Pump / water treatment unit (reverse osmosis for humidifiers) · Modbus register map

Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The SKRO is Neptronic's reverse osmosis unit that feeds purified water to its humidifiers. The Modbus RTU module exposes holding registers for inlet, permeate and concentrate pressures, the TDS reading, flow settings, motor and valve states, level floats, warnings, the operating state and an enumerated system alarm, plus a power on/off and request register.

This page lists 50 Modbus registers for the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKRO reverse osmosis water treatment unit (Modbus communication module)
Equipment type
Pump / water treatment unit (reverse osmosis for humidifiers)
Registers
50 (20 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus
Source document
SKRO Reverse Osmosis Water Treatment Unit - Modbus Communication Module User Guide · SKRO-Modbus Guide-250913 (V1.0) · rev. 2025-09-13
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)

Integration in brief

Read State (15061), System Alarm (15062), the three pressures (6000-6002) and TDS (6003); switch the unit with System Power State (15000) and send resets or a fast flush through Request (15060).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 15061StateUINT16Operating stateRead
HR 15062System AlarmUINT16System alarmRead
HR 15000System Power StateUINT16Power on/offRead/write
HR 6000Inlet PressureUINT16Inlet pressureRead
HR 6001Permeate PressureUINT16Permeate pressureRead
HR 6003TDS SensorUINT16TDSRead
HR 15060RequestUINT16Reset / fast flush requestRead/write

Enable Modbus control & writes

Fit the Modbus communication module and set the address from the device menu or register 0.

Communication loss & watchdog

Network Timeout Failsafe (12025) reads 0 = OK / 1 = Timeout and Modbus Network Timeout (12026) is an Off/On setting; the timeout delay itself (6030/6031, 30-600 s) spans two registers and is not listed. The guide does not describe what the unit does on timeout.

