Chiller · Modbus register map
Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's Ascend ACR is an air-cooled chiller with variable-speed compressors and an optional free-cooling package. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, compressor currents and speeds, power monitor values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 765 Modbus registers for the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- Ascend ACR Series C air-cooled chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 765 (14 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR
Integration notes: Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Chilled Water Setpoint | FLOAT32 ABCD | Active chilled water setpoint | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3010 | Run Enable | UINT16 | Run enable | Read |
| IR 3026 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 12 | Demand Limit Setpoint | FLOAT32 ABCD | Demand limit setpoint (BAS) | Read/write |
| HR 3018 | Chiller Auto Stop Command BAS | UINT16 | Chiller auto/stop command | Read/write |
| HR 3010 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats occupying two registers; read both registers in one request.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Modbus TCP uses Ethernet port 2; the rotary address is ignored for TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Active Demand Limit Setpoint | Needs: Ice Building not Installed | FLOAT32 | ABCD | % | Read | ||
| IR | 16doc 30017 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | Unit Power Consumption | Electrical power. Needs: Power Monitor | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Outdoor Air Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Differential Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | Differential Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Refrigerant Discharge Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | High Side Oil Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Refrigerant Discharge Temperature - Compressor 2A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | High Side Oil Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Air Flow Percentage Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 60doc 30061 | Air Flow Percentage Circuit 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 62doc 30063 | Drive Motor Average Voltage Circuit 1 | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Drive Motor Current U Circuit 1 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Drive Motor Current V Circuit 1 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Drive Motor Current W Circuit 1 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Drive Motor Current U RLA Circuit 1 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 72doc 30073 | Drive Motor Current V RLA Circuit 1 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 74doc 30075 | Drive Motor Current W RLA Circuit 1 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 76doc 30077 | Drive Motor Average Current RLA Circuit 1 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 78doc 30079 | Drive DC Bus Voltage Circuit 1 | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | Drive Output Power Circuit 1 | Electrical power. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 82doc 30083 | AFD Transistor Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Motor Winding Temperature 1 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Motor Winding Temperature 2 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Drive Motor Average Voltage Circuit 2 | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Drive Motor Current U Circuit 2 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Drive Motor Current V Circuit 2 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Drive Motor Current W Circuit 2 | Current. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Drive Motor Current U RLA Circuit 2 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 98doc 30099 | Drive Motor Current V RLA Circuit 2 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 100doc 30101 | Drive Motor Current W RLA Circuit 2 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 102doc 30103 | Drive Motor Average Current RLA Circuit 2 | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 104doc 30105 | Drive DC Bus Voltage Circuit 2 | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Drive Output Power Circuit 2 | Electrical power. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 | AFD Transistor Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: PF755 | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Motor Winding Temperature 1 Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Motor Winding Temperature 2 Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Sub Cooled Liquid Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Sub Cooled Liquid Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 118doc 30119 | Evaporator Differential Water Pressure | Differential water pressure; the list prints the unit as Temperature. Needs: Variable Primary Flow | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | System Chilled Water Differential Pressure | Pressure in the factory unit system (I-P or SI). Needs: Variable Primary Flow | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Phase AB Voltage - Compressor 1B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | Line 1 Current - Compressor 1B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | Line 2 Current - Compressor 1B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Line 3 Current - Compressor 1B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Line 1 Current RLA - Compressor 1B | FLOAT32 | ABCD | % | Read | |||
| IR | 136doc 30137 | Line 2 Current RLA - Compressor 1B | FLOAT32 | ABCD | % | Read | |||
| IR | 138doc 30139 | Line 3 Current RLA - Compressor 1B | FLOAT32 | ABCD | % | Read | |||
| IR | 140doc 30141 | Phase AB Voltage - Compressor 2B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Line 1 Current - Compressor 2B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Line 2 Current - Compressor 2B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Line 3 Current - Compressor 2B | Current. | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Line 1 Current RLA - Compressor 2B | FLOAT32 | ABCD | % | Read | |||
| IR | 150doc 30151 | Line 2 Current RLA - Compressor 2B | FLOAT32 | ABCD | % | Read | |||
| IR | 152doc 30153 | Line 3 Current RLA - Compressor 2B | FLOAT32 | ABCD | % | Read | |||
| IR | 156doc 30157 | Refrigerant Discharge Temperature - Compressor 1B | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | High Side Oil Pressure - Compressor 1B | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Refrigerant Discharge Temperature - Compressor 2B | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | High Side Oil Pressure - Compressor 2B | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 166doc 30167 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 168doc 30169 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 170doc 30171 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 172doc 30173 | Free Cooling Capacity Status | Needs: Free Cooling | FLOAT32 | ABCD | % | Read | ||
| IR | 174doc 30175 | Free Cooling Entering Water Temperature Active | Temperature in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 | Evaporator Differential Water Pressure Setpoint Status | Pressure in the factory unit system (I-P or SI). Needs: Variable Primary Flow | FLOAT32 | ABCD | Read | |||
| IR | 182doc 30183 | Energy Consumption Lifetime | Electrical energy. Needs: Power Monitor | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 | Energy Consumption | Electrical energy. Needs: Power Monitor | FLOAT32 | ABCD | Read | |||
| IR | 186doc 30187 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 188doc 30189 | Run Time - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 190doc 30191 | Starts - Compressor 2A | FLOAT32 | ABCD | Read | ||||
| IR | 192doc 30193 | Run Time - Compressor 2A | FLOAT32 | ABCD | Read | ||||
| IR | 194doc 30195 | Starts - Compressor 1B | FLOAT32 | ABCD | Read | ||||
| IR | 196doc 30197 | Run Time - Compressor 1B | FLOAT32 | ABCD | Read | ||||
| IR | 198doc 30199 | Starts - Compressor 2B | FLOAT32 | ABCD | Read | ||||
| IR | 200doc 30201 | Run Time - Compressor 2B | FLOAT32 | ABCD | Read | ||||
| IR | 202doc 30203 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 210doc 30211 | Unit Source ID | FLOAT32 | ABCD | Read | ||||
| IR | 212doc 30213 | Drive Input Voltage Calculated 1A | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 214doc 30215 | Drive Input Voltage Calculated 2A | Voltage. Needs: PF755 TR200 | FLOAT32 | ABCD | Read | |||
