Sensor (battery monitoring system) · Modbus register map

Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus register map

Updated 17 November 2026

Short answer

The Alber MPM-100 and BDS monitor stationary battery strings: cell voltages, intercell and intertier resistances, string voltage, currents, temperatures and alarms. They speak Modbus ASCII (7 data bits, 2 stop bits, 9600 baud) with functions 03 and 16; values are 16-bit integers with power-of-two scaling. This map covers representative cell voltage and resistance registers, overall voltage, time-to-go, system status, the firmware command register and configuration basics.

This page lists 19 Modbus registers for the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv (Alber)’s own free documentation (linked below) and checked against it.

Manufacturer
Vertiv (Alber)
Model
Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Equipment type
Sensor (battery monitoring system)
Registers
19 (2 writable)
Transport
Modbus ASCII
Default unit ID
1
Default serial
9600 baud, 7N2
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
MPM 1.20+, BDS controller 2.20+
Also known as
Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417
Source document
Modbus Protocol for MPM-100 and BDS Series Monitors · 590-2102-501A/SL-29417/4200-080 Rev 7.05 · rev. 2015-06-23
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)

Integration in brief

Poll with Modbus ASCII function 03 at 9600 baud, 7 data bits, no parity, 2 stop bits; read cell voltages from 0000H and string values from 0400H, applying the power-of-two scaling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Cell voltage 1UINT16Cell voltage 1Read
HR 1024Overall voltageUINT16Overall string voltageRead
HR 1135Time-to-go #1UINT16Time-to-goRead
HR 1540System statusBITMAP16System status bitsRead
HR 1152Alarm type of first current alarmUINT16First active alarmRead

Enable Modbus control & writes

Modbus ASCII is the monitor's native protocol; set the master to ASCII mode.

Byte order & addressing

Network setup

Watch out for

Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

19 of 19 shown
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001 / 0000HCell voltage 1Raw / 2^10. Cell voltages 1-512 run 40001-40512.UINT16× 0.0009765625VRead
HR1doc 40002 / 0001HCell voltage 2Raw / 2^10.UINT16× 0.0009765625VRead
HR511doc 40512 / 01FFHCell voltage 512Raw / 2^10.UINT16× 0.0009765625VRead
HR512doc 40513 / 0200HIntercell resistance 1Raw x 10^3 / 2^13. Intercell 1-48 run 40513-40560.UINT16× 0.1220703125µΩRead
HR559doc 40560 / 022FHIntercell resistance 48Raw x 10^3 / 2^13.UINT16× 0.1220703125µΩRead
HR1024doc 41025 / 0400HOverall voltageRaw / 2^4.UINT16× 0.0625VRead
HR1038doc 41039 / 040EHIntertier resistance 1 (MPM)Raw x 10^3 / 2^11. Intertier 1-8 for MPM run 41039-41046.UINT16× 0.48828125µΩRead
HR1068doc 41069 / 042CHIntertier resistance 1 (BDS)Raw x 10^3 / 2^11. BDS intertier 1-15 run 41069-41083.UINT16× 0.48828125µΩRead
HR1135doc 41136 / 046FHTime-to-go #1Hours x 100; 720 = 7.2 h. MPM 2.00+.UINT16× 0.01hRead
HR1137doc 41138 / 0471HTime-to-go #2Hours x 100; 720 = 7.2 h. MPM 2.00+.UINT16× 0.01hRead
HR1139doc 41140 / 0473HTime-to-go #3Hours x 100; 720 = 7.2 h. MPM 2.00+.UINT16× 0.01hRead
HR1141doc 41142 / 0475HTime-to-go #4Hours x 100; 720 = 7.2 h. MPM 2.00+.UINT16× 0.01hRead
HR1152doc 41153 / 0480HAlarm type of first current alarmBit 15: 0 = active; bits 9-14 alarm number; bits 0-8 cell/sensor number.UINT16Read
HR1536doc 41537 / 0600HString IDUINT16Read
HR1540doc 41541 / 0604HSystem statusBITMAP16Readbit 0 = Hardware problem; bit 1 = Calibration in progress; bit 2 = Memory test finished; bit 3 = In diagnostic mode; bit 4 = Warning; bit 5 = Resistance values logged; bit 6 = Resistance test in progress; bit 7 = Discharge report logged; bit 8 = Discharge in progress; bit 9 = Discharge disabled; bit 10 = Historical alarm logged; bit 11 = DCM communication error; bit 12 = Logging discharge data; bit 13 = Maintenance alarm happened; bit 14 = Critical alarm happened; bit 15 = Alarm disabled
HR1541doc 41542 / 0605HFirmware controlWrite a command code (function 16).UINT16Read/write0 = Start resistance test; 1 = Stop resistance test; 2 = Start firmware scan; 3 = Stop firmware scan; 5 = Load off; 6 = Start diagnostics; 7 = Stop diagnostics; 8 = Reset alarm; 10 = Start load test; 11 = Stop load test; 12 = Start EEPROM test; 16 = Enable alarm; 17 = Disable alarm; 18 = Close alarm contact; 19 = Open alarm contact; 20 = Close charger contact; 21 = Open charger contact
HR1553doc 41554 / 0611HDIP switchUINT16Read
HR1598doc 41599 / 063EHCell connectionBDS40 only (DCM 2.45+, controller 2.31+).UINT16Read128 = Good; 255 = Connection problem
HR1600doc 41601 / 0640HTotal cell numberUINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)

What Modbus registers does the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) have?

This map lists 19 registers: 19 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a 4xxxx reference and the hex data address used in the frame: Cell Voltage 1 is reference 40001 at data address 0000H, overall voltage is 41025 at 0400H. Wire address = reference - 40001.

What are the minimum Modbus registers to integrate the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)?

Start with HR 0 Cell voltage 1 (Cell voltage 1); HR 1024 Overall voltage (Overall string voltage); HR 1135 Time-to-go #1 (Time-to-go); HR 1540 System status (System status bits); HR 1152 Alarm type of first current alarm (First active alarm).

How do I enable Modbus control of the Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)?

Modbus ASCII is the monitor's native protocol; set the master to ASCII mode.

Where is the official Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII) Modbus documentation?

The source is Modbus Protocol for MPM-100 and BDS Series Monitors (590-2102-501A/SL-29417/4200-080 Rev 7.05), revision 2015-06-23, published free by Vertiv (Alber) at https://www.vertiv.com/4ab422/globalassets/shared/alber-bds-and-mpm-100-modbus-protocol-.pdf.

More Vertiv (Alber) Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: Modbus Protocol for MPM-100 and BDS Series Monitors · 590-2102-501A/SL-29417/4200-080 Rev 7.05 · rev. 2015-06-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.