Chiller · Modbus register map

Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's Sintesis RTAF is an air-cooled helical-rotary (screw) chiller with variable-speed compressors. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures, pressures, drive values, run hours), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 826 Modbus registers for the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Sintesis RTAF air-cooled screw chiller (Symbio 800)
Equipment type
Chiller
Registers
826 (23 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTAF, Sintesis RTAF, Sintesis air-cooled chiller
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Sintesis Model RTAF · BAS-PTS013B-EN · rev. 2026-04-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Cool/Heat Setpoint TemperatureFLOAT32 ABCDActive cool/heat setpointRead
IR 24Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 22Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 36Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 26Outdoor Air TemperatureFLOAT32 ABCDOutdoor air temperatureRead
IR 2010Running ModeUINT16Running modeRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write
HR 3010Chiller Auto Stop Command BASUINT16Chiller auto/stop commandRead/write
HR 3011Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

826 of 826 shown
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013External Chilled Water SetpointTemperature in the factory unit system (I-P or SI). Needs: External SetpointFLOAT32ABCDRead
IR14doc 30015Front Panel Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR16doc 30017Active Demand Limit SetpointFLOAT32ABCD%Read
IR18doc 30019External Demand Limit SetpointNeeds: External SetpointFLOAT32ABCD%Read
IR20doc 30021Front Panel Demand Limit SetpointFLOAT32ABCD%Read
IR22doc 30023Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR26doc 30027Outdoor Air TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR28doc 30029Number of CircuitsFLOAT32ABCDRead
IR30doc 30031Unit Source IDFLOAT32ABCDRead
IR32doc 30033Number of Compressors Circuit 1FLOAT32ABCDRead
IR34doc 30035Number of Compressors Circuit 2FLOAT32ABCDRead
IR36doc 30037Actual Running CapacityFLOAT32ABCD%Read
IR38doc 30039Air Flow Percentage Circuit 1FLOAT32ABCD%Read
IR40doc 30041Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR42doc 30043Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR44doc 30045Differential Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR46doc 30047Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR48doc 30049Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR50doc 30051Sub Cooled Liquid Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR52doc 30053Refrigerant Discharge Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR54doc 30055Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR56doc 30057Starts - Compressor 1AFLOAT32ABCDRead
IR58doc 30059Run Time - Compressor 1A (in seconds)FLOAT32ABCDsRead
IR60doc 30061Air Flow Percentage Circuit 2FLOAT32ABCD%Read
IR62doc 30063Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR64doc 30065Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR66doc 30067Differential Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR68doc 30069Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR70doc 30071Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR72doc 30073Sub Cooled Liquid Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR74doc 30075Refrigerant Discharge Temperature - Compressor 2ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR76doc 30077Oil Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR78doc 30079Refrigerant Discharge Temperature - Compressor 1BTemperature in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR80doc 30081Oil Pressure - Compressor 1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR82doc 30083Starts - Compressor 1BNeeds: Compressor 1BFLOAT32ABCDRead
IR84doc 30085Run Time - Compressor 1B (in seconds)Needs: Compressor 1BFLOAT32ABCDsRead
IR86doc 30087Starts - Compressor 2AFLOAT32ABCDRead
IR88doc 30089Run Time - Compressor 2A (in seconds)FLOAT32ABCDsRead
IR90doc 30091Refrigerant Discharge Temperature - Compressor 2BTemperature in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR92doc 30093Oil Pressure - Compressor 2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR94doc 30095Starts - Compressor 2BNeeds: Compressor 2BFLOAT32ABCDRead
IR96doc 30097Run Time - Compressor 2B (in seconds)Needs: Compressor 2BFLOAT32ABCDsRead
IR98doc 30099Free Cooling Capacity StatusNeeds: Free CoolingFLOAT32ABCD%Read
IR100doc 30101Free Cooling Entering Water Temperature ActiveTemperature in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR102doc 30103Free Cooling Entering Glycol TemperatureTemperature in the factory unit system (I-P or SI). Needs: Free Cooling, Glycol FreeFLOAT32ABCDRead
IR104doc 30105Free Cooling Leaving Glycol TemperatureTemperature in the factory unit system (I-P or SI). Needs: Free Cooling, Glycol FreeFLOAT32ABCDRead
IR106doc 30107Free Cooling Glycol PressurePressure in the factory unit system (I-P or SI). Needs: Free Cooling, Glycol FreeFLOAT32ABCDRead
IR108doc 30109Drive Motor Average Current RLA Compressor 1ANeeds: Generic AFDFLOAT32ABCD%Read
IR110doc 30111Drive Motor Average Current RLA Compressor 2ANeeds: Generic AFDFLOAT32ABCD%Read
IR112doc 30113Heat Recovery Entering Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR114doc 30115Heat Recovery Leaving Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR116doc 30117Evaporator Shell Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation ValvesFLOAT32ABCDRead
IR118doc 30119Evaporator Shell Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation ValvesFLOAT32ABCDRead
IR120doc 30121Phase AB Voltage - Compressor 1AVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR122doc 30123Phase AB Voltage - Compressor 1BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR124doc 30125Phase AB Voltage - Compressor 2AVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR126doc 30127Phase AB Voltage - Compressor 2BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR128doc 30129Oil Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR130doc 30131Oil Temperature - Compressor 1BTemperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR132doc 30133Oil Temperature - Compressor 2ATemperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR134doc 30135Oil Temperature - Compressor 2BTemperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR136doc 30137Oil Supply Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: GP4 CompressorFLOAT32ABCDRead
IR138doc 30139Oil Supply Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: GP4 CompressorFLOAT32ABCDRead
IR140doc 30141Unit Power ConsumptionElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR142doc 30143Energy Consumption LifetimeElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR144doc 30145Energy ConsumptionElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR146doc 30147Evaporator Differential Water PressurePressure in the factory unit system (I-P or SI). Needs: Variable Primary FlowFLOAT32ABCDRead
IR148doc 30149System Chilled Water Differential Water PressurePressure in the factory unit system (I-P or SI). Needs: Variable Primary FlowFLOAT32ABCDRead
IR150doc 30151Evaporator Differential Water Pressure Setpoint StatusPressure in the factory unit system (I-P or SI). Needs: Variable Primary FlowFLOAT32ABCDRead
IR152doc 30153Line 1 Current - Compressor 1ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR154doc 30155Line 2 Current - Compressor 1ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR156doc 30157Line 3 Current - Compressor 1ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR158doc 30159Line 1 Current RLA - Compressor 1ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR160doc 30161Line 2 Current RLA - Compressor 1ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR162doc 30163Line 3 Current RLA - Compressor 1ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR164doc 30165Line 1 Current - Compressor 1BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR166doc 30167Line 2 Current - Compressor 1BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR168doc 30169Line 3 Current - Compressor 1BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR170doc 30171Line 1 Current RLA - Compressor 1BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR172doc 30173Line 2 Current RLA - Compressor 1BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR174doc 30175Line 3 Current RLA - Compressor 1BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR176doc 30177Line 1 Current - Compressor 2ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR178doc 30179Line 2 Current - Compressor 2ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR180doc 30181Line 3 Current - Compressor 2ACurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR182doc 30183Line 1 Current RLA - Compressor 2ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR184doc 30185Line 2 Current RLA - Compressor 2ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR186doc 30187Line 3 Current RLA - Compressor 2ANeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR188doc 30189Line 1 Current - Compressor 2BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR190doc 30191Line 2 Current - Compressor 2BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR192doc 30193Line 3 Current - Compressor 2BCurrent. Needs: Wye-Delta StarterFLOAT32ABCDRead
