Air handler terminal (dual-duct VAV controller) · Modbus register map
Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus register map
Updated 19 November 2026
The EVCBM is Neptronic's VAV box controller with built-in actuator; the dual-duct version runs a master and a slave airflow loop. Its Modbus RTU module exposes holding registers for room, supply and external temperatures, humidity and CO2 from the TRL wall sensor, setpoints, PI bands, airflow readings and setpoints for both ducts, minimum/maximum airflows, K-factors, balancing modes, motor positions and overrides, TRIAC and analog output setup and the occupancy / mode commands.
This page lists 106 Modbus registers for the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) — 78 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- EVCBM dual-duct VAV controller (Modbus communication module)
- Equipment type
- Air handler terminal (dual-duct VAV controller)
- Registers
- 106 (78 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- V500 (guide title)
- Also known as
- EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus
Integration notes: Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Read supply and control temperatures (19, 20), airflow 1 and 2 (60, 90) with their setpoints (61, 91) and motor position (74). Command occupancy with register 105 and the user mode with 108; change setpoints at 25-29 (x10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20 | Control temperature | INT16 | Control (room) temperature | Read/write |
| HR 25 | Occupied temperature setpoint | UINT16 | Occupied setpoint | Read/write |
| HR 60 | Actual airflow 1 | UINT16 | Airflow 1 | Read |
| HR 90 | Actual airflow 2 | UINT16 | Airflow 2 | Read |
| HR 74 | Motor 1 position | UINT16 | Motor 1 position | Read |
| HR 105 | Occupancy / night setback command | UINT16 | Occupancy command | Read/write |
| HR 108 | User system control mode | UINT16 | System mode | Read/write |
| HR 113 | Zone occupancy status | UINT16 | Occupancy status | Read |
Enable Modbus control & writes
Fit the Modbus communication module and set the address from the device menu or register 0.
Communication loss & watchdog
Network fallback timeout (40096, 0-60 min).
Byte order & addressing
- Printed register numbers start at 40000 for address 0, not 40001.
- Auto baud detection is the default; the device steps to the next rate after two or more bad frames in one second.
Network setup
- RS-485 two-wire, RTU mode, 9600-57600 baud or auto.
- Device address 1-246.
Watch out for
- Airflow balancing writes only take effect in the right balancing mode (40131 / 40132).
Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Modbus address and product type | High byte = product type (111 for EVCB); low byte = Modbus address 1-246. | UINT16 | Read/write | ||||
| HR | 1doc 40001 | Baud rate | Baud / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 40002 | Modbus port configuration | UINT16 | Read/write | 1 = No parity, 2 stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit | ||||
| HR | 7doc 40007 | Firmware version | e.g. 409. | UINT16 | Read | ||||
| HR | 8doc 40008 | EEPROM version | e.g. 203. | UINT16 | Read | ||||
| HR | 9doc 40009 | System status 1 | Other bits reserved. | BITMAP16 | Read | bit 12 = CO2 alarm | |||
| HR | 10doc 40010 | System status 2 | Other bits reserved. | BITMAP16 | Read | bit 12 = Alarm override | |||
| HR | 11doc 40011 | Internal temperature | TRL sensor; 0-50. | UINT16 | × 0.01 | °C / °F | Read | ||
