Air handler (computer room air conditioner) · Modbus register map
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus register map
Updated 19 November 2026
Liebert DS, CW, HPM, PeX and Challenger units are perimeter computer-room air conditioners (DX and chilled water). With a Liebert IntelliSlot Modbus card in the iCOM controller they appear as a Modbus RTU or Modbus TCP slave. This map covers the unit on/off coil, operating state and status, return/supply air temperatures and humidity, temperature and humidity setpoints and bands, alarm thresholds, fan/cooling/reheat/humidifier utilisation, run hours, remote sensors and the full list of event bits.
This page lists 408 Modbus registers for the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) — 177 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv
- Model
- Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
- Equipment type
- Air handler (computer room air conditioner)
- Registers
- 408 (177 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML
Integration notes: Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Poll input registers 30100-30134 for state, temperatures and humidity, and the 1xxxx discrete inputs for events. Write coil 25 to start/stop the unit and holding registers 40023 / 40027 for the temperature (tenths of deg C) and humidity setpoints.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 24 | System On/Off Control | BIT | System on/off control | Read/write |
| IR 99 | System Operating State | UINT16 | System operating state | Read |
| IR 101 | System Status | UINT16 | System status | Read |
| IR 109 | Return Air Temperature | INT16 | Return air temperature | Read |
| IR 111 | Supply Air Temperature | INT16 | Supply air temperature | Read |
| IR 129 | Return Humidity | UINT16 | Return humidity | Read |
| HR 22 | Air Temperature Set Point | INT16 | Air temperature setpoint | Read/write |
| HR 26 | Humidity Set Point | UINT16 | Humidity setpoint | Read/write |
| IR 102 | Fan Speed | UINT16 | Fan speed | Read |
| HR 380 | System Event Acknowledge/Reset | UINT16 | Acknowledge / reset events | Read/write |
Enable Modbus control & writes
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Communication loss & watchdog
Holding register 40045 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS traffic before raising a BMS timeout; what the unit does on timeout is not described in this guide.
Byte order & addressing
- Modicon numbering: subtract 40001 / 30001 / 10001 for the wire address; coil 25 is wire address 24.
- Temperatures in tenths of deg C have a separate deg F twin register (not listed here); do not mix them up.
- Which points exist depends on the iCOM application firmware (iCOM_PA35, PA70, PA151, PA203 in the guide's Extra Notes).
Network setup
- RS-485 (2-wire) RTU settings for the IntelliSlot 485 card: 9600, 19200 or 38400 baud, 8 data bits, no parity, 1 stop bit.
- Each unit needs a unique Modbus slave address on the RS-485 line.
- For Modbus IP, use the IntelliSlot Modbus IP / BACnet IP card listed for the unit's controller in the guide's compatibility table.
Watch out for
- Supply/return air temperature setpoints at 40020 and 40263 are printed without a scale (whole degrees), while 40023 'Air Temperature Set Point' is in tenths.
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 12doc 13 | Minimum Chilled Water Temp Set Point Enable | BIT | Read/write | 0 = disabled; 1 = enabled | ||||
| CO | 18doc 19 | Return Air Sensor Event Control | BIT | Read/write | 0 = disabled; 1 = enabled | ||||
| CO | 19doc 20 | Ext Air Sensor A Event Control | BIT | Read/write | 0 = disabled; 1 = enabled | ||||
| CO | 24doc 25 | System On/Off Control | BIT | Read/write | 0 = off; 1 = on | ||||
| DI | 8doc 10009 | Ext Reheat Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 9doc 10010 | Ext Humidifier Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 12doc 10013 | Minimum Chilled Water Temp Set Point Enable | BIT | Read | 0 = disabled; 1 = enabled | ||||
| DI | 18doc 10019 | Return Air Sensor Event Control | BIT | Read | 0 = disabled; 1 = enabled | ||||
| DI | 19doc 10020 | Ext Air Sensor A Event Control | BIT | Read | 0 = disabled; 1 = enabled | ||||
| DI | 20doc 10021 | Ext Compressor Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 24doc 10025 | Fan State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 25doc 10026 | Cooling State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 26doc 10027 | Free Cooling State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 27doc 10028 | Hot Water / Hot Gas State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 28doc 10029 | Electric Reheat State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 29doc 10030 | Humidifier State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 30doc 10031 | Dehumidifier State | BIT | Read | 0 = off; 1 = on | ||||