IR194doc 30195Line 1 Current RLA - Compressor 2BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR196doc 30197Line 2 Current RLA - Compressor 2BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR198doc 30199Line 3 Current RLA - Compressor 2BNeeds: Wye-Delta StarterFLOAT32ABCD%Read
IR200doc 30201Drive Motor Current U Compressor 1ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR202doc 30203Drive Motor Current V Compressor 1ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR204doc 30205Drive Motor Current W Compressor 1ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR206doc 30207Drive Motor Current U RLA Compressor 1ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR208doc 30209Drive Motor Current V RLA Compressor 1ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR210doc 30211Drive Motor Current W RLA Compressor 1ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR212doc 30213Drive Motor Average Voltage Compressor 1AVoltage. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR214doc 30215Drive Motor Average Voltage Compressor 2AVoltage. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR216doc 30217Drive Motor Current U Compressor 2ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR218doc 30219Drive Motor Current V Compressor 2ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR220doc 30221Drive Motor Current W Compressor 2ACurrent. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR222doc 30223Drive Motor Current U RLA Compressor 2ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR224doc 30225Drive Motor Current V RLA Compressor 2ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR226doc 30227Drive Motor Current W RLA Compressor 2ANeeds: TR200 Modbus AFDFLOAT32ABCD%Read
IR228doc 30229Drive Motor Average Current RLA Compressor 1BNeeds: Generic AFDFLOAT32ABCD%Read
IR230doc 30231Drive Motor Average Current RLA Compressor 2BNeeds: Generic AFDFLOAT32ABCD%Read
IR232doc 30233Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR234doc 30235Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR236doc 30237Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR238doc 30239Evaporator Approach Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR240doc 30241Evaporator Approach Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR242doc 30243Unit Load CommandFLOAT32ABCD%Read
IR244doc 30245Chilled Water Pump 1 Run HoursNeeds: Single PumpFLOAT32ABCDRead
IR246doc 30247Chilled Water Pump 2 Run HoursNeeds: Dual PumpFLOAT32ABCDRead
IR248doc 30249Active Chilled Water Pump Service Interval SetpointNeeds: Single PumpFLOAT32ABCDRead
IR250doc 30251Evaporator Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR252doc 30253Condenser Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR254doc 30255Evaporator Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR256doc 30257Condenser Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR258doc 30259Oil Gauge Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR260doc 30261Oil Gauge Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR262doc 30263Oil Gauge Pressure - Compressor 1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR264doc 30265Oil Gauge Pressure - Compressor 2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR266doc 30267Free Cooling Glycol Gauge PressurePressure in the factory unit system (I-P or SI). Needs: Free Cooling, Glycol FreeFLOAT32ABCDRead
IR268doc 30269Evaporator Shell Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI). Needs: Isolation ValvesFLOAT32ABCDRead
IR270doc 30271Evaporator Shell Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Isolation ValvesFLOAT32ABCDRead
IR272doc 30273Active Heat Recovery SetpointTemperature in the factory unit system (I-P or SI). Needs: Total Heat RecoveryFLOAT32ABCDRead
IR274doc 30275Active Rapid Start Target Load CommandFLOAT32ABCD%Read
IR276doc 30277Free Cooling Valve Position StatusNeeds: Free CoolingFLOAT32ABCD%Read
IR278doc 30279Free Cooling Bypass Valve Position StatusNeeds: Free CoolingFLOAT32ABCD%Read
IR280doc 30281Free Cooling Target OffsetTemperature difference, factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR282doc 30283Free Cooling Pump Override Time RemainingNeeds: Free Cooling, Glycol FreeFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre- Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Front Panel Chiller Mode CommandUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2013doc 32014Refrigerant TypeUINT16Read5 = R-134a; 13 = R-513A; 16 = R-1234ze(E)
IR2014doc 32015Cooling TypeUINT16Read2 = Air Cooled
IR2015doc 32016Model Information [GEN2]UINT16Read5 = RTAF
IR2016doc 32017Manufacture LocationUINT16Read3 = Pueblo; 4 = Charmes
IR2017doc 32018Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR3010doc 33011Run EnableUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3011doc 33012Local Setpoint ControlUINT16Read0 = Remote control; 1 = Local control
IR3012doc 33013Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR3013doc 33014Chiller Running StateUINT16Read0 = Off; 1 = On
IR3014doc 33015Maximum CapacityUINT16Read0 = Off; 1 = On
IR3015doc 33016Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3016doc 33017Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop-Manual Reset Required
IR3017doc 33018Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3018doc 33019Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3019doc 33020Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3020doc 33021Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3021doc 33022Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3022doc 33023Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3023doc 33024Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3024doc 33025Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3025doc 33026Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3026doc 33027Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Compressor 1A Running StatusUINT16Read0 = Off; 1 = Running
IR3028doc 33029Compressor 1BRunning StatusNeeds: Compressor 1BUINT16Read0 = Off; 1 = Running
IR3029doc 33030Compressor 2A Running StatusUINT16Read0 = Off; 1 = Running
IR3030doc 33031Compressor 2B Running StatusNeeds: Compressor 2BUINT16Read0 = Off; 1 = Running
IR3031doc 33032External Auto Stop StatusUINT16Read0 = Stop; 1 = Auto
IR3032doc 33033Free Cooling ActiveNeeds: Free coolingUINT16Read0 = Normal; 1 = Active
IR3033doc 33034Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3034doc 33035Heat Recovery Control Active StatusNeeds: Total Heat RecoveryUINT16Read0 = Normal; 1 = Active
IR3035doc 33036Heat Recovery Ckt1 Active StatusNeeds: Total Heat RecoveryUINT16Read0 = Normal; 1 = Active
IR3036doc 33037Heat Recovery Ckt2 Active StatusNeeds: Total Heat RecoveryUINT16Read0 = Normal; 1 = Active
IR3037doc 33038Alarm - Latching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3038doc 33039Alarm - NonLatching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3039doc 33040Alarm - Ckt 1UINT16Read0 = Normal; 1 = In Alarm
IR3040doc 33041Alarm - Ckt 2UINT16Read0 = Normal; 1 = In Alarm
IR3041doc 33042Alarm - General Latching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3042doc 33043Alarm - General Non Latching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3043doc 33044Alarm - General Latching Ckt1UINT16Read0 = Normal; 1 = In Alarm
IR3044doc 33045Alarm - General Latching Ckt2UINT16Read0 = Normal; 1 = In Alarm
IR3045doc 33046Alarm - General Non Latching Ckt1UINT16Read0 = Normal; 1 = In Alarm
IR3046doc 33047Alarm - General Non Latching Ckt2UINT16Read0 = Normal; 1 = In Alarm
IR3047doc 33048Noise Reduction Request ActiveUINT16Read0 = Off; 1 = On
IR3048doc 33049Heat Recovery Water Flow StatusNeeds: Heat RecoveryUINT16Read0 = No; 1 = Flow
IR3049doc 33050Heat Recovery Water Pump CommandNeeds: Heat RecoveryUINT16Read0 = Off; 1 = On
IR3050doc 33051Circuit 1 Running StatusUINT16Read0 = Off; 1 = Running
IR3051doc 33052Circuit 2 Running StatusUINT16Read0 = Off; 1 = Running
IR3052doc 33053Emergency Stop Input StatusUINT16Read0 = Inactive; 1 = Active
IR3053doc 33054Evaporator Water Pump StatusUINT16Read0 = Off; 1 = On
IR3054doc 33055Active Heat Recovery CommandNeeds: Total Heat RecoveryUINT16Read0 = Off; 1 = On
IR3055doc 33056Active Rapid Start RequestUINT16Read0 = Off; 1 = On
