Battery charger (industrial float charger, UPS-type DC system) · Modbus register map

HindlePower ATevo battery charger (Modbus communications adapter) Modbus register map

Updated 17 November 2026

Short answer

HindlePower's ATevo industrial battery charger supports Modbus RTU on its serial communications adapter and Modbus TCP on the Ethernet adapter. Charger options are coils, about 60 alarm and status flags are discrete inputs, measurements (DC and AC voltages and currents, ground-fault data) are input registers and all setpoints are holding registers, with fixed multipliers. This map covers the published Modbus register set apart from a few values whose sign or units are not stated.

This page lists 114 Modbus registers for the HindlePower ATevo battery charger (Modbus communications adapter) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from HindlePower’s own free documentation (linked below) and checked against it.

Manufacturer
HindlePower
Model
ATevo battery charger (Modbus communications adapter)
Equipment type
Battery charger (industrial float charger, UPS-type DC system)
Registers
114 (32 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
ATevo, ATevo Communications
Source document
ATevo Communications (online manual) - Modbus sections 6.1-6.6 · Version 1.3 · rev. 2026-08-28
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: HindlePower ATevo battery charger (Modbus communications adapter)

Integration in brief

Assign Modbus to the serial port (or enable Modbus on the Ethernet adapter) and set the Modbus address in MENU > COMMUNICATION, then poll 30006/30007 for DC output voltage and current, the discrete inputs for alarms, and write setpoints to 40001-40021.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 5Charger DC output voltageUINT16DC output voltage, 0.1 VRead
IR 6Charger DC output currentUINT16DC output current, 0.1 ARead
DI 6Common alarm relay (CAR) alarmBITCommon alarmRead
DI 3No AC input alarmBITNo AC input alarmRead
DI 2DC output failure alarmBITDC output failureRead
HR 0Float voltage setpointUINT16Float voltage setpointRead/write
HR 13Charger mode settingUINT16Charger modeRead/write

Enable Modbus control & writes

Serial: MENU > COMMUNICATION > select the port > Protocol = Modbus, then set Address (1-247), Baud rate, Parity, Stop bits and Handshake (set none). Ethernet: MENU > COMMUNICATION > Ethernet setup > Modbus enabled, Port (default 502) and Address.

Byte order & addressing

Network setup

Watch out for

HindlePower ATevo battery charger (Modbus communications adapter) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