Byte order & addressing

Network setup

Watch out for

Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Inlet SignalUINT16× 0.001VRead
HR2001doc 2001 / 402002Permeate SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Concentrate SignalUINT16× 0.001VRead
HR2003doc 2003 / 402004Permeate PulseUINT16Read/write
HR2004doc 2004 / 402005Concentrate PulseUINT16Read/write
HR6000doc 6000 / 406001Inlet PressureUINT16psiRead
HR6001doc 6001 / 406002Permeate PressureUINT16psiRead
HR6002doc 6002 / 406003Concentrate PressureUINT16psiRead
HR6003doc 6003 / 406004TDS SensorTotal dissolved solids reading.UINT16PPMRead
HR6272doc 6272 / 406273Damaged Membrane DelayUINT16sRead/write
HR6273doc 6273 / 406274Permeate FlowUINT16l/minRead/write
HR6274doc 6274 / 406275Concentrate FlowUINT16l/minRead/write
HR11000doc 11000 / 411001MotorUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Inlet ValveUINT16Read0 = Closed; 1 = Open
HR11002doc 11002 / 411003Fast Flush ValveUINT16Read0 = Closed; 1 = Open
HR11003doc 11003 / 411004AlarmUINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005Work SignalUINT16Read0 = Off; 1 = On
HR11005doc 11005 / 411006Alarm LEDUINT16Read0 = Off; 1 = On
HR11006doc 11006 / 411007Power LEDUINT16Read0 = Off; 1 = On
HR12003doc 12003 / 412004High Level FloatUINT16Read0 = Off; 1 = On
HR12004doc 12004 / 412005Low Level FloatUINT16Read0 = Off; 1 = On
HR12005doc 12005 / 412006Alarm Level FloatUINT16Read0 = Off; 1 = On
HR12006doc 12006 / 412007InterlockUINT16Read/write0 = Open; 1 = Closed
HR12021doc 12021 / 412022AI8 PolarityUINT16Read/write0 = Direct; 1 = Reverse
HR12022doc 12022 / 412023Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12023doc 12023 / 412024Notify WarningUINT16Read/write0 = Off; 1 = On
HR12024doc 12024 / 412025Notify App MsgUINT16Read/write0 = Off; 1 = On
HR12025doc 12025 / 412026Network Timeout FailsafeUINT16Read/write0 = OK; 1 = Timeout
HR12026doc 12026 / 412027Modbus Network TimeoutUINT16Read/write0 = Off; 1 = On
HR12063doc 12063 / 412064Memory StatusUINT16Read0 = Ok; 1 = Fail
HR12064doc 12064 / 412065Inlet Low Pressure WarningUINT16Read0 = Off; 1 = On
HR12065doc 12065 / 412066Fast Flush Blocked WarningUINT16Read0 = Off; 1 = On
HR12066doc 12066 / 412067Inlet Valve Open WarningUINT16Read0 = Off; 1 = On
HR12067doc 12067 / 412068Insufficient Osmosis WarningUINT16Read0 = Off; 1 = On
HR12068doc 12068 / 412069Clogged Membrane Service WarningUINT16Read0 = Off; 1 = On
HR12069doc 12069 / 412070TDS Sensor Fail WarningUINT16Read0 = Off; 1 = On
HR12070doc 12070 / 412071Over Usage WarningUINT16Read0 = Off; 1 = On
HR12071doc 12071 / 412072RO Tank ProfileUINT16Read/write0 = Atmospheric; 1 = Pressurized
HR15000doc 15000 / 415001System Power StateUINT16Read/write0 = Off; 1 = On
HR15001doc 15001 / 415002SystemLogVerboseLevelUINT16Read/write0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug
HR15002doc 15002 / 415003Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15059doc 15059 / 415060Update Process StatusUINT16Read0 = Ok; 1 = CRC; 2 = Device; 3 = Failed
HR15060doc 15060 / 415061RequestUINT16Read/write0 = None; 1 = ResetAlarms; 2 = FastFlush; 3 = ResetService
HR15061doc 15061 / 415062StateUINT16Read0 = Off; 1 = Idle; 2 = Purifying; 3 = FastFlush; 4 = Alarm
HR15062doc 15062 / 415063System AlarmUINT16Read0 = Normal; 1 = InHiPress; 2 = DmgMembrane; 3 = BlocMembrane; 4 = ConcOpen; 5 = LoPumpPress; 6 = InletClog; 7 = PressReg; 8 = NoPureWater; 9 = TankClosed; 10 = FloatOff; 11 = InletSensor; 12 = PermeatSensor; 13 = ConcentSensor

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)

What Modbus registers does the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) have?

This map lists 50 registers: 50 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide states addresses follow the Protocol Address (base 0, add 1 for a PLC) and prints the convention notation (base 400001) next to each, e.g. 6000 / 406001. The protocol address is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)?

Start with HR 15061 State (Operating state); HR 15062 System Alarm (System alarm); HR 15000 System Power State (Power on/off); HR 6000 Inlet Pressure (Inlet pressure); HR 6001 Permeate Pressure (Permeate pressure); HR 6003 TDS Sensor (TDS); HR 15060 Request (Reset / fast flush request).

How do I enable Modbus control of the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)?

Fit the Modbus communication module and set the address from the device menu or register 0.

What happens when the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) loses Modbus communication?

Network Timeout Failsafe (12025) reads 0 = OK / 1 = Timeout and Modbus Network Timeout (12026) is an Off/On setting; the timeout delay itself (6030/6031, 30-600 s) spans two registers and is not listed. The guide does not describe what the unit does on timeout.

Where is the official Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus documentation?

The source is SKRO Reverse Osmosis Water Treatment Unit - Modbus Communication Module User Guide (SKRO-Modbus Guide-250913 (V1.0)), revision 2025-09-13, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKRO-Modbus%20Guide-250913%20(V1.0).pdf.

More Neptronic Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: SKRO Reverse Osmosis Water Treatment Unit - Modbus Communication Module User Guide · SKRO-Modbus Guide-250913 (V1.0) · rev. 2025-09-13. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.