Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's CGAM is an air-cooled scroll chiller with up to three compressors on each of two circuits. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, starts and run time, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 301 Modbus registers for the Trane CGAM air-cooled scroll chiller (Symbio 800) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
CGAM air-cooled scroll chiller (Symbio 800)
Equipment type
Chiller
Registers
301 (12 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
CGAM, Trane CGAM, CGAM air-cooled scroll chiller
Source document
Symbio 800 Integration Points List, BACnet/Modbus, CGAM · BAS-PTS019A-EN · rev. 2024-11-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane CGAM air-cooled scroll chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Cool/Heat Setpoint TemperatureFLOAT32 ABCDActive cool/heat setpointRead
IR 12Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 14Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 62Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 32Outdoor Air TemperatureFLOAT32 ABCDOutdoor air temperatureRead
IR 2010Running ModeUINT16Running modeRead
IR 3033Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write
HR 3016Chiller Auto Stop Command BASUINT16Chiller auto/stop commandRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

301 of 301 shown
Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR14doc 30015Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR16doc 30017Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR18doc 30019Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR20doc 30021Hot Water Setpoint ActiveTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR22doc 30023Hot Water Setpoint StatusTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR24doc 30025Active Demand Limit SetpointNeeds: Ice Building Not InstalledFLOAT32ABCD%Read
IR26doc 30027Active Demand Limit SetpointNeeds: Ice BuildingFLOAT32ABCD%Read
IR28doc 30029Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR30doc 30031Unit Power ConsumptionElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR32doc 30033Outdoor Air TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR36doc 30037Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR38doc 30039Differential Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR40doc 30041Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR42doc 30043Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR44doc 30045Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR46doc 30047Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR48doc 30049Differential Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR50doc 30051Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR52doc 30053Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR54doc 30055Evaporator Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR56doc 30057Condenser Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR58doc 30059Evaporator Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR60doc 30061Condenser Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR62doc 30063Actual Running CapacityFLOAT32ABCD%Read
IR64doc 30065Air Flow Percentage Circuit 1FLOAT32ABCD%Read
IR66doc 30067Air Flow Percentage Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR68doc 30069Starts - Compressor 1AFLOAT32ABCDRead
IR70doc 30071Run Time - Compressor 1AFLOAT32ABCDRead
IR72doc 30073Starts - Compressor 1BFLOAT32ABCDRead
IR74doc 30075Run Time - Compressor 1BFLOAT32ABCDRead
IR76doc 30077Starts - Compressor 1CNeeds: Compressor 1CFLOAT32ABCDRead
IR78doc 30079Run Time - Compressor 1CNeeds: Compressor 1CFLOAT32ABCDRead
IR80doc 30081Starts - Compressor 2ANeeds: Circuit 2FLOAT32ABCDRead
IR82doc 30083Run Time - Compressor 2ANeeds: Circuit 2FLOAT32ABCDRead
IR84doc 30085Starts - Compressor 2BNeeds: Circuit 2FLOAT32ABCDRead
IR86doc 30087Run Time - Compressor 2BNeeds: Circuit 2FLOAT32ABCDRead
IR88doc 30089Starts - Compressor 2CNeeds: Compressor 2CFLOAT32ABCDRead
IR90doc 30091Run Time - Compressor 2CNeeds: Compressor 2CFLOAT32ABCDRead
IR92doc 30093Heat Recovery Leaving Water Temperature Setpoint ActiveTemperature in the factory unit system (I-P or SI). Needs: Partial Heat RecoveryFLOAT32ABCDRead
IR94doc 30095Heat Recovery Entering Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat Recovery Water TempsFLOAT32ABCDRead
IR96doc 30097Heat Recovery Leaving Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat Recovery Water TempsFLOAT32ABCDRead
IR98doc 30099Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR100doc 30101Number of CircuitsFLOAT32ABCDRead
IR102doc 30103Number of Compressors Circuit 1FLOAT32ABCDRead
IR104doc 30105Number of Compressors Circuit 2FLOAT32ABCDRead
IR106doc 30107Refrigerant Discharge Temperature Estimate Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR108doc 30109Refrigerant Discharge Temperature Estimate Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR110doc 30111Refrigerant Discharge Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Discharge TempFLOAT32ABCDRead
IR112doc 30113Refrigerant Discharge Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp, Circuit 2FLOAT32ABCDRead
IR114doc 30115Unit Source ID (Last Diagnostic Code)FLOAT32ABCDRead
IR118doc 30119Energy Consumption LifetimeElectrical energy. Needs: Energy MeterFLOAT32ABCDRead
IR120doc 30121Energy ConsumptionElectrical energy. Needs: Energy MeterFLOAT32ABCDRead
IR122doc 30123Average CurrentCurrent. Needs: Energy MeterFLOAT32ABCDRead
IR124doc 30125Average Voltage L-LVoltage. Needs: Energy MeterFLOAT32ABCDRead
IR126doc 30127Current L1Current. Needs: Energy MeterFLOAT32ABCDRead
IR128doc 30129Current L2Current. Needs: Energy MeterFLOAT32ABCDRead
IR130doc 30131Current L3Current. Needs: Energy MeterFLOAT32ABCDRead
IR132doc 30133Voltage L1-L2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR134doc 30135Voltage L2-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR136doc 30137Voltage L1-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR138doc 30139Unit Power DemandElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR140doc 30141Line FrequencyNeeds: Energy MeterFLOAT32ABCDRead
IR142doc 30143Power FactorNeeds: Energy MeterFLOAT32ABCDRead
IR146doc 30147Supplemental Heat StatusNeeds: Supplemental HeaterFLOAT32ABCD%Read
