Pump (data-centre coolant distribution unit) · Modbus register map
Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus register map
Updated 19 November 2026
Liquid-to-liquid coolant distribution unit that moves heat from a direct-to-chip server loop (TCS) to facility water (FWS) using two variable-speed pumps and a control valve. Modbus TCP exposes one block of 16-bit holding registers: pressures, flows, temperatures, pump and valve values, setpoints, sensor range states and packed status and error words.
This page lists 89 Modbus registers for the Trane TCDU coolant distribution unit (data-centre liquid cooling) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- TCDU coolant distribution unit (data-centre liquid cooling)
- Equipment type
- Pump (data-centre coolant distribution unit)
- Registers
- 89 (20 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 503
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A
Integration notes: Trane TCDU coolant distribution unit (data-centre liquid cooling)
Connect to the TCDU's Telemetry Control RJ45 with Modbus TCP on port 503 (not 502) and read holding registers 40001-40096. Setpoints sit in 40046-40062 and the control word in 40092.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Summarized fault / common fault | INT16 | Common fault summary | Read |
| HR 31 | TCS supply temperature | INT16 | TCS supply temperature | Read |
| HR 32 | TCS return temperature | INT16 | TCS return temperature | Read |
| HR 29 | TCS flow rate 1 | INT16 | TCS flow rate | Read |
| HR 36 | TCS cooling | INT16 | TCS cooling kW | Read |
| HR 12 | FWS input temperature | INT16 | FWS supply temperature | Read |
| HR 48 | TCS supply temperature setpoint | INT16 | TCS supply temperature setpoint | Read/write |
| HR 90 | System status bits | BITMAP16 | System status bits | Read |
| HR 0 | Modbus comm check counter | INT16 | Heartbeat counter | Read |
Enable Modbus control & writes
Modbus TCP is served on the RJ45 port labelled Telemetry Control (also used for data-log download and the REST API). The port takes a DHCP address by default; a fixed IP is set by logging into the internal IOT2050 module over SSH, editing the connection with nmtui and rebooting it.
Byte order & addressing
- TCP port is 503, not the usual 502.
- All values are signed 16-bit with fixed decimal multipliers; there are no 32-bit registers, so each pump's energy is split into a kWh register and an MWh register.
Network setup
- Find the unit's IP on the DHCP server, or set a fixed IP on the IOT2050 module (service port P1-X1, default 192.168.2.40; credentials are supplied separately by Trane).
- Point the client at port 503; the manual does not state a unit ID.
Watch out for
- Several status bits are active-low (E-stop, safety relay, leak detection, inverter state): 1 means normal.
- Register 40001 counts 1-255 continuously; use it to confirm the link is alive.
Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Modbus comm check counter | Counts up and loops 1-255; use as a heartbeat. | INT16 | Read | ||||
| HR | 1doc 40002 | Summarized fault / common fault | INT16 | Read | 0 = Normal; 1 = At least one warning; 2 = At least one alarm or instrument failure | ||||
| HR | 2doc 40003 | System role | INT16 | Read | 0 = Master / standalone; 1 = Slave ID1; 2 = Slave ID2; 3 = Slave ID3 | ||||
| HR | 3doc 40004 | Ambient temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 4doc 40005 | Ambient dew point | Calculated dew point. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc 40006 | Ambient relative humidity | INT16 | × 0.1 | % | Read | |||
| HR | 6doc 40007 | FWS input pressure 1 | Facility water supply pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 7doc 40008 | FWS input pressure 2 | Facility water supply pressure after the strainer. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 8doc 40009 | FWS output pressure | Facility water return pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 9doc 40010 | FWS strainer dP | Pressure drop across the facility-side strainer. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 10doc 40011 | FWS loop dP | Facility supply minus return pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 11doc 40012 | FWS flow rate | INT16 | L/min | Read | ||||
| HR | 12doc 40013 | FWS input temperature | Facility water supply temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 13doc 40014 | FWS output temperature | Facility water return temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 14doc 40015 | FWS dT | Facility supply/return temperature difference. | INT16 | × 0.1 | °C | Read | ||
| HR | 15doc 40016 | FWS valve position command | INT16 | × 0.1 | % | Read | |||
| HR | 16doc 40017 | FWS valve position feedback | INT16 | × 0.1 | % | Read | |||
| HR | 17doc 40018 | FWS cooling | Cooling duty calculated on the facility side. | INT16 | × 0.1 | kW | Read | ||
