Variable SpeedFLOAT32ABCD%Read
IR320doc 30321Evaporator Water Pump Speed FeedbackNeeds: Evap Pump Control - Variable SpeedFLOAT32ABCD%Read
IR322doc 30323Evaporator Water Pump Speed Setpoint ActiveNeeds: Evap Pump Variable Speed Type - Direct Pump Speed ControlFLOAT32ABCD%Read
IR324doc 30325Evaporator Water Pump Flow Rate Setpoint AcNeeds: Evap Pump Variable Speed Type - Water Flow ControlFLOAT32ABCDRead
IR326doc 30327Free Cooling Dedicated Fans AirflowNeeds: Free Cooling Dedicated FansFLOAT32ABCD%Read
IR328doc 30329Drive Heat Sink Temperature Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: TR200FLOAT32ABCDRead
IR330doc 30331Drive Heat Sink Temperature Compressor 2ATemperature in the factory unit system (I-P or SI). Needs: TR200FLOAT32ABCDRead
IR332doc 30333Compressor 1A Speed StatusNeeds: PF755 TR200FLOAT32ABCD%Read
IR334doc 30335Compressor 2A Speed StatusNeeds: PF755 TR200FLOAT32ABCD%Read
IR336doc 30337Calculated Chiller CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR338doc 30339Free Cooling Target OffsetTemperature difference, factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR340doc 30341Free Cooling Valve Position StatusNeeds: Free CoolingFLOAT32ABCD%Read
IR342doc 30343Active Demand Limit SetpointNeeds: Ice BuildingFLOAT32ABCD%Read
IR344doc 30345Evaporator Refrigerant Absolute Pressure CircuPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR346doc 30347Condenser Refrigerant Absolute Pressure CircuPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR348doc 30349Evaporator Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR350doc 30351Condenser Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR352doc 30353High Side Oil Absolute Pressure - CompressorPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR354doc 30355High Side Oil Absolute Pressure - CompressorPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR356doc 30357High Side Oil Absolute Pressure - CompressorPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR358doc 30359High Side Oil Absolute Pressure - CompressorPressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR360doc 30361Entering Evaporator Water Absolute PressureNeeds: Evap Water Flow Measurement Dual Pressure SensorsFLOAT32ABCDRead
IR362doc 30363Leaving Evaporator Water Absolute PressureNeeds: Evap Water Flow Measurement Dual Pressure SensorsFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E)
IR2013doc 32014Cooling TypeUINT16Read1 = Water Cooled; 2 = Air Cooled
IR2014doc 32015Manufacture LocationUINT16Read1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey
IR2016doc 32017Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR3010doc 33011Run EnableUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3011doc 33012Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3012doc 33013Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR3013doc 33014Chiller Running StateUINT16Read0 = Off; 1 = On
IR3014doc 33015Maximum CapacityUINT16Read0 = Off; 1 = On
IR3016doc 33017Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3017doc 33018Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3018doc 33019Compressor 2A StatusUINT16Read0 = Off; 1 = Running
IR3019doc 33020Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3020doc 33021Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3021doc 33022Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3022doc 33023Compressor 1B StatusUINT16Read0 = Off; 1 = Running
IR3023doc 33024Compressor 2B StatusUINT16Read0 = Off; 1 = Running
IR3024doc 33025Free Cooling ActiveNeeds: Free CoolingUINT16Read0 = Inactive; 1 = Active
IR3026doc 33027Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3028doc 33029Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3029doc 33030Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3031doc 33032Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3032doc 33033Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3033doc 33034Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3034doc 33035External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3035doc 33036Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3036doc 33037Noise Reduction Request ActiveNeeds: Low NoiseUINT16Read0 = Off; 1 = On
IR3037doc 33038Circuit 1 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3038doc 33039Circuit 2 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3039doc 33040Circuit 1 Lockout ExternalUINT16Read0 = Normal; 1 = Locked Out
IR3040doc 33041Circuit 2 Lockout ExternalUINT16Read0 = Normal; 1 = Locked Out
IR3041doc 33042Circuit 1 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3042doc 33043Circuit 2 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3043doc 33044Circuit 1 AvailableUINT16Read0 = Unavailable; 1 = Available
IR3044doc 33045Circuit 2 AvailableUINT16Read0 = Unavailable; 1 = Available
IR3045doc 33046Oil Sensor Circuit 1UINT16Read0 = Dry; 1 = Wet
IR3046doc 33047Oil Sensor Circuit 2UINT16Read0 = Dry; 1 = Wet
IR3047doc 33048Evaporator Water Pump 1 Inverter Running StatusNeeds: Evap Pump Control Variable SpeedUINT16Read0 = Off; 1 = On
IR3048doc 33049Evaporator Water Pump 1 Fault StatusNeeds: Evap Pump Control Variable SpeedUINT16Read0 = Fault; 1 = No Fault
IR3049doc 33050Compressor 1B Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3050doc 33051Compressor 2B Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3051doc 33052Free Cooling Front Panel Command StatusNeeds: Free CoolingUINT16Read0 = Off; 1 = Auto
IR4000doc 34001Diagnostic: AFD 1A Bus Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic: AFD 1A Bus Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: AFD 1A Comm Loss: Main ProcessorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic: AFD 1A Customized Protection FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic: AFD 1A Gate Kill ActiveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: AFD 1A General Failure (PF755)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: AFD 1A General Failure (TR200)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: AFD 1A Ground FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: AFD 1A Input Phase LossDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: AFD 1A Input Transf or Filter Over TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic: AFD 1A Loss Of Motor ControlDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic: AFD 1A Low Rotor Flux FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic: AFD 1A Motor Current OverloadDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Diagnostic: AFD 1A Motor FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic: AFD 1A Motor ShortedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: AFD 1A Over TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: AFD 1A