Air handler (computer room air conditioner) · Modbus register map

Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus register map

Updated 19 November 2026

Short answer

Liebert DS, CW, HPM, PeX and Challenger units are perimeter computer-room air conditioners (DX and chilled water). With a Liebert IntelliSlot Modbus card in the iCOM controller they appear as a Modbus RTU or Modbus TCP slave. This map covers the unit on/off coil, operating state and status, return/supply air temperatures and humidity, temperature and humidity setpoints and bands, alarm thresholds, fan/cooling/reheat/humidifier utilisation, run hours, remote sensors and the full list of event bits.

This page lists 408 Modbus registers for the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) — 177 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.

Manufacturer
Vertiv
Model
Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Equipment type
Air handler (computer room air conditioner)
Registers
408 (177 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML
Source document
Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)

Integration in brief

Poll input registers 30100-30134 for state, temperatures and humidity, and the 1xxxx discrete inputs for events. Write coil 25 to start/stop the unit and holding registers 40023 / 40027 for the temperature (tenths of deg C) and humidity setpoints.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 24System On/Off ControlBITSystem on/off controlRead/write
IR 99System Operating StateUINT16System operating stateRead
IR 101System StatusUINT16System statusRead
IR 109Return Air TemperatureINT16Return air temperatureRead
IR 111Supply Air TemperatureINT16Supply air temperatureRead
IR 129Return HumidityUINT16Return humidityRead
HR 22Air Temperature Set PointINT16Air temperature setpointRead/write
HR 26Humidity Set PointUINT16Humidity setpointRead/write
IR 102Fan SpeedUINT16Fan speedRead
HR 380System Event Acknowledge/ResetUINT16Acknowledge / reset eventsRead/write

Enable Modbus control & writes

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Communication loss & watchdog

Holding register 40045 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS traffic before raising a BMS timeout; what the unit does on timeout is not described in this guide.