| DI | 33doc 10034 | Main Fan Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 34doc 10035 | Loss of Air Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 35doc 10036 | Ext Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 36doc 10037 | Compressor High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 37doc 10038 | Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 38doc 10039 | Compressor Thermal Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 39doc 10040 | Compressor Pump Down Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 40doc 10041 | Compressor High Head Pressure 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 41doc 10042 | Compressor Low Suction Pressure 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 42doc 10043 | Compressor Thermal Overload 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 43doc 10044 | Compressor Pump Down Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 44doc 10045 | Dig Scroll Comp Over Temp 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 45doc 10046 | Dig Scroll Comp Over Temp 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 46doc 10047 | Smoke Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 47doc 10048 | Water Under Floor | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 48doc 10049 | Humidifier Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 49doc 10050 | Ext Standby Glycol Pump On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 50doc 10051 | Ext Standby Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 51doc 10052 | Ext Condenser Pump High Water | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 52doc 10053 | Return Air Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 54doc 10055 | Ext Loss of Air Blower | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 57doc 10058 | Humidifier Low Water | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 58doc 10059 | Humidifier Over Current | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 59doc 10060 | Ext Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 60doc 10061 | Shutdown - Loss Of Power | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 64doc 10065 | Supply Chilled Water Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 66doc 10067 | Return Air Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 67doc 10068 | Return Air Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 68doc 10069 | High Return Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 69doc 10070 | Low Return Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 70doc 10071 | Ext Air Sensor A Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 71doc 10072 | Ext Air Sensor A Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 72doc 10073 | Ext Air Sensor A High Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 73doc 10074 | Ext Air Sensor A Low Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 74doc 10075 | Supply Chilled Water Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 75doc 10076 | Clogged Air Filter | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 76doc 10077 | Supply Air Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 77doc 10078 | Free Cooling Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 78doc 10079 | Ext Air Sensor A Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 79doc 10080 | Fan Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 80doc 10081 | Compressor Hours Exceeded 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 81doc 10082 | Compressor Hours Exceeded 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 82doc 10083 | Free Cooling Valve Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 83doc 10084 | Electric Reheater Hours Exceeded 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 84doc 10085 | Electric Reheater Hours Exceeded 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 85doc 10086 | Electric Reheater Hours Exceeded 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 86doc 10087 | Hot Water / Hot Gas Valve Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 87doc 10088 | Humidifier Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 88doc 10089 | Dehumidifier Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 90doc 10091 | Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 91doc 10092 | Master Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 93doc 10094 | Unit Code Missing | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 97doc 10098 | Service Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 98doc 10099 | Humidifier Control Board Not Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 103doc 10104 | Customer Input 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 104doc 10105 | Customer Input 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 105doc 10106 | Customer Input 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 106doc 10107 | Customer Input 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 107doc 10108 | Dig Scroll Comp Discharge Temp Sensor Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 108doc 10109 | Dig Scroll Comp Discharge Temp Sensor Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 208doc 10209 | Supply Air Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 209doc 10210 | Supply Air Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 210doc 10211 | Ambient Air Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 211doc 10212 | Compressor Short Cycle 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 212doc 10213 | Compressor Short Cycle 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 213doc 10214 | Ext Free Cooling Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 214doc 10215 | Reheater Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 215doc 10216 | Humidifier Cylinder Worn | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 216doc 10217 | Humidifier Under Current | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 217doc 10218 | Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 218doc 10219 | Condenser TVSS Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 219doc 10220 | Condenser VFD Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 