IR3056doc 33057Fan 1 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3057doc 33058Fan 2 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3058doc 33059Fan 3 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3059doc 33060Fan 4 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3060doc 33061Fan 5 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3061doc 33062Fan 6 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3062doc 33063Fan 7 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3063doc 33064Fan 8 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3064doc 33065Fan 9 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3065doc 33066Fan 10 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3066doc 33067Fan 11 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3067doc 33068Fan 12 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3068doc 33069Fan 13 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3069doc 33070Fan 14 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3070doc 33071Fan 15 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3071doc 33072Fan 16 circuit 1 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3072doc 33073Fan 1 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3073doc 33074Fan 2 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3074doc 33075Fan 3 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3075doc 33076Fan 4 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3076doc 33077Fan 5 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3077doc 33078Fan 6 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3078doc 33079Fan 7 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3079doc 33080Fan 8 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3080doc 33081Fan 9 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3081doc 33082Fan 10 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3082doc 33083Fan 11 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3083doc 33084Fan 12 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3084doc 33085Fan 13 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3085doc 33086Fan 14 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3086doc 33087Fan 15 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3087doc 33088Fan 16 circuit 2 running stateNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3088doc 33089Fan 1 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3089doc 33090Fan 2 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3090doc 33091Fan 3 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3091doc 33092Fan 4 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3092doc 33093Fan 5 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3093doc 33094Fan 6 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3094doc 33095Fan 7 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3095doc 33096Fan 8 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3096doc 33097Fan 9 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3097doc 33098Fan 10 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3098doc 33099Fan 11 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3099doc 33100Fan 12 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3100doc 33101Fan 13 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3101doc 33102Fan 14 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3102doc 33103Fan 15 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3103doc 33104Fan 16 circuit 1 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3104doc 33105Fan 1 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3105doc 33106Fan 2 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3106doc 33107Fan 3 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3107doc 33108Fan 4 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3108doc 33109Fan 5 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3109doc 33110Fan 6 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3110doc 33111Fan 7 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3111doc 33112Fan 8 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3112doc 33113Fan 9 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3113doc 33114Fan 10 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3114doc 33115Fan 11 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3115doc 33116Fan 12 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3116doc 33117Fan 13 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3117doc 33118Fan 14 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3118doc 33119Fan 15 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3119doc 33120Fan 16 circuit 2 faultNeeds: Modbus FansUINT16Read0 = Off; 1 = On
IR3120doc 33121Free Cooling Pump Command StatusNeeds: Free Cooling Glycol FreeUINT16Read0 = Off; 1 = On
IR3121doc 33122Free Cooling Front Panel Command StatusNeeds: Free coolingUINT16Read0 = Off; 1 = On
IR3122doc 33123Free Cooling Glycol Flow StatusNeeds: Free Cooling Glycol FreeUINT16Read0 = Off; 1 = On
IR4000doc 34001Comm Loss: %RLA Indication Output(Vdc)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Comm Loss: AFD Fault Input 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Comm Loss: AFD Fault Input 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Comm Loss: AFD Fault Input 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Comm Loss: AFD Fault Input 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Comm Loss: AFD Run Command - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Comm Loss: AFD Run Command - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Comm Loss: AFD Speed Command 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Comm Loss: AFD Speed Command 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Comm Loss: AFD Speed Command 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Comm Loss: AFD Speed Command 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Comm Loss: Auxiliary Setpoint CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Comm Loss: Chiller Bypass Valve OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Comm Loss: Cond Fan Enbl Shared Ckt 1&2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Comm Loss: Cond Rfgt Tank Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Comm Loss: Cond Rfgt Tank Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Comm Loss: Condenser Fan Enable - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Comm Loss: Condenser Fan Enable - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Comm Loss: Condenser Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Comm Loss: Condenser Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Comm Loss: Cprsr Disch Rfgt Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Comm Loss: Cprsr Disch Rfgt Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Comm Loss: Cprsr Disch Rfgt Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Comm Loss: Cprsr Disch Rfgt Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Comm Loss: Economizer Disch Press - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Comm Loss: Economizer Disch Press - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Comm Loss: Economizer Disch Press - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Comm Loss: Economizer Disch Press - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Comm Loss: Economizer Disch Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Comm Loss: Economizer Disch Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Comm Loss: Economizer Disch Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Comm Loss: Economizer Disch Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Comm Loss: Economizer Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Comm Loss: Economizer Valve - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Comm Loss: Economizer Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Comm Loss: Economizer Valve - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Comm Loss: Electronic Expansion Valve - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Comm Loss: Electronic Expansion Valve - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Comm Loss: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Comm Loss: Energy MeterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Comm Loss: Energy Meter Pulse InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Comm Loss: Evap Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Comm Loss: Evap Iso Valve Close Switch - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Comm Loss: Evap Iso Valve Close Switch - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Comm Loss: Evap Iso Valve Open Switch - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Comm Loss: Evap Iso Valve Open Switch - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Comm Loss: Evap Isolation Valve Relay - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Comm Loss: Evap Isolation Valve Relay - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Comm Loss: Evap Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Comm Loss: Evap Pump Inv1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Comm Loss: Evap Pump Inv1 Run CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Comm Loss: Evap Rfgt Pool Temp - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Comm Loss: Evap Rfgt Pool Temp - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Comm Loss: Evap Shell Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Comm Loss: Evap Shell Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Comm Loss: Evap Water Pump Inv Freq InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Comm Loss: Evap Water