- TUUB Series universal wall-mount controller (Modbus RTU)
Thermostat / heat pump and unitary controller · Modbus register map
Neptronic TUUB Series universal wall-mount controller (Modbus RTU) Modbus register map
Updated 19 November 2026
The TUUB is the larger Neptronic universal wall-mount controller, with four analog outputs, seven binary outputs and four universal inputs, plus options for heat pump and emergency-heat operation. Its Modbus RTU holding registers cover temperatures, humidity, CO2, pressure, light and VOC readings, ramp demands, output states, mode, fan and setpoint control, VFD loops, 6-way valve settings and the configuration set.
This page lists 189 Modbus registers for the Neptronic TUUB Series universal wall-mount controller (Modbus RTU) — 151 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- TUUB Series universal wall-mount controller (Modbus RTU)
- Equipment type
- Thermostat / heat pump and unitary controller
- Registers
- 189 (151 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TUUB Series, TUUB universal wall-mount controller
Integration notes: Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Read holding registers with function 03 at the wire address shown in the guide's Protocol Address column (Modicon 40001 = address 0). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 11 | Internal temperature sensor reading | INT16 | Internal (room) temperature x100 | Read |
| HR 14 | Control temperature reading | INT16 | Control temperature x100 | Read/write |
| HR 41 | System mode status | UINT16 | System mode | Read/write |
| HR 42 | Fan speed selection by user | UINT16 | Fan speed | Read/write |
| HR 43 | Temperature setpoint in occupancy or day mode | INT16 | Occupied setpoint x10 | Read/write |
| HR 26 | Actual heating demand of ramp 1 | UINT16 | Heating demand ramp 1 | Read |
| HR 28 | Actual cooling demand of ramp 1 | UINT16 | Cooling demand ramp 1 | Read |
| HR 9 | System Status 1 | BITMAP16 | Status 1 | Read |
| HR 10 | System Status 2 | BITMAP16 | Status 2 (alarms) | Read |
| HR 44 | System option1 | BITMAP16 | System option 1 (bit 1 = Modbus temp unit) | Read/write |
Enable Modbus control & writes
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Byte order & addressing
- The guide prints both the 0-based protocol address and the 40001-style notation, so there is no off-by-one guesswork.
- Baud register holds baud/100 (384 = 38400); 0 means automatic baud detection.
Network setup
- RS-485 two-wire, RTU. Supported baud rates 9600, 19200, 38400 and 57600; automatic baud detection is the default.
- Parity/stop bits come from the communication-port register: 1 = none + 2 stop, 2 = even + 1 stop, 3 = odd + 1 stop.
Watch out for
- Changing the Modbus temperature-unit bit changes the meaning of every temperature register at once.
- Some registers only apply to models with a humidity, CO2 or other optional sensor.
Neptronic TUUB Series universal wall-mount controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Address - Neptronic ID and Modbus address of current device | UINT16 | Read/write | |||||
| HR | 1doc 40002 | Baud rate (baud / 100) | 0 = automatic detection. | UINT16 | × 100 | Read/write | |||
| HR | 2doc 40003 | Communication port configuration | UINT16 | Read/write | 1 = No parity, 2 Stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit | ||||
| HR | 7doc 40008 | Controller Product_Version, actual firmware version | UINT16 | Read | |||||
| HR | 8doc 40009 | Controller parameters version | UINT16 | Read | |||||
| HR | 9doc 40010 | System Status 1 | BITMAP16 | Read | bit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB or OCC (0 = Normal, 1 = OFF); bit 3 = ChangeOverMode (0 = Cooling, 1 = Heating); bit 4 = AL_FlowSwitch (0 = No alarm, 1 = Alarm activated); bit 6 = AL_DirtyFilter (0 = No alarm, 1 = Alarm activated) | ||||