Precharge FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: AFD 2A Bus Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: AFD 2A Bus Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: AFD 2A Comm Loss: Main ProcessorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: AFD 2A Customized Protection FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: AFD 2A Gate Kill ActiveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: AFD 2A General Failure (PF755)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: AFD 2A General Failure (TR200)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: AFD 2A Ground FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: AFD 2A Input Phase LossDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: AFD 2A Input Transf or Filter Over TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: AFD 2A Loss Of Motor ControlDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: AFD 2A Low Rotor Flux FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: AFD 2A Motor Current OverloadDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: AFD 2A Motor FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic: AFD 2A Motor ShortedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: AFD 2A Over TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: AFD 2A Precharge FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: AFD Bus Over Voltage - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: AFD Bus Over Voltage - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Diagnostic: AFD Bus Under Voltage - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic: AFD Bus Under Voltage - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: AFD Comm Loss – 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic: AFD Comm Loss – 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Diagnostic: AFD Comm Loss: Main Processor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Diagnostic: AFD Comm Loss: Main Processor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Diagnostic: AFD Failure to Arm or Start - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: AFD Failure to Arm or Start - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: AFD Fault Mains - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: AFD Fault Mains - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: AFD General Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: AFD General Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: AFD Ground Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic: AFD Ground Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic: AFD Harmonic Filter Over Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Diagnostic: AFD Harmonic Filter Over Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: AFD High Pressure Cutout - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: AFD High Pressure Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: AFD High Torque - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic: AFD High Torque - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic: AFD Initialized - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Diagnostic: AFD Initialized - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic: AFD Internal Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Diagnostic: AFD Internal Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Diagnostic: AFD Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Diagnostic: AFD Interrupt Failure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Diagnostic: AFD Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Diagnostic: AFD Interrupt Failure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: AFD Inverter Heatsink Over Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: AFD Inverter Heatsink Over Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Diagnostic: AFD Locked Rotor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Diagnostic: AFD Locked Rotor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic: AFD Mains Phase Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: AFD Mains Phase Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: AFD Missing Motor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: AFD Missing Motor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Diagnostic: AFD Motor Current Overload - 1A (TR200)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Diagnostic: AFD Motor Current Overload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Diagnostic: AFD Motor Current Overload - 2A (TR200)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Diagnostic: AFD Motor Current Overload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Diagnostic: AFD Motor Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Diagnostic: AFD Motor Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Diagnostic: AFD New Spare Parts - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Diagnostic: AFD New Spare Parts - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Diagnostic: AFD Option Configuration Change - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Diagnostic: AFD Option Configuration Change - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Diagnostic: AFD Output Phase U Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Diagnostic: AFD Output Phase U Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Diagnostic: AFD Output Phase V Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Diagnostic: AFD Output Phase V Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Diagnostic: AFD Output Phase W Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Diagnostic: AFD Output Phase W Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Diagnostic: AFD Over Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Diagnostic: AFD Over Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Diagnostic: AFD Short Circuit - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Diagnostic: AFD Short Circuit - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Diagnostic: AFD Unexpected Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Diagnostic: AFD Unexpected Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Diagnostic: Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Diagnostic: Chiller Service RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: %RLA Indication Output(Vdc)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: AFD Fault Input 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: AFD Fault Input 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Comm Loss: AFD Fault Input 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: AFD Fault Input 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Auxiliary Setpoint CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Cond