Byte order & addressing

Network setup

Watch out for

Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

408 of 408 shown
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO12doc 13Minimum Chilled Water Temp Set Point EnableBITRead/write0 = disabled; 1 = enabled
CO18doc 19Return Air Sensor Event ControlBITRead/write0 = disabled; 1 = enabled
CO19doc 20Ext Air Sensor A Event ControlBITRead/write0 = disabled; 1 = enabled
CO24doc 25System On/Off ControlBITRead/write0 = off; 1 = on
DI8doc 10009Ext Reheat LockoutBITRead0 = Inactive; 1 = Active
DI9doc 10010Ext Humidifier LockoutBITRead0 = Inactive; 1 = Active
DI12doc 10013Minimum Chilled Water Temp Set Point EnableBITRead0 = disabled; 1 = enabled
DI18doc 10019Return Air Sensor Event ControlBITRead0 = disabled; 1 = enabled
DI19doc 10020Ext Air Sensor A Event ControlBITRead0 = disabled; 1 = enabled
DI20doc 10021Ext Compressor LockoutBITRead0 = Inactive; 1 = Active
DI24doc 10025Fan StateBITRead0 = off; 1 = on
DI25doc 10026Cooling StateBITRead0 = off; 1 = on
DI26doc 10027Free Cooling StateBITRead0 = off; 1 = on
DI27doc 10028Hot Water / Hot Gas StateBITRead0 = off; 1 = on
DI28doc 10029Electric Reheat StateBITRead0 = off; 1 = on
DI29doc 10030Humidifier StateBITRead0 = off; 1 = on
DI30doc 10031Dehumidifier StateBITRead0 = off; 1 = on
DI33doc 10034Main Fan OverloadBITRead0 = Inactive; 1 = Active
DI34doc 10035Loss of Air FlowBITRead0 = Inactive; 1 = Active
DI35doc 10036Ext Loss of FlowBITRead0 = Inactive; 1 = Active
DI36doc 10037Compressor High Head PressureBITRead0 = Inactive; 1 = Active
DI37doc 10038Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI38doc 10039Compressor Thermal OverloadBITRead0 = Inactive; 1 = Active
DI39doc 10040Compressor Pump Down IssueBITRead0 = Inactive; 1 = Active
DI40doc 10041Compressor High Head Pressure 2BITRead0 = Inactive; 1 = Active
DI41doc 10042Compressor Low Suction Pressure 2BITRead0 = Inactive; 1 = Active
DI42doc 10043Compressor Thermal Overload 2BITRead0 = Inactive; 1 = Active
DI43doc 10044Compressor Pump Down Issue 2BITRead0 = Inactive; 1 = Active
DI44doc 10045Dig Scroll Comp Over Temp 1BITRead0 = Inactive; 1 = Active
DI45doc 10046Dig Scroll Comp Over Temp 2BITRead0 = Inactive; 1 = Active
DI46doc 10047Smoke DetectedBITRead0 = Inactive; 1 = Active
DI47doc 10048Water Under FloorBITRead0 = Inactive; 1 = Active
DI48doc 10049Humidifier IssueBITRead0 = Inactive; 1 = Active
DI49doc 10050Ext Standby Glycol Pump OnBITRead0 = Inactive; 1 = Active
DI50doc 10051Ext Standby Unit OnBITRead0 = Inactive; 1 = Active
DI51doc 10052Ext Condenser Pump High WaterBITRead0 = Inactive; 1 = Active
DI52doc 10053Return Air Sensor IssueBITRead0 = Inactive; 1 = Active
DI54doc 10055Ext Loss of Air BlowerBITRead0 = Inactive; 1 = Active
DI57doc 10058Humidifier Low WaterBITRead0 = Inactive; 1 = Active
DI58doc 10059Humidifier Over CurrentBITRead0 = Inactive; 1 = Active
DI59doc 10060Ext Over TemperatureBITRead0 = Inactive; 1 = Active
DI60doc 10061Shutdown - Loss Of PowerBITRead0 = Inactive; 1 = Active
DI64doc 10065Supply Chilled Water Over TempBITRead0 = Inactive; 1 = Active
DI66doc 10067Return Air Over TemperatureBITRead0 = Inactive; 1 = Active
DI67doc 10068Return Air Under TemperatureBITRead0 = Inactive; 1 = Active
DI68doc 10069High Return HumidityBITRead0 = Inactive; 1 = Active
DI69doc 10070Low Return HumidityBITRead0 = Inactive; 1 = Active
DI70doc 10071Ext Air Sensor A Over TemperatureBITRead0 = Inactive; 1 = Active
DI71doc 10072Ext Air Sensor A Under TemperatureBITRead0 = Inactive; 1 = Active
DI72doc 10073Ext Air Sensor A High HumidityBITRead0 = Inactive; 1 = Active
DI73doc 10074Ext Air Sensor A Low HumidityBITRead0 = Inactive; 1 = Active
DI74doc 10075Supply Chilled Water Loss of FlowBITRead0 = Inactive; 1 = Active
DI75doc 10076Clogged Air FilterBITRead0 = Inactive; 1 = Active
DI76doc 10077Supply Air Sensor IssueBITRead0 = Inactive; 1 = Active
DI77doc 10078Free Cooling Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI78doc 10079Ext Air Sensor A IssueBITRead0 = Inactive; 1 = Active
DI79doc 10080Fan Hours ExceededBITRead0 = Inactive; 1 = Active
DI80doc 10081Compressor Hours Exceeded 1BITRead0 = Inactive; 1 = Active
DI81doc 10082Compressor Hours Exceeded 2BITRead0 = Inactive; 1 = Active
DI82doc 10083Free Cooling Valve Hours ExceededBITRead0 = Inactive; 1 = Active
DI83doc 10084Electric Reheater Hours Exceeded 1BITRead0 = Inactive; 1 = Active
DI84doc 10085Electric Reheater Hours Exceeded 2BITRead0 = Inactive; 1 = Active
DI85doc 10086Electric Reheater Hours Exceeded 3BITRead0 = Inactive; 1 = Active
DI86doc 10087Hot Water / Hot Gas Valve Hours ExceededBITRead0 = Inactive; 1 = Active