| HR | 22doc 40023 | TCS loop dP | Technology cooling loop supply minus return pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 23doc 40024 | TCS pump 1 pressure | Pump 1 outlet pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 24doc 40025 | TCS pump 2 pressure | Pump 2 outlet pressure. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 25doc 40026 | TCS supply pressure | Technology cooling supply pressure after the strainer. | INT16 | × 0.01 | bar(g) | Read | ||
| HR | 26doc 40027 | TCS return pressure | INT16 | × 0.01 | bar(g) | Read | |||
| HR | 27doc 40028 | TCS strainer 1 dP | INT16 | × 0.01 | bar(g) | Read | |||
| HR | 28doc 40029 | TCS strainer 2 dP | INT16 | × 0.01 | bar(g) | Read | |||
| HR | 29doc 40030 | TCS flow rate 1 | INT16 | L/min | Read | ||||
| HR | 30doc 40031 | TCS flow rate 2 | Redundant flow reading, if fitted. | INT16 | L/min | Read | |||
| HR | 31doc 40032 | TCS supply temperature | Coolant temperature to the IT load. | INT16 | × 0.1 | °C | Read | ||
| HR | 32doc 40033 | TCS return temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 33doc 40034 | TCS dT | INT16 | × 0.1 | °C | Read | |||
| HR | 34doc 40035 | TCS pump 1 speed | Commanded speed. | INT16 | × 0.1 | % | Read | ||
| HR | 35doc 40036 | TCS pump 2 speed | Commanded speed. | INT16 | × 0.1 | % | Read | ||
| HR | 36doc 40037 | TCS cooling | Cooling duty calculated on the technology side. | INT16 | × 0.1 | kW | Read | ||
| HR | 37doc 40038 | TCS pump 1 output power | INT16 | × 0.1 | kW | Read | |||
| HR | 38doc 40039 | TCS pump 1 inverter drive temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 39doc 40040 | TCS pump 1 kWh meter | INT16 | × 0.1 | kWh | Read | |||
| HR | 40doc 40041 | TCS pump 1 MWh meter | INT16 | MWh | Read | ||||
| HR | 41doc 40042 | TCS pump 2 output power | INT16 | × 0.1 | kW | Read | |||
| HR | 42doc 40043 | TCS pump 2 inverter drive temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 43doc 40044 | TCS pump 2 kWh meter | INT16 | × 0.1 | kWh | Read | |||
| HR | 44doc 40045 | TCS pump 2 MWh meter | INT16 | MWh | Read | ||||
| HR | 45doc 40046 | TCS static pressure setpoint | Pressure at which the fill pump switches on. | INT16 | × 0.01 | bar(g) | Read/write | ||
| HR | 46doc 40047 | Condensation control dew point | Dew point where condensation control starts limiting TCS supply temperature. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 47doc 40048 | System ATD target | Target approach (TCS supply minus FWS supply) for fault-tolerant operation. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 48doc 40049 | TCS supply temperature setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 50doc 40051 | TCS fixed flow rate setpoint | Used in fixed-flow pump mode. | INT16 | L/min | Read/write | |||
| HR | 51doc 40052 | TCS fixed dP setpoint | Used in fixed-dP pump mode. | INT16 | × 0.01 | bar(g) | Read/write | ||
| HR | 52doc 40053 | TCS fixed speed, single-pump mode | INT16 | × 0.1 | % | Read/write | |||
| HR | 53doc 40054 | TCS fixed speed, dual-pump mode | INT16 | × 0.1 | % | Read/write | |||
| HR | 54doc 40055 | TCS pump 1 speed in manual mode | Applies when pump 1 is in manual mode and switched on at the HMI. | INT16 | × 0.1 | % | Read/write | ||
| HR | 55doc 40056 | TCS pump 2 speed in manual mode | Applies when pump 2 is in manual mode and switched on at the HMI. | INT16 | × 0.1 | % | Read/write | ||
| HR | 56doc 40057 | TCS pump control mode | INT16 | Read/write | 1 = Fixed flow; 2 = Fixed dP; 3 = Fixed speed | ||||
| HR | 57doc 40058 | TCS pump cycle duty duration | Run time before changeover to the partner pump in single-pump mode. | INT16 | h | Read/write | |||
| HR | 58doc 40059 | FWS flow rate control mode | Facility-side ePICV valve control mode. | INT16 | Read/write | 0 = TCS temperature control; 1 = Flow control; 2 = Energy control | |||
| HR | 59doc 40060 | FWS valve manual % | Fixed valve opening in manual mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 60doc 40061 | Data log interval | 0 = 0.5 s; 1-300 = interval in seconds. | INT16 | s | Read/write | |||
| HR | 61doc 40062 | FWS fixed flow rate setpoint | ePICV fixed-flow mode setpoint. | INT16 | L/min | Read/write | |||
| HR | 64doc 40065 | Ambient temperature state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 65doc 40066 | Ambient dew point state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 66doc 40067 | Ambient RH state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 67doc 40068 | FWS input pressure 1 state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 68doc 40069 | FWS input pressure 2 state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 69doc 40070 | FWS output pressure state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 70doc 40071 | FWS strainer dP state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 71doc 40072 | TCS loop dP state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 72doc 40073 | FWS flow rate state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 73doc 40074 | FWS input temperature state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 74doc 