220doc 10221 | Condenser Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 221doc 10222 | Condenser Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 222doc 10223 | BMS Communications Timeout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 223doc 10224 | Digital Output Board Not Detected 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 224doc 10225 | Digital Output Board Not Detected 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 225doc 10226 | Digital Output Board Not Detected 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 226doc 10227 | RAM Battery Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 227doc 10228 | Water Leakage Detector Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 228doc 10229 | External Fire Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 229doc 10230 | Chilled Water Control Valve Failure 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 230doc 10231 | Chilled Water Control Valve Failure 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 231doc 10232 | Unit Off | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 232doc 10233 | Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 233doc 10234 | Unit Partial Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 234doc 10235 | Unit Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 235doc 10236 | High Power Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 236doc 10237 | Unit Standby | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 237doc 10238 | Maintenance Due | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 238doc 10239 | Maintenance Completed | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 239doc 10240 | Compressor Low Pressure Transducer Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 240doc 10241 | Compressor Low Pressure Transducer Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 241doc 10242 | Compressor High Pressure Transducer Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 242doc 10243 | Compressor High Pressure Transducer Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 243doc 10244 | Compressor Capacity Reduced | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 344doc 10345 | Dew Point Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 345doc 10346 | Dew Point Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 346doc 10347 | Ext Dew Point Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 347doc 10348 | Ext Dew Point Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 348doc 10349 | Compressor Superheat Over Threshold 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 349doc 10350 | Compressor Superheat Over Threshold 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 350doc 10351 | Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 351doc 10352 | Remote Sensor Average Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 352doc 10353 | Remote Sensor Average Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 353doc 10354 | Remote Sensor System Average Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 354doc 10355 | Remote Sensor System Average Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 355doc 10356 | Remote Sensor Over Temperature 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 356doc 10357 | Remote Sensor Over Temperature 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 357doc 10358 | Remote Sensor Over Temperature 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 358doc 10359 | Remote Sensor Over Temperature 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 359doc 10360 | Remote Sensor Over Temperature 5 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 360doc 10361 | Remote Sensor Over Temperature 6 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 361doc 10362 | Remote Sensor Over Temperature 7 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 362doc 10363 | Remote Sensor Over Temperature 8 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 363doc 10364 | Remote Sensor Over Temperature 9 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 364doc 10365 | Remote Sensor Over Temperature 10 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 365doc 10366 | Remote Sensor Under Temperature 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 366doc 10367 | Remote Sensor Under Temperature 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 367doc 10368 | Remote Sensor Under Temperature 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 368doc 10369 | Remote Sensor Under Temperature 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 369doc 10370 | Remote Sensor Under Temperature 5 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 370doc 10371 | Remote Sensor Under Temperature 6 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 371doc 10372 | Remote Sensor Under Temperature 7 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 372doc 10373 | Remote Sensor Under Temperature 8 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 373doc 10374 | Remote Sensor Under Temperature 9 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 374doc 10375 | Remote Sensor Under Temperature 10 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 375doc 10376 | Remote Sensor Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 376doc 10377 | Remote Sensor Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 377doc 10378 | Remote Sensor Issue 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 378doc 10379 | Remote Sensor Issue 