DI87doc 10088Humidifier Hours ExceededBITRead0 = Inactive; 1 = Active
DI88doc 10089Dehumidifier Hours ExceededBITRead0 = Inactive; 1 = Active
DI90doc 10091Unit Communication LostBITRead0 = Inactive; 1 = Active
DI91doc 10092Master Unit Communication LostBITRead0 = Inactive; 1 = Active
DI93doc 10094Unit Code MissingBITRead0 = Inactive; 1 = Active
DI97doc 10098Service RequiredBITRead0 = Inactive; 1 = Active
DI98doc 10099Humidifier Control Board Not DetectedBITRead0 = Inactive; 1 = Active
DI103doc 10104Customer Input 1BITRead0 = Inactive; 1 = Active
DI104doc 10105Customer Input 2BITRead0 = Inactive; 1 = Active
DI105doc 10106Customer Input 3BITRead0 = Inactive; 1 = Active
DI106doc 10107Customer Input 4BITRead0 = Inactive; 1 = Active
DI107doc 10108Dig Scroll Comp Discharge Temp Sensor Issue 1BITRead0 = Inactive; 1 = Active
DI108doc 10109Dig Scroll Comp Discharge Temp Sensor Issue 2BITRead0 = Inactive; 1 = Active
DI208doc 10209Supply Air Over TemperatureBITRead0 = Inactive; 1 = Active
DI209doc 10210Supply Air Under TemperatureBITRead0 = Inactive; 1 = Active
DI210doc 10211Ambient Air Sensor IssueBITRead0 = Inactive; 1 = Active
DI211doc 10212Compressor Short Cycle 1BITRead0 = Inactive; 1 = Active
DI212doc 10213Compressor Short Cycle 2BITRead0 = Inactive; 1 = Active
DI213doc 10214Ext Free Cooling LockoutBITRead0 = Inactive; 1 = Active
DI214doc 10215Reheater Over TemperatureBITRead0 = Inactive; 1 = Active
DI215doc 10216Humidifier Cylinder WornBITRead0 = Inactive; 1 = Active
DI216doc 10217Humidifier Under CurrentBITRead0 = Inactive; 1 = Active
DI217doc 10218Fan IssueBITRead0 = Inactive; 1 = Active
DI218doc 10219Condenser TVSS IssueBITRead0 = Inactive; 1 = Active
DI219doc 10220Condenser VFD IssueBITRead0 = Inactive; 1 = Active
DI220doc 10221Condenser Issue 1BITRead0 = Inactive; 1 = Active
DI221doc 10222Condenser Issue 2BITRead0 = Inactive; 1 = Active
DI222doc 10223BMS Communications TimeoutBITRead0 = Inactive; 1 = Active
DI223doc 10224Digital Output Board Not Detected 1BITRead0 = Inactive; 1 = Active
DI224doc 10225Digital Output Board Not Detected 2BITRead0 = Inactive; 1 = Active
DI225doc 10226Digital Output Board Not Detected 3BITRead0 = Inactive; 1 = Active
DI226doc 10227RAM Battery IssueBITRead0 = Inactive; 1 = Active
DI227doc 10228Water Leakage Detector Sensor IssueBITRead0 = Inactive; 1 = Active
DI228doc 10229External Fire DetectedBITRead0 = Inactive; 1 = Active
DI229doc 10230Chilled Water Control Valve Failure 1BITRead0 = Inactive; 1 = Active
DI230doc 10231Chilled Water Control Valve Failure 2BITRead0 = Inactive; 1 = Active
DI231doc 10232Unit OffBITRead0 = Inactive; 1 = Active
DI232doc 10233Unit OnBITRead0 = Inactive; 1 = Active
DI233doc 10234Unit Partial ShutdownBITRead0 = Inactive; 1 = Active
DI234doc 10235Unit ShutdownBITRead0 = Inactive; 1 = Active
DI235doc 10236High Power ShutdownBITRead0 = Inactive; 1 = Active
DI236doc 10237Unit StandbyBITRead0 = Inactive; 1 = Active
DI237doc 10238Maintenance DueBITRead0 = Inactive; 1 = Active
DI238doc 10239Maintenance CompletedBITRead0 = Inactive; 1 = Active
DI239doc 10240Compressor Low Pressure Transducer Issue 1BITRead0 = Inactive; 1 = Active
DI240doc 10241Compressor Low Pressure Transducer Issue 2BITRead0 = Inactive; 1 = Active
DI241doc 10242Compressor High Pressure Transducer Issue 1BITRead0 = Inactive; 1 = Active
DI242doc 10243Compressor High Pressure Transducer Issue 2BITRead0 = Inactive; 1 = Active
DI243doc 10244Compressor Capacity ReducedBITRead0 = Inactive; 1 = Active
DI344doc 10345Dew Point Over TemperatureBITRead0 = Inactive; 1 = Active
DI345doc 10346Dew Point Under TemperatureBITRead0 = Inactive; 1 = Active
DI346doc 10347Ext Dew Point Over TemperatureBITRead0 = Inactive; 1 = Active
DI347doc 10348Ext Dew Point Under TemperatureBITRead0 = Inactive; 1 = Active
DI348doc 10349Compressor Superheat Over Threshold 1BITRead0 = Inactive; 1 = Active
DI349doc 10350Compressor Superheat Over Threshold 2BITRead0 = Inactive; 1 = Active
DI350doc 10351Unspecified General EventBITRead0 = Inactive; 1 = Active
DI351doc 10352Remote Sensor Average Over TemperatureBITRead0 = Inactive; 1 = Active
DI352doc 10353Remote Sensor Average Under TemperatureBITRead0 = Inactive; 1 = Active
DI353doc 10354Remote Sensor System Average Over TemperatureBITRead0 = Inactive; 1 = Active
DI354doc 10355Remote Sensor System Average Under TemperatureBITRead0 = Inactive; 1 = Active
DI355doc 10356Remote Sensor Over Temperature 1BITRead0 = Inactive; 1 = Active
DI356doc 10357Remote Sensor Over Temperature 2BITRead0 = Inactive; 1 = Active
DI357doc 10358Remote Sensor Over Temperature 3BITRead0 = Inactive; 1 = Active
