Air handler terminal (dual-duct VAV controller) · Modbus register map

Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The EVCBM is Neptronic's VAV box controller with built-in actuator; the dual-duct version runs a master and a slave airflow loop. Its Modbus RTU module exposes holding registers for room, supply and external temperatures, humidity and CO2 from the TRL wall sensor, setpoints, PI bands, airflow readings and setpoints for both ducts, minimum/maximum airflows, K-factors, balancing modes, motor positions and overrides, TRIAC and analog output setup and the occupancy / mode commands.

This page lists 106 Modbus registers for the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) — 78 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
EVCBM dual-duct VAV controller (Modbus communication module)
Equipment type
Air handler terminal (dual-duct VAV controller)
Registers
106 (78 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Firmware
V500 (guide title)
Also known as
EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus
Source document
EVCBM Dual Duct Modbus Communication Module User Guide · EVCBM Dual Duct-V500-Modbus Guide-180927-ESA · rev. 2018-09-27
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic EVCBM dual-duct VAV controller (Modbus communication module)

Integration in brief

Read supply and control temperatures (19, 20), airflow 1 and 2 (60, 90) with their setpoints (61, 91) and motor position (74). Command occupancy with register 105 and the user mode with 108; change setpoints at 25-29 (x10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20Control temperatureINT16Control (room) temperatureRead/write
HR 25Occupied temperature setpointUINT16Occupied setpointRead/write
HR 60Actual airflow 1UINT16Airflow 1Read
HR 90Actual airflow 2UINT16Airflow 2Read
HR 74Motor 1 positionUINT16Motor 1 positionRead
HR 105Occupancy / night setback commandUINT16Occupancy commandRead/write
HR 108User system control modeUINT16System modeRead/write
HR 113Zone occupancy statusUINT16Occupancy statusRead

Enable Modbus control & writes

Fit the Modbus communication module and set the address from the device menu or register 0.

Communication loss & watchdog

Network fallback timeout (40096, 0-60 min).