Pump Inverter SpeedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Comm Loss: Evaporator Pump 1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Comm Loss: Evaporator Pump 2 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Comm Loss: Evaporator Water Pump 1 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Comm Loss: Evaporator Water Pump 2 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Comm Loss: Ext Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Comm Loss: Ext Noise Reduction RequestDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Comm Loss: External Ckt Lockout - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Comm Loss: External Ckt Lockout - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Comm Loss: External Heat Recovery Ckt LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Comm Loss: External Heat Recovery CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Comm Loss: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Comm Loss: Fan Board 1 Relay 1 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Comm Loss: Fan Board 1 Relay 1 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Comm Loss: Fan Board 1 Relay 2 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: Fan Board 1 Relay 2 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: Fan Board 1 Relay 3 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Fan Board 1 Relay 3 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: Fan Board 1 Relay 4 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: Fan Board 1 Relay 4 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Comm Loss: Fan Board 2 Relay 1 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Comm Loss: Fan Board 2 Relay 1 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Fan Board 2 Relay 2 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Comm Loss: Fan Board 2 Relay 2 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: Fan Board 2 Relay 3 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Fan Board 2 Relay 3 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Comm Loss: Fan Board 2 Relay 4 - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Comm Loss: Fan Board 2 Relay 4 - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: Fan Inverter Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: Fan Inverter Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Comm Loss: Fan Inverter Speed Command - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Comm Loss: Fan Inverter Speed Command - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Comm Loss: Free Cooling Bypass ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Comm Loss: Free Cooling Entering Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: Free Cooling Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: Free Cooling Glycol Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Comm Loss: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: Free Cooling Leaving Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Free Cooling PumpDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Free Cooling ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Comm Loss: Heat Recovery Mode Valve Command – Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Comm Loss: Heat Recovery Mode Valve Command – Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Comm Loss: Heat Recovery Water Flow Cmd - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: Heat Recovery Water Flow Cmd - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Heat Recovery Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: High Pressure Cutout Sw - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: High Pressure Cutout Sw - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: High Pressure Cutout Sw - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: High Pressure Cutout Sw - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: High Pressure Cutout Switch - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: High Pressure Cutout Switch - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: Hot Gas Bypass Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Comm Loss: Hot Gas Bypass Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Comm Loss: HR Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Comm Loss: HR Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Comm Loss: External Rapid Start CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: Liquid Line Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Liquid Line Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Liquid Line Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Liquid Line Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Comm Loss: Local BAS InterfaceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Comm Loss: Mains Voltage DetectionDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Comm Loss: Motor RLA Input - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Comm Loss: Motor RLA Input - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Comm Loss: Motor RLA Input - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Comm Loss: Motor RLA Input - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: Motor Winding Tstat Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Motor Winding Tstat Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Off-cycle Freeze Prot RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Oil Loss Level Sensor Input - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: Oil Loss Level Sensor Input - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Oil Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Oil Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Oil Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Oil Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: Oil Return Purge Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Comm Loss: Oil Return Purge Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Comm Loss: Oil Return Solenoid Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Oil Return Solenoid Valve - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Oil Return Solenoid Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Comm Loss: Oil Return Solenoid Valve - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Comm Loss: Oil Supply Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Comm Loss: Oil Supply Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Comm Loss: Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Comm Loss: Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Comm Loss: Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Comm Loss: Programmable Relay Board 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Comm Loss: Slide Valve Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Comm Loss: Slide Valve Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Comm Loss: Slide Valve Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Comm Loss: Slide Valve Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Comm Loss: Slide Valve Unload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Comm Loss: Slide Valve Unload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Comm Loss: Slide Valve Unload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Comm Loss: Slide Valve Unload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Comm Loss: Starter 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Comm Loss: Starter 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Comm Loss: Starter 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Comm Loss: Starter 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Comm Loss: Step Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Comm Loss: Step Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Comm Loss: Step Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Comm Loss: Step Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Comm Loss: Suction Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Comm Loss: Suction Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Comm Loss: Suction Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Comm Loss: Suction Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Comm Loss: Suction Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Comm Loss: Suction Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Comm Loss: Var Vi Valve – Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Comm Loss: Var Vi Valve – Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Comm Loss: Water System Diff PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Comm Loss: Winding Temp 1, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Comm Loss: Winding Temp 1, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Comm Loss: Winding Temp 2, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Comm Loss: Winding Temp 2, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: AFD %RLA Feedback - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Diagnostic: AFD %RLA Feedback - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: AFD %RLA Feedback - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: AFD %RLA