| HR | 10doc 40011 | System Status 2 | BITMAP16 | Read | bit 0 = Selector Switch Status (0 = Remote Mode, 1 = Local Mode); bit 2 = CO2 Alarm (0 = Normal, 1 = Alarm); bit 7 = AL_Override (0 = Off, 1 = On); bit 8 = AL_WindowOpened (0 = Off, 1 = On); bit 9 = AL_DoorOpened (0 = Off, 1 = On); bit 10 = AL_UI1 (0 = Off, 1 = On); bit 11 = AL_UI2 (0 = Off, 1 = On); bit 12 = AL_UI3 (0 = Off, 1 = On); bit 13 = AL_UI4 (0 = Off, 1 = On); bit 15 = AL_OverHeat (0 = Off, 1 = On) | ||||
| HR | 11doc 40012 | Internal temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 12doc 40013 | External temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 13doc 40014 | Changeover temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 14doc 40015 | Control temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 15doc 40016 | Internal humidity sensor reading. | Not on every model. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 16doc 40017 | External humidity sensor reading | UINT16 | × 0.1 | %RH | Read | |||
| HR | 17doc 40018 | Analog input 1 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 18doc 40019 | Analog input 2 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 19doc 40020 | Analog input 3 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 20doc 40021 | Analog input 4 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 21doc 40022 | External CO2 sensor value in ppm | INT16 | ppm | Read | ||||
| HR | 22doc 40023 | Internal CO2 sensor value in ppm | INT16 | ppm | Read | ||||
| HR | 23doc 40024 | CO2 control value in ppm | INT16 | ppm | Read | ||||
| HR | 24doc 40025 | Actual system occupancy state | UINT16 | Read | 1 = NoOccupancy; 2 = Occupancy; 3 = Override | ||||
| HR | 25doc 40026 | Actual night setback state of the system | UINT16 | Read | 1 = Day; 2 = Night; 3 = Override | ||||
| HR | 26doc 40027 | Actual heating demand of ramp 1 | UINT16 | × 0.1 | % | Read | |||
| HR | 27doc 40028 | Actual heating demand of ramp 2 | UINT16 | × 0.1 | % | Read | |||
| HR | 28doc 40029 | Actual cooling demand of ramp 1 | UINT16 | × 0.1 | % | Read | |||
| HR | 29doc 40030 | Actual cooling demand of ramp 2 | UINT16 | × 0.1 | % | Read | |||
| HR | 30doc 40031 | Actual changeover demand | UINT16 | × 0.1 | % | Read | |||
| HR | 31doc 40032 | Actual fan demand | UINT16 | × 0.1 | % | Read | |||
| HR | 32doc 40033 | Actual dehumidification demand | UINT16 | × 0.1 | % | Read | |||
| HR | 33doc 40034 | Actual humidification demand | UINT16 | × 0.1 | % | Read | |||
| HR | 34doc 40035 | Cooling/heating switch timer countdown | UINT16 | s | Read | ||||
| HR | 35doc 40036 | Analog output 1 value | Percent of control or electrical range, per system option 4 bit 12. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 36doc 40037 | Analog output 2 value | Percent of control or electrical range, per system option 4 bit 12. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 37doc 40038 | Analog output 3 value | Percent of control or electrical range, per system option 4 bit 12. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 40039 | Analog output 4 value | Percent of control or electrical range, per system option 4 bit 12. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 39doc 40040 | Binary output - 6 relays output status | BITMAP16 | Read/write | bit 0 = Binary Output 1 (0 = Open, 1 = Close); bit 1 = Binary Output 2 (0 = Open, 1 = Close); bit 2 = Binary Output 3 (0 = Open, 1 = Close); bit 3 = Binary Output 4 (0 = Open, 1 = Close); bit 4 = Binary Output 5 (0 = Open, 1 = Close); bit 5 = Binary Output 6 (0 = Open, 1 = Close); bit 6 = Binary Output 7 (0 = Open, 1 =Close) | ||||
| HR | 40doc 40041 | System command | BITMAP16 | Read/write | bit 0 = Cfg_ServiceDisplayAddress (0 = Normal, 1 = Display address on LCD); bit 1 = Cfg_CoolingRampLock (0 = Off, 1 = On); bit 3 = Cfg_HeatingRamp1Lock (0 = Off, 1 = On); bit 4 = Cfg_HeatingRamp2Lock (0 = Off, 1 = On); bit 5 = Cfg_ChangeOverRampLock (0 = Off, 1 = On); bit 7 = Cfg_HumidifyRampLock (0 = Off, 1 = On); bit 8 = Cfg_DehumidifyRampLock (0 = Off, 1 = On) | ||||
| HR | 41doc 40042 | System mode status | Each mode is only accepted when the system control mode and option bits allow it. | UINT16 | Read/write | 1 = Auto; 2 = Heating; 3 = Emergency heat (EMH); 4 = Cooling; 5 = Fan; 6 = Off | |||