Byte order & addressing

Network setup

Watch out for

Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

106 of 106 shown
Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Modbus address and product typeHigh byte = product type (111 for EVCB); low byte = Modbus address 1-246.UINT16Read/write
HR1doc 40001Baud rateBaud / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 40002Modbus port configurationUINT16Read/write1 = No parity, 2 stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit
HR7doc 40007Firmware versione.g. 409.UINT16Read
HR8doc 40008EEPROM versione.g. 203.UINT16Read
HR9doc 40009System status 1Other bits reserved.BITMAP16Readbit 12 = CO2 alarm
HR10doc 40010System status 2Other bits reserved.BITMAP16Readbit 12 = Alarm override
HR11doc 40011Internal temperatureTRL sensor; 0-50.UINT16× 0.01°C / °FRead
HR12doc 40012External temperature-40 to 100.INT16× 0.01°C / °FRead
HR14doc 40014Internal humidityTRLH / TRLGH sensor; 32767 if not fitted.INT16× 0.1%RHRead
HR15doc 40015Input 3 pressure sensor reading0-4000 mV.UINT16mVRead
HR16doc 40016Pressure input 2 valueSlave side, 0-4000 mV.UINT16mVRead
HR19doc 40019Supply air temperature-40 to 100.INT16× 0.01°C / °FRead
HR20doc 40020Control temperatureTemperature used for control; writable.INT16× 0.01°C / °FRead/write
HR21doc 40021Heating ramp 1 demandUINT16× 0.1%Read
HR22doc 40022Cooling ramp 1 demandUINT16× 0.1%Read
HR23doc 40023Internal temperature offset-5 to 5.INT16× 0.01°C / °FRead/write
HR24doc 40024External temperature offset-5 to 5.INT16× 0.01°C / °FRead/write
HR25doc 40025Occupied temperature setpointLimited by 40026 / 40027.UINT16× 0.1°C / °FRead/write
HR26doc 40026Minimum day setpointUINT16× 0.1°C / °FRead/write
HR27doc 40027Maximum day setpointUINT16× 0.1°C / °FRead/write
HR28doc 40028Night setback / unoccupied cooling setpointUINT16× 0.1°C / °FRead/write
HR29doc 40029Night setback / unoccupied heating setpointUINT16× 0.1°C / °FRead/write
HR30doc 40030Cooling proportional band 10.5-5.UINT16× 0.1°C / °FRead/write
HR31doc 40031Heating proportional band 10.5-5.UINT16× 0.1°C / °FRead/write
HR32doc 40032Cooling dead band 10-5.UINT16× 0.1°C / °FRead/write
HR33doc 40033Heating dead band 10-5.UINT16× 0.1°C / °FRead/write
HR35doc 40035Night setback override delay0-180 min.UINT16minRead/write
HR36doc 40036Heating integral time0-250 s.UINT16sRead/write
HR37doc 40037Cooling anti-cycle delay0-15 min before the cooling contact may restart.UINT16minRead/write
HR38doc 40038Floating time 1Actuator 90° run time, 15-250 s.UINT16sRead/write
HR39doc 40039Occupancy delay0-180 min.UINT16minRead/write
HR40doc 40040Cooling ramp 2 demandUINT16× 0.1%Read
HR41doc 40041Cooling ramp 2 proportional bandUINT16× 0.1°C / °FRead/write
HR42doc 40042Cooling ramp 2 dead bandUINT16× 0.1°C / °FRead/write
HR43doc 40043Heating ramp 2 demandPrinted as writable.UINT16× 0.1%Read/write
HR44doc 40044Heating ramp 2 proportional bandUINT16× 0.1°C / °FRead/write
HR45doc 40045Heating ramp 2 dead bandUINT16× 0.1°C / °FRead/write
HR50doc 40050AO2 minimum voltageUINT16× 0.1VRead/write
HR52doc 40052AO2 maximum voltageUINT16× 0.1VRead/write
HR53doc 40053Pressure 1 filterMaster side, 1-10 s.UINT16sRead/write
HR54doc 40054Airflow K-factor 1Master side, 100-9995 CFM.UINT16CFMRead/write
HR55doc 40055Minimum cooling airflowUINT16CFMRead/write
HR56doc 40056Maximum cooling airflowUINT16CFMRead/write
HR57doc 40057Minimum heating airflowUINT16CFMRead/write
HR58doc 40058Maximum heating airflowUINT16CFMRead/write
HR60doc 40060Actual airflow 1Master side, from the differential pressure sensor.UINT16CFMRead
HR61doc 40061Airflow setpoint 1Master side.UINT16CFMRead
HR62doc 40062Airflow 1 balancing maximumUsed in balancing mode 3 (maximum flow) for the K-factor.UINT16CFMRead/write
HR63doc 40063Motor 2 positionSlave side, 0-100 %.UINT16%Read/write
HR64doc 40064Analog output 2 valueUINT16× 0.1VRead/write
HR65doc 40065TRIAC 1 close demandDemand at which TO1 closes, 15-80 %.UINT16%Read/write
HR66doc 40066TRIAC 2 close demandDemand at which TO2 closes, 15-80 %.UINT16%Read/write
HR69doc 40069TRIAC 1 open demandUINT16%Read/write
HR70doc 40070TRIAC 2 open demandUINT16%Read/write
HR73doc 40073Cooling integral time0-250 s.UINT16sRead/write
HR74doc 40074Motor 1 positionMaster side, 0-100 %.UINT16%Read
HR81doc 40081Airflow 1 offset calibrationMaster side, -500 to 500 CFM; balancing mode must be 1 (close).INT16CFMRead/write
HR84doc 40084Airflow 1 balancing minimumMaster side.UINT16CFMRead/write
HR89doc 40089Airflow K-factor 2Slave side, 100-9995 CFM.UINT16CFMRead/write
HR90doc 40090Actual airflow 2Slave side.UINT16CFMRead
HR91doc 40091Airflow setpoint 2Slave side.UINT16CFMRead
HR92doc 40092Airflow 2 offset calibrationSlave side, -500 to 500 CFM; balancing mode must be 1 (close).INT16CFMRead/write
HR93doc 40093Airflow 2 balancing minimumSlave side; balancing mode must be 2 (minimum flow).UINT16CFMRead/write
HR94doc 40094Airflow 2 balancing maximumSlave side; balancing mode 3 (maximum flow) or higher.UINT16CFMRead/write
HR95doc 40095Pressure 2 filterSlave side, 1-10 s.UINT16sRead/write
HR96doc 40096Network fallback timeout0-60 min.UINT16minRead/write
HR98doc 40098CO2 sensor maximum range100-5000 ppm.UINT16ppmRead/write
HR99doc 40099CO2 alarm limitUINT16ppmRead/write
HR104doc 40104TRIAC on/offUINT16Read1 = TO1 on/off; 2 = TO2 on/off
HR105doc 40105Occupancy / night setback commandUINT16Read/write1 = Locally; 2 = Off; 3 = Occupancy; 4 = No occupancy; 5 = Day; 6 = Night
HR106doc 40106Digital input 1 statusUINT16Read0 = Open; 1 = Closed
HR108doc 40108User system control modeUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Off
HR109doc 40109User mode permissionsWhich modes the user may select.UINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Cool-Heat; 5 = Auto-Lock
HR110doc 40110Night setback statusUINT16Read1 = Day; 2 = Night; 3 = Derogation
HR111doc 40111DI1 modeUINT16Read/write1 = Off; 2 = Occupancy NO; 3 = Occupancy NC; 4 = Night setback NO; 5 = Night setback NC
HR112doc 40112AI2 input typeUINT16Read/write1 = Off; 2 = ETS; 3 = CO2; 4 = AST
HR113doc 40113Zone occupancy statusUINT16Read1 = No occupancy; 2 = Occupancy; 3 = Derogation
HR115doc 40115AO2 control ramp7-12 reserved.UINT16Read/write1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2
HR116doc 40116TO1 control ramp7-12 reserved.UINT16Read/write1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2
HR117doc 40117TO2 control ramp7-12 reserved.UINT16Read/write1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2
HR120doc 40120TO1 signal typeUINT16Read/write3 = Pulsing; 4 = On/Off; 5 = Floating
HR121doc 40121TO2 signal typeUINT16Read/write3 = Pulsing; 4 = On/Off
HR125doc 40125Motor rampUINT16Read/write2 = CR1 (cooling ramp 1); 4 = HR1 (heating ramp 1)
HR129doc 40129DI2 modeUINT16Read/write1 = Off; 2 = Override; 3 = OverHeat1; 4 = OverHeat2; 5 = OverHeatAll
HR130doc 40130Temperature control sourceProgramming mode.UINT16Read/write1 = Internal temperature; 2 = External temperature; 3 = Remote temperature
HR131doc 40131Airflow 1 balance modeMaster side.UINT16Read/write1 = Close; 2 = Minimum flow; 3 = Maximum flow; 4 = Full open
HR132doc 40132Airflow 2 balance modeSlave side.UINT16Read/write1 = Close; 2 = Minimum flow; 3 = Maximum flow; 4 = Full open
HR133doc 40133Night setback motor positionUINT16Read/write1 = Auto; 2 = Open
HR134doc 40134DI2 delay0-3600 s.UINT16sRead/write
HR138doc 40138Airflow hysteresis stop1-100 %.UINT16%Read/write
HR139doc 40139Airflow hysteresis startUINT16%Read/write
HR140doc 40140Airflow scaleUINT16Read/write1 = Scale 1; 2 = Scale 10; 3 = Scale 100
HR145doc 40145Heat/cool switch-over timerWait before swapping between heating and cooling, 0-120 min.UINT16minRead/write
HR147doc 40147Floating TRIAC demandTO1 or TO2 in floating mode.UINT16× 0.1%Read
HR149doc 40149TO1 pulsing demandUINT16× 0.1%Read
HR150doc 40150TO2 pulsing demandUINT16× 0.1%Read
HR153doc 40153Overheat statusUINT16Read1 = Normal; 2 = OverHeat1; 3 = OverHeat2; 4 = OverHeatAll
HR154doc 40154Motor 1 position overrideMaster side.UINT16Read/write1 = Auto; 2 = Open; 3 = Close; 4 = AirFlowCoolMin; 5 = AirFlowCoolMax
HR155doc 40155TRL display informationUINT16Read/write1 = Temp demand; 2 = Setpoint demand; 3 = Temp; 4 = Setpoint; 5 = Off
HR156doc 40156Digital input 2 statusUINT16Read0 = Open; 1 = Closed
HR157doc 40157Input 3 minimum readingPressure sensor dead band, 10-180 mV.UINT16mVRead/write
HR158doc 40158System options 3Other bits reserved.BITMAP16Read/writebit 2 = CO2 display (1 = yes); bit 3 = CO2 control source (0 = analog, 1 = TRLG); bit 5 = Constant flow option (1 = yes)
HR160doc 40160Internal CO2TRLG / TRLGH sensor; 32767 if not fitted.UINT16ppmRead
HR161doc 40161Motor 2 position overrideSlave side.UINT16Read/write1 = Auto; 2 = Open; 3 = Close; 4 = AirFlowCoolMin; 5 = AirFlowCoolMax
HR163doc 40163Occupancy minimum time0-240 min.UINT16minRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)