| HR | 12doc 40012 | External temperature | -40 to 100. | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 14doc 40014 | Internal humidity | TRLH / TRLGH sensor; 32767 if not fitted. | INT16 | × 0.1 | %RH | Read | ||
| HR | 15doc 40015 | Input 3 pressure sensor reading | 0-4000 mV. | UINT16 | mV | Read | |||
| HR | 16doc 40016 | Pressure input 2 value | Slave side, 0-4000 mV. | UINT16 | mV | Read | |||
| HR | 19doc 40019 | Supply air temperature | -40 to 100. | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 20doc 40020 | Control temperature | Temperature used for control; writable. | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 21doc 40021 | Heating ramp 1 demand | UINT16 | × 0.1 | % | Read | |||
| HR | 22doc 40022 | Cooling ramp 1 demand | UINT16 | × 0.1 | % | Read | |||
| HR | 23doc 40023 | Internal temperature offset | -5 to 5. | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 24doc 40024 | External temperature offset | -5 to 5. | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 25doc 40025 | Occupied temperature setpoint | Limited by 40026 / 40027. | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 26doc 40026 | Minimum day setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 27doc 40027 | Maximum day setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 28doc 40028 | Night setback / unoccupied cooling setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 29doc 40029 | Night setback / unoccupied heating setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 30doc 40030 | Cooling proportional band 1 | 0.5-5. | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 31doc 40031 | Heating proportional band 1 | 0.5-5. | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 32doc 40032 | Cooling dead band 1 | 0-5. | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 33doc 40033 | Heating dead band 1 | 0-5. | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 35doc 40035 | Night setback override delay | 0-180 min. | UINT16 | min | Read/write | |||
| HR | 36doc 40036 | Heating integral time | 0-250 s. | UINT16 | s | Read/write | |||
| HR | 37doc 40037 | Cooling anti-cycle delay | 0-15 min before the cooling contact may restart. | UINT16 | min | Read/write | |||
| HR | 38doc 40038 | Floating time 1 | Actuator 90° run time, 15-250 s. | UINT16 | s | Read/write | |||
| HR | 39doc 40039 | Occupancy delay | 0-180 min. | UINT16 | min | Read/write | |||
| HR | 40doc 40040 | Cooling ramp 2 demand | UINT16 | × 0.1 | % | Read | |||
| HR | 41doc 40041 | Cooling ramp 2 proportional band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 42doc 40042 | Cooling ramp 2 dead band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 43doc 40043 | Heating ramp 2 demand | Printed as writable. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 44doc 40044 | Heating ramp 2 proportional band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 45doc 40045 | Heating ramp 2 dead band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 50doc 40050 | AO2 minimum voltage | UINT16 | × 0.1 | V | Read/write | |||
| HR | 52doc 40052 | AO2 maximum voltage | UINT16 | × 0.1 | V | Read/write | |||
| HR | 53doc 40053 | Pressure 1 filter | Master side, 1-10 s. | UINT16 | s | Read/write | |||
| HR | 54doc 40054 | Airflow K-factor 1 | Master side, 100-9995 CFM. | UINT16 | CFM | Read/write | |||
| HR | 55doc 40055 | Minimum cooling airflow | UINT16 | CFM | Read/write | ||||
| HR | 56doc 40056 | Maximum cooling airflow | UINT16 | CFM | Read/write | ||||
| HR | 57doc 40057 | Minimum heating airflow | UINT16 | CFM | Read/write | ||||