| HR | 42doc 40043 | Fan speed selection by user | UINT16 | Read/write | 1 = Auto; 2 = Low; 3 = Med; 4 = High | ||||
| HR | 43doc 40044 | Temperature setpoint in occupancy or day mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 44doc 40045 | System option1 | BITMAP16 | Read/write | bit 0 = Cfg_TempUnitTstat (0 = °C, 1 = °F); bit 1 = Cfg_TempUnitModbus (0 = °C, 1 = °F); bit 2 = Cfg_TempSetPointLock (0 = Off, 1 = On); bit 3 = Cfg_HumSetPointLock (0 = Off, 1 = On); bit 4 = Cfg_ProgramModeLock (0 = Off, 1 = On); bit 5 = AL_FreezeProtection (0 = Off, 1 = On); bit 6 = Cfg_UserSysOffModes (0 = Enable, 1 = Disable); bit 7 = Cfg_KeyPadBottomLeftLock (0 = Off, 1 = On); bit 8 = Cfg_KeyPadUpperLeftLock (0 = Off, 1 = On); bit 9 = Cfg_KeyPadArrowsLock (0 = Off, 1 = On); bit 10 = Cfg_UserFanAutoMode (0 = Enable, 1 = Disable); bit 11 = Cfg_ NightOrNoOccMode (0 = Setpoint, 1 = OFF); bit 12 = Cfg_HumControlSource (0 = Intern Sensor, 1 = Extern Sensor Not available on all models.); bit 13 = Time Mode (0 = 24h, 1 = 12h); bit 14 = Cfg_WindowOpenedMode (0 = Setpoint, 1 = OFF); bit 15 = Cfg_DoorOpenedMode (0 = Setpoint, 1 = OFF) | ||||
| HR | 45doc 40046 | System option2 | BITMAP16 | Read/write | bit 0 = Baud Rate (0 = Auto, 1 = Manual); bit 1 = Cfg_ActivateSchedule (0 = Off, 1 = On); bit 2 = Cfg_AnalogOutput1Direction (0 = Direct, 1 = Reverse); bit 3 = Cfg_AnalogOutput2Direction (0 = Direct, 1 = Reverse); bit 4 = Cfg_AnalogOutput3Direction (0 = Direct, 1 = Reverse); bit 5 = Cfg_AnalogOutput4Direction (0 = Direct, 1 = Reverse); bit 6 = Cfg_BinaryOutput1Direction (0 = Direct, 1 = Reverse); bit 7 = Cfg_BinaryOutput2Direction (0 = Direct, 1 = Reverse); bit 8 = Cfg_BinaryOutput3Direction (0 = Direct, 1 = Reverse); bit 9 = Cfg_BinaryOutput4Direction (0 = Direct, 1 = Reverse); bit 11 = Cfg_BinaryOutput6Direction (0 = Direct, 1 = Reverse); bit 13 = Cfg_UserSysFanMode (0 = Disable, 1 = Enable); bit 14 = Cfg_HideFanDisplay (0 = No, 1 = Yes) | ||||
| HR | 46doc 40047 | System option3 | BITMAP16 | Read/write | bit 0 = DAYLIGHT_SAVINGS_STATUS (0 = Normal, 1 = Summer); bit 1 = Cfg_EMHOutput (0 = Disable, 1 = Enable); bit 2 = Cfg_ HeatPumpMode (0 = Off (General Unit), 1 = On (HeatPump)); bit 3 = Cfg_ReversingValve (O/B) (0 = O, 1 = B); bit 4 = Cfg_EMHAutoMode (0 = No, 1 = Yes); bit 5 = Cfg_Y2Output (0 = Disable, 1 = Enable); bit 6 = Cfg_AnalogInput1MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 7 = Cfg_AnalogInput2MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 8 = Cfg_AnalogInput3MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 9 = Cfg_AnalogInput4MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 12 = Cfg_FloatingBO1/BO2Direction (0 = Direct, 1 = Reverse); bit 13 = Cfg_FloatingBO3/BO7Direction (0 = Direct, 1 = Reverse); bit 15 = Cfg_DeltaTempLogic (0 = Off, 1 = On) | ||||
| HR | 47doc 40048 | System option4 | BITMAP16 | Read/write | bit 0 = Cfg_CO2ControlSource (0 = Internal Sensor, 1 = External Sensor); bit 1 = Cfg_DisplayHumidity (0 = Display the temperature only, 1 = Display the temperature and humidity); bit 2 = Cfg_DisplayCO2 (0 = Don’t display CO2 control value, 1 = Display CO2 control value); bit 6 = Cfg_VFDTempSetpointSource (0 = VFDTempSetpoint, 1 = TempSetpoint); bit 7 = Cfg_AnalogOutput1OffVoltage (0 = Off, 1 = Minimum); bit 8 = Cfg_AnalogOutput2OffVoltage (0 = Off, 1 = Minimum); bit 9 = Cfg_AnalogOutput3OffVoltage (0 = Off, 1 = Minimum); bit 10 = Cfg_AnalogOutput4OffVoltage (0 = Off, 1 = Minimum); bit 11 = Cfg_CO2AutoSelfCalib (0 = Off, 1 = On); bit 12 = Cfg_AnalogOutputRatio (0 = Control Range, 1 = Electrical Range) | ||||
| HR | 48doc 40049 | Display information | UINT16 | Read/write | 1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off | ||||
| HR | 49doc 40050 | Temperature control source | UINT16 | Read/write | 1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp | ||||
| HR | 50doc 40051 | Network fallback timeout | UINT16 | min | Read/write | ||||