40075 | FWS output temperature state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 75doc 40076 | FWS dT state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 76doc 40077 | TCS pump 1 pressure state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 77doc 40078 | TCS pump 2 pressure state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 78doc 40079 | TCS supply pressure state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 79doc 40080 | TCS return pressure state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 80doc 40081 | TCS strainer 1 dP state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 81doc 40082 | TCS strainer 2 dP state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 82doc 40083 | TCS flow rate 1 state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 83doc 40084 | TCS flow rate 2 state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 84doc 40085 | TCS supply temperature state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 85doc 40086 | TCS return temperature state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 86doc 40087 | TCS dT state | Range state of the reading; the manual does not list the state codes. | INT16 | Read | ||||
| HR | 87doc 40088 | Threshold setpoint pointer | Index of the alarm threshold to read or write via 40089/40090. | INT16 | Read/write | ||||
| HR | 88doc 40089 | Threshold value for write | New value for the threshold chosen in 40088; scale depends on the threshold. | INT16 | Read/write | ||||
| HR | 89doc 40090 | Threshold value for read | Echo of the selected threshold; -999 signals a write error. | INT16 | Read/write | ||||
| HR | 90doc 40091 | System status bits | Packed unit status flags. | BITMAP16 | Read | bit 0 = Unit in operating state (a pump can be switched on); bit 1 = E-stop: 1 = normal, 0 = emergency button pressed; bit 2 = Safety relay: 1 = on (pump start possible), 0 = off / emergency not acknowledged; bit 3 = Leak detection: 1 = no leak, 0 = leak or sensor failure; bit 4 = Reservoir high-level sensor sees liquid; bit 5 = Reservoir low-level sensor sees liquid (0 = reservoir empty); bit 6 = Inverter 1: 1 = normal, 0 = off or in error; bit 7 = Inverter 2: 1 = normal, 0 = off or in error; bit 8 = Condensation control acting; bit 9 = TCS fill pump on | |||
| HR | 91doc 40092 | System control bits | Packed control flags; write the whole word. | BITMAP16 | Read/write | bit 0 = Lock TCS pump 1 off for maintenance; bit 1 = Lock TCS pump 2 off for maintenance; bit 2 = Condensation control enabled; bit 3 = Reset safety relay (short pulse clears fault/off state); bit 4 = TCS pump duty mode: 0 = single, 1 = dual; bit 15 = Data logging on | |||
| HR | 92doc 40093 | System error bits 1 | Facility-side and ambient sensor errors (1 = error). | BITMAP16 | Read | bit 0 = Ambient temperature error; bit 1 = Ambient dew point error; bit 2 = Ambient RH error; bit 3 = FWS input pressure 1 error; bit 4 = FWS input pressure 2 error; bit 5 = FWS output pressure error; bit 6 = FWS strainer dP cannot be calculated; bit 7 = FWS loop dP cannot be calculated; bit 8 = FWS flow rate error; bit 9 = FWS input temperature error; bit 10 = FWS output temperature error; bit 11 = FWS dT cannot be calculated; bit 12 = FWS cooling status cannot be calculated; bit 13 = FWS ePICV abnormal / high deviation from command; bit 14 = FWS ePICV bubble detected / empty pipe | |||
| HR | 93doc 40094 | System error bits 2 | Technology-side errors (1 = error). | BITMAP16 | Read | bit 0 = TCS pump 1 pressure error; bit 1 = TCS pump 2 pressure error; bit 2 = TCS supply pressure error; bit 3 = TCS return pressure error; bit 4 = TCS strainer 1 dP cannot be calculated; bit 5 = TCS strainer 2 dP cannot be calculated; bit 6 = TCS flow rate 1 error; bit 7 = TCS flow rate 2 error; bit 8 = TCS supply temperature error; bit 9 = TCS return temperature error; bit 10 = TCS dT cannot be calculated; bit 11 = TCS cooling status cannot be calculated; bit 12 = TCS fill pump failure or run time-out; bit 13 = TCS pump 1 route not available (check pump 1 pressure); bit 14 = TCS pump 2 route not available (check pump 2 pressure); bit 15 = TCS loop dP cannot be calculated | |||
| HR | 94doc 40095 | System comm bits | Communication and battery flags (1 = fault). | BITMAP16 | Read | bit 0 = Comm lost to inverter 1; bit 1 = Comm lost to inverter 2; bit 2 = Comm lost to master (unit set as slave); bit 3 = Comm lost to FWS ePICV; bit 13 = Mains supply lost, running on batteries; bit 14 = Batteries bad, replace; bit 15 = Battery low (30 % state of charge) | |||
| HR | 95doc 40096 | Comm lost to slaves | Bit n set = link to slave n lost (bit 1 = slave 1). | BITMAP16 | Read |
Notes on this map
- Every register is a signed 16-bit value (data type 'INT 16'). The 'Multiplier' column is the factor applied before sending (x10 means 25.3 °C is sent as 253), so scales here are 0.1 / 0.01. The manual's REST API table states the same read scales (x0.1 for temperature, percent and kW, x0.01 for pressure).