| IR | 216doc 30217 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 | Phase BC Voltage - Compressor 1B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Phase CA Voltage - Compressor 1B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Phase BC Voltage - Compressor 2B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Phase CA Voltage - Compressor 2B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Average Line Current Circuit 1 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 | Average Line Current Circuit 2 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 230doc 30231 | Average Line Voltage Circuit 1 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 | Average Line Voltage Circuit 2 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | Line Current L1 Circuit 1 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Line Current L2 Circuit 1 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 238doc 30239 | Line Current L3 Circuit 1 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Line Current L1 Circuit 2 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | Line Current L2 Circuit 2 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Line Current L3 Circuit 2 | Current. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 | Voltage L1-L2 Circuit 1 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 | Voltage L2-L3 Circuit 1 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 250doc 30251 | Voltage L1-L3 Circuit 1 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 252doc 30253 | Voltage L1-L2 Circuit 2 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 254doc 30255 | Voltage L2-L1 Circuit 2 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 256doc 30257 | Voltage L1-L3 Circuit 2 | Voltage. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 258doc 30259 | Total Real Power | Electrical power. Needs: Power Monitor | FLOAT32 | ABCD | Read | |||
| IR | 260doc 30261 | Line Frequency Circuit 1 | Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 262doc 30263 | Line Frequency Circuit 2 | Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 264doc 30265 | Power Factor Circuit 1 | Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 266doc 30267 | Power Factor Circuit 2 | Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 268doc 30269 | Power Demand Circuit 1 | Electrical power. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 270doc 30271 | Power Demand Circuit 2 | Electrical power. Needs: Two Energy Meters Installed | FLOAT32 | ABCD | Read | |||
| IR | 272doc 30273 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 284doc 30285 | Evaporator Water Flow Rate | Flow in the factory unit system (I-P or SI). Needs: Evap Water Flow Measurement | FLOAT32 | ABCD | Read | |||
| IR | 286doc 30287 | Evaporator Differential Water Pressure | Needs: Evap Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 288doc 30289 | Entering Evaporator Water Pressure | Needs: Evap Water Flow Measurement Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 290doc 30291 | Leaving Evaporator Water Pressure | Needs: Evap Water Flow Measurement Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 292doc 30293 | Power Factor | Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 294doc 30295 | Current L1 | Current. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 296doc 30297 | Current L2 | Current. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 298doc 30299 | Current L3 | Current. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 300doc 30301 | Average Current | Current. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 302doc 30303 | Voltage L1-L2 | Voltage. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 304doc 30305 | Voltage L2-L3 | Voltage. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 306doc 30307 | Voltage L1-L3 | Voltage. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 310doc 30311 | Average Voltage L-L | Voltage. Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 312doc 30313 | Line Frequency | Needs: One Energy Meter Installed | FLOAT32 | ABCD | Read | |||
| IR | 314doc 30315 | AFD Coolant Supply Temperature Compressor | Temperature in the factory unit system (I-P or SI). Needs: PF755 | FLOAT32 | ABCD | Read | |||
| IR | 316doc 30317 | AFD Coolant Supply Temperature Compressor | Temperature in the factory unit system (I-P or SI). Needs: PF755 | FLOAT32 | ABCD | Read | |||
| IR | 318doc 30319 | Evaporator Water Pump Speed Command | Needs: Evap Pump Control - Variable Speed | FLOAT32 | ABCD | % | Read | ||
| IR | 320doc 30321 | Evaporator Water Pump Speed Feedback | Needs: Evap Pump Control - Variable Speed | FLOAT32 | ABCD | % | Read | ||
| IR | 322doc 30323 | Evaporator Water Pump Speed Setpoint Active | Needs: Evap Pump Variable Speed Type - Direct Pump Speed Control | FLOAT32 | ABCD | % | Read | ||
| IR | 324doc 30325 | Evaporator Water Pump Flow Rate Setpoint Ac | Needs: Evap Pump Variable Speed Type - Water Flow Control | FLOAT32 | ABCD | Read | |||
| IR | 326doc 30327 | Free Cooling Dedicated Fans Airflow | Needs: Free Cooling Dedicated Fans | FLOAT32 | ABCD | % | Read | ||
| IR | 328doc 30329 | Drive Heat Sink Temperature Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: TR200 | FLOAT32 | ABCD | Read | |||
| IR | 330doc 30331 | Drive Heat Sink Temperature Compressor 2A | Temperature in the factory unit system (I-P or SI). Needs: TR200 | FLOAT32 | ABCD | Read | |||
| IR | 332doc 30333 | Compressor 1A Speed Status | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 334doc 30335 | Compressor 2A Speed Status | Needs: PF755 TR200 | FLOAT32 | ABCD | % | Read | ||
| IR | 336doc 30337 | Calculated Chiller Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 338doc 30339 | Free Cooling Target Offset | Temperature difference, factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 340doc 30341 | Free Cooling Valve Position Status | Needs: Free Cooling | FLOAT32 | ABCD | % | Read | ||
| IR | 342doc 30343 | Active Demand Limit Setpoint | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 344doc 30345 | Evaporator Refrigerant Absolute Pressure Circu | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 346doc 30347 | Condenser Refrigerant Absolute Pressure Circu | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 348doc 30349 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 350doc 30351 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 352doc 30353 | High Side Oil Absolute Pressure - Compressor | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 354doc 30355 | High Side Oil Absolute Pressure - Compressor | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 356doc 30357 | High Side Oil Absolute Pressure - Compressor | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 358doc 30359 | High Side Oil Absolute Pressure - Compressor | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 360doc 30361 | Entering Evaporator Water Absolute Pressure | Needs: Evap Water Flow Measurement Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 362doc 30363 | Leaving Evaporator Water Absolute Pressure | Needs: Evap Water Flow Measurement Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2012doc 32013 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E) | ||||
| IR | 2013doc 32014 | Cooling Type | UINT16 | Read | 1 = Water Cooled; 2 = Air Cooled | ||||
| IR | 2014doc 32015 | Manufacture Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey | ||||
| IR | 2016doc 32017 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 3010doc 33011 | Run Enable | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3011doc 33012 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3012doc 33013 | Limit Mode Relay Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3014doc 33015 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3016doc 33017 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3017doc 33018 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3018doc 33019 | Compressor 2A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3019doc 33020 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3020doc 33021 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3021doc 33022 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3022doc 33023 | Compressor 1B Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3023doc 33024 | Compressor 2B Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3024doc 33025 | Free Cooling Active | Needs: Free Cooling | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3026doc 33027 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3027doc 33028 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3028doc 33029 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3029doc 33030 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3031doc 33032 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3032doc 33033 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3033doc 33034 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3034doc 33035 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3035doc 33036 | Front Panel Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3036doc 33037 | Noise Reduction Request Active | Needs: Low Noise | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3037doc 33038 | Circuit 1 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3038doc 33039 | Circuit 2 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3039doc 33040 | Circuit 1 Lockout External | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3040doc 33041 | Circuit 2 Lockout External | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3041doc 33042 | Circuit 1 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3042doc 33043 | Circuit 2 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3043doc 33044 | Circuit 1 Available | UINT16 | Read | 0 = Unavailable; 1 = Available | ||||
