- CGAM air-cooled scroll chiller (Symbio 800)
Chiller · Modbus register map
Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's CGAM is an air-cooled scroll chiller with up to three compressors on each of two circuits. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, starts and run time, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 301 Modbus registers for the Trane CGAM air-cooled scroll chiller (Symbio 800) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- CGAM air-cooled scroll chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 301 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CGAM, Trane CGAM, CGAM air-cooled scroll chiller
Integration notes: Trane CGAM air-cooled scroll chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Cool/Heat Setpoint Temperature | FLOAT32 ABCD | Active cool/heat setpoint | Read |
| IR 12 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 14 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 62 | Actual Running Capacity | FLOAT32 ABCD | Actual running capacity | Read |
| IR 32 | Outdoor Air Temperature | FLOAT32 ABCD | Outdoor air temperature | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3033 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | BAS chiller mode command | Read/write |
| HR 3016 | Chiller Auto Stop Command BAS | UINT16 | Chiller auto/stop command | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats occupying two registers; read both registers in one request.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Modbus TCP uses Ethernet port 2; the rotary address is ignored for TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 14doc 30015 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 16doc 30017 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Hot Water Setpoint Active | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | Hot Water Setpoint Status | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Active Demand Limit Setpoint | Needs: Ice Building Not Installed | FLOAT32 | ABCD | % | Read | ||
| IR | 26doc 30027 | Active Demand Limit Setpoint | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 28doc 30029 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 30doc 30031 | Unit Power Consumption | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Outdoor Air Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Differential Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Differential Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 64doc 30065 | Air Flow Percentage Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 66doc 30067 | Air Flow Percentage Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 68doc 30069 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Run Time - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Starts - Compressor 1B | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Run Time - Compressor 1B | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | Starts - Compressor 1C | Needs: Compressor 1C | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | Run Time - Compressor 1C | Needs: Compressor 1C | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | Starts - Compressor 2A | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 82doc 30083 | Run Time - Compressor 2A | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Starts - Compressor 2B | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Run Time - Compressor 2B | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Starts - Compressor 2C | Needs: Compressor 2C | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Run Time - Compressor 2C | Needs: Compressor 2C | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Heat Recovery Leaving Water Temperature Setpoint Active | Temperature in the factory unit system (I-P or SI). Needs: Partial Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Heat Recovery Entering Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery Water Temps | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Heat Recovery Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery Water Temps | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 102doc 30103 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 104doc 30105 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | Refrigerant Discharge Temperature Estimate Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 | Refrigerant Discharge Temperature Estimate Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Refrigerant Discharge Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Refrigerant Discharge Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp, Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Unit Source ID (Last Diagnostic Code) | FLOAT32 | ABCD | Read | ||||
| IR | 118doc 30119 | Energy Consumption Lifetime | Electrical energy. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Energy Consumption | Electrical energy. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | Average Current | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Average Voltage L-L | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Current L1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | Current L2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | Current L3 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Voltage L1-L2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Voltage L2-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Voltage L1-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Unit Power Demand | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Line Frequency | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Power Factor | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Supplemental Heat Status | Needs: Supplemental Heater | FLOAT32 | ABCD | % | Read | ||
| IR | 148doc 30149 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Evaporator Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 154doc 30155 | Condenser Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control, Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Compressor Suction Superheat Ckt1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Compressor Suction Superheat Ckt2 | Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2012doc 32013 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 2013doc 32014 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E); 17 = R-454B; 18 = R-515B | ||||
| IR | 2014doc 32015 | Cooling Type | UINT16 | Read | 1 = Water Cooled; 2 = Air Cooled | ||||
