Pump / water treatment unit (reverse osmosis for humidifiers) · Modbus register map
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus register map
Updated 19 November 2026
The SKRO is Neptronic's reverse osmosis unit that feeds purified water to its humidifiers. The Modbus RTU module exposes holding registers for inlet, permeate and concentrate pressures, the TDS reading, flow settings, motor and valve states, level floats, warnings, the operating state and an enumerated system alarm, plus a power on/off and request register.
This page lists 50 Modbus registers for the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKRO reverse osmosis water treatment unit (Modbus communication module)
- Registers
- 50 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus
Integration notes: Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Read State (15061), System Alarm (15062), the three pressures (6000-6002) and TDS (6003); switch the unit with System Power State (15000) and send resets or a fast flush through Request (15060).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 15061 | State | UINT16 | Operating state | Read |
| HR 15062 | System Alarm | UINT16 | System alarm | Read |
| HR 15000 | System Power State | UINT16 | Power on/off | Read/write |
| HR 6000 | Inlet Pressure | UINT16 | Inlet pressure | Read |
| HR 6001 | Permeate Pressure | UINT16 | Permeate pressure | Read |
| HR 6003 | TDS Sensor | UINT16 | TDS | Read |
| HR 15060 | Request | UINT16 | Reset / fast flush request | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module and set the address from the device menu or register 0.
Communication loss & watchdog
Network Timeout Failsafe (12025) reads 0 = OK / 1 = Timeout and Modbus Network Timeout (12026) is an Off/On setting; the timeout delay itself (6030/6031, 30-600 s) spans two registers and is not listed. The guide does not describe what the unit does on timeout.
Byte order & addressing
- All points are holding registers (FC03/06/16 only).
- Auto baud detection is the default.
Network setup
- RS-485 two-wire, RTU mode, 9600-57600 baud or auto.
- Parity / stop bits via register 2 (default no parity, 2 stop bits).
Watch out for
- Warnings 12064-12070 are separate 0/1 registers; the System Alarm code in 15062 is the main fault.
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Inlet Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2001doc 2001 / 402002 | Permeate Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Concentrate Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2003doc 2003 / 402004 | Permeate Pulse | UINT16 | Read/write | |||||
| HR | 2004doc 2004 / 402005 | Concentrate Pulse | UINT16 | Read/write | |||||
| HR | 6000doc 6000 / 406001 | Inlet Pressure | UINT16 | psi | Read | ||||
| HR | 6001doc 6001 / 406002 | Permeate Pressure | UINT16 | psi | Read | ||||
| HR | 6002doc 6002 / 406003 | Concentrate Pressure | UINT16 | psi | Read | ||||
| HR | 6003doc 6003 / 406004 | TDS Sensor | Total dissolved solids reading. | UINT16 | PPM | Read | |||
| HR | 6272doc 6272 / 406273 | Damaged Membrane Delay | UINT16 | s | Read/write | ||||
| HR | 6273doc 6273 / 406274 | Permeate Flow | UINT16 | l/min | Read/write | ||||
| HR | 6274doc 6274 / 406275 | Concentrate Flow | UINT16 | l/min | Read/write | ||||
| HR | 11000doc 11000 / 411001 | Motor | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Inlet Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 11002doc 11002 / 411003 | Fast Flush Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 11003doc 11003 / 411004 | Alarm | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Work Signal | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11005doc 11005 / 411006 | Alarm LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11006doc 11006 / 411007 | Power LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12003doc 12003 / 412004 | High Level Float | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12004doc 12004 / 412005 | Low Level Float | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12005doc 12005 / 412006 | Alarm Level Float | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12006doc 12006 / 412007 | Interlock | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 12021doc 12021 / 412022 | AI8 Polarity | UINT16 | Read/write | 0 = Direct; 1 = Reverse | ||||
| HR | 12022doc 12022 / 412023 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12023doc 12023 / 412024 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12024doc 12024 / 412025 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12025doc 12025 / 412026 | Network Timeout Failsafe | UINT16 | Read/write | 0 = OK; 1 = Timeout | ||||
| HR | 12026doc 12026 / 412027 | Modbus Network Timeout | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12063doc 12063 / 412064 | Memory Status | UINT16 | Read | 0 = Ok; 1 = Fail | ||||