Fan Enbl Shared Ckt 1&2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Comm Loss: Cond Rfgt Tank Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Comm Loss: Cond Rfgt Tank Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Comm Loss: Condenser Fan Enable Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: Condenser Fan Enable Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Condenser Rfgt Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: Condenser Rfgt Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: Cprsr Disch Rfgt Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: Cprsr Disch Rfgt Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: Cprsr Disch Rfgt Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: Cprsr Disch Rfgt Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: Drive Cooling Bypass Valve 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: Drive Cooling Bypass Valve 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Comm Loss: Drive Cooling Supply Temp 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Comm Loss: Drive Cooling Supply Temp 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Comm Loss: Economizer Disch Press - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Comm Loss: Economizer Disch Press - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: Economizer Disch Press - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Economizer Disch Press - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Economizer Disch Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Economizer Disch Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Comm Loss: Economizer Disch Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Comm Loss: Economizer Disch Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Comm Loss: Economizer Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Comm Loss: Economizer Valve - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Comm Loss: Economizer Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Comm Loss: Economizer Valve - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: Electronic Expansion Valve 1 Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Electronic Expansion Valve 1 Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Electronic Expansion Valve 2 Compressor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Electronic Expansion Valve 2 Compressor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Energy Meter 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Energy Meter 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Evap Diff Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: Evap Iso Valve Close Switch Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Comm Loss: Evap Iso Valve Close Switch Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Comm Loss: Evap Iso Valve Open Switch Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Evap Iso Valve Open Switch Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Evap Isolation Valve Relay Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Comm Loss: Evap Isolation Valve Relay Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Comm Loss: Evap Pump Inv1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Comm Loss: Evap Pump Inv1 Run CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Comm Loss: Evap Rfgt Pool Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Evap Rfgt Pool Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Comm Loss: Evap Water Pump Inv Freq InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Comm Loss: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Comm Loss: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Comm Loss: Evaporator Oil Return Purge Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Comm Loss: Evaporator Oil Return Purge Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Comm Loss: Evaporator Pump 1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Comm Loss: Evaporator Pump 2 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Comm Loss: Evaporator Pump Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Comm Loss: Evaporator Pump Inverter Running StatusDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Comm Loss: Evaporator Pump Speed CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Comm Loss: Evaporator Pump Speed FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Comm Loss: Evaporator Water Pump 1 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Comm Loss: Evaporator Water Pump 2 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Comm Loss: Ext Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Comm Loss: Ext Noise Reduction RequestDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Comm Loss: External Ckt Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Comm Loss: External Ckt Lockout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Comm Loss: External Heat Recovery CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Comm Loss: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Comm Loss: Fan Board 1 Relay 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Comm Loss: Fan Board 1 Relay 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Comm Loss: Fan Board 1 Relay 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Comm Loss: Fan Board 1 Relay 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Comm Loss: Fan Board 1 Relay 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Comm Loss: Fan Board 1 Relay 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Comm Loss: Fan Board 1 Relay 4 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Comm Loss: Fan Board 1 Relay 4 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Comm Loss: Fan Board 2 Relay 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Comm Loss: Fan Board 2 Relay 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Comm Loss: Fan Board 2 Relay 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Comm Loss: Fan Board 2 Relay 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Comm Loss: Fan Board 2 Relay 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Comm Loss: Fan Board 2 Relay 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Comm Loss: Fan Board 2 Relay 4 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Comm Loss: Fan Board 2 Relay 4 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1 & 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Comm Loss: Fan Inverter Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Comm Loss: Fan Inverter Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Comm Loss: Fan Inverter Speed Command Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Comm Loss: Fan Inverter Speed Command Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Comm