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 379doc 10380 | Remote Sensor Issue 5 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 380doc 10381 | Remote Sensor Issue 6 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 381doc 10382 | Remote Sensor Issue 7 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 382doc 10383 | Remote Sensor Issue 8 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 383doc 10384 | Remote Sensor Issue 9 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 384doc 10385 | Remote Sensor Issue 10 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 385doc 10386 | Air Economizer Emergency Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 386doc 10387 | Air Economizer Reduced Airflow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 387doc 10388 | Temperature Control Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 487doc 10488 | EEV Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 488doc 10489 | Static Pressure Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 489doc 10490 | High Static Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 490doc 10491 | Low Static Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 491doc 10492 | Pump Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 492doc 10493 | Condenser Unit Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 493doc 10494 | Condenser Circuit Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| IR | 99doc 30100 | System Operating State | UINT16 | Read | 0 = off; 1 = on; 2 = standby | ||||
| IR | 101doc 30102 | System Status | UINT16 | Read | 1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation | ||||
| IR | 102doc 30103 | Fan Speed | UINT16 | % | Read | ||||
| IR | 103doc 30104 | Compressor Utilization | UINT16 | % | Read | ||||
| IR | 104doc 30105 | Free Cooling Valve Open Position | UINT16 | % | Read | ||||
| IR | 105doc 30106 | Reheat Utilization | UINT16 | % | Read | ||||
| IR | 106doc 30107 | Humidifier Utilization | UINT16 | % | Read | ||||
| IR | 107doc 30108 | Dehumidifier Utilization | UINT16 | % | Read | ||||
| IR | 108doc 30109 | Free Cooling Status | UINT16 | Read | 0 = off; 2 = on; 3 = No Support | ||||
| IR | 109doc 30110 | Return Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 111doc 30112 | Supply Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 112doc 30113 | Supply Air Temperature Set Point | INT16 | deg C | Read | ||||
| IR | 114doc 30115 | Free Cooling Fluid Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 115doc 30116 | Ext Air Sensor A Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 116doc 30117 | Ext Air Sensor B Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 117doc 30118 | Ext Air Sensor C Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 118doc 30119 | Dig Scroll Comp Discharge Temp 1 | INT16 | deg C | Read | ||||
| IR | 119doc 30120 | Dig Scroll Comp Discharge Temp 2 | INT16 | deg C | Read | ||||
| IR | 129doc 30130 | Return Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 131doc 30132 | Ext Air Sensor A Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 132doc 30133 | Ext Air Sensor B Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 133doc 30134 | Ext Air Sensor C Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 150doc 30151 | Today's High Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 152doc 30153 | Today's Low Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 154doc 30155 | Today's High Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 156doc 30157 | Today's Low Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 256doc 30257 | Server Class | UINT16 | Read | 1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU | ||||
| IR | 268doc 30269 | Fixed Compressor State 1 | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 269doc 30270 | Fixed Compressor State 2 | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 270doc 30271 | Compressor Capacity Control State 1 | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 271doc 30272 | Compressor Capacity Control State 2 | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 274doc 30275 | Analog Input Reading 1 | UINT16 | × 0.01 | Read | ||||
| IR | 275doc 30276 | Analog Input Reading 2 | UINT16 | × 0.01 | Read | ||||
| IR | 276doc 30277 | Analog Input Reading 3 | UINT16 | × 0.01 | Read | ||||
| IR | 277doc 30278 | Analog Input Reading 4 | UINT16 | × 0.01 | Read | ||||
| IR | 279doc 30280 | System Control Mode | UINT16 | Read | 0 = Internal (Auto); 1 = External (Manual) | ||||
| IR | 280doc 30281 | System Operating State Reason | UINT16 | Read | 0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display | ||||
| IR | 281doc 30282 | Maintenance Ramp | UINT16 | % | Read | ||||
| IR | 282doc 30283 | Calculated Next Maintenance Month | UINT16 | Read | |||||
| IR | 283doc 30284 | Calculated Next Maintenance Year | UINT16 | Read | |||||
| IR | 284doc 30285 | Hot Water / Hot Gas Valve Open Position | UINT16 | % | Read | ||||
| IR | 285doc 30286 | Maintenance Tracking State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 483doc 30484 | Outside Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 485doc 30486 | Ext Air Sensor A Dew Point Temp | INT16 | × 0.1 | deg C | Read | |||
| IR | 498doc 30499 | Adjusted Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 499doc 30500 | Return Dew Point | INT16 | × 0.1 | deg C | Read | |||
| IR | 500doc 30501 | Actual Air Temperature Set Point | INT16 | × 0.1 | deg C | Read | |||
| IR | 501doc 30502 | Actual Humidity Set Point | UINT16 | % RH | Read | ||||