DI358doc 10359Remote Sensor Over Temperature 4BITRead0 = Inactive; 1 = Active
DI359doc 10360Remote Sensor Over Temperature 5BITRead0 = Inactive; 1 = Active
DI360doc 10361Remote Sensor Over Temperature 6BITRead0 = Inactive; 1 = Active
DI361doc 10362Remote Sensor Over Temperature 7BITRead0 = Inactive; 1 = Active
DI362doc 10363Remote Sensor Over Temperature 8BITRead0 = Inactive; 1 = Active
DI363doc 10364Remote Sensor Over Temperature 9BITRead0 = Inactive; 1 = Active
DI364doc 10365Remote Sensor Over Temperature 10BITRead0 = Inactive; 1 = Active
DI365doc 10366Remote Sensor Under Temperature 1BITRead0 = Inactive; 1 = Active
DI366doc 10367Remote Sensor Under Temperature 2BITRead0 = Inactive; 1 = Active
DI367doc 10368Remote Sensor Under Temperature 3BITRead0 = Inactive; 1 = Active
DI368doc 10369Remote Sensor Under Temperature 4BITRead0 = Inactive; 1 = Active
DI369doc 10370Remote Sensor Under Temperature 5BITRead0 = Inactive; 1 = Active
DI370doc 10371Remote Sensor Under Temperature 6BITRead0 = Inactive; 1 = Active
DI371doc 10372Remote Sensor Under Temperature 7BITRead0 = Inactive; 1 = Active
DI372doc 10373Remote Sensor Under Temperature 8BITRead0 = Inactive; 1 = Active
DI373doc 10374Remote Sensor Under Temperature 9BITRead0 = Inactive; 1 = Active
DI374doc 10375Remote Sensor Under Temperature 10BITRead0 = Inactive; 1 = Active
DI375doc 10376Remote Sensor Issue 1BITRead0 = Inactive; 1 = Active
DI376doc 10377Remote Sensor Issue 2BITRead0 = Inactive; 1 = Active
DI377doc 10378Remote Sensor Issue 3BITRead0 = Inactive; 1 = Active
DI378doc 10379Remote Sensor Issue 4BITRead0 = Inactive; 1 = Active
DI379doc 10380Remote Sensor Issue 5BITRead0 = Inactive; 1 = Active
DI380doc 10381Remote Sensor Issue 6BITRead0 = Inactive; 1 = Active
DI381doc 10382Remote Sensor Issue 7BITRead0 = Inactive; 1 = Active
DI382doc 10383Remote Sensor Issue 8BITRead0 = Inactive; 1 = Active
DI383doc 10384Remote Sensor Issue 9BITRead0 = Inactive; 1 = Active
DI384doc 10385Remote Sensor Issue 10BITRead0 = Inactive; 1 = Active
DI385doc 10386Air Economizer Emergency OverrideBITRead0 = Inactive; 1 = Active
DI386doc 10387Air Economizer Reduced AirflowBITRead0 = Inactive; 1 = Active
DI387doc 10388Temperature Control Sensor IssueBITRead0 = Inactive; 1 = Active
DI487doc 10488EEV Unspecified General EventBITRead0 = Inactive; 1 = Active
DI488doc 10489Static Pressure Sensor IssueBITRead0 = Inactive; 1 = Active
DI489doc 10490High Static PressureBITRead0 = Inactive; 1 = Active
DI490doc 10491Low Static PressureBITRead0 = Inactive; 1 = Active
DI491doc 10492Pump Unspecified General EventBITRead0 = Inactive; 1 = Active
DI492doc 10493Condenser Unit Unspecified General EventBITRead0 = Inactive; 1 = Active
DI493doc 10494Condenser Circuit Unspecified General EventBITRead0 = Inactive; 1 = Active
IR99doc 30100System Operating StateUINT16Read0 = off; 1 = on; 2 = standby
IR101doc 30102System StatusUINT16Read1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation
IR102doc 30103Fan SpeedUINT16%Read
IR103doc 30104Compressor UtilizationUINT16%Read
IR104doc 30105Free Cooling Valve Open PositionUINT16%Read
IR105doc 30106Reheat UtilizationUINT16%Read
IR106doc 30107Humidifier UtilizationUINT16%Read
IR107doc 30108Dehumidifier UtilizationUINT16%Read
IR108doc 30109Free Cooling StatusUINT16Read0 = off; 2 = on; 3 = No Support
IR109doc 30110Return Air TemperatureINT16× 0.1deg CRead
IR111doc 30112Supply Air TemperatureINT16× 0.1deg CRead
IR112doc 30113Supply Air Temperature Set PointINT16deg CRead
IR114doc 30115Free Cooling Fluid TemperatureINT16× 0.1deg CRead
IR115doc 30116Ext Air Sensor A TemperatureINT16× 0.1deg CRead
IR116doc 30117Ext Air Sensor B TemperatureINT16× 0.1deg CRead
IR117doc 30118Ext Air Sensor C TemperatureINT16× 0.1deg CRead
IR118doc 30119Dig Scroll Comp Discharge Temp 1INT16deg CRead
IR119doc 30120Dig Scroll Comp Discharge Temp 2INT16deg CRead
IR129doc 30130Return HumidityUINT16× 0.1% RHRead
IR131doc 30132Ext Air Sensor A HumidityUINT16× 0.1% RHRead
IR132doc 30133Ext Air Sensor B HumidityUINT16× 0.1% RHRead
IR133doc 30134Ext Air Sensor C HumidityUINT16× 0.1% RHRead
IR150doc 30151Today's High Air TemperatureINT16× 0.1deg CRead
IR152doc 30153Today's Low Air TemperatureINT16× 0.1deg CRead
IR154doc 30155Today's High HumidityUINT16× 0.1% RHRead
IR156doc 30157Today's Low HumidityUINT16× 0.1% RHRead
IR256doc 30257Server ClassUINT16Read1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU
IR268doc 30269Fixed Compressor State 1UINT16Read0 = off; 1 = on
IR269doc 30270Fixed Compressor State 2UINT16Read0 = off; 1 = on
IR270doc 30271Compressor Capacity Control State 1UINT16Read0 = off; 1 = on