Loss: FC Entering Glycol TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Comm Loss: FC Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Comm Loss: FC Leaving Glycol TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Comm Loss: Free Cooling Bypass ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Comm Loss: Free Cooling Dedicated Fan EnableDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Comm Loss: Free Cooling Dedicated Fan Inverter FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Comm Loss: Free Cooling Dedicated Fan Inverter Speed CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Comm Loss: Free Cooling Glycol Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Comm Loss: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Comm Loss: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Comm Loss: Free Cooling PumpDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Comm Loss: Free Cooling ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Comm Loss: Heat Recovery Mode Valve Command - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Comm Loss: Heat Recovery Mode Valve Command - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Comm Loss: Heat Recovery Water Flow CmdDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Comm Loss: Heat Recovery Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Comm Loss: Heat Recovery Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Comm Loss: High Pressure Cutout Sw - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Comm Loss: High Pressure Cutout Sw - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Comm Loss: High Pressure Cutout Sw - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Comm Loss: High Pressure Cutout Sw - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Comm Loss: Hot Gas Oil Return Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Comm Loss: Hot Gas Oil Return Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Comm Loss: HR Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Comm Loss: HR Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Comm Loss: Liquid Line Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Comm Loss: Liquid Line Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Comm Loss: Liquid Line Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Comm Loss: Liquid Line Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Comm Loss: Motor Winding Tstat Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Comm Loss: Motor Winding Tstat Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Comm Loss: Off-cycle Freeze Prot RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Comm Loss: Oil Loss Level Sensor Input Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Comm Loss: Oil Loss Level Sensor Input Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Comm Loss: Oil Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Comm Loss: Oil Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Comm Loss: Oil Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Comm Loss: Oil Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Comm Loss: Oil Return Solenoid Valve - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Comm Loss: Oil Return Solenoid Valve - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Comm Loss: Oil Return Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Comm Loss: Oil Return Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Comm Loss: Oil Supply TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Comm Loss: Oil Supply TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Comm Loss: Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Comm Loss: Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Comm Loss: Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Comm Loss: Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Comm Loss: Programmable Relay Board 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Comm Loss: Slide Valve Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Comm Loss: Slide Valve Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Comm Loss: Slide Valve Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Comm Loss: Slide Valve Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Comm Loss: Slide Valve Unload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Comm Loss: Slide Valve Unload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Comm Loss: Slide Valve Unload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Comm Loss: Slide Valve Unload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Comm Loss: Starter 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Comm Loss: Starter 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4257doc 34258Comm Loss: Starter 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4258doc 34259Comm Loss: Starter 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4259doc 34260Comm Loss: Step Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4260doc 34261Comm Loss: Step Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4261doc 34262Comm Loss: Step Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4262doc 34263Comm Loss: Step Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4263doc 34264Comm Loss: Suction Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4264doc 34265Comm Loss: Suction Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4265doc 34266Comm Loss: Suction Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4266doc 34267Comm Loss: Suction Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4267doc 34268Comm Loss: Var Vi Valve – Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4268doc 34269Comm Loss: Var Vi Valve – Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4269doc 34270Comm Loss: Winding Temp 1, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4270doc 34271Comm Loss: Winding Temp 1, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4271doc 34272Comm Loss: Winding Temp 2, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4272doc 34273Comm Loss: Winding Temp 2, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4273doc 34274Diagnostic: Condenser Rfgt Pressure Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4274doc 34275Diagnostic: Condenser Rfgt Pressure Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4275doc 34276Diagnostic: Cprsr Did Not Accel: Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4276doc 34277Diagnostic: Cprsr Did Not Accel: Shutdown - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4277doc 34278Diagnostic: Cprsr Did Not Accel: Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4278doc 34279Diagnostic: Cprsr Did Not Accel: Shutdown - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4279doc 34280Diagnostic: Cprsr Did Not Accel: Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4280doc 