IR148doc 30149Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR150doc 30151Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR152doc 30153Evaporator Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR154doc 30155Condenser Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control, Circuit 2FLOAT32ABCDRead
IR156doc 30157Compressor Suction Superheat Ckt1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR158doc 30159Compressor Suction Superheat Ckt2Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR2013doc 32014Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E); 17 = R-454B; 18 = R-515B
IR2014doc 32015Cooling TypeUINT16Read1 = Water Cooled; 2 = Air Cooled
IR2015doc 32016Manufacture LocationUINT16Read1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey; 19 = Bari
IR2016doc 32017Model Information [GEN2]UINT16Read1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HWSA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small; 38 = CVHE; 39 = CVHG; 40 = CVHL; 41 = RTWF XSE; 42 = CGWF; 43 = CDHG; 44 = ACCA; 45 = RTWD; 46 = RTUD; 47 = CXWF; 48 = CCUF; 49 = RTHG; 50 = CGAM; 51 = CXAM
IR3010doc 33011Limit Mode Relay StatusUINT16Read0 = Auto; 1 = On
IR3011doc 33012Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3012doc 33013Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3013doc 33014Front Panel Auto Stop StatusUINT16Read0 = Stop; 1 = Auto
IR3014doc 33015External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3015doc 33016Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3016doc 33017Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3017doc 33018Maximum CapacityUINT16Read0 = Off; 1 = On
IR3018doc 33019Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3019doc 33020Compressor 1B StatusUINT16Read0 = Off; 1 = Running
IR3020doc 33021Compressor 1C StatusNeeds: Compressor 1CUINT16Read0 = Off; 1 = Running
IR3021doc 33022Compressor 2A StatusNeeds: Circuit 2UINT16Read0 = Off; 1 = Running
IR3022doc 33023Compressor 2B StatusNeeds: Circuit 2UINT16Read0 = Off; 1 = Running
IR3023doc 33024Compressor 2C StatusNeeds: Compressor 2CUINT16Read0 = Off; 1 = Running
IR3024doc 33025Chiller Running StateUINT16Read0 = Off; 1 = On
IR3025doc 33026Heat Recovery Control Active StatusNeeds: Partial Heat RecoveryUINT16Read0 = Inactive; 1 = Active
IR3026doc 33027Heat Recovery Request ActiveNeeds: Partial Heat RecoveryUINT16Read0 = Off; 1 = On
IR3027doc 33028Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3028doc 33029Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3029doc 33030Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3031doc 33032Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3032doc 33033Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3033doc 33034Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3034doc 33035Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3035doc 33036Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3036doc 33037Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3037doc 33038Noise Reduction Request ActiveNeeds: Noise ReductionUINT16Read0 = Off; 1 = On
IR3038doc 33039In DefrostNeeds: Hot Water ControlUINT16Read0 = Not In Defrost; 1 = Defrost
IR3039doc 33040Circuit 1 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3040doc 33041Circuit 2 Lockout Front PanelNeeds: Circuit 2UINT16Read0 = Normal; 1 = Locked Out
IR3041doc 33042Circuit 1 Lockout ExternalNeeds: External Circuit LockoutUINT16Read0 = Normal; 1 = Locked Out
IR3042doc 33043Circuit 2 Lockout ExternalNeeds: External Circuit LockoutUINT16Read0 = Normal; 1 = Locked Out
IR3043doc 33044Circuit 1 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3044doc 33045Circuit 2 Lockout ActiveNeeds: Circuit 2UINT16Read0 = Normal; 1 = Locked Out
IR3045doc 33046Circuit 1 AvailableUINT16Read0 = Unavailable; 1 = Available
IR3046doc 33047Circuit 2 AvailableNeeds: Circuit 2UINT16Read0 = Unavailable; 1 = Available
IR3047doc 33048Circuit 1 Running StatusUINT16Read0 = Off; 1 = On
IR3048doc 33049Circuit 2 Running StatusNeeds: Circuit 2UINT16Read0 = Off; 1 = On
IR4000doc 34001Diagnostic: Comm Loss: Percent Capacity OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic: Comm Loss: Supplemental Heater Relay 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: Comm Loss: Supplemental Heater Relay 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic: Comm Loss: Supplemental Heater Relay 3Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic: Comm Loss: Supplemental Heater Relay 4Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: Comm Loss: Energy MeterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: Comm Loss: Phase Protection Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: Energy Meter Write Value FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic: Phase Protection FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic: Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic: Pumpdown Terminated By Time - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: Pumpdown Terminated By Time - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: Comm Loss: Discharge Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: Comm Loss: Discharge Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: Comm Loss: Discharge Temperature Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: Comm Loss: Discharge Temperature Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: Comm Loss: External Ckt1 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: Comm Loss: External Ckt2 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: Comm Loss: Reversing Valve - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: Comm Loss: Reversing Valve - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: Comm Loss: Suction Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: Comm Loss: Suction Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: Comm Loss: Suction Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: Comm Loss: Suction Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: Discharge Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: Discharge Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: Discharge Temperature Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic: Discharge