- Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Sensor (battery monitoring system) · Modbus register map
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus register map
Updated 17 November 2026
The Alber MPM-100 and BDS monitor stationary battery strings: cell voltages, intercell and intertier resistances, string voltage, currents, temperatures and alarms. They speak Modbus ASCII (7 data bits, 2 stop bits, 9600 baud) with functions 03 and 16; values are 16-bit integers with power-of-two scaling. This map covers representative cell voltage and resistance registers, overall voltage, time-to-go, system status, the firmware command register and configuration basics.
This page lists 19 Modbus registers for the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv (Alber)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv (Alber)
- Model
- Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
- Equipment type
- Sensor (battery monitoring system)
- Registers
- 19 (2 writable)
- Transport
- Modbus ASCII
- Default unit ID
- 1
- Default serial
- 9600 baud, 7N2
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- MPM 1.20+, BDS controller 2.20+
- Also known as
- Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417
Integration notes: Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Poll with Modbus ASCII function 03 at 9600 baud, 7 data bits, no parity, 2 stop bits; read cell voltages from 0000H and string values from 0400H, applying the power-of-two scaling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Cell voltage 1 | UINT16 | Cell voltage 1 | Read |
| HR 1024 | Overall voltage | UINT16 | Overall string voltage | Read |
| HR 1135 | Time-to-go #1 | UINT16 | Time-to-go | Read |
| HR 1540 | System status | BITMAP16 | System status bits | Read |
| HR 1152 | Alarm type of first current alarm | UINT16 | First active alarm | Read |
Enable Modbus control & writes
Modbus ASCII is the monitor's native protocol; set the master to ASCII mode.
Byte order & addressing
- ASCII framing with 7 data bits and 2 stop bits.
- Power-of-two scaling on voltages and resistances.
- Temperatures are sign-magnitude, not two's complement.
Network setup
- 9600 baud, 7 data bits, no parity, 2 stop bits.
- MPM address 01H; BDS string n = address n.
Watch out for
- Alarm reset and tests are commands written to 41542 (data address 0605H).
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 / 0000H | Cell voltage 1 | Raw / 2^10. Cell voltages 1-512 run 40001-40512. | UINT16 | × 0.0009765625 | V | Read | ||
| HR | 1doc 40002 / 0001H | Cell voltage 2 | Raw / 2^10. | UINT16 | × 0.0009765625 | V | Read | ||
| HR | 511doc 40512 / 01FFH | Cell voltage 512 | Raw / 2^10. | UINT16 | × 0.0009765625 | V | Read | ||
| HR | 512doc 40513 / 0200H | Intercell resistance 1 | Raw x 10^3 / 2^13. Intercell 1-48 run 40513-40560. | UINT16 | × 0.1220703125 | µΩ | Read | ||
| HR | 559doc 40560 / 022FH | Intercell resistance 48 | Raw x 10^3 / 2^13. | UINT16 | × 0.1220703125 | µΩ | Read | ||
| HR | 1024doc 41025 / 0400H | Overall voltage | Raw / 2^4. | UINT16 | × 0.0625 | V | Read | ||
| HR | 1038doc 41039 / 040EH | Intertier resistance 1 (MPM) | Raw x 10^3 / 2^11. Intertier 1-8 for MPM run 41039-41046. | UINT16 | × 0.48828125 | µΩ | Read | ||
| HR | 1068doc 41069 / 042CH | Intertier resistance 1 (BDS) | Raw x 10^3 / 2^11. BDS intertier 1-15 run 41069-41083. | UINT16 | × 0.48828125 | µΩ | Read | ||
| HR | 1135doc 41136 / 046FH | Time-to-go #1 | Hours x 100; 720 = 7.2 h. MPM 2.00+. | UINT16 | × 0.01 | h | Read | ||
| HR | 1137doc 41138 / 0471H | Time-to-go #2 | Hours x 100; 720 = 7.2 h. MPM 2.00+. | UINT16 | × 0.01 | h | Read | ||
| HR | 1139doc 41140 / 0473H | Time-to-go #3 | Hours x 100; 720 = 7.2 h. MPM 2.00+. | UINT16 | × 0.01 | h | Read | ||
| HR | 1141doc 41142 / 0475H | Time-to-go #4 | Hours x 100; 720 = 7.2 h. MPM 2.00+. | UINT16 | × 0.01 | h | Read | ||
| HR | 1152doc 41153 / 0480H | Alarm type of first current alarm | Bit 15: 0 = active; bits 9-14 alarm number; bits 0-8 cell/sensor number. | UINT16 | Read | ||||
| HR | 1536doc 41537 / 0600H | String ID | UINT16 | Read | |||||
| HR | 1540doc 41541 / 0604H | System status | BITMAP16 | Read | bit 0 = Hardware problem; bit 1 = Calibration in progress; bit 2 = Memory test finished; bit 3 = In diagnostic mode; bit 4 = Warning; bit 5 = Resistance values logged; bit 6 = Resistance test in progress; bit 7 = Discharge report logged; bit 8 = Discharge in progress; bit 9 = Discharge disabled; bit 10 = Historical alarm logged; bit 11 = DCM communication error; bit 12 = Logging discharge data; bit 13 = Maintenance alarm happened; bit 14 = Critical alarm happened; bit 15 = Alarm disabled | ||||
| HR | 1541doc 41542 / 0605H | Firmware control | Write a command code (function 16). | UINT16 | Read/write | 0 = Start resistance test; 1 = Stop resistance test; 2 = Start firmware scan; 3 = Stop firmware scan; 5 = Load off; 6 = Start diagnostics; 7 = Stop diagnostics; 8 = Reset alarm; 10 = Start load test; 11 = Stop load test; 12 = Start EEPROM test; 16 = Enable alarm; 17 = Disable alarm; 18 = Close alarm contact; 19 = Open alarm contact; 20 = Close charger contact; 21 = Open charger contact | |||
| HR | 1553doc 41554 / 0611H | DIP switch | UINT16 | Read | |||||
| HR | 1598doc 41599 / 063EH | Cell connection | BDS40 only (DCM 2.45+, controller 2.31+). | UINT16 | Read | 128 = Good; 255 = Connection problem | |||
| HR | 1600doc 41601 / 0640H | Total cell number | UINT16 | Read/write |
Notes on this map
- Left out: discharge time (41026), the battery amp-hour rows (41818-41825) and amp-hours remaining #1-#4 (41137, 41139, 41141, 41143). All are marked '(High - Low)' and the list does not explain whether that means two registers or a split value, so size or encoding is not settled.