| HR | 58doc 40058 | Maximum heating airflow | UINT16 | CFM | Read/write | ||||
| HR | 60doc 40060 | Actual airflow 1 | Master side, from the differential pressure sensor. | UINT16 | CFM | Read | |||
| HR | 61doc 40061 | Airflow setpoint 1 | Master side. | UINT16 | CFM | Read | |||
| HR | 62doc 40062 | Airflow 1 balancing maximum | Used in balancing mode 3 (maximum flow) for the K-factor. | UINT16 | CFM | Read/write | |||
| HR | 63doc 40063 | Motor 2 position | Slave side, 0-100 %. | UINT16 | % | Read/write | |||
| HR | 64doc 40064 | Analog output 2 value | UINT16 | × 0.1 | V | Read/write | |||
| HR | 65doc 40065 | TRIAC 1 close demand | Demand at which TO1 closes, 15-80 %. | UINT16 | % | Read/write | |||
| HR | 66doc 40066 | TRIAC 2 close demand | Demand at which TO2 closes, 15-80 %. | UINT16 | % | Read/write | |||
| HR | 69doc 40069 | TRIAC 1 open demand | UINT16 | % | Read/write | ||||
| HR | 70doc 40070 | TRIAC 2 open demand | UINT16 | % | Read/write | ||||
| HR | 73doc 40073 | Cooling integral time | 0-250 s. | UINT16 | s | Read/write | |||
| HR | 74doc 40074 | Motor 1 position | Master side, 0-100 %. | UINT16 | % | Read | |||
| HR | 81doc 40081 | Airflow 1 offset calibration | Master side, -500 to 500 CFM; balancing mode must be 1 (close). | INT16 | CFM | Read/write | |||
| HR | 84doc 40084 | Airflow 1 balancing minimum | Master side. | UINT16 | CFM | Read/write | |||
| HR | 89doc 40089 | Airflow K-factor 2 | Slave side, 100-9995 CFM. | UINT16 | CFM | Read/write | |||
| HR | 90doc 40090 | Actual airflow 2 | Slave side. | UINT16 | CFM | Read | |||
| HR | 91doc 40091 | Airflow setpoint 2 | Slave side. | UINT16 | CFM | Read | |||
| HR | 92doc 40092 | Airflow 2 offset calibration | Slave side, -500 to 500 CFM; balancing mode must be 1 (close). | INT16 | CFM | Read/write | |||
| HR | 93doc 40093 | Airflow 2 balancing minimum | Slave side; balancing mode must be 2 (minimum flow). | UINT16 | CFM | Read/write | |||
| HR | 94doc 40094 | Airflow 2 balancing maximum | Slave side; balancing mode 3 (maximum flow) or higher. | UINT16 | CFM | Read/write | |||
| HR | 95doc 40095 | Pressure 2 filter | Slave side, 1-10 s. | UINT16 | s | Read/write | |||
| HR | 96doc 40096 | Network fallback timeout | 0-60 min. | UINT16 | min | Read/write | |||
| HR | 98doc 40098 | CO2 sensor maximum range | 100-5000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 99doc 40099 | CO2 alarm limit | UINT16 | ppm | Read/write | ||||
| HR | 104doc 40104 | TRIAC on/off | UINT16 | Read | 1 = TO1 on/off; 2 = TO2 on/off | ||||
| HR | 105doc 40105 | Occupancy / night setback command | UINT16 | Read/write | 1 = Locally; 2 = Off; 3 = Occupancy; 4 = No occupancy; 5 = Day; 6 = Night | ||||
| HR | 106doc 40106 | Digital input 1 status | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 108doc 40108 | User system control mode | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Off | ||||
| HR | 109doc 40109 | User mode permissions | Which modes the user may select. | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Cool-Heat; 5 = Auto-Lock | |||
| HR | 110doc 40110 | Night setback status | UINT16 | Read | 1 = Day; 2 = Night; 3 = Derogation | ||||
| HR | 111doc 40111 | DI1 mode | UINT16 | Read/write | 1 = Off; 2 = Occupancy NO; 3 = Occupancy NC; 4 = Night setback NO; 5 = Night setback NC | ||||
| HR | 112doc 40112 | AI2 input type | UINT16 | Read/write | 1 = Off; 2 = ETS; 3 = CO2; 4 = AST | ||||
| HR | 113doc 40113 | Zone occupancy status | UINT16 | Read | 1 = No occupancy; 2 = Occupancy; 3 = Derogation | ||||
