- ATevo battery charger (Modbus communications adapter)
Battery charger (industrial float charger, UPS-type DC system) · Modbus register map
HindlePower ATevo battery charger (Modbus communications adapter) Modbus register map
Updated 17 November 2026
HindlePower's ATevo industrial battery charger supports Modbus RTU on its serial communications adapter and Modbus TCP on the Ethernet adapter. Charger options are coils, about 60 alarm and status flags are discrete inputs, measurements (DC and AC voltages and currents, ground-fault data) are input registers and all setpoints are holding registers, with fixed multipliers. This map covers the published Modbus register set apart from a few values whose sign or units are not stated.
This page lists 114 Modbus registers for the HindlePower ATevo battery charger (Modbus communications adapter) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from HindlePower’s own free documentation (linked below) and checked against it.
- Manufacturer
- HindlePower
- Model
- ATevo battery charger (Modbus communications adapter)
- Registers
- 114 (32 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- ATevo, ATevo Communications
Integration notes: HindlePower ATevo battery charger (Modbus communications adapter)
Assign Modbus to the serial port (or enable Modbus on the Ethernet adapter) and set the Modbus address in MENU > COMMUNICATION, then poll 30006/30007 for DC output voltage and current, the discrete inputs for alarms, and write setpoints to 40001-40021.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 5 | Charger DC output voltage | UINT16 | DC output voltage, 0.1 V | Read |
| IR 6 | Charger DC output current | UINT16 | DC output current, 0.1 A | Read |
| DI 6 | Common alarm relay (CAR) alarm | BIT | Common alarm | Read |
| DI 3 | No AC input alarm | BIT | No AC input alarm | Read |
| DI 2 | DC output failure alarm | BIT | DC output failure | Read |
| HR 0 | Float voltage setpoint | UINT16 | Float voltage setpoint | Read/write |
| HR 13 | Charger mode setting | UINT16 | Charger mode | Read/write |
Enable Modbus control & writes
Serial: MENU > COMMUNICATION > select the port > Protocol = Modbus, then set Address (1-247), Baud rate, Parity, Stop bits and Handshake (set none). Ethernet: MENU > COMMUNICATION > Ethernet setup > Modbus enabled, Port (default 502) and Address.
Byte order & addressing
- Values are scaled integers; divide by the multiplier.
- 32-bit timestamps are low word first.
Network setup
- Handshaking should be set to none; it is never used on RS-485.
- HindlePower recommends leaving the Modbus TCP port at 502.
Watch out for
- Some values are reported only with the matching optional hardware; discrete input 10051 shows whether the AC meter option is installed.
HindlePower ATevo battery charger (Modbus communications adapter) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Float / equalize mode | 0 = float, 1 = equalize. | BIT | Read/write | ||||
| CO | 3doc 00004 | Manual / auto equalize timer | 0 = manual, 1 = auto. | BIT | Read/write | ||||
| CO | 4doc 00005 | HVDC shutdown | 1 = enabled. | BIT | Read/write | ||||
| CO | 6doc 00007 | Battery temperature compensation | 1 = enabled. | BIT | Read/write | ||||
| CO | 7doc 00008 | Battery discharge | 1 = enabled. | BIT | Read/write | ||||
| CO | 8doc 00009 | Remote sense | 1 = enabled. | BIT | Read/write | ||||