| IR | 2015doc 32016 | Manufacture Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey; 19 = Bari | ||||
| IR | 2016doc 32017 | Model Information [GEN2] | UINT16 | Read | 1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HWSA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small; 38 = CVHE; 39 = CVHG; 40 = CVHL; 41 = RTWF XSE; 42 = CGWF; 43 = CDHG; 44 = ACCA; 45 = RTWD; 46 = RTUD; 47 = CXWF; 48 = CCUF; 49 = RTHG; 50 = CGAM; 51 = CXAM | ||||
| IR | 3010doc 33011 | Limit Mode Relay Status | UINT16 | Read | 0 = Auto; 1 = On | ||||
| IR | 3011doc 33012 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3012doc 33013 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Front Panel Auto Stop Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3014doc 33015 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3015doc 33016 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3016doc 33017 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3017doc 33018 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3018doc 33019 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3019doc 33020 | Compressor 1B Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3020doc 33021 | Compressor 1C Status | Needs: Compressor 1C | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3021doc 33022 | Compressor 2A Status | Needs: Circuit 2 | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3022doc 33023 | Compressor 2B Status | Needs: Circuit 2 | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3023doc 33024 | Compressor 2C Status | Needs: Compressor 2C | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3024doc 33025 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3025doc 33026 | Heat Recovery Control Active Status | Needs: Partial Heat Recovery | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3026doc 33027 | Heat Recovery Request Active | Needs: Partial Heat Recovery | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3027doc 33028 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3028doc 33029 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3029doc 33030 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3031doc 33032 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3032doc 33033 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3033doc 33034 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3034doc 33035 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3035doc 33036 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3036doc 33037 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3037doc 33038 | Noise Reduction Request Active | Needs: Noise Reduction | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3038doc 33039 | In Defrost | Needs: Hot Water Control | UINT16 | Read | 0 = Not In Defrost; 1 = Defrost | |||
| IR | 3039doc 33040 | Circuit 1 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3040doc 33041 | Circuit 2 Lockout Front Panel | Needs: Circuit 2 | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3041doc 33042 | Circuit 1 Lockout External | Needs: External Circuit Lockout | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3042doc 33043 | Circuit 2 Lockout External | Needs: External Circuit Lockout | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3043doc 33044 | Circuit 1 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3044doc 33045 | Circuit 2 Lockout Active | Needs: Circuit 2 | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3045doc 33046 | Circuit 1 Available | UINT16 | Read | 0 = Unavailable; 1 = Available | ||||
| IR | 3046doc 33047 | Circuit 2 Available | Needs: Circuit 2 | UINT16 | Read | 0 = Unavailable; 1 = Available | |||
| IR | 3047doc 33048 | Circuit 1 Running Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3048doc 33049 | Circuit 2 Running Status | Needs: Circuit 2 | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 4000doc 34001 | Diagnostic: Comm Loss: Percent Capacity Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic: Comm Loss: Supplemental Heater Relay 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: Comm Loss: Supplemental Heater Relay 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic: Comm Loss: Supplemental Heater Relay 3 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic: Comm Loss: Supplemental Heater Relay 4 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: Comm Loss: Energy Meter | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: Comm Loss: Phase Protection Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: Energy Meter Write Value Failure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic: Phase Protection Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic: Software Error 1002: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Diagnostic: Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic: Pumpdown Terminated By Time - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: Pumpdown Terminated By Time - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: Comm Loss: Discharge Pressure Transducer - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: Comm Loss: Discharge Pressure Transducer - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: Comm Loss: Discharge Temperature Sensor - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: Comm Loss: Discharge Temperature Sensor - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: Comm Loss: External Ckt1 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: Comm Loss: External Ckt2 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: Comm Loss: Reversing Valve - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: Comm Loss: Reversing Valve - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: Comm Loss: Suction Pressure Transducer - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: Comm Loss: Suction Pressure Transducer - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: Comm Loss: Suction Temperature - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: Comm Loss: Suction Temperature - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: Discharge Pressure Transducer - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: Discharge Pressure Transducer - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: Discharge Temperature Sensor - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic: Discharge Temperature Sensor - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: Suction Pressure Transducer - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: Suction Pressure Transducer - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: Suction Temperature Sensor - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: Suction Temperature Sensor - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Diagnostic: Comm Loss: Subcooler Shutoff Valve Relay - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic: Comm Loss: Subcooler Shutoff Valve Relay - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: Comm Loss: Receiver Fill Valve Relay - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic: Comm Loss: Receiver Fill Valve Relay - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Diagnostic: High Compressor Pressure Differential - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Diagnostic: High Compressor Pressure Differential - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Diagnostic: High Discharge Refrigerant Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: High Discharge Refrigerant Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: High Discharge Temperature - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: High Discharge Temperature - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: High Discharge Temperature Lockout - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: High Discharge Temperature Lockout - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: Loss of Charge - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic: Loss of Charge - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic: Low Discharge Saturated Temperature - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Diagnostic: Low Discharge Saturated Temperature - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: Low Refrigerant Temperature - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: Low Refrigerant Temperature - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: Low Suction Refrigerant Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic: Low Suction Refrigerant Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic: Low Suction Superheat - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Diagnostic: Low Suction Superheat - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic: Suction Temperature Too High - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Diagnostic: Suction Temperature Too High - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Diagnostic: Very Low Suction Pressure - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Diagnostic: Very Low Suction Pressure - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Diagnostic: Low Differential Refrigerant Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Diagnostic: Low Differential Refrigerant Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: Comm Loss: Compressor 1A Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: Comm Loss: Compressor 1B Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Diagnostic: Comm Loss: Compressor 1C Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Diagnostic: Compressor 1A Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic: Compressor 1B Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: Compressor 1C Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: Compressor 1A Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: Compressor 1B Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Diagnostic: Compressor 1C Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Diagnostic: Starts/Hours Modified 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Diagnostic: Starts/Hours Modified 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Diagnostic: Starts/Hours Modified 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Diagnostic: Comm Loss: Compressor 2A Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Diagnostic: Comm Loss: Compressor 2B Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Diagnostic: Comm Loss: Compressor 2C Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Diagnostic: Compressor 2A Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Diagnostic: Compressor 2B Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Diagnostic: Compressor 2C Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Diagnostic: Compressor 2A Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Diagnostic: Compressor 2B Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Diagnostic: Compressor 2C Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Diagnostic: Starts/Hours Modified 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Diagnostic: Starts/Hours Modified 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Diagnostic: Starts/Hours Modified 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Diagnostic: Comm Loss: High Pressure Cutout Switch - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Diagnostic: Comm Loss: High Pressure Cutout Switch - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Diagnostic: High Pressure Cutout - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Diagnostic: High Pressure Cutout - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Diagnostic: Comm Loss: Evaporator Antifreeze Heater | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Diagnostic: Evaporator Water Flow Lost Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Diagnostic: High Suction Rfgt Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Diagnostic: Inverted Water Temp (Heating) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Diagnostic: Low Evaporator Water Temp (Unit On) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Diagnostic: Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Diagnostic: Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Diagnostic: Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Diagnostic: Comm Loss: Cooling EXV - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Diagnostic: Comm Loss: Cooling EXV - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Diagnostic: Comm Loss: Electronic Expansion Valve - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Diagnostic: Comm Loss: Electronic Expansion Valve - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Diagnostic: Comm Loss: Heating EXV - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Diagnostic: Comm Loss: Heating EXV - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Diagnostic: Comm Loss: Auxiliary Setpoint Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Diagnostic: Comm Loss: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Diagnostic: Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Diagnostic: Comm Loss: Ext Noise Reduction Request | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Diagnostic: Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Diagnostic: Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Diagnostic: Comm Loss: External Hot Water Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Diagnostic: Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Diagnostic: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Diagnostic: Comm Loss: Condenser Fan Enable - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Diagnostic: Comm Loss: Condenser Fan Enable - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Diagnostic: Comm Loss: Condenser Fan Fault - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Diagnostic: Comm Loss: Condenser Fan Fault - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Diagnostic: Comm Loss: Fan Inverter Speed Command - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Diagnostic: Comm Loss: Fan Inverter Speed Command - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Diagnostic: Condenser Fan Fault - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Diagnostic: Condenser Fan Fault - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Diagnostic: Comm Loss: Comm Loss: Fan Inverter Fault - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Diagnostic: Comm Loss: Comm Loss: Fan Inverter Fault - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Diagnostic: Fan Inverter Fault - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Diagnostic: Fan Inverter Fault - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Diagnostic: Comm Loss: Noise Reduction Request Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Diagnostic: Comm Loss: Heat Recovery Entering Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Diagnostic: Comm Loss: Heat Recovery Leaving Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Diagnostic: No Partial Heat Recovery - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Diagnostic: No Partial Heat Recovery - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Diagnostic: Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic: Comm Loss: Run Command Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic: Comm Loss: Run Command Compressor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Diagnostic: Comm Loss: Run Command Compressor 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Diagnostic: Comm Loss: Run Command Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Diagnostic: Comm Loss: Run Command Compressor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Diagnostic: Comm Loss: Run Command Compressor 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Diagnostic: Comm Loss: Evap Pump Inv1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Diagnostic: Comm Loss: Evap Pump Inv1 Freq Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Diagnostic: Comm Loss: Evap Pump Inv1 Run Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Diagnostic: Comm Loss: Evaporator Pump 1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Diagnostic: Comm Loss: Evaporator Pump 2 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Diagnostic: Comm Loss: Evaporator Water Pump 1 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Diagnostic: Comm Loss: Evaporator Water Pump 2 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Diagnostic: Evaporator Pump 1 Starts/Hours Modified | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Diagnostic: Evaporator Pump 2 Starts/Hours Modified | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Diagnostic: Evaporator Pump 1 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Diagnostic: Evaporator Pump 2 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Diagnostic: Evaporator Water Flow Too Low | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Diagnostic: Power Factor Correction Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Diagnostic: Comm Loss: Power Factor Correction Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Heat Recovery Leaving Water Temperature Setpoint BAS | Temperature in the factory unit system (I-P or SI). Needs: Partial Heat Recovery | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3011doc 43012 | Noise Reduction Request BAS | Needs: Noise Reduction | UINT16 | Read/write | 0 = Normal; 1 = Reduce Noise | |||
| HR | 3012doc 43013 | Heat Recovery Request | Needs: Partial Heat Recovery | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3013doc 43014 | Energy Consumption Reset | Needs: Energy Meter | UINT16 | Read/write | 0 = Accumulating; 1 = Reset | |||
| HR | 3014doc 43015 | Circuit 1 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3015doc 43016 | Circuit 2 Lockout BAS | Needs: Circuit 2 | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | |||
| HR | 3016doc 43017 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup and the I-P/SI units statement come from Trane's Symbio 800 integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
- Evaporator and condenser saturated refrigerant temperature for circuit 2 (30051, 30053) are printed with the unit 'Percentage'; they are temperatures like their circuit 1 copies, so units are left blank.
- Emergency Stop (33012) state 1 text runs into the next row in the PDF; it reads 'Emergency Stop - Manual Reset Required'.
- Hot-water setpoints, defrost and condenser-approach points depend on the 'Hot Water Control' configuration.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane CGAM air-cooled scroll chiller (Symbio 800)
What Modbus registers does the Trane CGAM air-cooled scroll chiller (Symbio 800) have?
This map lists 301 registers: 289 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane CGAM air-cooled scroll chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane CGAM air-cooled scroll chiller (Symbio 800)?
Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 12 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 62 Actual Running Capacity (Actual running capacity); IR 32 Outdoor Air Temperature (Outdoor air temperature); IR 2010 Running Mode (Running mode); IR 3033 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3016 Chiller Auto Stop Command BAS (Chiller auto/stop command).
How do I enable Modbus control of the Trane CGAM air-cooled scroll chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane CGAM air-cooled scroll chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, CGAM (BAS-PTS019A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS019A-EN_11152024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, CGAM · BAS-PTS019A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.