| HR | 51doc 40052 | Minimum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 52doc 40053 | Maximum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 53doc 40054 | Cooling temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 54doc 40055 | Heating temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 55doc 40056 | Heating proportional band for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 56doc 40057 | Heating proportional band for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 57doc 40058 | Cooling proportional band for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 58doc 40059 | Cooling proportional band for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 59doc 40060 | Changeover proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 60doc 40061 | Heating deadband for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 61doc 40062 | Heating deadband for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 62doc 40063 | Cooling deadband for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 63doc 40064 | Cooling deadband for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 64doc 40065 | Changeover deadband | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 65doc 40066 | Changeover setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 66doc 40067 | Fan time out in seconds | UINT16 | s | Read/write | ||||
| HR | 67doc 40068 | Fan damping factor in seconds | UINT16 | s | Read/write | ||||
| HR | 68doc 40069 | Heating integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 69doc 40070 | Cooling integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 70doc 40071 | Cooling Heating SwitchTimer - Delay between cool and heat or vice versa | UINT16 | min | Read/write | ||||
| HR | 71doc 40072 | Cooling anticycle delay in minutes | UINT16 | min | Read/write | ||||
| HR | 72doc 40073 | NSB override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 73doc 40074 | Unoccupied override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 74doc 40075 | Occupancy minimum time in minutes | UINT16 | min | Read/write | ||||
| HR | 75doc 40076 | Unoccupied override delay count down in minutes | UINT16 | min | Read/write | ||||
| HR | 76doc 40077 | Fan mode (speed) in unoccupied or NSB mode | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 77doc 40078 | Fan mode (speed) when window is opened (alarm) | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 78doc 40079 | Fan mode (speed) when door is opened (alarm) | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 79doc 40080 | System control mode | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock | ||||
| HR | 80doc 40081 | Override System occupancy/NSB mode | UINT16 | Read/write | 1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night | ||||
| HR | 81doc 40082 | Internal temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 82doc 40083 | Universal Input 1 signal | UINT16 | Read/write | 1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Fan Feedback; 19 = Humidity sensor 0-10V; 20 = Pressure sensor 0-10V; 21 = Extern sensor TT-012; 22 = Delta T Inlet 10K; 23 = Delta T Inlet 0-10V; 24 = Delta T Outlet 10K; 25 = Delta T Outlet 0-10V | ||||
| HR | 83doc 40084 | Universal Input 2 signal | UINT16 | Read/write | 1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Fan Feedback; 19 = Humidity sensor 0-10V; 20 = Pressure sensor 0-10V; 21 = Extern sensor TT-012; 22 = Delta T Inlet 10K; 23 = Delta T Inlet 0-10V; 24 = Delta T Outlet 10K; 25 = Delta T Outlet 0-10V | ||||
| HR | 84doc 40085 | Universal Input 3 signal | Guide numbers two options as 1; compare the UI2 list. | UINT16 | Read/write | ||||
| HR | 85doc 40086 | Universal Input 4 signal | UINT16 | Read/write | 1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy digital input; 10 = NSB digital input; 11 = Override digital input; 12 = Window digital input; 13 = Door digital input; 14 = Dirty Filter digital input; 15 = Flow switch digital input; 16 = OverHeat digital input; 17 = Selector switch digital input; 18 = Fan Feedback; 19 = Humidity sensor 0-10V; 20 = Pressure sensor 0-10V; 21 = Extern Sensor TT-012; 22 = Delta T Inlet 10K; 23 = Delta T Inlet 0-10V; 24 = Delta T Outlet 10K; 25 = Delta T Outlet 0-10V | ||||