| HR | 12064doc 12064 / 412065 | Inlet Low Pressure Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12065doc 12065 / 412066 | Fast Flush Blocked Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12066doc 12066 / 412067 | Inlet Valve Open Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12067doc 12067 / 412068 | Insufficient Osmosis Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12068doc 12068 / 412069 | Clogged Membrane Service Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12069doc 12069 / 412070 | TDS Sensor Fail Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12070doc 12070 / 412071 | Over Usage Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12071doc 12071 / 412072 | RO Tank Profile | UINT16 | Read/write | 0 = Atmospheric; 1 = Pressurized | ||||
| HR | 15000doc 15000 / 415001 | System Power State | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15001doc 15001 / 415002 | SystemLogVerboseLevel | UINT16 | Read/write | 0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug | ||||
| HR | 15002doc 15002 / 415003 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15059doc 15059 / 415060 | Update Process Status | UINT16 | Read | 0 = Ok; 1 = CRC; 2 = Device; 3 = Failed | ||||
| HR | 15060doc 15060 / 415061 | Request | UINT16 | Read/write | 0 = None; 1 = ResetAlarms; 2 = FastFlush; 3 = ResetService | ||||
| HR | 15061doc 15061 / 415062 | State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = Purifying; 3 = FastFlush; 4 = Alarm | ||||
| HR | 15062doc 15062 / 415063 | System Alarm | UINT16 | Read | 0 = Normal; 1 = InHiPress; 2 = DmgMembrane; 3 = BlocMembrane; 4 = ConcOpen; 5 = LoPumpPress; 6 = InletClog; 7 = PressReg; 8 = NoPureWater; 9 = TankClosed; 10 = FloatOff; 11 = InletSensor; 12 = PermeatSensor; 13 = ConcentSensor |
Notes on this map
- Only function codes 03, 06 and 16 are supported; binary points are 16-bit holding registers holding 0 or 1.
- A 'Scale N' data type with 'Value x N' means raw = engineering value x N; this map stores the multiplier 1/N.
- Units follow Modbus Server Units (15002): 0 metric, 1 imperial.
- Left out because they span two registers with no stated word order: Modbus TCP keep-alive (6016/6017), Network Timeout Delay (6030/6031), Run Time (6265/6266) and On Time (6267/6268).
- Left out because the scale column and the 'Value x' text disagree: Regulator Pressure 6269 (Scale 1 vs x100), Pump On Fast Flush Delay 6270 (Scale 1 vs x10) and Idle Drain Time 6271 (Scale 1 vs x11).
- Product name (3-6) and database version (16000-16015) ASCII registers are left out; 12000-12002 and 12027-12062 are printed as reserved ranges.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
What Modbus registers does the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) have?
This map lists 50 registers: 50 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide states addresses follow the Protocol Address (base 0, add 1 for a PLC) and prints the convention notation (base 400001) next to each, e.g. 6000 / 406001. The protocol address is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)?
Start with HR 15061 State (Operating state); HR 15062 System Alarm (System alarm); HR 15000 System Power State (Power on/off); HR 6000 Inlet Pressure (Inlet pressure); HR 6001 Permeate Pressure (Permeate pressure); HR 6003 TDS Sensor (TDS); HR 15060 Request (Reset / fast flush request).
How do I enable Modbus control of the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)?
Fit the Modbus communication module and set the address from the device menu or register 0.
What happens when the Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) loses Modbus communication?
Network Timeout Failsafe (12025) reads 0 = OK / 1 = Timeout and Modbus Network Timeout (12026) is an Off/On setting; the timeout delay itself (6030/6031, 30-600 s) spans two registers and is not listed. The guide does not describe what the unit does on timeout.
Where is the official Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module) Modbus documentation?
The source is SKRO Reverse Osmosis Water Treatment Unit - Modbus Communication Module User Guide (SKRO-Modbus Guide-250913 (V1.0)), revision 2025-09-13, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKRO-Modbus%20Guide-250913%20(V1.0).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other pumps register maps
- Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Heat pump
Acond Acond heat pumps (Modbus TCP interface v2.35)
Acond air-to-water and brine heat pumps with the ModbusTCP function activated, interface description version 2.35 dated 01.12.2022.
Also known as: Acond PRO series, Acond ModbusTCP v2.35 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Pump controller (wastewater lift station)
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Grundfos Dedicated Controls wastewater pit controller (CU 361 / CU 362, up to six pumps and a mixer) with a CIM 200 Modbus RTU, CIM 260 cellular or CIM 500 Modbus TCP module; functional profile 98393520 (2023-03).
Also known as: Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520 - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP
All pumps Modbus register maps →
Source: SKRO Reverse Osmosis Water Treatment Unit - Modbus Communication Module User Guide · SKRO-Modbus Guide-250913 (V1.0) · rev. 2025-09-13. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.