| IR | 506doc 30507 | Remote Sensor Average Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 507doc 30508 | Remote Sensor Maximum Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 508doc 30509 | Remote Sensor System Average Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 509doc 30510 | Remote Sensor System Maximum Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 550doc 30551 | Remote Sensor Temperature 1 | INT16 | × 0.1 | deg C | Read | |||
| IR | 551doc 30552 | Remote Sensor Temperature 2 | INT16 | × 0.1 | deg C | Read | |||
| IR | 552doc 30553 | Remote Sensor Temperature 3 | INT16 | × 0.1 | deg C | Read | |||
| IR | 553doc 30554 | Remote Sensor Temperature 4 | INT16 | × 0.1 | deg C | Read | |||
| IR | 554doc 30555 | Remote Sensor Temperature 5 | INT16 | × 0.1 | deg C | Read | |||
| IR | 555doc 30556 | Remote Sensor Temperature 6 | INT16 | × 0.1 | deg C | Read | |||
| IR | 556doc 30557 | Remote Sensor Temperature 7 | INT16 | × 0.1 | deg C | Read | |||
| IR | 557doc 30558 | Remote Sensor Temperature 8 | INT16 | × 0.1 | deg C | Read | |||
| IR | 558doc 30559 | Remote Sensor Temperature 9 | INT16 | × 0.1 | deg C | Read | |||
| IR | 559doc 30560 | Remote Sensor Temperature 10 | INT16 | × 0.1 | deg C | Read | |||
| IR | 560doc 30561 | Air Economizer Availability | UINT16 | Read | 0 = Not Available; 1 = Available | ||||
| IR | 563doc 30564 | Cooling Capacity | UINT16 | % | Read | ||||
| IR | 564doc 30565 | Cooling Control Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 565doc 30566 | Fan Speed Control Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 667doc 30668 | Digital Scroll Compressor Loading 1 | UINT16 | % | Read | ||||
| IR | 668doc 30669 | Digital Scroll Compressor Loading 2 | UINT16 | % | Read | ||||
| IR | 672doc 30673 | Unit Static Pressure | UINT16 | Pa | Read | ||||
| IR | 673doc 30674 | System Static Pressure | UINT16 | Pa | Read | ||||
| IR | 674doc 30675 | Condenser Low Noise Mode State | UINT16 | Read | 0 = Inactive; 1 = Active (Interval); 2 = Active (Full Day) | ||||
| HR | 16doc 40017 | Free Cooling Internal Control Mode | UINT16 | Read/write | 0 = Disabled; 1 = Contact; 2 = Value | ||||
| HR | 17doc 40018 | Humidity Proportional Control Type | UINT16 | Read/write | 0 = Relative; 1 = Compensated; 2 = Predictive | ||||
| HR | 18doc 40019 | Fan Speed Maximum Set Point | UINT16 | % | Read/write | ||||
| HR | 19doc 40020 | Supply Air Temperature Set Point | INT16 | deg C | Read/write | ||||
| HR | 20doc 40021 | Free Cooling Internal Temperature Delta | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 21doc 40022 | Minimum Chilled Water Temp Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 22doc 40023 | Air Temperature Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 23doc 40024 | Air Temperature Proportional Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 24doc 40025 | Air Temperature Dead Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 25doc 40026 | Air Temperature Control Integration Time | UINT16 | × 0.1 | min | Read/write | |||
| HR | 26doc 40027 | Humidity Set Point | UINT16 | % RH | Read/write | ||||
| HR | 27doc 40028 | Humidity Proportional Band | UINT16 | % RH | Read/write | ||||
| HR | 28doc 40029 | Humidity Proportional Control Integration Time | UINT16 | min | Read/write | ||||
| HR | 29doc 40030 | Humidity Dead Band | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 30doc 40031 | Auto Restart Delay | UINT16 | sec | Read/write | ||||
| HR | 32doc 40033 | Air Temperature Control Type | UINT16 | Read/write | 0 = Proportional; 1 = Prop+Integral; 3 = Intelligent | ||||
| HR | 44doc 40045 | BMS Timeout Period | UINT16 | min | Read/write | ||||
| HR | 49doc 40050 | Return Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 50doc 40051 | Return Air Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 51doc 40052 | Ext Air Sensor A Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 52doc 40053 | Ext Air Sensor A Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 53doc 40054 | High Return Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 54doc 40055 | Low Return Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 55doc 40056 | Ext Air Sensor A High Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 56doc 40057 | Ext Air Sensor A Low Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 69doc 40070 | Fan Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 70doc 40071 | Compressor Hours Threshold 1 | UINT16 | hr | Read/write | ||||
| HR | 71doc 40072 | Compressor Hours Threshold 2 | UINT16 | hr | Read/write | ||||
| HR | 72doc 40073 | Humidifier Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 73doc 40074 | Dehumidifier Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 74doc 40075 | Free Cooling Valve Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 75doc 40076 | Electric Reheater Hours Threshold 1 | UINT16 | hr | Read/write | ||||
| HR | 76doc 40077 | Electric Reheater Hours Threshold 2 | UINT16 | hr | Read/write | ||||
| HR | 77doc 40078 | Electric Reheater Hours Threshold 3 | UINT16 | hr | Read/write | ||||
| HR | 78doc 40079 | Hot Water / Hot Gas Valve Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 140doc 40141 | Fan Hours | UINT16 | hr | Read/write | ||||
| HR | 141doc 40142 | Compressor Hours 1 | UINT16 | hr | Read/write | ||||
| HR | 142doc 40143 | Compressor Hours 2 | UINT16 | hr | Read/write | ||||
| HR | 143doc 40144 | Humidifier Hours | UINT16 | hr | Read/write | ||||
| HR | 144doc 40145 | Dehumidifier Hours | UINT16 | hr | Read/write | ||||