| IR | 3044doc 33045 | Circuit 2 Available | UINT16 | Read | 0 = Unavailable; 1 = Available | ||||
| IR | 3045doc 33046 | Oil Sensor Circuit 1 | UINT16 | Read | 0 = Dry; 1 = Wet | ||||
| IR | 3046doc 33047 | Oil Sensor Circuit 2 | UINT16 | Read | 0 = Dry; 1 = Wet | ||||
| IR | 3047doc 33048 | Evaporator Water Pump 1 Inverter Running Status | Needs: Evap Pump Control Variable Speed | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3048doc 33049 | Evaporator Water Pump 1 Fault Status | Needs: Evap Pump Control Variable Speed | UINT16 | Read | 0 = Fault; 1 = No Fault | |||
| IR | 3049doc 33050 | Compressor 1B Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3050doc 33051 | Compressor 2B Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3051doc 33052 | Free Cooling Front Panel Command Status | Needs: Free Cooling | UINT16 | Read | 0 = Off; 1 = Auto | |||
| IR | 4000doc 34001 | Diagnostic: AFD 1A Bus Over Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic: AFD 1A Bus Under Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: AFD 1A Comm Loss: Main Processor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic: AFD 1A Customized Protection Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic: AFD 1A Gate Kill Active | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: AFD 1A General Failure (PF755) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: AFD 1A General Failure (TR200) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: AFD 1A Ground Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: AFD 1A Input Phase Loss | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: AFD 1A Input Transf or Filter Over Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic: AFD 1A Loss Of Motor Control | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic: AFD 1A Low Rotor Flux Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic: AFD 1A Motor Current Overload | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Diagnostic: AFD 1A Motor Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic: AFD 1A Motor Shorted | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: AFD 1A Over Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: AFD 1A Precharge Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: AFD 2A Bus Over Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: AFD 2A Bus Under Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: AFD 2A Comm Loss: Main Processor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: AFD 2A Customized Protection Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: AFD 2A Gate Kill Active | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: AFD 2A General Failure (PF755) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: AFD 2A General Failure (TR200) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: AFD 2A Ground Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: AFD 2A Input Phase Loss | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: AFD 2A Input Transf or Filter Over Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: AFD 2A Loss Of Motor Control | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: AFD 2A Low Rotor Flux Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: AFD 2A Motor Current Overload | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: AFD 2A Motor Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic: AFD 2A Motor Shorted | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: AFD 2A Over Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: AFD 2A Precharge Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: AFD Bus Over Voltage - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: AFD Bus Over Voltage - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Diagnostic: AFD Bus Under Voltage - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic: AFD Bus Under Voltage - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: AFD Comm Loss – 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic: AFD Comm Loss – 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Diagnostic: AFD Comm Loss: Main Processor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Diagnostic: AFD Comm Loss: Main Processor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Diagnostic: AFD Failure to Arm or Start - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: AFD Failure to Arm or Start - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: AFD Fault Mains - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: AFD Fault Mains - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: AFD General Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: AFD General Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: AFD Ground Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic: AFD Ground Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic: AFD Harmonic Filter Over Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Diagnostic: AFD Harmonic Filter Over Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: AFD High Pressure Cutout - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: AFD High Pressure Cutout - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: AFD High Torque - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic: AFD High Torque - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic: AFD Initialized - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Diagnostic: AFD Initialized - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic: AFD Internal Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Diagnostic: AFD Internal Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Diagnostic: AFD Interrupt Failure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Diagnostic: AFD Interrupt Failure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Diagnostic: AFD Interrupt Failure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Diagnostic: AFD Interrupt Failure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: AFD Inverter Heatsink Over Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: AFD Inverter Heatsink Over Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Diagnostic: AFD Locked Rotor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Diagnostic: AFD Locked Rotor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic: AFD Mains Phase Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: AFD Mains Phase Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: AFD Missing Motor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: AFD Missing Motor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Diagnostic: AFD Motor Current Overload - 1A (TR200) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Diagnostic: AFD Motor Current Overload - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Diagnostic: AFD Motor Current Overload - 2A (TR200) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Diagnostic: AFD Motor Current Overload - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Diagnostic: AFD Motor Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Diagnostic: AFD Motor Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Diagnostic: AFD New Spare Parts - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Diagnostic: AFD New Spare Parts - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Diagnostic: AFD Option Configuration Change - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Diagnostic: AFD Option Configuration Change - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Diagnostic: AFD Output Phase U Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Diagnostic: AFD Output Phase U Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Diagnostic: AFD Output Phase V Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Diagnostic: AFD Output Phase V Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Diagnostic: AFD Output Phase W Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Diagnostic: AFD Output Phase W Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Diagnostic: AFD Over Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Diagnostic: AFD Over Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Diagnostic: AFD Short Circuit - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Diagnostic: AFD Short Circuit - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Diagnostic: AFD Unexpected Shutdown - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Diagnostic: AFD Unexpected Shutdown - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Diagnostic: Check Clock | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Diagnostic: Chiller Service Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: %RLA Indication Output(Vdc) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Comm Loss: AFD Fault Input 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Comm Loss: AFD Fault Input 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Comm Loss: AFD Fault Input 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Comm Loss: AFD Fault Input 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Comm Loss: Auxiliary Setpoint Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Comm Loss: Cond Rfgt Tank Valve Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Comm Loss: Cond Rfgt Tank Valve Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Comm Loss: Condenser Fan Enable Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Comm Loss: Condenser Fan Enable Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Comm Loss: Condenser Rfgt Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Comm Loss: Condenser Rfgt Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Comm Loss: Cprsr Disch Rfgt Temp - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Comm Loss: Cprsr Disch Rfgt Temp - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: Cprsr Disch Rfgt Temp - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Comm Loss: Cprsr Disch Rfgt Temp - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Comm Loss: Drive Cooling Bypass Valve 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Comm Loss: Drive Cooling Bypass Valve 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Comm Loss: Drive Cooling Supply Temp 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Comm Loss: Drive Cooling Supply Temp 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Comm Loss: Economizer Disch Press - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Comm Loss: Economizer Disch Press - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Comm Loss: Economizer Disch Press - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Comm Loss: Economizer Disch Press - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Comm Loss: Economizer Disch Temp - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Comm Loss: Economizer Disch Temp - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Comm Loss: Economizer Disch Temp - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Comm Loss: Economizer Disch Temp - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Comm Loss: Economizer Valve - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Comm Loss: Economizer Valve - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Comm Loss: Economizer Valve - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Comm Loss: Economizer Valve - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Comm Loss: Electronic Expansion Valve 1 Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Comm Loss: Electronic Expansion Valve 1 Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Comm Loss: Electronic Expansion Valve 2 Compressor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Electronic Expansion Valve 2 Compressor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Comm Loss: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Comm Loss: Energy Meter 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Comm Loss: Energy Meter 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Comm Loss: Evap Diff Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: Evap Iso Valve Close Switch Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Comm Loss: Evap Iso Valve Close Switch Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Comm Loss: Evap Iso Valve Open Switch Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: Evap Iso Valve Open Switch Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Comm Loss: Evap Isolation Valve Relay Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Comm Loss: Evap Isolation Valve Relay Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Comm Loss: Evap Pump Inv1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Comm Loss: Evap Pump Inv1 Run Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Comm Loss: Evap Rfgt Pool Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Comm Loss: Evap Rfgt Pool Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Comm Loss: Evap Water Pump Inv Freq Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Comm Loss: Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Comm Loss: Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Comm Loss: Evaporator Oil Return Purge Valve - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Comm Loss: Evaporator Oil Return Purge Valve - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Comm Loss: Evaporator Pump 1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Comm Loss: Evaporator Pump 2 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Comm Loss: Evaporator Pump Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Comm Loss: Evaporator Pump Inverter Running Status | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Comm Loss: Evaporator Pump Speed Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Comm Loss: Evaporator Pump Speed Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Comm Loss: Evaporator Water Pump 1 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Comm Loss: Evaporator Water Pump 2 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Comm Loss: Ext Chilled Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Comm Loss: Ext Noise Reduction Request | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Comm Loss: External Ckt Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Comm Loss: External Ckt Lockout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Comm Loss: External Heat Recovery Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Comm Loss: External Heat Recovery Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Comm Loss: Fan Board 1 Relay 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Comm Loss: Fan Board 1 Relay 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Comm Loss: Fan Board 1 Relay 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Comm Loss: Fan Board 1 Relay 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Comm Loss: Fan Board 1 Relay 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Comm Loss: Fan Board 1 Relay 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Comm Loss: Fan Board 1 Relay 4 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Comm Loss: Fan Board 1 Relay 4 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Comm Loss: Fan Board 2 Relay 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Comm Loss: Fan Board 2 Relay 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Comm Loss: Fan Board 2 Relay 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Comm Loss: Fan Board 2 Relay 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Comm Loss: Fan Board 2 Relay 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Comm Loss: Fan Board 2 Relay 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Comm Loss: Fan Board 2 Relay 4 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Comm Loss: Fan Board 2 Relay 4 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1 & 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Comm Loss: Fan Inverter Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Comm Loss: Fan Inverter Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Comm Loss: Fan Inverter Speed Command Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Comm Loss: Fan Inverter Speed Command Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Comm Loss: FC Entering Glycol Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Comm Loss: FC Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Comm Loss: FC Leaving Glycol Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Comm Loss: Free Cooling Bypass Valve | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Comm Loss: Free Cooling Dedicated Fan Enable | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Comm Loss: Free Cooling Dedicated Fan Inverter Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Comm Loss: Free Cooling Dedicated Fan Inverter Speed Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Comm Loss: Free Cooling Glycol Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Comm Loss: Free Cooling Glycol Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Comm