Pump (data-centre coolant distribution unit) · Modbus register map

Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus register map

Updated 19 November 2026

Short answer

Liquid-to-liquid coolant distribution unit that moves heat from a direct-to-chip server loop (TCS) to facility water (FWS) using two variable-speed pumps and a control valve. Modbus TCP exposes one block of 16-bit holding registers: pressures, flows, temperatures, pump and valve values, setpoints, sensor range states and packed status and error words.

This page lists 89 Modbus registers for the Trane TCDU coolant distribution unit (data-centre liquid cooling) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
TCDU coolant distribution unit (data-centre liquid cooling)
Equipment type
Pump (data-centre coolant distribution unit)
Registers
89 (20 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
503
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A
Source document
Installation, Operation, and Maintenance: Coolant Distribution Unit · DC-SVX001A-EN · rev. 2025-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane TCDU coolant distribution unit (data-centre liquid cooling)

Integration in brief

Connect to the TCDU's Telemetry Control RJ45 with Modbus TCP on port 503 (not 502) and read holding registers 40001-40096. Setpoints sit in 40046-40062 and the control word in 40092.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Summarized fault / common faultINT16Common fault summaryRead
HR 31TCS supply temperatureINT16TCS supply temperatureRead
HR 32TCS return temperatureINT16TCS return temperatureRead
HR 29TCS flow rate 1INT16TCS flow rateRead
HR 36TCS coolingINT16TCS cooling kWRead
HR 12FWS input temperatureINT16FWS supply temperatureRead
HR 48TCS supply temperature setpointINT16TCS supply temperature setpointRead/write
HR 90System status bitsBITMAP16System status bitsRead
HR 0Modbus comm check counterINT16Heartbeat counterRead

Enable Modbus control & writes

Modbus TCP is served on the RJ45 port labelled Telemetry Control (also used for data-log download and the REST API). The port takes a DHCP address by default; a fixed IP is set by logging into the internal IOT2050 module over SSH, editing the connection with nmtui and rebooting it.