Feedback - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: AFD Bump Complete - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic: AFD Bump Complete - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic: AFD Bump Current High - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic: AFD Bump Current High - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: AFD Comm Loss – 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: AFD Comm Loss – 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic: AFD Comm Loss – 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: AFD Comm Loss – 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: AFD Failure to Arm or Start - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: AFD Failure to Arm or Start - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: AFD Failure to Arm or Start - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: AFD Failure to Arm or Start - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: AFD Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic: AFD Fault - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: AFD Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: AFD Fault - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: AFD Fault Mains - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Diagnostic: AFD Fault Mains - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Diagnostic: AFD Fault Mains - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic: AFD Fault Mains - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic: AFD Harmonic Filter Over Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic: AFD Harmonic Filter Over Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: AFD High Pressure Cutout - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: AFD High Pressure Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: AFD Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic: AFD Interrupt Failure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: AFD Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: AFD Interrupt Failure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: AFD Motor Current Overload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: AFD Motor Current Overload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: AFD Motor Current Overload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic: AFD Motor Current Overload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic: AFD Motor Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: AFD Motor Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: AFD Motor Speed Too High - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: AFD Motor Speed Too High - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: AFD Motor Speed Too Low - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: AFD Motor Speed Too Low - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic: AFD Pump Out Speed Low - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic: AFD Pump Out Speed Low - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic: AFD Unexpected Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Diagnostic: AFD Unexpected Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: AFD Unhandled Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic: AFD Unhandled Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: BAS Communication LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic: BAS Failed to Establish CommunicationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic: Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: Chiller Service RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: Compressor Speed Too High - Thrust Load - Cprs1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic: Compressor Speed Too High - Thrust Load - Cprs1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: Compressor Speed Too High - Thrust Load - Cprs2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: Compressor Speed Too High - Thrust Load - Cprs2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: Compressor Speed Too Low - Discharge Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: Compressor Speed Too Low - Discharge Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Diagnostic: Compressor Speed Too Low - Discharge Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Diagnostic: Compressor Speed Too Low - Discharge Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Diagnostic: Compressor Speed Too Low - Oil Viscosity - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic: Compressor Speed Too Low - Oil Viscosity - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic: Compressor Speed Too Low - Oil Viscosity - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic: Compressor Speed Too Low - Oil Viscosity - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Diagnostic: Condenser Rfgt Pressure Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Diagnostic: Condenser Rfgt Pressure Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Diagnostic: Cprsr Did Not Accel: Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Diagnostic: Cprsr Did Not Accel: Shutdown - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Diagnostic: Cprsr Did Not Accel: Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Diagnostic: Cprsr Did Not Accel: Shutdown - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Diagnostic: Cprsr Did Not Accel: Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Diagnostic: Cprsr Did Not Accel: Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Diagnostic: Cprsr Did Not Accel: Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4257doc 34258Diagnostic: Cprsr Did Not Accel: Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4258doc 34259Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4259doc 34260Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4260doc 34261Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4261doc 34262Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4262doc 34263Diagnostic: Economizer Disch Press Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4263doc 34264Diagnostic: Economizer Disch Press Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4264doc 34265Diagnostic: Economizer Disch Press Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4265doc 34266Diagnostic: Economizer Disch Press Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4266doc 34267Diagnostic: Economizer Disch Temp Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4267doc 34268Diagnostic: Economizer Disch Temp Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4268doc 34269Diagnostic: Economizer Disch Temp Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4269doc 34270Diagnostic: Economizer Disch Temp Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4270doc 34271Diagnostic: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4271doc 34272Diagnostic: Energy Meter Write Command FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4272doc 34273Diagnostic: Evap Iso Valve Illegal Switch State - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4273doc 34274Diagnostic: Evap Iso Valve Illegal Switch State - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4274doc 34275Diagnostic: Evap Isolation Valve Closed Switch Failure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4275doc 34276Diagnostic: Evap Isolation Valve Closed Switch Failure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4276doc 34277Diagnostic: Evap Isolation Valve Failed To Close - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4277doc 34278Diagnostic: Evap Isolation Valve Failed To Close - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4278doc 34279Diagnostic: Evap Isolation Valve Failed To Open - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4279doc 34280Diagnostic: Evap Isolation Valve Failed To Open - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4280doc 34281Diagnostic: Evap Isolation Valve Open Switch Failure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4281doc 34282Diagnostic: Evap Isolation Valve Open Switch Failure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4282doc 34283Diagnostic: Evap Pump 1 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4283doc 34284Diagnostic: Evap Pump 2 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4284doc 34285Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4285doc 34286Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4286doc 34287Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4287doc 34288Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4288doc 34289Diagnostic: Evap Water Pump 1 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4289doc 34290Diagnostic: Evap Water Pump 2 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4290doc 34291Diagnostic: Evaporator Approach Error - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4291doc 34292Diagnostic: Evaporator Approach Error - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4292doc 34293Diagnostic: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4293doc 34294Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4294doc 