Loss: Free Cooling Glycol Pump Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Comm Loss: Free Cooling Pump | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Comm Loss: Free Cooling Valve | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Comm Loss: Heat Recovery Mode Valve Command - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Comm Loss: Heat Recovery Mode Valve Command - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Comm Loss: Heat Recovery Water Flow Cmd | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Comm Loss: Heat Recovery Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Comm Loss: Heat Recovery Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Comm Loss: High Pressure Cutout Sw - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Comm Loss: High Pressure Cutout Sw - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Comm Loss: High Pressure Cutout Sw - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Comm Loss: High Pressure Cutout Sw - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Comm Loss: Hot Gas Oil Return Valve - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Comm Loss: Hot Gas Oil Return Valve - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Comm Loss: HR Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Comm Loss: HR Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Comm Loss: Liquid Line Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Comm Loss: Liquid Line Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Comm Loss: Liquid Line Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Comm Loss: Liquid Line Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Comm Loss: Motor Winding Tstat Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Comm Loss: Motor Winding Tstat Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Comm Loss: Off-cycle Freeze Prot Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Comm Loss: Oil Loss Level Sensor Input Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Comm Loss: Oil Loss Level Sensor Input Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Comm Loss: Oil Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Comm Loss: Oil Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Comm Loss: Oil Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Comm Loss: Oil Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Comm Loss: Oil Return Solenoid Valve - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Comm Loss: Oil Return Solenoid Valve - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Comm Loss: Oil Return Valve - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Comm Loss: Oil Return Valve - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Comm Loss: Oil Supply Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Comm Loss: Oil Supply Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Comm Loss: Oil Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Comm Loss: Oil Temperature - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Comm Loss: Oil Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Comm Loss: Oil Temperature - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Comm Loss: Programmable Relay Board 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Comm Loss: Slide Valve Load - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Comm Loss: Slide Valve Load - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Comm Loss: Slide Valve Load - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Comm Loss: Slide Valve Load - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Comm Loss: Slide Valve Unload - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Comm Loss: Slide Valve Unload - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Comm Loss: Slide Valve Unload - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4254doc 34255 | Comm Loss: Slide Valve Unload - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4255doc 34256 | Comm Loss: Starter 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4256doc 34257 | Comm Loss: Starter 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4257doc 34258 | Comm Loss: Starter 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4258doc 34259 | Comm Loss: Starter 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4259doc 34260 | Comm Loss: Step Load - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4260doc 34261 | Comm Loss: Step Load - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4261doc 34262 | Comm Loss: Step Load - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4262doc 34263 | Comm Loss: Step Load - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4263doc 34264 | Comm Loss: Suction Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4264doc 34265 | Comm Loss: Suction Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4265doc 34266 | Comm Loss: Suction Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4266doc 34267 | Comm Loss: Suction Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4267doc 34268 | Comm Loss: Var Vi Valve – Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4268doc 34269 | Comm Loss: Var Vi Valve – Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4269doc 34270 | Comm Loss: Winding Temp 1, Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4270doc 34271 | Comm Loss: Winding Temp 1, Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4271doc 34272 | Comm Loss: Winding Temp 2, Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4272doc 34273 | Comm Loss: Winding Temp 2, Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4273doc 34274 | Diagnostic: Condenser Rfgt Pressure Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4274doc 34275 | Diagnostic: Condenser Rfgt Pressure Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4275doc 34276 | Diagnostic: Cprsr Did Not Accel: Shutdown - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4276doc 34277 | Diagnostic: Cprsr Did Not Accel: Shutdown - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4277doc 34278 | Diagnostic: Cprsr Did Not Accel: Shutdown - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4278doc 34279 | Diagnostic: Cprsr Did Not Accel: Shutdown - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4279doc 34280 | Diagnostic: Cprsr Did Not Accel: Transition - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4280doc 34281 | Diagnostic: Cprsr Did Not Accel: Transition - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4281doc 34282 | Diagnostic: Cprsr Did Not Accel: Transition - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4282doc 34283 | Diagnostic: Cprsr Did Not Accel: Transition - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4283doc 34284 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4284doc 34285 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4285doc 34286 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4286doc 34287 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4287doc 34288 | Diagnostic: Drive Cooling Supply Temp Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4288doc 34289 | Diagnostic: Drive Cooling Supply Temp Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4289doc 34290 | Diagnostic: Economizer Disch Press Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4290doc 34291 | Diagnostic: Economizer Disch Press Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4291doc 34292 | Diagnostic: Economizer Disch Press Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4292doc 34293 | Diagnostic: Economizer Disch Press Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4293doc 34294 | Diagnostic: Economizer Disch Temp Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4294doc 34295 | Diagnostic: Economizer Disch Temp Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4295doc 34296 | Diagnostic: Economizer Disch Temp Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4296doc 34297 | Diagnostic: Economizer Disch Temp Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4297doc 34298 | Diagnostic: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4298doc 34299 | Diagnostic: Evap Iso Valve Illegal Switch State Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4299doc 34300 | Diagnostic: Evap Iso Valve Illegal Switch State Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4300doc 34301 | Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4301doc 34302 | Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4302doc 34303 | Diagnostic: Evap Isolation Valve Failed To Close Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4303doc 34304 | Diagnostic: Evap Isolation Valve Failed To Close Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4304doc 34305 | Diagnostic: Evap Isolation Valve Failed To Open Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4305doc 34306 | Diagnostic: Evap Isolation Valve Failed To Open Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4306doc 34307 | Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4307doc 34308 | Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4308doc 34309 | Diagnostic: Evap Pump 1 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4309doc 34310 | Diagnostic: Evap Pump 2 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4310doc 34311 | Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4311doc 34312 | Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4312doc 34313 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4313doc 34314 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4314doc 34315 | Diagnostic: Evap Water Pump 1 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4315doc 34316 | Diagnostic: Evap Water Pump 2 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4316doc 34317 | Diagnostic: Evaporator Approach Error Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4317doc 34318 | Diagnostic: Evaporator Approach Error Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4318doc 34319 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4319doc 34320 | Diagnostic: Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4320doc 34321 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4321doc 34322 | Diagnostic: Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4322doc 34323 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4323doc 34324 | Diagnostic: Evaporator Pump 1 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4324doc 34325 | Diagnostic: Evaporator Pump 2 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4325doc 34326 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4326doc 34327 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4327doc 34328 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4328doc 34329 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4329doc 34330 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4330doc 34331 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4331doc 34332 | Diagnostic: Evaporator Water Pump Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4332doc 34333 | Diagnostic: Evaporator Water Pump Speed Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4333doc 34334 | Diagnostic: Excessive Condenser Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4334doc 34335 | Diagnostic: Excessive Condenser Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4335doc 34336 | Diagnostic: External Chilled Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4336doc 34337 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4337doc 34338 | Diagnostic: External Heat Recovery Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4338doc 34339 | Diagnostic: Fan Inverter Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4339doc 34340 | Diagnostic: Fan Inverter Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4340doc 34341 | Diagnostic: Free Cooling Dedicated Fan Inverter Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4341doc 34342 | Diagnostic: Free Cooling Entering Glycol Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4342doc 34343 | Diagnostic: Free Cooling Entering Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4343doc 34344 | Diagnostic: Free Cooling Glycol Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4344doc 34345 | Diagnostic: Free Cooling Glycol Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4345doc 34346 | Diagnostic: Free Cooling Glycol Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4346doc 34347 | Diagnostic: Free Cooling Glycol Pump Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4347doc 34348 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4348doc 34349 | Diagnostic: Free Cooling Leaving Glycol Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4349doc 34350 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4350doc 34351 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4351doc 34352 | Diagnostic: Heat Recovery Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4352doc 34353 | Diagnostic: Heat Recovery Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4353doc 34354 | Diagnostic: High Cprsr Rfgt Discharge Temp - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4354doc 34355 | Diagnostic: High Cprsr Rfgt Discharge Temp - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4355doc 34356 | Diagnostic: High Cprsr Rfgt Discharge Temp - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4356doc 34357 | Diagnostic: High Cprsr Rfgt Discharge Temp - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4357doc 34358 | Diagnostic: High Differential Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4358doc 34359 | Diagnostic: High Differential Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4359doc 34360 | Diagnostic: High Differential Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4360doc 34361 | Diagnostic: High Differential Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4361doc 34362 | Diagnostic: High Evaporator Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4362doc 34363 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4363doc 34364 | Diagnostic: High Motor Winding Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4364doc 34365 | Diagnostic: High Motor Winding Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4365doc 34366 | Diagnostic: High Oil Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4366doc 34367 | Diagnostic: High Oil Temperature - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4367doc 34368 | Diagnostic: High Oil Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4368doc 34369 | Diagnostic: High Oil Temperature - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4369doc 34370 | Diagnostic: High Pressure Cutout - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4370doc 34371 | Diagnostic: High Pressure Cutout - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4371doc 34372 | Diagnostic: High Pressure Cutout - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4372doc 34373 | Diagnostic: High Pressure Cutout - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4373doc 34374 | Diagnostic: High Refrigerant Pressure Ratio - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4374doc 34375 | Diagnostic: High Refrigerant Pressure Ratio - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4375doc 34376 | Diagnostic: High Refrigerant Pressure Ratio - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4376doc 34377 | Diagnostic: High Refrigerant Pressure Ratio - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4377doc 34378 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4378doc 34379 | Diagnostic: Liquid Line Pressure Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4379doc 34380 | Diagnostic: Liquid Line Pressure Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4380doc 34381 | Diagnostic: Liquid Line Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4381doc 34382 | Diagnostic: Liquid Line Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4382doc 34383 | Diagnostic: Loss of Oil for Compressor (Running) Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4383doc 34384 | Diagnostic: Loss of Oil for Compressor (Running) Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4384doc 34385 | Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4385doc 34386 | Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4386doc 34387 | Diagnostic: Low Differential Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4387doc 34388 | Diagnostic: Low Differential Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4388doc 34389 | Diagnostic: Low Differential Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4389doc 34390 | Diagnostic: Low Differential Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4390doc 34391 | Diagnostic: Low Discharge Superheat - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4391doc 34392 | Diagnostic: Low Discharge Superheat - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4392doc 34393 | Diagnostic: Low Discharge Superheat - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4393doc 34394 | Diagnostic: Low Discharge Superheat - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4394doc 34395 | Diagnostic: Low Drive Cooling Supply Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4395doc 34396 | Diagnostic: Low Drive Cooling Supply Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4396doc 34397 | Diagnostic: Low Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4397doc 34398 | Diagnostic: Low Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4398doc 34399 | Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4399doc 34400 | Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4400doc 34401 | Diagnostic: Low Evaporator Water Flow | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4401doc 34402 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4402doc 34403 | Diagnostic: Low Evaporator Water Temp (Unit On) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4403doc 34404 | Diagnostic: Low Glycol Pressure Free Cooling | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4404doc 34405 | Diagnostic: Low Glycol Temp Free Cooling | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4405doc 34406 | Diagnostic: Low Oil Flow - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4406doc 34407 | Diagnostic: Low Oil Flow - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4407doc 34408 | Diagnostic: Low Oil Flow - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4408doc 34409 | Diagnostic: Low Oil Flow - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4409doc 34410 | Diagnostic: Low Refrigerant Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4410doc 34411 | Diagnostic: Low Refrigerant Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4411doc 34412 | Diagnostic: Low Suction Refrigerant Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4412doc 34413 | Diagnostic: Low Suction Refrigerant Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4413doc 34414 | Diagnostic: Low Suction Refrigerant Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4414doc 34415 | Diagnostic: Low Suction Refrigerant Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4415doc 34416 | Diagnostic: Mfr Maintenance Recommended - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4416doc 34417 | Diagnostic: Mfr Maintenance Recommended - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4417doc 34418 | Diagnostic: Mfr Maintenance Recommended - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4418doc 34419 | Diagnostic: Mfr Maintenance Recommended - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4419doc 34420 | Diagnostic: Momentary Power Loss Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4420doc 34421 | Diagnostic: Momentary Power Loss Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4421doc 34422 | Diagnostic: Motor Current Overload - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4422doc 34423 | Diagnostic: Motor Current Overload - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4423doc 34424 | Diagnostic: Motor Current Overload - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4424doc 34425 | Diagnostic: Motor Current Overload - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4425doc 34426 | Diagnostic: Motor Winding Temp Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4426doc 34427 | Diagnostic: Motor Winding Temp Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4427doc 34428 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4428doc 34429 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4429doc 34430 | Diagnostic: No Differential Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4430doc 34431 | Diagnostic: No Differential Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4431doc 34432 | Diagnostic: No Differential Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4432doc 34433 | Diagnostic: No Differential Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4433doc 34434 | Diagnostic: Oil Filter Change Recommended - Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4434doc 34435 | Diagnostic: Oil Filter Change Recommended - Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4435doc 34436 | Diagnostic: Oil Flow Protection Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4436doc 34437 | Diagnostic: Oil Flow Protection Fault - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4437doc 34438 | Diagnostic: Oil Flow Protection Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4438doc 34439 | Diagnostic: Oil Flow Protection Fault - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4439doc 34440 | Diagnostic: Oil Pressure Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4440doc 34441 | Diagnostic: Oil Pressure Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4441doc 34442 | Diagnostic: Oil Pressure Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4442doc 34443 | Diagnostic: Oil Pressure Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4443doc 34444 | Diagnostic: Oil Supply Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4444doc 34445 | Diagnostic: Oil Supply Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4445doc 34446 | Diagnostic: Oil Temperature Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4446doc 34447 | Diagnostic: Oil Temperature Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4447doc 34448 | Diagnostic: Oil Temperature Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4448doc 34449 | Diagnostic: Oil Temperature Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4449doc 34450 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4450doc 34451 | Diagnostic: Over Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4451doc 34452 | Diagnostic: Phase Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4452doc 34453 | Diagnostic: Phase Loss - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4453doc 34454 | Diagnostic: Phase Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4454doc 34455 | Diagnostic: Phase Loss - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4455doc 34456 | Diagnostic: Phase Reversal - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4456doc 34457 | Diagnostic: Phase Reversal - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4457doc 34458 | Diagnostic: Phase Reversal - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4458doc 34459 | Diagnostic: Phase Reversal - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4459doc 34460 | Diagnostic: Power Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4460doc 34461 | Diagnostic: Power Loss - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4461doc 34462 | Diagnostic: Power Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4462doc 34463 | Diagnostic: Power Loss - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4463doc 34464 | Diagnostic: Pumpdown Terminated By Time Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4464doc 34465 | Diagnostic: Pumpdown Terminated By Time Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4465doc 34466 | Diagnostic: Restart Inhibit Invoked - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4466doc 34467 | Diagnostic: Restart Inhibit Invoked - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4467doc 34468 | Diagnostic: Restart Inhibit Invoked - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4468doc 34469 | Diagnostic: Restart Inhibit Invoked - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4469doc 34470 | Diagnostic: Severe Current Imbalance - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4470doc 34471 | Diagnostic: Severe Current Imbalance - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4471doc 34472 | Diagnostic: Severe Current Imbalance - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4472doc 34473 | Diagnostic: Severe Current Imbalance - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4473doc 34474 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4474doc 34475 | Diagnostic: Software Error 1002: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4475doc 34476 | Diagnostic: Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4476doc 34477 | Diagnostic: Starter Comm Loss: Main Processor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4477doc 34478 | Diagnostic: Starter Comm Loss: Main Processor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4478doc 34479 | Diagnostic: Starter Comm Loss: Main Processor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4479doc 34480 | Diagnostic: Starter Comm Loss: Main Processor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4480doc 34481 | Diagnostic: Starter Contactor Interrupt Failure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4481doc 34482 | Diagnostic: Starter Contactor Interrupt Failure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4482doc 34483 | Diagnostic: Starter Contactor Interrupt Failure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4483doc 34484 | Diagnostic: Starter Contactor Interrupt Failure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4484doc 34485 | Diagnostic: Starter Did Not Fully Accelerate | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4485doc 34486 | Diagnostic: Starter Did Not Transition - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4486doc 34487 | Diagnostic: Starter Did Not Transition - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4487doc 34488 | Diagnostic: Starter Did Not Transition - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4488doc 34489 | Diagnostic: Starter Did Not Fully Accelerate Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4489doc 34490 | Diagnostic: Starter Did Not Transition - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4490doc 34491 | Diagnostic: Starter Dry Run Test - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4491doc 34492 | Diagnostic: Starter Dry