IR271doc 30272Compressor Capacity Control State 2UINT16Read0 = off; 1 = on
IR274doc 30275Analog Input Reading 1UINT16× 0.01Read
IR275doc 30276Analog Input Reading 2UINT16× 0.01Read
IR276doc 30277Analog Input Reading 3UINT16× 0.01Read
IR277doc 30278Analog Input Reading 4UINT16× 0.01Read
IR279doc 30280System Control ModeUINT16Read0 = Internal (Auto); 1 = External (Manual)
IR280doc 30281System Operating State ReasonUINT16Read0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display
IR281doc 30282Maintenance RampUINT16%Read
IR282doc 30283Calculated Next Maintenance MonthUINT16Read
IR283doc 30284Calculated Next Maintenance YearUINT16Read
IR284doc 30285Hot Water / Hot Gas Valve Open PositionUINT16%Read
IR285doc 30286Maintenance Tracking StateUINT16Read0 = off; 1 = on
IR483doc 30484Outside Air TemperatureINT16× 0.1deg CRead
IR485doc 30486Ext Air Sensor A Dew Point TempINT16× 0.1deg CRead
IR498doc 30499Adjusted HumidityUINT16× 0.1% RHRead
IR499doc 30500Return Dew PointINT16× 0.1deg CRead
IR500doc 30501Actual Air Temperature Set PointINT16× 0.1deg CRead
IR501doc 30502Actual Humidity Set PointUINT16% RHRead
IR506doc 30507Remote Sensor Average TemperatureINT16× 0.1deg CRead
IR507doc 30508Remote Sensor Maximum TemperatureINT16× 0.1deg CRead
IR508doc 30509Remote Sensor System Average TemperatureINT16× 0.1deg CRead
IR509doc 30510Remote Sensor System Maximum TemperatureINT16× 0.1deg CRead
IR550doc 30551Remote Sensor Temperature 1INT16× 0.1deg CRead
IR551doc 30552Remote Sensor Temperature 2INT16× 0.1deg CRead
IR552doc 30553Remote Sensor Temperature 3INT16× 0.1deg CRead
IR553doc 30554Remote Sensor Temperature 4INT16× 0.1deg CRead
IR554doc 30555Remote Sensor Temperature 5INT16× 0.1deg CRead
IR555doc 30556Remote Sensor Temperature 6INT16× 0.1deg CRead
IR556doc 30557Remote Sensor Temperature 7INT16× 0.1deg CRead
IR557doc 30558Remote Sensor Temperature 8INT16× 0.1deg CRead
IR558doc 30559Remote Sensor Temperature 9INT16× 0.1deg CRead
IR559doc 30560Remote Sensor Temperature 10INT16× 0.1deg CRead
IR560doc 30561Air Economizer AvailabilityUINT16Read0 = Not Available; 1 = Available
IR563doc 30564Cooling CapacityUINT16%Read
IR564doc 30565Cooling Control TemperatureINT16× 0.1deg CRead
IR565doc 30566Fan Speed Control TemperatureINT16× 0.1deg CRead
IR667doc 30668Digital Scroll Compressor Loading 1UINT16%Read
IR668doc 30669Digital Scroll Compressor Loading 2UINT16%Read
IR672doc 30673Unit Static PressureUINT16PaRead
IR673doc 30674System Static PressureUINT16PaRead
IR674doc 30675Condenser Low Noise Mode StateUINT16Read0 = Inactive; 1 = Active (Interval); 2 = Active (Full Day)
HR16doc 40017Free Cooling Internal Control ModeUINT16Read/write0 = Disabled; 1 = Contact; 2 = Value
HR17doc 40018Humidity Proportional Control TypeUINT16Read/write0 = Relative; 1 = Compensated; 2 = Predictive
HR18doc 40019Fan Speed Maximum Set PointUINT16%Read/write
HR19doc 40020Supply Air Temperature Set PointINT16deg CRead/write
HR20doc 40021Free Cooling Internal Temperature DeltaINT16× 0.1deg CRead/write
HR21doc 40022Minimum Chilled Water Temp Set PointINT16× 0.1deg CRead/write
HR22doc 40023Air Temperature Set PointINT16× 0.1deg CRead/write
HR23doc 40024Air Temperature Proportional BandINT16× 0.1deg CRead/write
HR24doc 40025Air Temperature Dead BandINT16× 0.1deg CRead/write
HR25doc 40026Air Temperature Control Integration TimeUINT16× 0.1minRead/write
HR26doc 40027Humidity Set PointUINT16% RHRead/write
HR27doc 40028Humidity Proportional BandUINT16% RHRead/write
HR28doc 40029Humidity Proportional Control Integration TimeUINT16minRead/write
HR29doc 40030Humidity Dead BandUINT16× 0.1% RHRead/write
HR30doc 40031Auto Restart DelayUINT16secRead/write
HR32doc 40033Air Temperature Control TypeUINT16Read/write0 = Proportional; 1 = Prop+Integral; 3 = Intelligent
HR44doc 40045BMS Timeout PeriodUINT16minRead/write
HR49doc 40050Return Air Over Temp ThresholdINT16× 0.1deg CRead/write
HR50doc 40051Return Air Under Temp ThresholdINT16× 0.1deg CRead/write
HR51doc 40052Ext Air Sensor A Over Temp ThresholdINT16× 0.1deg CRead/write
HR52doc 40053Ext Air Sensor A Under Temp ThresholdINT16× 0.1deg CRead/write
HR53doc 40054High Return Humidity ThresholdUINT16× 0.1% RHRead/write
HR54doc 40055Low Return Humidity ThresholdUINT16× 0.1% RHRead/write
HR55doc 40056Ext Air Sensor A High Humidity ThresholdUINT16× 0.1% RHRead/write
HR56doc 40057Ext Air Sensor A Low Humidity ThresholdUINT16× 0.1% RHRead/write
HR69doc 40070Fan Hours ThresholdUINT16hrRead/write
HR70doc 40071Compressor Hours Threshold 1UINT16hrRead/write
HR71doc 40072Compressor Hours Threshold 2UINT16hrRead/write