| HR | 86doc 40087 | External temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 87doc 40088 | Changeover control mode | UINT16 | Read/write | 1 = Local; 2 = Cool; 3 = Heat | ||||
| HR | 88doc 40089 | Minimum external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 89doc 40090 | Maximum external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 90doc 40091 | Maximum CO2 reading | INT16 | ppm | Read/write | ||||
| HR | 91doc 40092 | Alarm level of CO2 | INT16 | ppm | Read/write | ||||
| HR | 92doc 40093 | Fan output signal | UINT16 | Read/write | 1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog | ||||
| HR | 93doc 40094 | Ramp to control analog output 1 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 Way Valve; 12 = Delta temperture; 13 = VFD/ECMTempLoopEnable; 14 = VFD Pressure Loop | ||||
| HR | 94doc 40095 | Minimum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 95doc 40096 | Maximum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 96doc 40097 | Ramp to control analog output 2 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 Way Valve; 12 = Delta temperature; 13 = VFD/ECMTempLoopEnable; 14 = VFD Pressure Loop; 15 = FAN (not available when AO1 is set to VFD/ECMTempLoopEnable or VFD Pressure Loop) | ||||
| HR | 97doc 40098 | Minimum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 98doc 40099 | Maximum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 100doc 40101 | Minimum voltage for analog output 3 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 101doc 40102 | Maximum voltage for analog output 3 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 103doc 40104 | Minimum voltage for analog output 4 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 104doc 40105 | Maximum voltage for analog output 4 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 105doc 40106 | Position of CH1 AO output while heating (%) | UINT16 | % | Read/write | ||||
| HR | 106doc 40107 | Ramp to control binary output 1 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 107doc 40108 | Delay before activation of BO1 in minutes | UINT16 | min | Read/write | ||||
| HR | 108doc 40109 | Close position percentage for contact BO1 | UINT16 | % | Read/write | ||||
| HR | 109doc 40110 | Open position percentage for contact BO1 | UINT16 | % | Read/write | ||||
| HR | 110doc 40111 | Ramp to control binary output 2 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 111doc 40112 | Delay before activation of BO2 in minutes | UINT16 | min | Read/write | ||||
| HR | 112doc 40113 | Close position percentage for contact BO2 | UINT16 | % | Read/write | ||||
| HR | 113doc 40114 | Open position percentage for contact BO2 | UINT16 | % | Read/write | ||||
| HR | 114doc 40115 | Ramp to control binary output 3 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 115doc 40116 | Delay before activation of BO3 in minutes | UINT16 | min | Read/write | ||||
| HR | 116doc 40117 | Close position percentage for contact BO3 | UINT16 | % | Read/write | ||||
| HR | 117doc 40118 | Open position percentage for contact BO3 | UINT16 | % | Read/write | ||||
| HR | 118doc 40119 | Ramp to control binary output 4 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN | ||||
| HR | 119doc 40120 | Delay before activation of BO4 in minutes | UINT16 | min | Read/write | ||||
| HR | 120doc 40121 | Close position percentage for contact BO4 | UINT16 | % | Read/write | ||||
| HR | 121doc 40122 | Open position percentage for contact BO4 | UINT16 | % | Read/write | ||||
| HR | 122doc 40123 | Ramp to control binary output 5 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN | ||||
| HR | 123doc 40124 | Delay before activation of BO5 in minutes | UINT16 | min | Read/write | ||||
