Easy Modbus
  1. Home
  2. Modbus register maps
  3. Vertiv (Alber)

Manufacturer

Vertiv (Alber) Modbus register maps

Updated 19 November 2026

6 Vertiv (Alber) models, 1,217 registers in all, each re-typed from Vertiv (Alber)’s own free documentation and checked against it.

6 of 6 shown

Vertiv (Alber): default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
Alber MPM-100 and BDS series battery monitors (Modbus ASCII)ASCII19600 baud, 7N216-bit onlyModicon19
Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)RTU/TCPNot stated8N116-bit onlyModicon176
Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)RTU/TCPNot stated8N116-bit onlyModicon408
Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)RTU/TCPNot stated8N116-bit onlyModicon151
Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)RTU/TCPNot stated8N116-bit onlyModicon221
Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)RTU/TCPNot stated8N116-bit onlyModicon242