What Modbus registers does the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) have?

This map lists 106 registers: 106 holding registers. 78 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints a 'Register Index' from 40000. The intro says the device address is at holding register index 0, the auto-baud setting at index 1 and the port setting at index 2, and those are the rows printed 40000, 40001 and 40002, so the wire address is the printed number minus 40000 (e.g. 40019 supply temperature = address 19). Same layout as Neptronic's TUXB guide.

What are the minimum Modbus registers to integrate the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)?

Start with HR 20 Control temperature (Control (room) temperature); HR 25 Occupied temperature setpoint (Occupied setpoint); HR 60 Actual airflow 1 (Airflow 1); HR 90 Actual airflow 2 (Airflow 2); HR 74 Motor 1 position (Motor 1 position); HR 105 Occupancy / night setback command (Occupancy command); HR 108 User system control mode (System mode); HR 113 Zone occupancy status (Occupancy status).

How do I enable Modbus control of the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)?

Fit the Modbus communication module and set the address from the device menu or register 0.

What happens when the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) loses Modbus communication?

Network fallback timeout (40096, 0-60 min).

Where is the official Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus documentation?

The source is EVCBM Dual Duct Modbus Communication Module User Guide (EVCBM Dual Duct-V500-Modbus Guide-180927-ESA), revision 2018-09-27, published free by Neptronic at https://www.neptronic.com/controls/PDF/EVC/BACnetModbus/20181001/EVCBM%20Dual%20Duct-V500-Modbus%20Guide-180927-ESA.pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: EVCBM Dual Duct Modbus Communication Module User Guide · EVCBM Dual Duct-V500-Modbus Guide-180927-ESA · rev. 2018-09-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.