| HR | 145doc 40146 | Free Cooling Valve Hours | UINT16 | hr | Read/write | ||||
| HR | 146doc 40147 | Electric Reheater Hours 1 | UINT16 | hr | Read/write | ||||
| HR | 147doc 40148 | Electric Reheater Hours 2 | UINT16 | hr | Read/write | ||||
| HR | 148doc 40149 | Electric Reheater Hours 3 | UINT16 | hr | Read/write | ||||
| HR | 149doc 40150 | Hot Water / Hot Gas Valve Hours | UINT16 | hr | Read/write | ||||
| HR | 261doc 40262 | Supply Air Temperature Sensor Control | UINT16 | Read/write | 0 = Disabled; 1 = Limit; 2 = Control; 3 = Temp Only | ||||
| HR | 262doc 40263 | Return Air Temperature Set Point | INT16 | deg C | Read/write | ||||
| HR | 263doc 40264 | Return Humidity Set Point | UINT16 | % RH | Read/write | ||||
| HR | 272doc 40273 | Infrared Humidifier Flush Rate | UINT16 | % | Read/write | ||||
| HR | 273doc 40274 | Fan Control Mode | UINT16 | Read/write | 0 = Auto; 1 = Manual; 2 = Economy; 4 = Delta | ||||
| HR | 286doc 40287 | Customer Input 1 - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 287doc 40288 | Customer Input 1 - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 288doc 40289 | Customer Input 2 - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 289doc 40290 | Customer Input 2 - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 290doc 40291 | Customer Input 3 - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 291doc 40292 | Customer Input 3 - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 292doc 40293 | Customer Input 4 - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 293doc 40294 | Customer Input 4 - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 294doc 40295 | Ext Free Cooling Lockout - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 295doc 40296 | Ext Free Cooling Lockout - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 296doc 40297 | Ext Condenser Pump High Water - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 297doc 40298 | Ext Condenser Pump High Water - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 298doc 40299 | Ext Standby Glycol Pump On - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 299doc 40300 | Ext Standby Glycol Pump On - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 300doc 40301 | Ext Standby Unit On - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 301doc 40302 | Ext Standby Unit On - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 302doc 40303 | Ext Humidifier Lockout - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 303doc 40304 | Ext Humidifier Lockout - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 304doc 40305 | Ext Loss of Flow - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 305doc 40306 | Ext Loss of Flow - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 306doc 40307 | Ext Over Temperature - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 307doc 40308 | Ext Over Temperature - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 308doc 40309 | Ext Reheat Lockout - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 309doc 40310 | Ext Reheat Lockout - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 310doc 40311 | High Power Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 311doc 40312 | High Power Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 312doc 40313 | Humidifier Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 313doc 40314 | Humidifier Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 314doc 40315 | Master Unit Communication Lost - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 315doc 40316 | Master Unit Communication Lost - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 316doc 40317 | Service Required - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 317doc 40318 | Service Required - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 318doc 40319 | Shutdown - Loss Of Power - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 319doc 40320 | Shutdown - Loss Of Power - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 320doc 40321 | Smoke Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 321doc 40322 | Smoke Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 322doc 40323 | Water Under Floor - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 323doc 40324 | Water Under Floor - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 324doc 40325 | Ext Compressor Lockout - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 325doc 40326 | Ext Compressor Lockout - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 326doc 40327 | Clogged Air Filter - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 327doc 40328 | Clogged Air Filter - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 328doc 40329 | Ext Loss of Air Blower - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 329doc 40330 | Ext Loss of Air Blower - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 330doc 40331 | Compressor High Head Pressure - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 331doc 40332 | Compressor High Head Pressure - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 332doc 40333 | Compressor High Head Pressure - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 333doc 40334 | Compressor High Head Pressure - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 334doc 40335 | Compressor Low Suction Pressure - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 335doc 40336 | Compressor Low Suction Pressure - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 