34281Diagnostic: Cprsr Did Not Accel: Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4281doc 34282Diagnostic: Cprsr Did Not Accel: Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4282doc 34283Diagnostic: Cprsr Did Not Accel: Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4283doc 34284Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4284doc 34285Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4285doc 34286Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4286doc 34287Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4287doc 34288Diagnostic: Drive Cooling Supply Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4288doc 34289Diagnostic: Drive Cooling Supply Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4289doc 34290Diagnostic: Economizer Disch Press Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4290doc 34291Diagnostic: Economizer Disch Press Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4291doc 34292Diagnostic: Economizer Disch Press Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4292doc 34293Diagnostic: Economizer Disch Press Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4293doc 34294Diagnostic: Economizer Disch Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4294doc 34295Diagnostic: Economizer Disch Temp Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4295doc 34296Diagnostic: Economizer Disch Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4296doc 34297Diagnostic: Economizer Disch Temp Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4297doc 34298Diagnostic: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4298doc 34299Diagnostic: Evap Iso Valve Illegal Switch State Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4299doc 34300Diagnostic: Evap Iso Valve Illegal Switch State Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4300doc 34301Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4301doc 34302Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4302doc 34303Diagnostic: Evap Isolation Valve Failed To Close Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4303doc 34304Diagnostic: Evap Isolation Valve Failed To Close Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4304doc 34305Diagnostic: Evap Isolation Valve Failed To Open Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4305doc 34306Diagnostic: Evap Isolation Valve Failed To Open Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4306doc 34307Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4307doc 34308Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4308doc 34309Diagnostic: Evap Pump 1 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4309doc 34310Diagnostic: Evap Pump 2 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4310doc 34311Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4311doc 34312Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4312doc 34313Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4313doc 34314Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4314doc 34315Diagnostic: Evap Water Pump 1 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4315doc 34316Diagnostic: Evap Water Pump 2 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4316doc 34317Diagnostic: Evaporator Approach Error Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4317doc 34318Diagnostic: Evaporator Approach Error Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4318doc 34319Diagnostic: Evaporator Diff Water Pressure XdcrDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4319doc 34320Diagnostic: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4320doc 34321Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4321doc 34322Diagnostic: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4322doc 34323Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4323doc 34324Diagnostic: Evaporator Pump 1 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4324doc 34325Diagnostic: Evaporator Pump 2 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4325doc 34326Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4326doc 34327Diagnostic: Evaporator Water Flow Lost - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4327doc 34328Diagnostic: Evaporator Water Flow Lost - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4328doc 34329Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4329doc 34330Diagnostic: Evaporator Water Flow Overdue - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4330doc 34331Diagnostic: Evaporator Water Flow Overdue - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4331doc 34332Diagnostic: Evaporator Water Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4332doc 34333Diagnostic: Evaporator Water Pump Speed FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4333doc 34334Diagnostic: Excessive Condenser Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4334doc 34335Diagnostic: Excessive Condenser Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4335doc 34336Diagnostic: External Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4336doc 34337Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4337doc 34338Diagnostic: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4338doc 34339Diagnostic: Fan Inverter Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4339doc 34340Diagnostic: Fan Inverter Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4340doc 34341Diagnostic: Free Cooling Dedicated Fan Inverter FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4341doc 34342Diagnostic: Free Cooling Entering Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4342doc 34343Diagnostic: Free Cooling Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4343doc 34344Diagnostic: Free Cooling Glycol Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4344doc 34345Diagnostic: Free Cooling Glycol Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4345doc 34346Diagnostic: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4346doc 34347Diagnostic: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4347doc 34348Diagnostic: Free Cooling Glycol Temperature Equalization OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4348doc 34349Diagnostic: Free Cooling Leaving Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4349doc 34350Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4350doc 34351Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4351doc 34352Diagnostic: Heat Recovery Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4352doc 34353Diagnostic: Heat Recovery Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4353doc 34354Diagnostic: High Cprsr Rfgt Discharge Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4354doc 34355Diagnostic: High Cprsr Rfgt Discharge Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4355doc 