HR72doc 40073Humidifier Hours ThresholdUINT16hrRead/write
HR73doc 40074Dehumidifier Hours ThresholdUINT16hrRead/write
HR74doc 40075Free Cooling Valve Hours ThresholdUINT16hrRead/write
HR75doc 40076Electric Reheater Hours Threshold 1UINT16hrRead/write
HR76doc 40077Electric Reheater Hours Threshold 2UINT16hrRead/write
HR77doc 40078Electric Reheater Hours Threshold 3UINT16hrRead/write
HR78doc 40079Hot Water / Hot Gas Valve Hours ThresholdUINT16hrRead/write
HR140doc 40141Fan HoursUINT16hrRead/write
HR141doc 40142Compressor Hours 1UINT16hrRead/write
HR142doc 40143Compressor Hours 2UINT16hrRead/write
HR143doc 40144Humidifier HoursUINT16hrRead/write
HR144doc 40145Dehumidifier HoursUINT16hrRead/write
HR145doc 40146Free Cooling Valve HoursUINT16hrRead/write
HR146doc 40147Electric Reheater Hours 1UINT16hrRead/write
HR147doc 40148Electric Reheater Hours 2UINT16hrRead/write
HR148doc 40149Electric Reheater Hours 3UINT16hrRead/write
HR149doc 40150Hot Water / Hot Gas Valve HoursUINT16hrRead/write
HR261doc 40262Supply Air Temperature Sensor ControlUINT16Read/write0 = Disabled; 1 = Limit; 2 = Control; 3 = Temp Only
HR262doc 40263Return Air Temperature Set PointINT16deg CRead/write
HR263doc 40264Return Humidity Set PointUINT16% RHRead/write
HR272doc 40273Infrared Humidifier Flush RateUINT16%Read/write
HR273doc 40274Fan Control ModeUINT16Read/write0 = Auto; 1 = Manual; 2 = Economy; 4 = Delta
HR286doc 40287Customer Input 1 - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR287doc 40288Customer Input 1 - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR288doc 40289Customer Input 2 - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR289doc 40290Customer Input 2 - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR290doc 40291Customer Input 3 - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR291doc 40292Customer Input 3 - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR292doc 40293Customer Input 4 - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR293doc 40294Customer Input 4 - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR294doc 40295Ext Free Cooling Lockout - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR295doc 40296Ext Free Cooling Lockout - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR296doc 40297Ext Condenser Pump High Water - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR297doc 40298Ext Condenser Pump High Water - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR298doc 40299Ext Standby Glycol Pump On - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR299doc 40300Ext Standby Glycol Pump On - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR300doc 40301Ext Standby Unit On - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR301doc 40302Ext Standby Unit On - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR302doc 40303Ext Humidifier Lockout - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR303doc 40304Ext Humidifier Lockout - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR304doc 40305Ext Loss of Flow - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR305doc 40306Ext Loss of Flow - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR306doc 40307Ext Over Temperature - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR307doc 40308Ext Over Temperature - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR308doc 40309Ext Reheat Lockout - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR309doc 40310Ext Reheat Lockout - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR310doc 40311High Power Shutdown - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR311doc 40312High Power Shutdown - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR312doc 40313Humidifier Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR313doc 40314Humidifier Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR314doc 40315Master Unit Communication Lost - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR315doc 40316Master Unit Communication Lost - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR316doc 40317Service Required - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR317doc 40318Service Required - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR318doc 40319Shutdown - Loss Of Power - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR319doc 40320Shutdown - Loss Of Power - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR320doc 40321Smoke Detected - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR321doc 40322Smoke Detected - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR322doc 40323Water Under Floor - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR323doc 