| CO | 9doc 00010 | Auto run battery open test | 1 = enabled. | BIT | Read/write | ||||
| CO | 10doc 00011 | Battery open test ran | BIT | Read/write | |||||
| CO | 11doc 00012 | Dynamic current limit | 1 = enabled. | BIT | Read/write | ||||
| CO | 12doc 00013 | Battery temperature probe | 1 = enabled. | BIT | Read/write | ||||
| DI | 0doc 10001 | High voltage DC (HVDC) alarm | 1 = active / true. | BIT | Read | ||||
| DI | 1doc 10002 | Low voltage DC (LVDC) alarm | 1 = active / true. | BIT | Read | ||||
| DI | 2doc 10003 | DC output failure alarm | 1 = active / true. | BIT | Read | ||||
| DI | 3doc 10004 | No AC input alarm | 1 = active / true. | BIT | Read | ||||
| DI | 4doc 10005 | Positive ground fault alarm | 1 = active / true. | BIT | Read | ||||
| DI | 5doc 10006 | Negative ground fault alarm | 1 = active / true. | BIT | Read | ||||
| DI | 6doc 10007 | Common alarm relay (CAR) alarm | 1 = active / true. | BIT | Read | ||||
| DI | 7doc 10008 | HVDC shutdown active | 1 = active / true. | BIT | Read | ||||
| DI | 8doc 10009 | Low voltage AC shutdown (<65 % nominal) | 1 = active / true. | BIT | Read | ||||
| DI | 9doc 10010 | Forced load sharing enabled | 1 = active / true. | BIT | Read | ||||
| DI | 10doc 10011 | Temperature compensation enabled | 1 = active / true. | BIT | Read | ||||
| DI | 11doc 10012 | Defective temperature probe | 1 = active / true. | BIT | Read | ||||
| DI | 12doc 10013 | Equalize mode (0 = float) | 1 = active / true. | BIT | Read | ||||
| DI | 15doc 10016 | Auto-equalize timer enabled | 1 = active / true. | BIT | Read | ||||
| DI | 16doc 10017 | HVDC shutdown enabled | 1 = active / true. | BIT | Read | ||||
| DI | 18doc 10019 | High ripple alarm | 1 = active / true. | BIT | Read | ||||
| DI | 19doc 10020 | End of discharge alarm | 1 = active / true. | BIT | Read | ||||
| DI | 20doc 10021 | Rectifier over temperature alarm | 1 = active / true. | BIT | Read | ||||
| DI | 21doc 10022 | DC breaker open | 1 = active / true. | BIT | Read | ||||
| DI | 22doc 10023 | Open external feedback alarm | 1 = active / true. | BIT | Read | ||||
| DI | 23doc 10024 | Open internal feedback alarm | 1 = active / true. | BIT | Read | ||||
| DI | 24doc 10025 | DC power supply alarm | 1 = active / true. | BIT | Read | ||||
| DI | 25doc 10026 | Open DC output alarm | 1 = active / true. | BIT | Read | ||||
| DI | 26doc 10027 | High level detect alarm | 1 = active / true. | BIT | Read | ||||
| DI | 27doc 10028 | Low level detect alarm | 1 = active / true. | BIT | Read | ||||
| DI | 28doc 10029 | Low AC supply alarm (<75 % nominal) | 1 = active / true. | BIT | Read | ||||
| DI | 29doc 10030 | Current limit active | 1 = active / true. | BIT | Read | ||||
| DI | 30doc 10031 | High level detect shutdown | 1 = active / true. | BIT | Read | ||||
| DI | 31doc 10032 | Alarm relay failure | 1 = active / true. | BIT | Read | ||||
| DI | 32doc 10033 | Rectifier temperature sense failure | 1 = active / true. | BIT | Read | ||||
| DI | 33doc 10034 | Display / UI processor failure | 1 = active / true. | BIT | Read | ||||
| DI | 34doc 10035 | Battery open alarm | 1 = active / true. | BIT | Read | ||||
| DI | 35doc 10036 | Loadshare communication failure | 1 = active / true. | BIT | Read | ||||
| DI | 36doc 10037 | Loadshare independent mode | 1 = active / true. | BIT | Read | ||||
| DI | 37doc 10038 | Loadshare not ready | 1 = active / true. | BIT | Read | ||||