34356Diagnostic: High Cprsr Rfgt Discharge Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4356doc 34357Diagnostic: High Cprsr Rfgt Discharge Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4357doc 34358Diagnostic: High Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4358doc 34359Diagnostic: High Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4359doc 34360Diagnostic: High Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4360doc 34361Diagnostic: High Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4361doc 34362Diagnostic: High Evaporator Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4362doc 34363Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4363doc 34364Diagnostic: High Motor Winding Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4364doc 34365Diagnostic: High Motor Winding Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4365doc 34366Diagnostic: High Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4366doc 34367Diagnostic: High Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4367doc 34368Diagnostic: High Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4368doc 34369Diagnostic: High Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4369doc 34370Diagnostic: High Pressure Cutout - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4370doc 34371Diagnostic: High Pressure Cutout - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4371doc 34372Diagnostic: High Pressure Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4372doc 34373Diagnostic: High Pressure Cutout - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4373doc 34374Diagnostic: High Refrigerant Pressure Ratio - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4374doc 34375Diagnostic: High Refrigerant Pressure Ratio - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4375doc 34376Diagnostic: High Refrigerant Pressure Ratio - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4376doc 34377Diagnostic: High Refrigerant Pressure Ratio - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4377doc 34378Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4378doc 34379Diagnostic: Liquid Line Pressure Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4379doc 34380Diagnostic: Liquid Line Pressure Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4380doc 34381Diagnostic: Liquid Line Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4381doc 34382Diagnostic: Liquid Line Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4382doc 34383Diagnostic: Loss of Oil for Compressor (Running) Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4383doc 34384Diagnostic: Loss of Oil for Compressor (Running) Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4384doc 34385Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4385doc 34386Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4386doc 34387Diagnostic: Low Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4387doc 34388Diagnostic: Low Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4388doc 34389Diagnostic: Low Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4389doc 34390Diagnostic: Low Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4390doc 34391Diagnostic: Low Discharge Superheat - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4391doc 34392Diagnostic: Low Discharge Superheat - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4392doc 34393Diagnostic: Low Discharge Superheat - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4393doc 34394Diagnostic: Low Discharge Superheat - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4394doc 34395Diagnostic: Low Drive Cooling Supply Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4395doc 34396Diagnostic: Low Drive Cooling Supply Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4396doc 34397Diagnostic: Low Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4397doc 34398Diagnostic: Low Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4398doc 34399Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4399doc 34400Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4400doc 34401Diagnostic: Low Evaporator Water FlowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4401doc 34402Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4402doc 34403Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4403doc 34404Diagnostic: Low Glycol Pressure Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4404doc 34405Diagnostic: Low Glycol Temp Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4405doc 34406Diagnostic: Low Oil Flow - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4406doc 34407Diagnostic: Low Oil Flow - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4407doc 34408Diagnostic: Low Oil Flow - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4408doc 34409Diagnostic: Low Oil Flow - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4409doc 34410Diagnostic: Low Refrigerant Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4410doc 34411Diagnostic: Low Refrigerant Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4411doc 34412Diagnostic: Low Suction Refrigerant Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4412doc 34413Diagnostic: Low Suction Refrigerant Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4413doc 34414Diagnostic: Low Suction Refrigerant Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4414doc 34415Diagnostic: Low Suction Refrigerant Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4415doc 34416Diagnostic: Mfr Maintenance Recommended - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4416doc 34417Diagnostic: Mfr Maintenance Recommended - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4417doc 34418Diagnostic: Mfr Maintenance Recommended - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4418doc 34419Diagnostic: Mfr Maintenance Recommended - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4419doc 34420Diagnostic: Momentary Power Loss Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4420doc 34421Diagnostic: Momentary Power Loss Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4421doc 34422Diagnostic: Motor Current Overload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4422doc 34423Diagnostic: Motor Current Overload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4423doc 34424Diagnostic: Motor Current Overload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4424doc 34425Diagnostic: Motor Current Overload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4425doc 34426Diagnostic: Motor Winding Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4426doc 34427Diagnostic: Motor Winding Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4427doc 34428Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4428doc 