34295Diagnostic: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4295doc 34296Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4296doc 34297Diagnostic: Evaporator Pump 1 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4297doc 34298Diagnostic: Evaporator Pump 2 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4298doc 34299Diagnostic: Evaporator Shell Rfgt Pressure Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4299doc 34300Diagnostic: Evaporator Shell Rfgt Pressure Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4300doc 34301Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4301doc 34302Diagnostic: Evaporator Water Flow Lost - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4302doc 34303Diagnostic: Evaporator Water Flow Lost - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4303doc 34304Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4304doc 34305Diagnostic: Evaporator Water Flow Overdue - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4305doc 34306Diagnostic: Evaporator Water Flow Overdue - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4306doc 34307Diagnostic: Excessive Condenser Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4307doc 34308Diagnostic: Excessive Condenser Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4308doc 34309Diagnostic: External Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4309doc 34310Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4310doc 34311Diagnostic: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4311doc 34312Diagnostic: EXV Pressure Equalization Failed - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4312doc 34313Diagnostic: EXV Pressure Equalization Failed - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4313doc 34314Diagnostic: Fan Inverter Fault - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4314doc 34315Diagnostic: Fan Inverter Fault - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4315doc 34316Diagnostic: Free Cooling Entering Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4316doc 34317Diagnostic: Free Cooling Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4317doc 34318Diagnostic: Free Cooling Glycol Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4318doc 34319Diagnostic: Free Cooling Glycol Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4319doc 34320Diagnostic: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4320doc 34321Diagnostic: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4321doc 34322Diagnostic: Free Cooling Glycol Temperature Equalization OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4322doc 34323Diagnostic: Free Cooling Leaving Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4323doc 34324Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4324doc 34325Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4325doc 34326Diagnostic: Heat Recovery Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4326doc 34327Diagnostic: Heat Recovery Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4327doc 34328Diagnostic: High Cprsr Rfgt Discharge Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4328doc 34329Diagnostic: High Cprsr Rfgt Discharge Temp - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4329doc 34330Diagnostic: High Cprsr Rfgt Discharge Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4330doc 34331Diagnostic: High Cprsr Rfgt Discharge Temp - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4331doc 34332Diagnostic: High Differential Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4332doc 34333Diagnostic: High Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4333doc 34334Diagnostic: High Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4334doc 34335Diagnostic: High Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4335doc 34336Diagnostic: High Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4336doc 34337Diagnostic: High Evap Shell Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4337doc 34338Diagnostic: High Evap Shell Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4338doc 34339Diagnostic: High Evaporator Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4339doc 34340Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4340doc 34341Diagnostic: High Motor Winding Temperature - 1A - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4341doc 34342Diagnostic: High Motor Winding Temperature - 1A - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4342doc 34343Diagnostic: High Motor Winding Temperature - 2A - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4343doc 34344Diagnostic: High Motor Winding Temperature - 2A - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4344doc 34345Diagnostic: High Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4345doc 34346Diagnostic: High Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4346doc 34347Diagnostic: High Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4347doc 34348Diagnostic: High Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4348doc 34349Diagnostic: High Pressure Cutout - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4349doc 34350Diagnostic: High Pressure Cutout - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4350doc 34351Diagnostic: High Pressure Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4351doc 34352Diagnostic: High Pressure Cutout - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4352doc 34353Diagnostic: High Pressure Cutout - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4353doc 34354Diagnostic: High Pressure Cutout - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4354doc 34355Diagnostic: High Refrigerant Pressure RatioDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4355doc 34356Diagnostic: High Refrigerant Pressure Ratio - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4356doc 34357Diagnostic: High Refrigerant Pressure Ratio - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4357doc 34358Diagnostic: High Refrigerant Pressure Ratio - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4358doc 34359Diagnostic: High Refrigerant Pressure Ratio - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4359doc 34360Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4360doc 34361Diagnostic: LCI-C Software Mismatch: Use BAS ToolDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4361doc 34362Diagnostic: Liquid Line Pressure Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4362doc 34363Diagnostic: Liquid Line Pressure Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4363doc 34364Diagnostic: Liquid Line Temp Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4364doc 34365Diagnostic: Liquid Line Temp Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4365doc 34366Diagnostic: Loss of Oil at Compressor (Running) - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4366doc 34367Diagnostic: Loss of Oil at Compressor (Running) - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4367doc 34368Diagnostic: Loss of Oil at Compressor (Stopped) - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4368doc 34369Diagnostic: Loss of Oil at Compressor (Stopped) - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4369doc 34370Diagnostic: Loss of Oil for Compressor (Running) - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4370doc 34371Diagnostic: Loss of Oil for Compressor (Running) - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4371doc 34372Diagnostic: Loss of Oil for Compressor (Stopped) - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4372doc 34373Diagnostic: Loss of Oil for Compressor (Stopped) - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4373doc 34374Diagnostic: Low Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4374doc 34375Diagnostic: Low Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4375doc 34376Diagnostic: Low Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4376doc 34377Diagnostic: Low Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4377doc 34378Diagnostic: Low Discharge Superheat - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4378doc 34379Diagnostic: Low Discharge Superheat - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4379doc 34380Diagnostic: Low Discharge Superheat - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4380doc 34381Diagnostic: Low Discharge Superheat - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4381doc 34382Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4382doc 34383Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4383doc 34384Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4384doc 34385Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4385doc 34386Diagnostic: Low Glycol Pressure Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4386doc 34387Diagnostic: Low Glycol Temp Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4387doc 34388Diagnostic: Low Oil Flow - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4388doc 34389Diagnostic: Low Oil Flow - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4389doc 34390Diagnostic: Low Oil Flow - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4390doc 