| DI | 38doc 10039 | Battery discharging | 1 = active / true. | BIT | Read | ||||
| DI | 39doc 10040 | Battery overtemp (>= setpoint) | 1 = active / true. | BIT | Read | ||||
| DI | 40doc 10041 | Vgnd imbalance warning | 1 = active / true. | BIT | Read | ||||
| DI | 41doc 10042 | Vgnd imbalance critical | 1 = active / true. | BIT | Read | ||||
| DI | 42doc 10043 | Positive ground fault warning | 1 = active / true. | BIT | Read | ||||
| DI | 43doc 10044 | Negative ground fault warning | 1 = active / true. | BIT | Read | ||||
| DI | 44doc 10045 | Dynamic current limit active | 1 = active / true. | BIT | Read | ||||
| DI | 45doc 10046 | Power board EEROM failure | 1 = active / true. | BIT | Read | ||||
| DI | 46doc 10047 | Main EEROM failure | 1 = active / true. | BIT | Read | ||||
| DI | 47doc 10048 | Level detect digital potentiometer failure | 1 = active / true. | BIT | Read | ||||
| DI | 48doc 10049 | Ambient temperature probe failure | 1 = active / true. | BIT | Read | ||||
| DI | 49doc 10050 | AC breaker open (tripped) | 1 = active / true. | BIT | Read | ||||
| DI | 50doc 10051 | AC meter option installed | 1 = active / true. | BIT | Read | ||||
| DI | 51doc 10052 | AC supply three-phase (0 = single) | 1 = active / true. | BIT | Read | ||||
| DI | 52doc 10053 | Low priority alarm | 1 = active / true. | BIT | Read | ||||
| DI | 53doc 10054 | High priority alarm | 1 = active / true. | BIT | Read | ||||
| DI | 54doc 10055 | Equalize active | 1 = active / true. | BIT | Read | ||||
| DI | 55doc 10056 | AC meter failure | 1 = active / true. | BIT | Read | ||||
| DI | 56doc 10057 | DC short circuit detected | 1 = active / true. | BIT | Read | ||||
| DI | 57doc 10058 | Equalize disabled (cannot be activated) | 1 = active / true. | BIT | Read | ||||
| DI | 58doc 10059 | HH+ sensor registered | 1 = active / true. | BIT | Read | ||||
| DI | 59doc 10060 | HH+ sensor fail | 1 = active / true. | BIT | Read | ||||
| DI | 60doc 10061 | HH+ Vbat probe error | 1 = active / true. | BIT | Read | ||||
| DI | 61doc 10062 | Open battery test in progress | 1 = active / true. | BIT | Read | ||||
| IR | 0doc 30001 | ATevo firmware version major/minor | Major x 100 + minor. | UINT16 | × 0.01 | Read | |||
| IR | 2doc 30003 | ATevo firmware version build | UINT16 | Read | |||||
| IR | 3doc 30004 | Nominal output voltage rating | UINT16 | V | Read | ||||
| IR | 4doc 30005 | Nominal output current rating | UINT16 | A | Read | ||||
| IR | 5doc 30006 | Charger DC output voltage | UINT16 | × 0.1 | V | Read | |||
| IR | 6doc 30007 | Charger DC output current | UINT16 | × 0.1 | A | Read | |||
| IR | 7doc 30008 | Equalize time remaining | UINT16 | min | Read | ||||
| IR | 11doc 30012 | Vgnd imbalance lean | UINT16 | Read | 0 = Less than 5 %; 1 = Positive > 5 %; 2 = Negative > 5 % | ||||
| IR | 12doc 30013 | Positive terminal to ground | Value as reported; units not stated. | UINT16 | Read | ||||
| IR | 13doc 30014 | Negative terminal to ground | Value as reported; units not stated. | UINT16 | Read | ||||
| IR | 14doc 30015 | Vgnd imbalance | UINT16 | × 0.1 | V | Read | |||
| IR | 15doc 30016 | Resistance to ground indicator | UINT16 | Read | 0 = Invalid; 1 = Positive to ground; 2 = Negative to ground | ||||
| IR | 16doc 30017 | Loadshare enabled | UINT16 | Read | 0 = Not enabled; 1 = Primary; 2 = Secondary | ||||