336doc 40337 | Compressor Low Suction Pressure - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 337doc 40338 | Compressor Low Suction Pressure - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 338doc 40339 | Compressor Pump Down Issue - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 339doc 40340 | Compressor Pump Down Issue - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 340doc 40341 | Compressor Pump Down Issue - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 341doc 40342 | Compressor Pump Down Issue - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 342doc 40343 | Compressor Short Cycle - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 343doc 40344 | Compressor Short Cycle - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 344doc 40345 | Compressor Short Cycle - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 345doc 40346 | Compressor Short Cycle - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 346doc 40347 | Compressor Thermal Overload - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 347doc 40348 | Compressor Thermal Overload - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 348doc 40349 | Compressor Thermal Overload - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 349doc 40350 | Compressor Thermal Overload - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 350doc 40351 | Dig Scroll Comp Discharge Over Temp - Event Ctrl 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 351doc 40352 | Dig Scroll Comp Discharge Over Temp - Event Ctrl 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 352doc 40353 | Dig Scroll Comp Discharge Over Temp - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 353doc 40354 | Dig Scroll Comp Discharge Over Temp - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 354doc 40355 | Ext Air Sensor A High Humidity - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 355doc 40356 | Ext Air Sensor A High Humidity - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 356doc 40357 | Ext Air Sensor A Low Humidity - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 357doc 40358 | Ext Air Sensor A Low Humidity - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 358doc 40359 | Ext Air Sensor A Over Temp - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 359doc 40360 | Ext Air Sensor A Over Temp - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 360doc 40361 | Ext Air Sensor A Under Temp - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 361doc 40362 | Ext Air Sensor A Under Temp - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 362doc 40363 | High Return Humidity - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 363doc 40364 | High Return Humidity - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 364doc 40365 | Low Return Humidity - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 365doc 40366 | Low Return Humidity - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 366doc 40367 | Return Air Over Temp - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 367doc 40368 | Return Air Over Temp - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 368doc 40369 | Return Air Under Temp - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 369doc 40370 | Return Air Under Temp - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 370doc 40371 | Fan Hours Exceeded - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 371doc 40372 | Fan Hours Exceeded - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 372doc 40373 | Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 373doc 40374 | Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 374doc 40375 | Main Fan Overload - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 375doc 40376 | Main Fan Overload - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 376doc 40377 | Condenser Issue - Event Control 1 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 377doc 40378 | Condenser Issue - Event Control 2 | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 378doc 40379 | Condenser Issue - Event Type 1 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 379doc 40380 | Condenser Issue - Event Type 2 | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 380doc 40381 | System Event Acknowledge/Reset | UINT16 | Read/write | 2 = Reset; 4 = Acknowledge | ||||
| HR | 480doc 40481 | Air Temperature Control Sensor | UINT16 | Read/write | 0 = Supply; 1 = Remote; 2 = Return | ||||
| HR | 481doc 40482 | Supply Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 482doc 40483 | Supply Air Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 484doc 40485 | Humidity Proportional Control Type | UINT16 | Read/write | 0 = Relative; 1 = Compensated; 2 = Predictive; 3 = Dew Point | ||||
| HR | 486doc 40487 | Ext Dew Point Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 487doc 40488 | Ext Dew Point Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 488doc 40489 | Compressor Lockout | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 490doc 40491 | Main Chilled Water Valve | UINT16 | Read/write | 0 = Valve 1; 1 = Valve 2 | ||||
| HR | 491doc 40492 | Reheater Lockout | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 492doc 40493 | Humidifier Lockout | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 493doc 40494 | Fan Control Sensor | UINT16 | Read/write | 0 = Supply; 1 = Remote; 2 = Return; 3 = Manual | ||||
| HR | 494doc 40495 | Fan Speed Minimum Set Point | UINT16 | % | Read/write | ||||