| HR | 115doc 40115 | AO2 control ramp | 7-12 reserved. | UINT16 | Read/write | 1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2 | |||
| HR | 116doc 40116 | TO1 control ramp | 7-12 reserved. | UINT16 | Read/write | 1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2 | |||
| HR | 117doc 40117 | TO2 control ramp | 7-12 reserved. | UINT16 | Read/write | 1 = Off; 2 = CR1 (cool ramp 1); 3 = CR2 (cool ramp 2); 4 = HR1 (heat ramp 1); 5 = HR2 (heat ramp 2); 6 = CO2 | |||
| HR | 120doc 40120 | TO1 signal type | UINT16 | Read/write | 3 = Pulsing; 4 = On/Off; 5 = Floating | ||||
| HR | 121doc 40121 | TO2 signal type | UINT16 | Read/write | 3 = Pulsing; 4 = On/Off | ||||
| HR | 125doc 40125 | Motor ramp | UINT16 | Read/write | 2 = CR1 (cooling ramp 1); 4 = HR1 (heating ramp 1) | ||||
| HR | 129doc 40129 | DI2 mode | UINT16 | Read/write | 1 = Off; 2 = Override; 3 = OverHeat1; 4 = OverHeat2; 5 = OverHeatAll | ||||
| HR | 130doc 40130 | Temperature control source | Programming mode. | UINT16 | Read/write | 1 = Internal temperature; 2 = External temperature; 3 = Remote temperature | |||
| HR | 131doc 40131 | Airflow 1 balance mode | Master side. | UINT16 | Read/write | 1 = Close; 2 = Minimum flow; 3 = Maximum flow; 4 = Full open | |||
| HR | 132doc 40132 | Airflow 2 balance mode | Slave side. | UINT16 | Read/write | 1 = Close; 2 = Minimum flow; 3 = Maximum flow; 4 = Full open | |||
| HR | 133doc 40133 | Night setback motor position | UINT16 | Read/write | 1 = Auto; 2 = Open | ||||
| HR | 134doc 40134 | DI2 delay | 0-3600 s. | UINT16 | s | Read/write | |||
| HR | 138doc 40138 | Airflow hysteresis stop | 1-100 %. | UINT16 | % | Read/write | |||
| HR | 139doc 40139 | Airflow hysteresis start | UINT16 | % | Read/write | ||||
| HR | 140doc 40140 | Airflow scale | UINT16 | Read/write | 1 = Scale 1; 2 = Scale 10; 3 = Scale 100 | ||||
| HR | 145doc 40145 | Heat/cool switch-over timer | Wait before swapping between heating and cooling, 0-120 min. | UINT16 | min | Read/write | |||
| HR | 147doc 40147 | Floating TRIAC demand | TO1 or TO2 in floating mode. | UINT16 | × 0.1 | % | Read | ||
| HR | 149doc 40149 | TO1 pulsing demand | UINT16 | × 0.1 | % | Read | |||
| HR | 150doc 40150 | TO2 pulsing demand | UINT16 | × 0.1 | % | Read | |||
| HR | 153doc 40153 | Overheat status | UINT16 | Read | 1 = Normal; 2 = OverHeat1; 3 = OverHeat2; 4 = OverHeatAll | ||||
| HR | 154doc 40154 | Motor 1 position override | Master side. | UINT16 | Read/write | 1 = Auto; 2 = Open; 3 = Close; 4 = AirFlowCoolMin; 5 = AirFlowCoolMax | |||
| HR | 155doc 40155 | TRL display information | UINT16 | Read/write | 1 = Temp demand; 2 = Setpoint demand; 3 = Temp; 4 = Setpoint; 5 = Off | ||||
| HR | 156doc 40156 | Digital input 2 status | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 157doc 40157 | Input 3 minimum reading | Pressure sensor dead band, 10-180 mV. | UINT16 | mV | Read/write | |||
| HR | 158doc 40158 | System options 3 | Other bits reserved. | BITMAP16 | Read/write | bit 2 = CO2 display (1 = yes); bit 3 = CO2 control source (0 = analog, 1 = TRLG); bit 5 = Constant flow option (1 = yes) | |||
| HR | 160doc 40160 | Internal CO2 | TRLG / TRLGH sensor; 32767 if not fitted. | UINT16 | ppm | Read | |||
| HR | 161doc 40161 | Motor 2 position override | Slave side. | UINT16 | Read/write | 1 = Auto; 2 = Open; 3 = Close; 4 = AirFlowCoolMin; 5 = AirFlowCoolMax | |||
| HR | 163doc 40163 | Occupancy minimum time | 0-240 min. | UINT16 | min | Read/write |
Notes on this map
- Only function codes 03, 06 and 16 are supported; everything is a holding register.