Byte order & addressing

Network setup

Watch out for

Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

89 of 89 shown
Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Modbus comm check counterCounts up and loops 1-255; use as a heartbeat.INT16Read
HR1doc 40002Summarized fault / common faultINT16Read0 = Normal; 1 = At least one warning; 2 = At least one alarm or instrument failure
HR2doc 40003System roleINT16Read0 = Master / standalone; 1 = Slave ID1; 2 = Slave ID2; 3 = Slave ID3
HR3doc 40004Ambient temperatureINT16× 0.1°CRead
HR4doc 40005Ambient dew pointCalculated dew point.INT16× 0.1°CRead
HR5doc 40006Ambient relative humidityINT16× 0.1%Read
HR6doc 40007FWS input pressure 1Facility water supply pressure.INT16× 0.01bar(g)Read
HR7doc 40008FWS input pressure 2Facility water supply pressure after the strainer.INT16× 0.01bar(g)Read
HR8doc 40009FWS output pressureFacility water return pressure.INT16× 0.01bar(g)Read
HR9doc 40010FWS strainer dPPressure drop across the facility-side strainer.INT16× 0.01bar(g)Read
HR10doc 40011FWS loop dPFacility supply minus return pressure.INT16× 0.01bar(g)Read
HR11doc 40012FWS flow rateINT16L/minRead
HR12doc 40013FWS input temperatureFacility water supply temperature.INT16× 0.1°CRead
HR13doc 40014FWS output temperatureFacility water return temperature.INT16× 0.1°CRead
HR14doc 40015FWS dTFacility supply/return temperature difference.INT16× 0.1°CRead
HR15doc 40016FWS valve position commandINT16× 0.1%Read
HR16doc 40017FWS valve position feedbackINT16× 0.1%Read
HR17doc 40018FWS coolingCooling duty calculated on the facility side.INT16× 0.1kWRead
HR22doc 40023TCS loop dPTechnology cooling loop supply minus return pressure.INT16× 0.01bar(g)Read
HR23doc 40024TCS pump 1 pressurePump 1 outlet pressure.INT16× 0.01bar(g)Read
HR24doc 40025TCS pump 2 pressurePump 2 outlet pressure.INT16× 0.01bar(g)Read
HR25doc 40026TCS supply pressureTechnology cooling supply pressure after the strainer.INT16× 0.01bar(g)Read
HR26doc 40027TCS return pressureINT16× 0.01bar(g)Read
HR27doc 40028TCS strainer 1 dPINT16× 0.01bar(g)Read
HR28doc 40029TCS strainer 2 dPINT16× 0.01bar(g)Read
HR29doc 40030TCS flow rate 1INT16L/minRead
HR30doc 40031TCS flow rate 2Redundant flow reading, if fitted.INT16L/minRead
HR31doc 40032TCS supply temperatureCoolant temperature to the IT load.INT16× 0.1°CRead
HR32doc 40033TCS return temperatureINT16× 0.1°CRead
HR33doc 40034TCS dTINT16× 0.1°CRead
HR34doc 40035TCS pump 1 speedCommanded speed.INT16× 0.1%Read
HR35doc 40036TCS pump 2 speedCommanded speed.INT16× 0.1%Read
HR36doc 40037TCS coolingCooling duty calculated on the technology side.INT16× 0.1kWRead
HR37doc 40038TCS pump 1 output powerINT16× 0.1kWRead
HR38doc 40039TCS pump 1 inverter drive temperatureINT16× 0.1°CRead
HR39doc 40040TCS pump 1 kWh meterINT16× 0.1kWhRead
HR40doc 40041TCS pump 1 MWh meterINT16MWhRead
HR41doc 40042TCS pump 2 output powerINT16× 0.1kWRead
HR42doc 40043TCS pump 2 inverter drive temperatureINT16× 0.1°CRead
HR43doc 40044TCS pump 2 kWh meterINT16× 0.1kWhRead
HR44doc 40045TCS pump 2 MWh meterINT16MWhRead
HR45doc 40046TCS static pressure setpointPressure at which the fill pump switches on.INT16× 0.01bar(g)Read/write
HR46doc 40047Condensation control dew pointDew point where condensation control starts limiting TCS supply temperature.INT16× 0.1°CRead/write
HR47doc 40048System ATD targetTarget approach (TCS supply minus FWS supply) for fault-tolerant operation.INT16× 0.1°CRead/write
HR48doc 40049TCS supply temperature setpointINT16× 0.1°CRead/write
HR50doc 40051TCS fixed flow rate setpointUsed in fixed-flow pump mode.INT16L/minRead/write
HR51doc 40052TCS fixed dP setpointUsed in fixed-dP pump mode.INT16× 0.01bar(g)Read/write
HR52doc 40053TCS fixed speed, single-pump modeINT16× 0.1%Read/write
HR53doc 40054TCS fixed speed, dual-pump modeINT16× 0.1%Read/write
HR54doc 40055TCS pump 1 speed in manual modeApplies when pump 1 is in manual mode and switched on at the HMI.INT16× 0.1%Read/write
HR55doc 40056TCS pump 2 speed in manual modeApplies when pump 2 is in manual mode and switched on at the HMI.INT16× 0.1%Read/write
HR56doc 40057TCS pump control modeINT16Read/write1 = Fixed flow; 2 = Fixed dP; 3 = Fixed speed
HR57doc 40058TCS pump cycle duty durationRun time before changeover to the partner pump in single-pump mode.INT16hRead/write
HR58doc 40059FWS flow rate control modeFacility-side ePICV valve control mode.INT16Read/write0 = TCS temperature control; 1 = Flow control; 2 = Energy control
HR59doc 40060FWS valve manual %Fixed valve opening in manual mode.INT16× 0.1%Read/write
HR60doc 40061Data log interval0 = 0.5 s; 1-300 = interval in seconds.INT16sRead/write
HR61doc 40062FWS fixed flow rate setpointePICV fixed-flow mode setpoint.INT16L/minRead/write
HR64doc 40065Ambient temperature stateRange state of the reading; the manual does not list the state codes.INT16Read
HR65doc 40066Ambient dew point stateRange state of the reading; the manual does not list the state codes.INT16Read
HR66doc 40067Ambient RH stateRange state of the reading; the manual does not list the state codes.INT16Read
HR67doc 40068FWS input pressure 1 stateRange state of the reading; the manual does not list the state codes.INT16Read
HR68doc 40069FWS input pressure 2 stateRange state of the reading; the manual does not list the state codes.INT16Read