34429Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4429doc 34430Diagnostic: No Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4430doc 34431Diagnostic: No Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4431doc 34432Diagnostic: No Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4432doc 34433Diagnostic: No Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4433doc 34434Diagnostic: Oil Filter Change Recommended - Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4434doc 34435Diagnostic: Oil Filter Change Recommended - Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4435doc 34436Diagnostic: Oil Flow Protection Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4436doc 34437Diagnostic: Oil Flow Protection Fault - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4437doc 34438Diagnostic: Oil Flow Protection Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4438doc 34439Diagnostic: Oil Flow Protection Fault - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4439doc 34440Diagnostic: Oil Pressure Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4440doc 34441Diagnostic: Oil Pressure Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4441doc 34442Diagnostic: Oil Pressure Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4442doc 34443Diagnostic: Oil Pressure Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4443doc 34444Diagnostic: Oil Supply Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4444doc 34445Diagnostic: Oil Supply Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4445doc 34446Diagnostic: Oil Temperature Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4446doc 34447Diagnostic: Oil Temperature Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4447doc 34448Diagnostic: Oil Temperature Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4448doc 34449Diagnostic: Oil Temperature Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4449doc 34450Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4450doc 34451Diagnostic: Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4451doc 34452Diagnostic: Phase Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4452doc 34453Diagnostic: Phase Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4453doc 34454Diagnostic: Phase Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4454doc 34455Diagnostic: Phase Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4455doc 34456Diagnostic: Phase Reversal - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4456doc 34457Diagnostic: Phase Reversal - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4457doc 34458Diagnostic: Phase Reversal - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4458doc 34459Diagnostic: Phase Reversal - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4459doc 34460Diagnostic: Power Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4460doc 34461Diagnostic: Power Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4461doc 34462Diagnostic: Power Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4462doc 34463Diagnostic: Power Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4463doc 34464Diagnostic: Pumpdown Terminated By Time Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4464doc 34465Diagnostic: Pumpdown Terminated By Time Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4465doc 34466Diagnostic: Restart Inhibit Invoked - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4466doc 34467Diagnostic: Restart Inhibit Invoked - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4467doc 34468Diagnostic: Restart Inhibit Invoked - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4468doc 34469Diagnostic: Restart Inhibit Invoked - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4469doc 34470Diagnostic: Severe Current Imbalance - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4470doc 34471Diagnostic: Severe Current Imbalance - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4471doc 34472Diagnostic: Severe Current Imbalance - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4472doc 34473Diagnostic: Severe Current Imbalance - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4473doc 34474Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4474doc 34475Diagnostic: Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4475doc 34476Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4476doc 34477Diagnostic: Starter Comm Loss: Main Processor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4477doc 34478Diagnostic: Starter Comm Loss: Main Processor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4478doc 34479Diagnostic: Starter Comm Loss: Main Processor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4479doc 34480Diagnostic: Starter Comm Loss: Main Processor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4480doc 34481Diagnostic: Starter Contactor Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4481doc 34482Diagnostic: Starter Contactor Interrupt Failure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4482doc 34483Diagnostic: Starter Contactor Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4483doc 34484Diagnostic: Starter Contactor Interrupt Failure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4484doc 34485Diagnostic: Starter Did Not Fully AccelerateDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4485doc 34486Diagnostic: Starter Did Not Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4486doc 34487Diagnostic: Starter Did Not Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4487doc 34488Diagnostic: Starter Did Not Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4488doc 34489Diagnostic: Starter Did Not Fully Accelerate Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4489doc 34490Diagnostic: Starter Did Not Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4490doc 34491Diagnostic: Starter Dry Run Test - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4491doc 34492Diagnostic: Starter Dry Run Test - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4492doc 34493Diagnostic: Starter Dry Run Test - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4493doc 34494Diagnostic: Starter Dry Run Test - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4494doc 34495Diagnostic: Starter Failed to Arm/Start - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4495doc 34496Diagnostic: Starter Failed to Arm/Start - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4496doc 34497Diagnostic: Starter Failed to Arm/Start - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4497doc 34498Diagnostic: Starter Failed to Arm/Start - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4498doc 34499Diagnostic: Starter Fault Type I - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4499doc 34500Diagnostic: Starter Fault Type I - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4500doc 34501Diagnostic: Starter Fault Type I - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4501doc 34502Diagnostic: Starter Fault Type I - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4502doc 34503Diagnostic: Starter Fault Type II - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4503doc 34504Diagnostic: Starter Fault Type II - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4504doc 34505Diagnostic: Starter Fault Type II - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4505doc 34506Diagnostic: Starter Fault Type II - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4506doc 34507Diagnostic: Starter Fault Type III - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4507doc 34508Diagnostic: Starter Fault Type III - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4508doc 34509Diagnostic: Starter Fault Type III - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4509doc 34510Diagnostic: Starter Fault Type III - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4510doc 34511Diagnostic: Starter Module Memory Error Type 1 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4511doc 34512Diagnostic: Starter Module Memory Error Type 1 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4512doc 34513Diagnostic: Starter Module Memory Error Type 1 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4513doc 34514Diagnostic: Starter Module Memory Error Type 1 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4514doc 34515Diagnostic: Starter Module Memory Error Type 2 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4515doc 34516Diagnostic: Starter Module Memory Error Type 2 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4516doc 34517Diagnostic: Starter Module Memory Error Type 2 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4517doc 34518Diagnostic: Starter Module Memory Error Type 2 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4518doc 34519Diagnostic: Starts/Hours Modified 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4519doc 34520Diagnostic: Starts/Hours Modified 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4520doc 34521Diagnostic: Starts/Hours Modified 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4521doc 34522Diagnostic: Starts/Hours Modified 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4522doc 34523Diagnostic: Suction Refrigerant Pressure Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4523doc 34524Diagnostic: Suction Refrigerant Pressure Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4524doc 34525Diagnostic: Suction Refrigerant Pressure Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4525doc 34526Diagnostic: Suction Refrigerant Pressure Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4526doc 34527Diagnostic: Transition Complete Input Opened - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4527doc 34528Diagnostic: Transition Complete Input Opened - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4528doc 34529Diagnostic: Transition Complete Input Opened - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4529doc 34530Diagnostic: Transition Complete Input Opened - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4530doc 34531Diagnostic: Transition Complete Input Shorted - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4531doc 34532Diagnostic: Transition Complete Input Shorted - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4532doc 34533Diagnostic: Transition Complete Input Shorted - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4533doc 34534Diagnostic: Transition Complete Input Shorted - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4534doc 34535Diagnostic: Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4535doc 34536Diagnostic: Unexpected Starter Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4536doc 34537Diagnostic: Unexpected Starter Shutdown - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4537doc 34538Diagnostic: Unexpected Starter Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4538doc 34539Diagnostic: Unexpected Starter Shutdown - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4539doc 34540Diagnostic: Very Low Evap Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4540doc 34541Diagnostic: Very Low Evap Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4541doc 34542Diagnostic: Very Low Evap Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4542doc 34543Diagnostic: Very Low Evap Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4543doc 34544Diagnostic: Write Command Failure Energy Meter 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4544doc 34545Diagnostic: Write Command Failure Energy Meter 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4545doc 34546Comm Loss: Ice Building Status RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Evaporator Water Pump Flow Rate Setpoint BANeeds: Evap Variable Speed Pump Control - Water Flow ControlFLOAT32ABCDRead/write
HR16doc 40017Evaporator Water Pump Speed Setpoint BASNeeds: Evap Variable Speed Pump Control - Direct Pump Speed ControlFLOAT32ABCD%Read/write
HR3010doc 43011Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3011doc 43012Noise Reduction Request BASNeeds: Low NoiseUINT16Read/write0 = Normal; 1 = Reduce Noise
HR3012doc 43013Circuit 1 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3013doc 43014Circuit 2 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3017doc 43018Energy Consumption ResetNeeds: Power MonitorUINT16Read/write0 = Accumulating; 1 = Reset
HR3018doc 43019Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3019doc 43020Free Cooling Auto Stop Command BASNeeds: Free CoolingUINT16Read/write0 = Stop; 1 = Auto
HR3020doc 43021Free Cooling Compressor LockoutNeeds: Free CoolingUINT16Read/write0 = Nornal; 1 = Locked Out
HR3021doc 43022Compressor 1B Lockout BASUINT16Read/write0 = Nornal; 1 = Locked Out
HR3022doc 43023Compressor 2B Lockout BASUINT16Read/write0 = Nornal; 1 = Locked Out

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)

What Modbus registers does the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) have?

This map lists 765 registers: 751 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)?

Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 2010 Running Mode (Running mode); IR 3010 Run Enable (Run enable); IR 3026 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 12 Demand Limit Setpoint (Demand limit setpoint (BAS)); HR 3018 Chiller Auto Stop Command BAS (Chiller auto/stop command); HR 3010 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Ascend Model ACR Series C (BAS-PTS021A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS021A-EN_11152024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.