- Pressure units are bar gauge as printed ('barg'); flow is litres per minute ('LPM').
- The 23 'State' registers (40065-40087) are described only as 'per enumeration range state below', but no state table follows in this revision; their codes are left blank.
- The threshold pointer block (40088-40090) needs an index-to-threshold table that the register list does not include, and the threshold value's multiplier is printed as 'Varies'.
- Left out: spare and reserved registers (40019-40022, 40050, 40064, 40097-40101) and FWS dT limiting setpoint 40063 (printed with no multiplier, unit or description).
- TCS Pump 2 Pressure (40025) carries the description of pump 1 in the source; the register name says pump 2 and is used here.
- Register numbers are printed from 40001 in 5-digit Modicon form; the manual gives no separate offset statement, so 40001 is taken as wire address 0.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane TCDU coolant distribution unit (data-centre liquid cooling)
What Modbus registers does the Trane TCDU coolant distribution unit (data-centre liquid cooling) have?
This map lists 89 registers: 89 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list prints Modicon holding registers starting at 40001, so 40001 is wire address 0 and 40049 is wire address 48.
What are the minimum Modbus registers to integrate the Trane TCDU coolant distribution unit (data-centre liquid cooling)?
Start with HR 1 Summarized fault / common fault (Common fault summary); HR 31 TCS supply temperature (TCS supply temperature); HR 32 TCS return temperature (TCS return temperature); HR 29 TCS flow rate 1 (TCS flow rate); HR 36 TCS cooling (TCS cooling kW); HR 12 FWS input temperature (FWS supply temperature); HR 48 TCS supply temperature setpoint (TCS supply temperature setpoint); HR 90 System status bits (System status bits); HR 0 Modbus comm check counter (Heartbeat counter).
How do I enable Modbus control of the Trane TCDU coolant distribution unit (data-centre liquid cooling)?
Modbus TCP is served on the RJ45 port labelled Telemetry Control (also used for data-log download and the REST API). The port takes a DHCP address by default; a fixed IP is set by logging into the internal IOT2050 module over SSH, editing the connection with nmtui and rebooting it.
Where is the official Trane TCDU coolant distribution unit (data-centre liquid cooling) Modbus documentation?
The source is Installation, Operation, and Maintenance: Coolant Distribution Unit (DC-SVX001A-EN), revision 2025-04, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Installation%20Operation%20and%20Maintenance/DC-SVX001A-EN_04302025.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other pumps register maps
- Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Heat pump (water-to-air heat pump controller)
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Bosch commercial water-to-air heat pumps fitted with the Control Air 5600 DDC controller running the water-to-air standard software (integration points list version 1.03).
Also known as: Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101 - Heat pump (packaged wall-mount)
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Eubank EAH1020H-1060H / EAH2024H-2042H wall-mount heat pumps (I&O manual rev. 6); the HAH1024-1060 A/C with gas heat manual (rev. 5) prints the same table.
Also known as: EAH1020H, EAH1024H, EAH1030H, EAH1036H, EAH1042H, EAH1048H, EAH1060H, EAH2024H, EAH2042H, HAH1024A, HAH1030A, HAH1036A, HAH1042A, HAH1048A, HAH1060A, Eubank EAH heat pump, Eubank HAH - Pump motor protection relay
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Grundfos MP 204 electronic motor protector connected over GENIbus to a CIU 200 (Modbus RTU), CIU 250 (GSM/GPRS) or CIU 500 (Modbus TCP) box; functional profile 98393513 (2014-11).
Also known as: MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513 - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W
All pumps Modbus register maps →
Source: Installation, Operation, and Maintenance: Coolant Distribution Unit · DC-SVX001A-EN · rev. 2025-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.