| IR | 17doc 30018-30019 | Battery open test timestamp | Seconds since 2000-01-01; low word first. | UINT32 | CDAB | s | Read | ||
| IR | 20doc 30021 | Heartbeat | UINT16 | Read | |||||
| IR | 21doc 30022 | AC input voltage phase A | UINT16 | × 0.1 | V | Read | |||
| IR | 22doc 30023 | AC input voltage phase B | UINT16 | × 0.1 | V | Read | |||
| IR | 23doc 30024 | AC input voltage phase C | UINT16 | × 0.1 | V | Read | |||
| IR | 24doc 30025 | AC input current phase A | UINT16 | × 0.1 | A | Read | |||
| IR | 25doc 30026 | AC input current phase B | UINT16 | × 0.1 | A | Read | |||
| IR | 26doc 30027 | AC input current phase C | UINT16 | × 0.1 | A | Read | |||
| IR | 27doc 30028 | AC line frequency | UINT16 | × 0.01 | Hz | Read | |||
| IR | 30doc 30031 | Battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 0doc 40001 | Float voltage setpoint | Range per JA5124-02. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 1doc 40002 | Equalize voltage setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 2doc 40003 | Equalize timer setpoint | 1-99 hours. | UINT16 | h | Read/write | |||
| HR | 3doc 40004 | Current limit setpoint | UINT16 | × 0.1 | A | Read/write | |||
| HR | 4doc 40005 | HVDC alarm setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 5doc 40006 | LVDC alarm setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 6doc 40007 | High level detect setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 7doc 40008 | Low level detect setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 8doc 40009 | End of discharge setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 9doc 40010 | AC ripple alarm setpoint | 50-500 mV in 5 mV steps. | UINT16 | mV | Read/write | |||
| HR | 10doc 40011 | Positive ground fault setpoint | 10-40 kOhm. | UINT16 | kOhm | Read/write | |||
| HR | 11doc 40012 | Negative ground fault setpoint | 10-40 kOhm. | UINT16 | kOhm | Read/write | |||
| HR | 12doc 40013 | Battery type | UINT16 | Read/write | 0 = Lead acid; 1 = NiCd | ||||
| HR | 13doc 40014 | Charger mode setting | UINT16 | Read/write | 0 = Shutdown; 1 = Battery open test; 2 = Float; 3 = Timed equalize | ||||
| HR | 14doc 40015 | Ground fault critical setpoint | 1-50 kOhm. | UINT16 | kOhm | Read/write | |||
| HR | 15doc 40016 | Vgnd imbalance warning setpoint | UINT16 | V | Read/write | ||||
| HR | 16doc 40017 | Vgnd imbalance critical setpoint | UINT16 | V | Read/write | ||||
| HR | 17doc 40018 | Battery overtemp setpoint | 30-60 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 18doc 40019 | Battery open test frequency | 1-180 days. | UINT16 | days | Read/write | |||
| HR | 19doc 40020 | Battery open test duration | 1-8 minutes. | UINT16 | min | Read/write | |||
| HR | 20doc 40021 | Battery open test setpoint | UINT16 | V | Read/write | ||||
| HR | 21doc 40022-40023 | Date/time | Seconds since 2000-01-01; 40022 low word, 40023 high word. | UINT32 | CDAB | s | Read/write |
Notes on this map
- This is HindlePower's own manual, published on the manula.com documentation platform (each section is a separate page).
- Scaling: divide the raw value by the Multiplier column (10 for XXX.X values, 100 for XXX.XX). Scale = 1 / multiplier.
- 32-bit timestamps are split into a 'Low' and a 'High' register with the low word in the lower address (CDAB): 30018/30019 battery open test time and 40022/40023 date/time, both seconds since 1 January 2000.