- 'Scale N' with 'Value x N' means raw = engineering value x N; the multiplier here is 1/N.
- The guide's examples are in °C; System Option 1 has a temperature-units bit (Celsius / Fahrenheit), so temperatures are marked °C / °F.
- 'Master' rows belong to the first (master) airflow loop and 'Slave' rows to the second duct.
- Left out: product name ASCII registers 40003-40006; System Option 1 and 2 (40100/40101), whose bit lists are scrambled across columns in the PDF; System Command Status 40103 (mixed command codes and bit states); System Options 4 (40159, all reserved); CL_HT SwitchTimerCount 40146 (range 0-4,294,967,295 s in a single register); Cfg_MixAirDeadBand 40162 (range given only as a reference to other settings, no units).
- Heating ramp 2 demand (40043) is printed writable while the cooling counterpart (40040) is read only; kept as printed.
- Port configuration codes start at 1 in this guide (1 = no parity / 2 stop bits), unlike Neptronic's newer guides.
- Left out by the verifier: CO2 value 40018 (Value x 100, but the range runs up to the CO2 sensor maximum of 5000 ppm, which cannot fit one 16-bit register at x100) and Analog Input 2 value 40017 (0-1000 at Value x 100 with an mV example, unclear whether the range is raw or scaled).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
What Modbus registers does the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) have?
This map lists 106 registers: 106 holding registers. 78 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints a 'Register Index' from 40000. The intro says the device address is at holding register index 0, the auto-baud setting at index 1 and the port setting at index 2, and those are the rows printed 40000, 40001 and 40002, so the wire address is the printed number minus 40000 (e.g. 40019 supply temperature = address 19). Same layout as Neptronic's TUXB guide.
What are the minimum Modbus registers to integrate the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)?
Start with HR 20 Control temperature (Control (room) temperature); HR 25 Occupied temperature setpoint (Occupied setpoint); HR 60 Actual airflow 1 (Airflow 1); HR 90 Actual airflow 2 (Airflow 2); HR 74 Motor 1 position (Motor 1 position); HR 105 Occupancy / night setback command (Occupancy command); HR 108 User system control mode (System mode); HR 113 Zone occupancy status (Occupancy status).
How do I enable Modbus control of the Neptronic EVCBM dual-duct VAV controller (Modbus communication module)?
Fit the Modbus communication module and set the address from the device menu or register 0.
What happens when the Neptronic EVCBM dual-duct VAV controller (Modbus communication module) loses Modbus communication?
Network fallback timeout (40096, 0-60 min).
Where is the official Neptronic EVCBM dual-duct VAV controller (Modbus communication module) Modbus documentation?
The source is EVCBM Dual Duct Modbus Communication Module User Guide (EVCBM Dual Duct-V500-Modbus Guide-180927-ESA), revision 2018-09-27, published free by Neptronic at https://www.neptronic.com/controls/PDF/EVC/BACnetModbus/20181001/EVCBM%20Dual%20Duct-V500-Modbus%20Guide-180927-ESA.pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat / temperature and process PID controller
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Omega CN2200 and CN2400 series controllers with the Modbus comms option (CN2400 software 1.03-3.05, CN2200 1.00-2.10 per the handbook).
Also known as: CN2204, CN2208, CN2408 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Air handler (heat recovery ventilation unit)
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Futura L/M/S from firmware FUA.P.06.71, register list v5.0 (13.10.2025). Futura L+ uses different addresses and is not covered.
Also known as: Futura L, Futura M, Futura S, JABLOTRON FUTURA
All hvac equipment Modbus register maps →
Source: EVCBM Dual Duct Modbus Communication Module User Guide · EVCBM Dual Duct-V500-Modbus Guide-180927-ESA · rev. 2018-09-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.