34391Diagnostic: Low Oil Flow - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4391doc 34392Diagnostic: Low Refrigerant Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4392doc 34393Diagnostic: Low Refrigerant Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4393doc 34394Diagnostic: Low Suction Refrigerant Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4394doc 34395Diagnostic: Low Suction Refrigerant Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4395doc 34396Diagnostic: Main Power LossDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4396doc 34397Diagnostic: Mfr Maintenance Recommended - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4397doc 34398Diagnostic: Mfr Maintenance Recommended - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4398doc 34399Diagnostic: Mfr Maintenance Recommended - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4399doc 34400Diagnostic: Mfr Maintenance Recommended - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4400doc 34401Diagnostic: Momentary Power Loss - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4401doc 34402Diagnostic: Momentary Power Loss - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4402doc 34403Diagnostic: Motor Current Overload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4403doc 34404Diagnostic: Motor Current Overload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4404doc 34405Diagnostic: Motor Current Overload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4405doc 34406Diagnostic: Motor Current Overload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4406doc 34407Diagnostic: Motor Winding Temp Sensor - Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4407doc 34408Diagnostic: Motor Winding Temp Sensor - Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4408doc 34409Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4409doc 34410Diagnostic: MP: Non-Volatile Block Test ErrorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4410doc 34411Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4411doc 34412Diagnostic: No Differential Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4412doc 34413Diagnostic: No Differential Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4413doc 34414Diagnostic: No Differential Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4414doc 34415Diagnostic: No Differential Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4415doc 34416Diagnostic: Oil Analysis Recommended - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4416doc 34417Diagnostic: Oil Analysis Recommended - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4417doc 34418Diagnostic: Oil Filter Change Recommended - Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4418doc 34419Diagnostic: Oil Filter Change Recommended - Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4419doc 34420Diagnostic: Oil Flow Protection Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4420doc 34421Diagnostic: Oil Flow Protection Fault - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4421doc 34422Diagnostic: Oil Flow Protection Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4422doc 34423Diagnostic: Oil Flow Protection Fault - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4423doc 34424Diagnostic: Oil Pressure Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4424doc 34425Diagnostic: Oil Pressure Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4425doc 34426Diagnostic: Oil Pressure Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4426doc 34427Diagnostic: Oil Pressure Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4427doc 34428Diagnostic: Oil Supply Temperature Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4428doc 34429Diagnostic: Oil Supply Temperature Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4429doc 34430Diagnostic: Oil Temperature Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4430doc 34431Diagnostic: Oil Temperature Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4431doc 34432Diagnostic: Oil Temperature Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4432doc 34433Diagnostic: Oil Temperature Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4433doc 34434Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4434doc 34435Diagnostic: Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4435doc 34436Diagnostic: Phase Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4436doc 34437Diagnostic: Phase Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4437doc 34438Diagnostic: Phase Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4438doc 34439Diagnostic: Phase Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4439doc 34440Diagnostic: Phase Reversal - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4440doc 34441Diagnostic: Phase Reversal - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4441doc 34442Diagnostic: Phase Reversal - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4442doc 34443Diagnostic: Phase Reversal - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4443doc 34444Diagnostic: Power Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4444doc 34445Diagnostic: Power Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4445doc 34446Diagnostic: Power Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4446doc 34447Diagnostic: Power Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4447doc 34448Diagnostic: Pumpdown Terminated By Time - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4448doc 34449Diagnostic: Pumpdown Terminated By Time - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4449doc 34450Diagnostic: Restart Inhibit Invoked - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4450doc 34451Diagnostic: Restart Inhibit Invoked - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4451doc 34452Diagnostic: Restart Inhibit Invoked - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4452doc 34453Diagnostic: Restart Inhibit Invoked - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4453doc 34454Diagnostic: Severe Current Imbalance - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4454doc 34455Diagnostic: Severe Current Imbalance - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4455doc 34456Diagnostic: Severe Current Imbalance - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4456doc 34457Diagnostic: Severe Current Imbalance - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4457doc 34458Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4458doc 34459Diagnostic: Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4459doc 34460Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4460doc 34461Diagnostic: Starter Comm Loss: Main Processor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4461doc 34462Diagnostic: Starter Comm Loss: Main Processor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4462doc 34463Diagnostic: Starter Comm Loss: Main Processor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4463doc 34464Diagnostic: Starter Comm Loss: Main Processor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4464doc 34465Diagnostic: Starter Contactor Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4465doc 34466Diagnostic: Starter Contactor Interrupt Failure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4466doc 34467Diagnostic: Starter Contactor Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4467doc 34468Diagnostic: Starter Contactor Interrupt Failure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4468doc 34469Diagnostic: Starter Did Not Fully Accelerate - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4469doc 34470Diagnostic: Starter Did Not Fully Accelerate - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4470doc 34471Diagnostic: Starter Did Not Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4471doc 34472Diagnostic: Starter Did Not Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4472doc 34473Diagnostic: Starter Did Not Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4473doc 34474Diagnostic: Starter Did Not Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4474doc 34475Diagnostic: Starter Dry Run Test - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4475doc 34476Diagnostic: Starter Dry Run Test - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4476doc 34477Diagnostic: Starter Dry Run Test - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4477doc 34478Diagnostic: Starter Dry Run Test - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4478doc 34479Diagnostic: Starter Failed to Arm/Start - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4479doc 34480Diagnostic: Starter Failed to Arm/Start - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4480doc 34481Diagnostic: Starter Failed to Arm/Start - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4481doc 34482Diagnostic: Starter Failed to Arm/Start - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4482doc 34483Diagnostic: Starter Fault Type I - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4483doc 34484Diagnostic: Starter Fault Type I - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4484doc 34485Diagnostic: Starter Fault Type I - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4485doc 34486Diagnostic: Starter Fault Type I - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4486doc 34487Diagnostic: Starter Fault Type II - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4487doc 34488Diagnostic: Starter Fault Type II - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4488doc 34489Diagnostic: Starter Fault Type II - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4489doc 34490Diagnostic: Starter Fault Type II - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4490doc 34491Diagnostic: Starter Fault Type III - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4491doc 34492Diagnostic: Starter Fault Type III - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4492doc 34493Diagnostic: Starter Fault Type III - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4493doc 34494Diagnostic: Starter Fault Type III - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4494doc 34495Diagnostic: Starter Module Memory Error Type 1 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4495doc 34496Diagnostic: Starter Module Memory Error Type 1 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4496doc 34497Diagnostic: Starter Module Memory Error Type 1 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4497doc 34498Diagnostic: Starter Module Memory Error Type 1 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4498doc 34499Diagnostic: Starter Module Memory Error Type 2 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4499doc 34500Diagnostic: Starter Module Memory Error Type 2 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4500doc 34501Diagnostic: Starter Module Memory Error Type 2 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4501doc 34502Diagnostic: Starter Module Memory Error Type 2 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4502doc 34503Diagnostic: Starts/Hours Modified 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4503doc 34504Diagnostic: Starts/Hours Modified 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4504doc 34505Diagnostic: Starts/Hours Modified 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4505doc 34506Diagnostic: Starts/Hours Modified 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4506doc 34507Diagnostic: Suction Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4507doc 34508Diagnostic: Suction Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4508doc 34509Diagnostic: Suction Refrigerant Pressure Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4509doc 34510Diagnostic: Suction Refrigerant Pressure Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4510doc 34511Diagnostic: Suction Refrigerant Pressure Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4511doc 34512Diagnostic: Suction Refrigerant Pressure Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4512doc 34513Diagnostic: Transition Complete Input Opened - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4513doc 34514Diagnostic: Transition Complete Input Opened - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4514doc 34515Diagnostic: Transition Complete Input Opened - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4515doc 34516Diagnostic: Transition Complete Input Opened - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4516doc 34517Diagnostic: Transition Complete Input Shorted - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4517doc 34518Diagnostic: Transition Complete Input Shorted - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4518doc 34519Diagnostic: Transition Complete Input Shorted - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4519doc 34520Diagnostic: Transition Complete Input Shorted - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4520doc 34521Diagnostic: Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4521doc 34522Diagnostic: Unexpected Starter Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4522doc 34523Diagnostic: Unexpected Starter Shutdown - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4523doc 34524Diagnostic: Unexpected Starter Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4524doc 34525Diagnostic: Unexpected Starter Shutdown - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4525doc 34526Diagnostic: Very Low Discharge Superheat - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4526doc 34527Diagnostic: Very Low Discharge Superheat - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4527doc 34528Diagnostic: Very Low Evap Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4528doc 34529Diagnostic: Very Low Evap Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4529doc 34530Diagnostic: Very Low Evap Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4530doc 34531Diagnostic: Very Low Evap Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4531doc 34532Diagnostic: Water System Differential PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4532doc 34533Comm Loss: Fan Control ModuleDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4533doc 34534Comm Loss: Condenser Fan Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4534doc 34535Comm Loss: Condenser Fan Shared CircuitDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4535doc 34536Comm Loss: Condenser Fan Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4536doc 34537Diagnostic: Drive 1A configuration may be not completeDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4537doc 34538Diagnostic: Drive 1B configuration may be not completeDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4538doc 34539Diagnostic: Drive 2A configuration may be not completeDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4539doc 34540Diagnostic: Drive 2B configuration may be not completeDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4540doc 34541Comm Loss: Refrigerant Leak DetectorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4541doc 34542Diagnostic: Refrigerant Leakage DetectedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4542doc 34543Comm Loss: Evap Water Pump Inlet PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4543doc 34544Diagnostic: Low Evaporator Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4544doc 34545Diagnostic: Evaporator Water Pump Inlet Pressure TransducerDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Heat Recovery Leaving Water Temperature Setpoint BASTemperature in the factory unit system (I-P or SI). Needs: Total Heat RecoveryFLOAT32ABCDRead/write
HR16doc 40017Evaporator Water Pump Speed SetpointNeeds: Variable Speed PumpFLOAT32ABCD%Read/write
HR18doc 40019Rapid Start Target Load Command BASFLOAT32ABCD%Read/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3011doc 43012Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3012doc 43013Noise Reduction Request BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3013doc 43014Circuit 1 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3014doc 43015Circuit 2 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3015doc 43016Compressor 1A Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3016doc 43017Compressor 1B Lockout BASNeeds: Compressor 1BUINT16Read/write0 = Normal; 1 = Locked Out
HR3017doc 43018Compressor 2A Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3018doc 43019Compressor 2B Lockout BASNeeds: Compressor 2BUINT16Read/write0 = Normal; 1 = Locked Out
HR3019doc 43020Free Cooling Auto Stop Command BASNeeds: Free CoolingUINT16Read/write0 = Stop; 1 = Auto
HR3020doc 43021Energy Consumption ResetNeeds: Energy MeterUINT16Read/write0 = Accumulating; 1 = Reset
HR3021doc 43022Heat Recovery Enable BASNeeds: Heat RecoveryUINT16Read/write0 = Off; 1 = On
HR3022doc 43023Heat Recovery Lockout Circuit 1 BASNeeds: Heat RecoveryUINT16Read/write0 = Normal; 1 = Locked Out
HR3023doc 43024Heat Recovery Lockout Circuit 2 BASNeeds: Heat RecoveryUINT16Read/write0 = Normal; 1 = Locked Out
HR3024doc 43025Evaporator Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3025doc 43026Rapid Start Request BASUINT16Read/write0 = Off; 1 = On
HR3026doc 43027Free Cooling Compressor LockoutNeeds: Free CoolingUINT16Read/write0 = Normal; 1 = Locked Out

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)

What Modbus registers does the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) have?

This map lists 826 registers: 803 input registers, 23 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)?

Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 24 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 22 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 36 Actual Running Capacity (Actual running capacity); IR 26 Outdoor Air Temperature (Outdoor air temperature); IR 2010 Running Mode (Running mode); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3010 Chiller Auto Stop Command BAS (Chiller auto/stop command); HR 3011 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane Sintesis RTAF air-cooled screw chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Sintesis Model RTAF (BAS-PTS013B-EN), revision 2026-04-07, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS013B-EN_04072026.pdf.