- Left out: 30002 Modbus firmware revision (format 'XXX.xxx.0' cannot be decoded from one register), 30009 (not used), 30010 battery temperature, 30011 rectifier temperature, 30020 ambient temperature, 30029/30030 battery current (the manual does not say whether negative values are sent as signed integers).
- 30013/30014 (positive/negative terminal to ground) are listed without units because the manual gives none.
- Some entries are only reported when the matching optional hardware is installed (e.g. AC meter option for 30022-30028).
- Valid ranges of many setpoints depend on the charger rating; see HindlePower supplement JA5124-02. Writing outside the range returns an exception.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the HindlePower ATevo battery charger (Modbus communications adapter)
What Modbus registers does the HindlePower ATevo battery charger (Modbus communications adapter) have?
This map lists 114 registers: 10 coils, 59 discrete inputs, 23 input registers, 22 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the HindlePower ATevo battery charger (Modbus communications adapter) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables use Modicon references (00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers) and the implementation follows the Modicon PI-MBUS-300 guide, so 30001 is input register 0 on the wire and 40001 holding register 0.
What byte order does the HindlePower ATevo battery charger (Modbus communications adapter) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the HindlePower ATevo battery charger (Modbus communications adapter)?
Start with IR 5 Charger DC output voltage (DC output voltage, 0.1 V); IR 6 Charger DC output current (DC output current, 0.1 A); DI 6 Common alarm relay (CAR) alarm (Common alarm); DI 3 No AC input alarm (No AC input alarm); DI 2 DC output failure alarm (DC output failure); HR 0 Float voltage setpoint (Float voltage setpoint); HR 13 Charger mode setting (Charger mode).
How do I enable Modbus control of the HindlePower ATevo battery charger (Modbus communications adapter)?
Serial: MENU > COMMUNICATION > select the port > Protocol = Modbus, then set Address (1-247), Baud rate, Parity, Stop bits and Handshake (set none). Ethernet: MENU > COMMUNICATION > Ethernet setup > Modbus enabled, Port (default 502) and Address.
Where is the official HindlePower ATevo battery charger (Modbus communications adapter) Modbus documentation?
The source is ATevo Communications (online manual) - Modbus sections 6.1-6.6 (Version 1.3), revision 2026-08-28, published free by HindlePower at https://www.manula.com/manuals/hindlepower-inc/atevo-communications/1.3/en/topic/modbus-holding-registers.
More HindlePower Modbus register maps
Other solar & battery inverters register maps
- Solar charge controller (PWM charge / load / diversion)
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Morningstar TriStar TS-45 and TS-60 (non-MPPT) on the RS-232 port; Modbus specification V07 (31 Jan 2020).
Also known as: TS-45, TS-60, TriStar, TriStar PWM - Sensor (battery monitor for Studer systems)
Studer Innotec BSP battery status processor (via Xcom-485i)
Studer BSP-500 and BSP-1200 battery status processors read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: BSP-500, BSP-1200, BSP500, BSP1200, Xcom-485i - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus - Solar inverter gateway (smart dongle)
Huawei SDongleA smart dongle (Modbus TCP)
Huawei SDongleA WLAN/WLAN-FE/4G dongles with firmware V100R001C00SPC100 or later, per MODBUS Interface Definitions issue 05.
Also known as: SDongleA-01, SDongleA-02-CN, SDongleA-03-EU, SDongleA-03-AU, SDongleA-03-KR, SDongleA-03-JP, SDongleA-03-CN - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioString MPPT solar charge controller (via Xcom-485i)
Studer VarioString VS-70 and VS-120 MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VS-70, VS-120, VarioString VS-120, Xcom-485i
All solar & battery inverters Modbus register maps →
Source: ATevo Communications (online manual) - Modbus sections 6.1-6.6 · Version 1.3 · rev. 2026-08-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.