40324Water Under Floor - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR324doc 40325Ext Compressor Lockout - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR325doc 40326Ext Compressor Lockout - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR326doc 40327Clogged Air Filter - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR327doc 40328Clogged Air Filter - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR328doc 40329Ext Loss of Air Blower - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR329doc 40330Ext Loss of Air Blower - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR330doc 40331Compressor High Head Pressure - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR331doc 40332Compressor High Head Pressure - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR332doc 40333Compressor High Head Pressure - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR333doc 40334Compressor High Head Pressure - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR334doc 40335Compressor Low Suction Pressure - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR335doc 40336Compressor Low Suction Pressure - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR336doc 40337Compressor Low Suction Pressure - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR337doc 40338Compressor Low Suction Pressure - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR338doc 40339Compressor Pump Down Issue - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR339doc 40340Compressor Pump Down Issue - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR340doc 40341Compressor Pump Down Issue - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR341doc 40342Compressor Pump Down Issue - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR342doc 40343Compressor Short Cycle - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR343doc 40344Compressor Short Cycle - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR344doc 40345Compressor Short Cycle - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR345doc 40346Compressor Short Cycle - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR346doc 40347Compressor Thermal Overload - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR347doc 40348Compressor Thermal Overload - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR348doc 40349Compressor Thermal Overload - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR349doc 40350Compressor Thermal Overload - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR350doc 40351Dig Scroll Comp Discharge Over Temp - Event Ctrl 1UINT16Read/write0 = disabled; 1 = enabled
HR351doc 40352Dig Scroll Comp Discharge Over Temp - Event Ctrl 2UINT16Read/write0 = disabled; 1 = enabled
HR352doc 40353Dig Scroll Comp Discharge Over Temp - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR353doc 40354Dig Scroll Comp Discharge Over Temp - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR354doc 40355Ext Air Sensor A High Humidity - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR355doc 40356Ext Air Sensor A High Humidity - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR356doc 40357Ext Air Sensor A Low Humidity - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR357doc 40358Ext Air Sensor A Low Humidity - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR358doc 40359Ext Air Sensor A Over Temp - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR359doc 40360Ext Air Sensor A Over Temp - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR360doc 40361Ext Air Sensor A Under Temp - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR361doc 40362Ext Air Sensor A Under Temp - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR362doc 40363High Return Humidity - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR363doc 40364High Return Humidity - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR364doc 40365Low Return Humidity - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR365doc 40366Low Return Humidity - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR366doc 40367Return Air Over Temp - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR367doc 40368Return Air Over Temp - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR368doc 40369Return Air Under Temp - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR369doc 40370Return Air Under Temp - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR370doc 40371Fan Hours Exceeded - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR371doc 40372Fan Hours Exceeded - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR372doc 40373Fan Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR373doc 40374Fan Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR374doc 40375Main Fan Overload - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR375doc 40376Main Fan Overload - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR376doc 40377Condenser Issue - Event Control 1UINT16Read/write0 = disabled; 1 = enabled