| HR | 496doc 40497 | Fan Speed Temperature Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 497doc 40498 | Standby Units | UINT16 | Read/write | |||||
| HR | 502doc 40503 | Dew Point Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 503doc 40504 | Supply Air Over/Under Temperature - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 504doc 40505 | Remote Sensor Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 505doc 40506 | Remote Sensor Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 561doc 40562 | Air Economizer Control Source | UINT16 | Read/write | 0 = disabled; 1 = internal; 2 = external | ||||
| HR | 562doc 40563 | Chilled Water Valve Hours | UINT16 | hr | Read/write | ||||
| HR | 566doc 40567 | Free Cooling Internal Control Mode | UINT16 | Read/write | 0 = Disabled; 1 = Contact; 2 = Temperature; 3 = Set Point | ||||
| HR | 666doc 40667 | Humidity Control Sensor | UINT16 | Read/write | 0 = Supply; 1 = Remote; 2 = Return | ||||
| HR | 671doc 40672 | Static Pressure Set Point | UINT16 | Pa | Read/write | ||||
| HR | 675doc 40676 | Condenser Low Noise Mode Schedule Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 676doc 40677 | Condenser Low Noise Mode Max Fan Speed | UINT16 | % | Read/write | ||||
| HR | 677doc 40678 | Condenser Normal Mode Max Fan Speed | UINT16 | % | Read/write | ||||
| HR | 678doc 40679 | Condenser Low Noise Mode - Interval Days | BITMAP16 | Read/write | bit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday | ||||
| HR | 679doc 40680 | Condenser Low Noise Mode - Full Days | BITMAP16 | Read/write | bit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday |
Notes on this map
- Source: Emerson Network Power / Liebert reference guide SL-28170 (Rev 9). Vertiv does not host this guide publicly; the linked copy is the unaltered PDF on the Contemporary Controls support site.
- Scale column: 'x / 10' means the raw value is tenths (scale 0.1); '-' or blank means no scaling. Some temperature setpoints are printed without a scale while similar points use x / 10; they are transcribed exactly as printed.
- Most temperatures exist twice: once in deg C and once in deg F at a different register. Only the deg C registers are listed here.
- Points that the guide lists with both an input register (3xxxx) and a holding register (4xxxx) are the writable settings; we list the holding register (read/write). The same value can also be read at the matching 3xxxx input register (same offset).
- Signedness is not stated in the guide. Temperature values are listed as INT16 (they can be below zero); everything else as UINT16.
- Points that take two registers (date/time and schedule start/stop times, 32-bit values) are left out because the guide does not state their word order.
- Event/alarm discrete inputs read 1 while the event is active ('Active on Alarm').
- The guide marks each point with the iCOM application software that supports it (PA35, PA70, PA151, PA203). Not every unit has every point.
- Registers 30745, 40733 and 40754 are left out: they sit in the deg F block but the guide labels them deg C, so their unit is unclear.
- The glossary (Table 8) explains each point; descriptions here are kept short.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
What Modbus registers does the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) have?
This map lists 408 registers: 4 coils, 160 discrete inputs, 71 input registers, 173 holding registers. 177 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.
What are the minimum Modbus registers to integrate the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)?
Start with CO 24 System On/Off Control (System on/off control); IR 99 System Operating State (System operating state); IR 101 System Status (System status); IR 109 Return Air Temperature (Return air temperature); IR 111 Supply Air Temperature (Supply air temperature); IR 129 Return Humidity (Return humidity); HR 22 Air Temperature Set Point (Air temperature setpoint); HR 26 Humidity Set Point (Humidity setpoint); IR 102 Fan Speed (Fan speed); HR 380 System Event Acknowledge/Reset (Acknowledge / reset events).
How do I enable Modbus control of the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)?
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
What happens when the Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) loses Modbus communication?
Holding register 40045 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS traffic before raising a BMS timeout; what the unit does on timeout is not described in this guide.
Where is the official Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus) Modbus documentation?
The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.
More Vertiv Modbus register maps
- Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit
Other hvac equipment register maps
- Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Air handler (heat recovery ventilation unit)
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Futura L/M/S from firmware FUA.P.06.71, register list v5.0 (13.10.2025). Futura L+ uses different addresses and is not covered.
Also known as: Futura L, Futura M, Futura S, JABLOTRON FUTURA - Thermostat (room operating unit with sensors)
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
LSTAT-800/801/802 room operating units (all button layouts), user manual version 3.2.8 (document 88085811).
Also known as: L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus
All hvac equipment Modbus register maps →
Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.