| HR | 124doc 40125 | Close position percentage for contact BO5 | UINT16 | % | Read/write | ||||
| HR | 125doc 40126 | Open position percentage for contact BO5 | UINT16 | % | Read/write | ||||
| HR | 126doc 40127 | Ramp to control binary output 6 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 Way valve; 12 = Delta temperature; 13 = FAN (only when the fan type is 1, 2 or 3 speeds); 14 = VFD/ECMTempLoopEnable; 15 = VFD Pressure Loop | ||||
| HR | 127doc 40128 | Delay before activation of BO6 in minutes | UINT16 | min | Read/write | ||||
| HR | 128doc 40129 | Close position percentage for contact BO6 | UINT16 | % | Read/write | ||||
| HR | 129doc 40130 | Open position percentage for contact BO6 | UINT16 | % | Read/write | ||||
| HR | 130doc 40131 | Ramp to control binary output 7 | UINT16 | Read/write | 1 = Off; 2 = Change Over with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 131doc 40132 | Delay before activation of BO7 in minutes | UINT16 | min | Read/write | ||||
| HR | 132doc 40133 | Close position percentage for contact BO7 | UINT16 | % | Read/write | ||||
| HR | 133doc 40134 | Open position percentage for contact BO7 | UINT16 | % | Read/write | ||||
| HR | 134doc 40135 | Input contact of analog 1, 2, 3 and 4 | BITMAP16 | Read/write | bit 0 = Analog input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Analog input 2 (0 = Normally Open, 1 = Normally Close); bit 2 = Analog input 3 (0 = Normally Open, 1 = Normally Close); bit 3 = Analog input 4 (0 = Normally Open, 1 = Normally Close) | ||||
| HR | 135doc 40136 | Delay before activation of UI1 in seconds | UINT16 | s | Read/write | ||||
| HR | 136doc 40137 | Delay before activation of UI2 in seconds | UINT16 | s | Read/write | ||||
| HR | 137doc 40138 | Delay before activation of UI3 in seconds | UINT16 | s | Read/write | ||||
| HR | 138doc 40139 | Delay before activation of UI4 in seconds | UINT16 | s | Read/write | ||||
| HR | 139doc 40140 | Humidity control mode status | UINT16 | Read/write | 1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off | ||||
| HR | 140doc 40141 | Humidity setpoint (%RH) in occupancy or day mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 141doc 40142 | Dehumidification setpoint (%RH) in unoccupied or night mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 142doc 40143 | Humidification setpoint (%RH) in unoccupied or night mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 143doc 40144 | Minimum user setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 144doc 40145 | Maximum user setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 145doc 40146 | Humidity proportional band | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 146doc 40147 | Humidity deadband | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 147doc 40148 | Internal humidity sensor offset correction | Not on every model. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 148doc 40149 | External humidity sensor offset correction | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 149doc 40150 | Pressure sensor value in Pascals | UINT16 | Pa | Read | ||||
| HR | 150doc 40151 | Maximum pressure value range | UINT16 | Pa | Read/write | ||||
| HR | 151doc 40152 | Actual VFD pressure loop x 10 (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 152doc 40153 | VFD pressure loop setpoint | UINT16 | Pa | Read/write | ||||
| HR | 153doc 40154 | VFD pressure loop deadband | UINT16 | Pa | Read/write | ||||
| HR | 154doc 40155 | VFD pressure loop proportional band | UINT16 | Pa | Read/write | ||||
| HR | 155doc 40156 | VFD pressure loop integral time | UINT16 | s | Read/write | ||||
| HR | 156doc 40157 | Actual VFD temperature loop while cooling x 10 (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 157doc 40158 | Actual VFD temperature loop while heating x 10 (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 158doc 40159 | VFD temperature loop setpoint x 10 (ºC or ºF) | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 159doc 40160 | VFD temperature loop deadband x 10 (ºC or ºF) | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 160doc 40161 | VFD temperature loop proportional band x 10 (ºC or ºF) | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 161doc 40162 | VFD temperature loop integral time | UINT16 | s | Read/write | ||||