HR69doc 40070FWS output pressure stateRange state of the reading; the manual does not list the state codes.INT16Read
HR70doc 40071FWS strainer dP stateRange state of the reading; the manual does not list the state codes.INT16Read
HR71doc 40072TCS loop dP stateRange state of the reading; the manual does not list the state codes.INT16Read
HR72doc 40073FWS flow rate stateRange state of the reading; the manual does not list the state codes.INT16Read
HR73doc 40074FWS input temperature stateRange state of the reading; the manual does not list the state codes.INT16Read
HR74doc 40075FWS output temperature stateRange state of the reading; the manual does not list the state codes.INT16Read
HR75doc 40076FWS dT stateRange state of the reading; the manual does not list the state codes.INT16Read
HR76doc 40077TCS pump 1 pressure stateRange state of the reading; the manual does not list the state codes.INT16Read
HR77doc 40078TCS pump 2 pressure stateRange state of the reading; the manual does not list the state codes.INT16Read
HR78doc 40079TCS supply pressure stateRange state of the reading; the manual does not list the state codes.INT16Read
HR79doc 40080TCS return pressure stateRange state of the reading; the manual does not list the state codes.INT16Read
HR80doc 40081TCS strainer 1 dP stateRange state of the reading; the manual does not list the state codes.INT16Read
HR81doc 40082TCS strainer 2 dP stateRange state of the reading; the manual does not list the state codes.INT16Read
HR82doc 40083TCS flow rate 1 stateRange state of the reading; the manual does not list the state codes.INT16Read
HR83doc 40084TCS flow rate 2 stateRange state of the reading; the manual does not list the state codes.INT16Read
HR84doc 40085TCS supply temperature stateRange state of the reading; the manual does not list the state codes.INT16Read
HR85doc 40086TCS return temperature stateRange state of the reading; the manual does not list the state codes.INT16Read
HR86doc 40087TCS dT stateRange state of the reading; the manual does not list the state codes.INT16Read
HR87doc 40088Threshold setpoint pointerIndex of the alarm threshold to read or write via 40089/40090.INT16Read/write
HR88doc 40089Threshold value for writeNew value for the threshold chosen in 40088; scale depends on the threshold.INT16Read/write
HR89doc 40090Threshold value for readEcho of the selected threshold; -999 signals a write error.INT16Read/write
HR90doc 40091System status bitsPacked unit status flags.BITMAP16Readbit 0 = Unit in operating state (a pump can be switched on); bit 1 = E-stop: 1 = normal, 0 = emergency button pressed; bit 2 = Safety relay: 1 = on (pump start possible), 0 = off / emergency not acknowledged; bit 3 = Leak detection: 1 = no leak, 0 = leak or sensor failure; bit 4 = Reservoir high-level sensor sees liquid; bit 5 = Reservoir low-level sensor sees liquid (0 = reservoir empty); bit 6 = Inverter 1: 1 = normal, 0 = off or in error; bit 7 = Inverter 2: 1 = normal, 0 = off or in error; bit 8 = Condensation control acting; bit 9 = TCS fill pump on
HR91doc 40092System control bitsPacked control flags; write the whole word.BITMAP16Read/writebit 0 = Lock TCS pump 1 off for maintenance; bit 1 = Lock TCS pump 2 off for maintenance; bit 2 = Condensation control enabled; bit 3 = Reset safety relay (short pulse clears fault/off state); bit 4 = TCS pump duty mode: 0 = single, 1 = dual; bit 15 = Data logging on
HR92doc 40093System error bits 1Facility-side and ambient sensor errors (1 = error).BITMAP16Readbit 0 = Ambient temperature error; bit 1 = Ambient dew point error; bit 2 = Ambient RH error; bit 3 = FWS input pressure 1 error; bit 4 = FWS input pressure 2 error; bit 5 = FWS output pressure error; bit 6 = FWS strainer dP cannot be calculated; bit 7 = FWS loop dP cannot be calculated; bit 8 = FWS flow rate error; bit 9 = FWS input temperature error; bit 10 = FWS output temperature error; bit 11 = FWS dT cannot be calculated; bit 12 = FWS cooling status cannot be calculated; bit 13 = FWS ePICV abnormal / high deviation from command; bit 14 = FWS ePICV bubble detected / empty pipe
HR93doc 40094System error bits 2Technology-side errors (1 = error).BITMAP16Readbit 0 = TCS pump 1 pressure error; bit 1 = TCS pump 2 pressure error; bit 2 = TCS supply pressure error; bit 3 = TCS return pressure error; bit 4 = TCS strainer 1 dP cannot be calculated; bit 5 = TCS strainer 2 dP cannot be calculated; bit 6 = TCS flow rate 1 error; bit 7 = TCS flow rate 2 error; bit 8 = TCS supply temperature error; bit 9 = TCS return temperature error; bit 10 = TCS dT cannot be calculated; bit 11 = TCS cooling status cannot be calculated; bit 12 = TCS fill pump failure or run time-out; bit 13 = TCS pump 1 route not available (check pump 1 pressure); bit 14 = TCS pump 2 route not available (check pump 2 pressure); bit 15 = TCS loop dP cannot be calculated
HR94doc 40095System comm bitsCommunication and battery flags (1 = fault).BITMAP16Readbit 0 = Comm lost to inverter 1; bit 1 = Comm lost to inverter 2; bit 2 = Comm lost to master (unit set as slave); bit 3 = Comm lost to FWS ePICV; bit 13 = Mains supply lost, running on batteries; bit 14 = Batteries bad, replace; bit 15 = Battery low (30 % state of charge)
HR95doc 40096Comm lost to slavesBit n set = link to slave n lost (bit 1 = slave 1).BITMAP16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane TCDU coolant distribution unit (data-centre liquid cooling)