Temperature Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: Suction Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: Suction Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: Suction Temperature Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: Suction Temperature Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Diagnostic: Comm Loss: Subcooler Shutoff Valve Relay - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic: Comm Loss: Subcooler Shutoff Valve Relay - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: Comm Loss: Receiver Fill Valve Relay - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic: Comm Loss: Receiver Fill Valve Relay - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Diagnostic: High Compressor Pressure Differential - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Diagnostic: High Compressor Pressure Differential - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Diagnostic: High Discharge Refrigerant Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: High Discharge Refrigerant Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: High Discharge Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: High Discharge Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: High Discharge Temperature Lockout - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: High Discharge Temperature Lockout - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: Loss of Charge - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic: Loss of Charge - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic: Low Discharge Saturated Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Diagnostic: Low Discharge Saturated Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: Low Refrigerant Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: Low Refrigerant Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: Low Suction Refrigerant Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic: Low Suction Refrigerant Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic: Low Suction Superheat - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Diagnostic: Low Suction Superheat - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic: Suction Temperature Too High - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Diagnostic: Suction Temperature Too High - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Diagnostic: Very Low Suction Pressure - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Diagnostic: Very Low Suction Pressure - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Diagnostic: Low Differential Refrigerant Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Diagnostic: Low Differential Refrigerant Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: Comm Loss: Compressor 1A Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: Comm Loss: Compressor 1B Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Diagnostic: Comm Loss: Compressor 1C Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Diagnostic: Compressor 1A FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic: Compressor 1B FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: Compressor 1C FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: Compressor 1A Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: Compressor 1B Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Diagnostic: Compressor 1C Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Diagnostic: Starts/Hours Modified 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Diagnostic: Starts/Hours Modified 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Diagnostic: Starts/Hours Modified 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Diagnostic: Comm Loss: Compressor 2A Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Diagnostic: Comm Loss: Compressor 2B Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Diagnostic: Comm Loss: Compressor 2C Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Diagnostic: Compressor 2A FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Diagnostic: Compressor 2B FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Diagnostic: Compressor 2C FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Diagnostic: Compressor 2A Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Diagnostic: Compressor 2B Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Diagnostic: Compressor 2C Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Diagnostic: Starts/Hours Modified 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Diagnostic: Starts/Hours Modified 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Diagnostic: Starts/Hours Modified 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Diagnostic: Comm Loss: High Pressure Cutout Switch - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Diagnostic: Comm Loss: High Pressure Cutout Switch - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Diagnostic: High Pressure Cutout - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Diagnostic: High Pressure Cutout - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Diagnostic: Comm Loss: Evaporator Antifreeze HeaterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Diagnostic: Evaporator Water Flow Lost LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Diagnostic: High Suction Rfgt PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Diagnostic: Inverted Water Temp (Heating)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Diagnostic: Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Diagnostic: Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Diagnostic: Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Diagnostic: Comm Loss: Cooling EXV - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Diagnostic: Comm Loss: Cooling EXV - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Diagnostic: Comm Loss: Electronic Expansion Valve - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Diagnostic: Comm Loss: Electronic Expansion Valve - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Diagnostic: Comm Loss: Heating EXV - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Diagnostic: Comm Loss: Heating EXV - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Diagnostic: Comm Loss: Auxiliary Setpoint CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Diagnostic: Comm Loss: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Diagnostic: Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Diagnostic: Comm Loss: Ext Noise Reduction RequestDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Diagnostic: Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Diagnostic: Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Diagnostic: Comm Loss: External Hot Water CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Diagnostic: Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Diagnostic: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Diagnostic: Comm Loss: Condenser Fan Enable - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Diagnostic: Comm Loss: Condenser Fan Enable - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Diagnostic: Comm Loss: Condenser Fan Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Diagnostic: Comm Loss: Condenser Fan Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Diagnostic: Comm Loss: Fan Inverter Speed Command - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Diagnostic: Comm Loss: Fan Inverter Speed Command - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Diagnostic: Condenser Fan Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Diagnostic: Condenser Fan Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Diagnostic: Comm Loss: Comm Loss: Fan Inverter Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Diagnostic: Comm Loss: Comm Loss: Fan Inverter Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Diagnostic: Fan Inverter Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Diagnostic: Fan Inverter Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Diagnostic: Comm Loss: Noise Reduction Request RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Diagnostic: Comm Loss: Heat Recovery Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Diagnostic: Comm Loss: Heat Recovery Leaving Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Diagnostic: No Partial Heat Recovery - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Diagnostic: No Partial Heat Recovery - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Diagnostic: Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic: Comm Loss: Run Command Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic: Comm Loss: Run Command Compressor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Diagnostic: Comm Loss: Run Command Compressor 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Diagnostic: Comm Loss: Run Command Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Diagnostic: Comm Loss: Run Command Compressor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Diagnostic: Comm Loss: Run Command Compressor 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Diagnostic: Comm Loss: Evap Pump Inv1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Diagnostic: Comm Loss: Evap Pump Inv1 Freq FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Diagnostic: Comm Loss: Evap Pump Inv1 Run CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Diagnostic: Comm Loss: Evaporator Pump 1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Diagnostic: Comm Loss: Evaporator Pump 2 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Diagnostic: Comm Loss: Evaporator Water Pump 1 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Diagnostic: Comm Loss: Evaporator Water Pump 2 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Diagnostic: Evaporator Pump 1 Starts/Hours ModifiedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Diagnostic: Evaporator Pump 2 Starts/Hours ModifiedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Diagnostic: Evaporator Pump 1 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Diagnostic: Evaporator Pump 2 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Diagnostic: Evaporator Water Flow Lost - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Diagnostic: Evaporator Water Flow Lost - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Diagnostic: Evaporator Water Flow Overdue - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Diagnostic: Evaporator Water Flow Overdue - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Diagnostic: Evaporator Water Flow Too LowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Diagnostic: Power Factor Correction FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Diagnostic: Comm Loss: Power Factor Correction Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017Heat Recovery Leaving Water Temperature Setpoint BASTemperature in the factory unit system (I-P or SI). Needs: Partial Heat RecoveryFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3011doc 43012Noise Reduction Request BASNeeds: Noise ReductionUINT16Read/write0 = Normal; 1 = Reduce Noise
HR3012doc 43013Heat Recovery RequestNeeds: Partial Heat RecoveryUINT16Read/write0 = Off; 1 = On
HR3013doc 43014Energy Consumption ResetNeeds: Energy MeterUINT16Read/write0 = Accumulating; 1 = Reset
HR3014doc 43015Circuit 1 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3015doc 43016Circuit 2 Lockout BASNeeds: Circuit 2UINT16Read/write0 = Normal; 1 = Locked Out
HR3016doc 43017Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane CGAM air-cooled scroll chiller (Symbio 800)

What Modbus registers does the Trane CGAM air-cooled scroll chiller (Symbio 800) have?

This map lists 301 registers: 289 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane CGAM air-cooled scroll chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane CGAM air-cooled scroll chiller (Symbio 800)?

Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 12 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 62 Actual Running Capacity (Actual running capacity); IR 32 Outdoor Air Temperature (Outdoor air temperature); IR 2010 Running Mode (Running mode); IR 3033 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3016 Chiller Auto Stop Command BAS (Chiller auto/stop command).

How do I enable Modbus control of the Trane CGAM air-cooled scroll chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, CGAM (BAS-PTS019A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS019A-EN_11152024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, CGAM · BAS-PTS019A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.