HR377doc 40378Condenser Issue - Event Control 2UINT16Read/write0 = disabled; 1 = enabled
HR378doc 40379Condenser Issue - Event Type 1UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR379doc 40380Condenser Issue - Event Type 2UINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR380doc 40381System Event Acknowledge/ResetUINT16Read/write2 = Reset; 4 = Acknowledge
HR480doc 40481Air Temperature Control SensorUINT16Read/write0 = Supply; 1 = Remote; 2 = Return
HR481doc 40482Supply Air Over Temp ThresholdINT16× 0.1deg CRead/write
HR482doc 40483Supply Air Under Temp ThresholdINT16× 0.1deg CRead/write
HR484doc 40485Humidity Proportional Control TypeUINT16Read/write0 = Relative; 1 = Compensated; 2 = Predictive; 3 = Dew Point
HR486doc 40487Ext Dew Point Over Temp ThresholdINT16× 0.1deg CRead/write
HR487doc 40488Ext Dew Point Under Temp ThresholdINT16× 0.1deg CRead/write
HR488doc 40489Compressor LockoutUINT16Read/write0 = disabled; 1 = enabled
HR490doc 40491Main Chilled Water ValveUINT16Read/write0 = Valve 1; 1 = Valve 2
HR491doc 40492Reheater LockoutUINT16Read/write0 = disabled; 1 = enabled
HR492doc 40493Humidifier LockoutUINT16Read/write0 = disabled; 1 = enabled
HR493doc 40494Fan Control SensorUINT16Read/write0 = Supply; 1 = Remote; 2 = Return; 3 = Manual
HR494doc 40495Fan Speed Minimum Set PointUINT16%Read/write
HR496doc 40497Fan Speed Temperature Set PointINT16× 0.1deg CRead/write
HR497doc 40498Standby UnitsUINT16Read/write
HR502doc 40503Dew Point Set PointINT16× 0.1deg CRead/write
HR503doc 40504Supply Air Over/Under Temperature - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR504doc 40505Remote Sensor Over Temp ThresholdINT16× 0.1deg CRead/write
HR505doc 40506Remote Sensor Under Temp ThresholdINT16× 0.1deg CRead/write
HR561doc 40562Air Economizer Control SourceUINT16Read/write0 = disabled; 1 = internal; 2 = external
HR562doc 40563Chilled Water Valve HoursUINT16hrRead/write
HR566doc 40567Free Cooling Internal Control ModeUINT16Read/write0 = Disabled; 1 = Contact; 2 = Temperature; 3 = Set Point
HR666doc 40667Humidity Control SensorUINT16Read/write0 = Supply; 1 = Remote; 2 = Return
HR671doc 40672Static Pressure Set PointUINT16PaRead/write
HR675doc 40676Condenser Low Noise Mode Schedule ControlUINT16Read/write0 = disabled; 1 = enabled
HR676doc 40677Condenser Low Noise Mode Max Fan SpeedUINT16%Read/write
HR677doc 40678Condenser Normal Mode Max Fan SpeedUINT16%Read/write
HR678doc 40679Condenser Low Noise Mode - Interval DaysBITMAP16Read/writebit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday
HR679doc 40680Condenser Low Noise Mode - Full DaysBITMAP16Read/writebit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)

What Modbus registers does the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) have?

This map lists 408 registers: 4 coils, 160 discrete inputs, 71 input registers, 173 holding registers. 177 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.

What are the minimum Modbus registers to integrate the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)?

Start with CO 24 System On/Off Control (System on/off control); IR 99 System Operating State (System operating state); IR 101 System Status (System status); IR 109 Return Air Temperature (Return air temperature); IR 111 Supply Air Temperature (Supply air temperature); IR 129 Return Humidity (Return humidity); HR 22 Air Temperature Set Point (Air temperature setpoint); HR 26 Humidity Set Point (Humidity setpoint); IR 102 Fan Speed (Fan speed); HR 380 System Event Acknowledge/Reset (Acknowledge / reset events).

How do I enable Modbus control of the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)?

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

What happens when the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) loses Modbus communication?

Holding register 40045 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS traffic before raising a BMS timeout; what the unit does on timeout is not described in this guide.

Where is the official Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus documentation?

The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.

More Vertiv Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.