Run Test - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4492doc 34493 | Diagnostic: Starter Dry Run Test - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4493doc 34494 | Diagnostic: Starter Dry Run Test - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4494doc 34495 | Diagnostic: Starter Failed to Arm/Start - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4495doc 34496 | Diagnostic: Starter Failed to Arm/Start - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4496doc 34497 | Diagnostic: Starter Failed to Arm/Start - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4497doc 34498 | Diagnostic: Starter Failed to Arm/Start - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4498doc 34499 | Diagnostic: Starter Fault Type I - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4499doc 34500 | Diagnostic: Starter Fault Type I - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4500doc 34501 | Diagnostic: Starter Fault Type I - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4501doc 34502 | Diagnostic: Starter Fault Type I - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4502doc 34503 | Diagnostic: Starter Fault Type II - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4503doc 34504 | Diagnostic: Starter Fault Type II - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4504doc 34505 | Diagnostic: Starter Fault Type II - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4505doc 34506 | Diagnostic: Starter Fault Type II - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4506doc 34507 | Diagnostic: Starter Fault Type III - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4507doc 34508 | Diagnostic: Starter Fault Type III - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4508doc 34509 | Diagnostic: Starter Fault Type III - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4509doc 34510 | Diagnostic: Starter Fault Type III - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4510doc 34511 | Diagnostic: Starter Module Memory Error Type 1 - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4511doc 34512 | Diagnostic: Starter Module Memory Error Type 1 - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4512doc 34513 | Diagnostic: Starter Module Memory Error Type 1 - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4513doc 34514 | Diagnostic: Starter Module Memory Error Type 1 - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4514doc 34515 | Diagnostic: Starter Module Memory Error Type 2 - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4515doc 34516 | Diagnostic: Starter Module Memory Error Type 2 - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4516doc 34517 | Diagnostic: Starter Module Memory Error Type 2 - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4517doc 34518 | Diagnostic: Starter Module Memory Error Type 2 - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4518doc 34519 | Diagnostic: Starts/Hours Modified 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4519doc 34520 | Diagnostic: Starts/Hours Modified 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4520doc 34521 | Diagnostic: Starts/Hours Modified 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4521doc 34522 | Diagnostic: Starts/Hours Modified 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4522doc 34523 | Diagnostic: Suction Refrigerant Pressure Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4523doc 34524 | Diagnostic: Suction Refrigerant Pressure Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4524doc 34525 | Diagnostic: Suction Refrigerant Pressure Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4525doc 34526 | Diagnostic: Suction Refrigerant Pressure Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4526doc 34527 | Diagnostic: Transition Complete Input Opened - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4527doc 34528 | Diagnostic: Transition Complete Input Opened - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4528doc 34529 | Diagnostic: Transition Complete Input Opened - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4529doc 34530 | Diagnostic: Transition Complete Input Opened - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4530doc 34531 | Diagnostic: Transition Complete Input Shorted - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4531doc 34532 | Diagnostic: Transition Complete Input Shorted - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4532doc 34533 | Diagnostic: Transition Complete Input Shorted - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4533doc 34534 | Diagnostic: Transition Complete Input Shorted - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4534doc 34535 | Diagnostic: Under Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4535doc 34536 | Diagnostic: Unexpected Starter Shutdown - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4536doc 34537 | Diagnostic: Unexpected Starter Shutdown - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4537doc 34538 | Diagnostic: Unexpected Starter Shutdown - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4538doc 34539 | Diagnostic: Unexpected Starter Shutdown - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4539doc 34540 | Diagnostic: Very Low Evap Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4540doc 34541 | Diagnostic: Very Low Evap Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4541doc 34542 | Diagnostic: Very Low Evap Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4542doc 34543 | Diagnostic: Very Low Evap Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4543doc 34544 | Diagnostic: Write Command Failure Energy Meter 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4544doc 34545 | Diagnostic: Write Command Failure Energy Meter 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4545doc 34546 | Comm Loss: Ice Building Status Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Evaporator Water Pump Flow Rate Setpoint BA | Needs: Evap Variable Speed Pump Control - Water Flow Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Evaporator Water Pump Speed Setpoint BAS | Needs: Evap Variable Speed Pump Control - Direct Pump Speed Control | FLOAT32 | ABCD | % | Read/write | ||
| HR | 3010doc 43011 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3011doc 43012 | Noise Reduction Request BAS | Needs: Low Noise | UINT16 | Read/write | 0 = Normal; 1 = Reduce Noise | |||
| HR | 3012doc 43013 | Circuit 1 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3013doc 43014 | Circuit 2 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3017doc 43018 | Energy Consumption Reset | Needs: Power Monitor | UINT16 | Read/write | 0 = Accumulating; 1 = Reset | |||
| HR | 3018doc 43019 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3019doc 43020 | Free Cooling Auto Stop Command BAS | Needs: Free Cooling | UINT16 | Read/write | 0 = Stop; 1 = Auto | |||
| HR | 3020doc 43021 | Free Cooling Compressor Lockout | Needs: Free Cooling | UINT16 | Read/write | 0 = Nornal; 1 = Locked Out | |||
| HR | 3021doc 43022 | Compressor 1B Lockout BAS | UINT16 | Read/write | 0 = Nornal; 1 = Locked Out | ||||
| HR | 3022doc 43023 | Compressor 2B Lockout BAS | UINT16 | Read/write | 0 = Nornal; 1 = Locked Out |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup and the I-P/SI units statement come from Trane's Symbio 800 integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
- Left out: Evaporator Approach Temperature Circuit 2 (30275) and Discharge Superheat Compressor 1A/1B/2A/2B (30276-30279). The list numbers these four floats one register apart, so 30275-30279 overlap and their real positions are not settled.
- Evaporator Differential Water Pressure (30119) is printed with the unit 'Temperature'; units are left blank.
- Some Binary Value states are printed as 'Nornal'; copied as printed (read it as Normal).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
What Modbus registers does the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) have?
This map lists 765 registers: 751 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane Ascend ACR Series C air-cooled chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)?
Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 2010 Running Mode (Running mode); IR 3010 Run Enable (Run enable); IR 3026 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 12 Demand Limit Setpoint (Demand limit setpoint (BAS)); HR 3018 Chiller Auto Stop Command BAS (Chiller auto/stop command); HR 3010 Reset Diagnostic (Reset diagnostic).
How do I enable Modbus control of the Trane Ascend ACR Series C air-cooled chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane Ascend ACR Series C air-cooled chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, Ascend Model ACR Series C (BAS-PTS021A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS021A-EN_11152024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.