- Scaling comes from the data transformation table: overall voltage / 2^4, cell voltage / 2^10, intertier resistance x 10^3 / 2^11, intercell resistance x 10^3 / 2^13. Scales are written here as decimals (0.0625, 0.0009765625, 0.48828125, 0.1220703125).
- Left out: currents (scaled by the shunt value or a float-current constant), internal cell resistance (model-dependent RConstant), and temperatures, which use sign-and-magnitude encoding (bit 15 = negative) divided by 128 or by 45 depending on DCM/MPM firmware.
- Only the first, second and last cell voltage and the first/last intercell rows are listed; the rest follow at one register per cell.
- Device address: MPM is 01H; BDS strings 1-16 are 01H-10H.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
What Modbus registers does the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) have?
This map lists 19 registers: 19 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a 4xxxx reference and the hex data address used in the frame: Cell Voltage 1 is reference 40001 at data address 0000H, overall voltage is 41025 at 0400H. Wire address = reference - 40001.
What are the minimum Modbus registers to integrate the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)?
Start with HR 0 Cell voltage 1 (Cell voltage 1); HR 1024 Overall voltage (Overall string voltage); HR 1135 Time-to-go #1 (Time-to-go); HR 1540 System status (System status bits); HR 1152 Alarm type of first current alarm (First active alarm).
How do I enable Modbus control of the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)?
Modbus ASCII is the monitor's native protocol; set the master to ASCII mode.
Where is the official Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus documentation?
The source is Modbus Protocol for MPM-100 and BDS Series Monitors (590-2102-501A/SL-29417/4200-080 Rev 7.05), revision 2015-06-23, published free by Vertiv (Alber) at https://www.vertiv.com/4ab422/globalassets/shared/alber-bds-and-mpm-100-modbus-protocol-.pdf.
More Vertiv (Alber) Modbus register maps
- Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit
Other solar & battery inverters register maps
- Battery charger (industrial float charger, UPS-type DC system)
HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)
HindlePower AT10.1 and AT30 microprocessor-controlled float battery chargers fitted with the AT Series Communications Module (EJ5037-##) set to Modbus, per operating instructions JA0102-04 Rev. 02-2025.
Also known as: AT10.1, AT30, EJ5037, AT Series Communications Module - Battery inverter (off-grid sine wave)
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Morningstar SureSine-300 (115 V and 220 V versions) via the MSC MeterBus adapter; Modbus specification V03 (29 Oct 2008).
Also known as: SureSine, SureSine-300 - Solar inverter
SolarEdge SolarEdge inverters (SunSpec logging)
SolarEdge single-, split- and three-phase inverters with SunSpec enabled (SolarEdge Go/SetApp units, or LCD units on firmware 3.xxxx+); meter 1 at the non-Synergy default base.
Also known as: SE5000, Synergy, SolarEdge SunSpec - Battery inverter (GX gateway for inverter/chargers, batteries and solar chargers)
Victron Energy GX device Modbus-TCP (Cerbo GX, Venus GX, Color Control GX)
Victron GX devices running Venus OS with the Modbus-TCP service enabled; register list version 3.81 (document Rev 54). Core system, VE.Bus inverter/charger, battery, solar charger and ESS registers only.
Also known as: Cerbo GX, Cerbo-S GX, Venus GX, Color Control GX, CCGX, Ekrano GX, Octo GX, MultiPlus-II GX, EasySolar-II GX, Venus OS, dbus-modbustcp - Battery charger (industrial float charger, UPS-type DC system)
HindlePower ATevo battery charger (Modbus communications adapter)
HindlePower ATevo battery chargers with the serial or Ethernet communications adapter set to Modbus, per the ATevo Communications online manual version 1.3.
Also known as: ATevo, ATevo Communications - Solar charge controller (PWM charge / load / diversion)
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Morningstar TriStar TS-45 and TS-60 (non-MPPT) on the RS-232 port; Modbus specification V07 (31 Jan 2020).
Also known as: TS-45, TS-60, TriStar, TriStar PWM
All solar & battery inverters Modbus register maps →
Source: Modbus Protocol for MPM-100 and BDS Series Monitors · 590-2102-501A/SL-29417/4200-080 Rev 7.05 · rev. 2015-06-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.