What Modbus registers does the Trane TCDU coolant distribution unit (data-centre liquid cooling) have?

This map lists 89 registers: 89 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list prints Modicon holding registers starting at 40001, so 40001 is wire address 0 and 40049 is wire address 48.

What are the minimum Modbus registers to integrate the Trane TCDU coolant distribution unit (data-centre liquid cooling)?

Start with HR 1 Summarized fault / common fault (Common fault summary); HR 31 TCS supply temperature (TCS supply temperature); HR 32 TCS return temperature (TCS return temperature); HR 29 TCS flow rate 1 (TCS flow rate); HR 36 TCS cooling (TCS cooling kW); HR 12 FWS input temperature (FWS supply temperature); HR 48 TCS supply temperature setpoint (TCS supply temperature setpoint); HR 90 System status bits (System status bits); HR 0 Modbus comm check counter (Heartbeat counter).

How do I enable Modbus control of the Trane TCDU coolant distribution unit (data-centre liquid cooling)?

Modbus TCP is served on the RJ45 port labelled Telemetry Control (also used for data-log download and the REST API). The port takes a DHCP address by default; a fixed IP is set by logging into the internal IOT2050 module over SSH, editing the connection with nmtui and rebooting it.

Where is the official Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus documentation?

The source is Installation, Operation, and Maintenance: Coolant Distribution Unit (DC-SVX001A-EN), revision 2025-04, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Installation%20Operation%20and%20Maintenance/DC-SVX001A-EN_04302025.pdf.

More Trane Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Installation, Operation, and Maintenance: Coolant Distribution Unit · DC-SVX001A-EN · rev. 2025-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.