| HR | 162doc 40163 | Voltage required for closing the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 163doc 40164 | Minimum output voltage required for cooling for the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 164doc 40165 | Minimum output voltage required for heating for the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 165doc 40166 | 6-way valve size selection in inches | UINT16 | Read/write | 1 = 1/2; 2 = 3/4; 3 = 1 | ||||
| HR | 166doc 40167 | Signal type for Analog output 1 | UINT16 | Read/write | 1 = Analog; 2 = On-Off; 3 = Pulsing | ||||
| HR | 167doc 40168 | Signal type for Analog output 2 | UINT16 | Read/write | 1 = Analog; 2 = On-Off; 3 = Pulsing | ||||
| HR | 168doc 40169 | Signal type for Analog output 3 | UINT16 | Read/write | 1 = Analog; 2 = On-Off; 3 = Pulsing | ||||
| HR | 169doc 40170 | Signal type for Analog output 4 | UINT16 | Read/write | 1 = Analog; 2 = On-Off; 3 = Pulsing | ||||
| HR | 170doc 40171 | Signal type for Binary output 1 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off; 3 = Floating | ||||
| HR | 171doc 40172 | Signal type for Binary output 2 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off | ||||
| HR | 172doc 40173 | Signal type for Binary output 3 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off; 3 = Floating | ||||
| HR | 173doc 40174 | Signal type for Binary output 4 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off | ||||
| HR | 174doc 40175 | Signal type for Binary output 5 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off | ||||
| HR | 175doc 40176 | Signal type for Binary output 6 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off | ||||
| HR | 176doc 40177 | Signal type for Binary output 7 | UINT16 | Read/write | 1 = Pulsing; 2 = On-Off | ||||
| HR | 177doc 40178 | PIR Relay sensor | UINT16 | Read/write | 0 = Relay was not activated; 1 = Relay was activated | ||||
| HR | 178doc 40179 | Floating output motor timing for BO1/BO2 | UINT16 | s | Read/write | ||||
| HR | 179doc 40180 | Floating output motor timing for BO3/BO7 | UINT16 | s | Read/write | ||||
| HR | 193doc 40194 | Light intensity sensor value | UINT16 | lx | Read | ||||
| HR | 194doc 40195 | Light intensity sensor maximum range | UINT16 | lx | Read/write | ||||
| HR | 196doc 40197 | VOC sensor value | UINT16 | PPB | Read | ||||
| HR | 199doc 40200 | User backlight or contrast intensity | UINT16 | % | Read/write | ||||
| HR | 200doc 40201 | Occupancy backlight or contrast intensity | UINT16 | % | Read/write | ||||
| HR | 201doc 40202 | Unoccupancy backlight or contrast intensity | UINT16 | % | Read/write | ||||
| HR | 202doc 40203 | Configuration value to select the source for VFD temperature control | UINT16 | Read/write | 1 = InternSensor; 2 = ExternSensor; 3 = ExternSensor2 | ||||
| HR | 203doc 40204 | External Temperature sensor 2 reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 204doc 40205 | Configuration value used to calibrate External Temp Sensor 2 offset | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 205doc 40206 | External Temp 2 reading minimum value for voltage sensor | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 206doc 40207 | External Temp 2 reading maximum value for voltage sensor | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 207doc 40208 | AO1 voltage present value | INT16 | × 0.01 | V | Read | |||
| HR | 208doc 40209 | AO2 voltage present value | INT16 | × 0.01 | V | Read | |||
| HR | 209doc 40210 | AO3 voltage present value | INT16 | × 0.01 | V | Read | |||
| HR | 210doc 40211 | AO4 voltage present value | INT16 | × 0.01 | V | Read |
Notes on this map
- Every register is a 16-bit holding register (function 03 to read, 06 or 16 to write); there are no 32-bit values.
- Temperatures, setpoints, bands and offsets are reported in °C or °F according to the "temperature unit in Modbus" bit of the system-options register; scaling is x100 for sensor readings and offsets and x10 for setpoints and bands, as listed per register.
- Register 0 packs the Neptronic product ID in the high byte and the Modbus address in the low byte.
- Left out: the four product-name registers (two ASCII characters each, byte order not spelled out) and every register the guide marks Reserved.
- Left out: pulse output values 40185-40191 (data-type column and range text give different scales), the delta-temperature registers 40192-40193, 40100 (analog output 3 ramp, an option list printed with Scale 10) and the floating output values 40182-40183 (Scale 10 in the data-type column but Value x 1 in the range text).
- The UI3 signal register (40085) is kept without its option list because the guide numbers two options as 1.
- The guide's remarks next to the system-mode values point at register numbers that do not match the table; only the value list is kept.
- System option 2 (40046) bit 12 is printed twice in the guide (binary output 7 direction and fan speed option), so that bit is left undefined here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
What Modbus registers does the Neptronic TUUB Series universal wall-mount controller (Modbus RTU) have?
This map lists 189 registers: 189 holding registers. 151 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic TUUB Series universal wall-mount controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both the protocol (wire) address, starting at 0, and the 40001-style notation; e.g. 40046 is protocol address 45. The documented field holds the 4xxxx notation.
What are the minimum Modbus registers to integrate the Neptronic TUUB Series universal wall-mount controller (Modbus RTU)?
Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 41 System mode status (System mode); HR 42 Fan speed selection by user (Fan speed); HR 43 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 26 Actual heating demand of ramp 1 (Heating demand ramp 1); HR 28 Actual cooling demand of ramp 1 (Cooling demand ramp 1); HR 9 System Status 1 (Status 1); HR 10 System Status 2 (Status 2 (alarms)); HR 44 System option1 (System option 1 (bit 1 = Modbus temp unit)).
How do I enable Modbus control of the Neptronic TUUB Series universal wall-mount controller (Modbus RTU)?
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Where is the official Neptronic TUUB Series universal wall-mount controller (Modbus RTU) Modbus documentation?
The source is TUUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide (TUUB-Modbus Guide-250829 (V1.13)), revision 2025-08-29, published free by Neptronic at https://www.neptronic.com/controls/PDF/2025/TUUB-Modbus%20Guide-250829%20(V1.13).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB
Other pumps register maps
- Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Heat pump (water-to-air heat pump controller)
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Bosch commercial water-to-air heat pumps fitted with the Control Air 5600 DDC controller running the water-to-air standard software (integration points list version 1.03).
Also known as: Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101 - Heat pump (packaged wall-mount)
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Eubank EAH1020H-1060H / EAH2024H-2042H wall-mount heat pumps (I&O manual rev. 6); the HAH1024-1060 A/C with gas heat manual (rev. 5) prints the same table.
Also known as: EAH1020H, EAH1024H, EAH1030H, EAH1036H, EAH1042H, EAH1048H, EAH1060H, EAH2024H, EAH2042H, HAH1024A, HAH1030A, HAH1036A, HAH1042A, HAH1048A, HAH1060A, Eubank EAH heat pump, Eubank HAH - Pump motor protection relay
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Grundfos MP 204 electronic motor protector connected over GENIbus to a CIU 200 (Modbus RTU), CIU 250 (GSM/GPRS) or CIU 500 (Modbus TCP) box; functional profile 98393513 (2014-11).
Also known as: MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513 - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W
All pumps Modbus register maps →
Source: TUUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TUUB-Modbus Guide-250829 (V1.13) · rev. 2025-08-29. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.