114 of 114 shown
HindlePower ATevo battery charger (Modbus communications adapter) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Float / equalize mode0 = float, 1 = equalize.BITRead/write
CO3doc 00004Manual / auto equalize timer0 = manual, 1 = auto.BITRead/write
CO4doc 00005HVDC shutdown1 = enabled.BITRead/write
CO6doc 00007Battery temperature compensation1 = enabled.BITRead/write
CO7doc 00008Battery discharge1 = enabled.BITRead/write
CO8doc 00009Remote sense1 = enabled.BITRead/write
CO9doc 00010Auto run battery open test1 = enabled.BITRead/write
CO10doc 00011Battery open test ranBITRead/write
CO11doc 00012Dynamic current limit1 = enabled.BITRead/write
CO12doc 00013Battery temperature probe1 = enabled.BITRead/write
DI0doc 10001High voltage DC (HVDC) alarm1 = active / true.BITRead
DI1doc 10002Low voltage DC (LVDC) alarm1 = active / true.BITRead
DI2doc 10003DC output failure alarm1 = active / true.BITRead
DI3doc 10004No AC input alarm1 = active / true.BITRead
DI4doc 10005Positive ground fault alarm1 = active / true.BITRead
DI5doc 10006Negative ground fault alarm1 = active / true.BITRead
DI6doc 10007Common alarm relay (CAR) alarm1 = active / true.BITRead
DI7doc 10008HVDC shutdown active1 = active / true.BITRead
DI8doc 10009Low voltage AC shutdown (<65 % nominal)1 = active / true.BITRead
DI9doc 10010Forced load sharing enabled1 = active / true.BITRead
DI10doc 10011Temperature compensation enabled1 = active / true.BITRead
DI11doc 10012Defective temperature probe1 = active / true.BITRead
DI12doc 10013Equalize mode (0 = float)1 = active / true.BITRead
DI15doc 10016Auto-equalize timer enabled1 = active / true.BITRead
DI16doc 10017HVDC shutdown enabled1 = active / true.BITRead
DI18doc 10019High ripple alarm1 = active / true.BITRead
DI19doc 10020End of discharge alarm1 = active / true.BITRead
DI20doc 10021Rectifier over temperature alarm1 = active / true.BITRead
DI21doc 10022DC breaker open1 = active / true.BITRead
DI22doc 10023Open external feedback alarm1 = active / true.BITRead
DI23doc 10024Open internal feedback alarm1 = active / true.BITRead
DI24doc 10025DC power supply alarm1 = active / true.BITRead
DI25doc 10026Open DC output alarm1 = active / true.BITRead
DI26doc 10027High level detect alarm1 = active / true.BITRead
DI27doc 10028Low level detect alarm1 = active / true.BITRead
DI28doc 10029Low AC supply alarm (<75 % nominal)1 = active / true.BITRead
DI29doc 10030Current limit active1 = active / true.BITRead
DI30doc 10031High level detect shutdown1 = active / true.BITRead
DI31doc 10032Alarm relay failure1 = active / true.BITRead
DI32doc 10033Rectifier temperature sense failure1 = active / true.BITRead
DI33doc 10034Display / UI processor failure1 = active / true.BITRead
DI34doc 10035Battery open alarm1 = active / true.BITRead
DI35doc 10036Loadshare communication failure1 = active / true.BITRead
DI36doc 10037Loadshare independent mode1 = active / true.BITRead
DI37doc 10038Loadshare not ready1 = active / true.BITRead
DI38doc 10039Battery discharging1 = active / true.BITRead
DI39doc 10040Battery overtemp (>= setpoint)1 = active / true.BITRead
DI40doc 10041Vgnd imbalance warning1 = active / true.BITRead
DI41doc 10042Vgnd imbalance critical1 = active / true.BITRead
DI42doc 10043Positive ground fault warning1 = active / true.BITRead
DI43doc 10044Negative ground fault warning1 = active / true.BITRead
DI44doc 10045Dynamic current limit active1 = active / true.BITRead
DI45doc 10046Power board EEROM failure1 = active / true.BITRead
DI46doc 10047Main EEROM failure1 = active / true.BITRead
DI47doc 10048Level detect digital potentiometer failure1 = active / true.BITRead
DI48doc 10049Ambient temperature probe failure1 = active / true.BITRead
DI49doc 10050AC breaker open (tripped)1 = active / true.BITRead
DI50doc 10051AC meter option installed1 = active / true.BITRead
DI51doc 10052AC supply three-phase (0 = single)1 = active / true.BITRead
DI52doc 10053Low priority alarm1 = active / true.BITRead
DI53doc 10054High priority alarm1 = active / true.BITRead
DI54doc 10055Equalize active1 = active / true.BITRead
DI55doc 10056AC meter failure1 = active / true.BITRead
DI56doc 10057DC short circuit detected1 = active / true.BITRead
DI57doc 10058Equalize disabled (cannot be activated)1 = active / true.BITRead
DI58doc 10059HH+ sensor registered1 = active / true.BITRead
DI59doc 10060HH+ sensor fail1 = active / true.BITRead
DI60doc 10061HH+ Vbat probe error1 = active / true.BITRead
DI61doc 10062Open battery test in progress1 = active / true.BITRead
IR0doc 30001ATevo firmware version major/minorMajor x 100 + minor.UINT16× 0.01Read
IR2doc 30003ATevo firmware version buildUINT16Read
IR3doc 30004Nominal output voltage ratingUINT16VRead
IR4doc 30005Nominal output current ratingUINT16ARead
IR5doc 30006Charger DC output voltageUINT16× 0.1VRead
IR6doc 30007Charger DC output currentUINT16× 0.1ARead
IR7doc 30008Equalize time remainingUINT16minRead
IR11doc 30012Vgnd imbalance leanUINT16Read0 = Less than 5 %; 1 = Positive > 5 %; 2 = Negative > 5 %
IR12doc 30013Positive terminal to groundValue as reported; units not stated.UINT16Read
IR13doc 30014Negative terminal to groundValue as reported; units not stated.UINT16Read
IR14doc 30015Vgnd imbalanceUINT16× 0.1VRead
IR15doc 30016Resistance to ground indicatorUINT16Read0 = Invalid; 1 = Positive to ground; 2 = Negative to ground
IR16doc 30017Loadshare enabledUINT16Read0 = Not enabled; 1 = Primary; 2 = Secondary
IR17doc 30018-30019Battery open test timestampSeconds since 2000-01-01; low word first.UINT32CDABsRead
IR20doc 30021HeartbeatUINT16Read
IR21doc 30022AC input voltage phase AUINT16× 0.1VRead
IR22doc 30023AC input voltage phase BUINT16× 0.1VRead
IR23doc 30024AC input voltage phase CUINT16× 0.1VRead
IR24doc 30025AC input current phase AUINT16× 0.1ARead
IR25doc 30026AC input current phase BUINT16× 0.1ARead
IR26doc 30027AC input current phase CUINT16× 0.1ARead
IR27doc 30028AC line frequencyUINT16× 0.01HzRead
IR30doc 30031Battery voltageUINT16× 0.1VRead
HR0doc 40001Float voltage setpointRange per JA5124-02.UINT16× 0.1VRead/write
HR1doc 40002Equalize voltage setpointUINT16× 0.1VRead/write
HR2doc 40003Equalize timer setpoint1-99 hours.UINT16hRead/write
HR3doc 40004Current limit setpointUINT16× 0.1ARead/write
HR4doc 40005HVDC alarm setpointUINT16× 0.1VRead/write
HR5doc 40006LVDC alarm setpointUINT16× 0.1VRead/write
HR6doc 40007High level detect setpointUINT16× 0.1VRead/write
HR7doc 40008Low level detect setpointUINT16× 0.1VRead/write
HR8doc 40009End of discharge setpointUINT16× 0.1VRead/write
HR9doc 40010AC ripple alarm setpoint50-500 mV in 5 mV steps.UINT16mVRead/write
HR10doc 40011Positive ground fault setpoint10-40 kOhm.UINT16kOhmRead/write
HR11doc 40012Negative ground fault setpoint10-40 kOhm.UINT16kOhmRead/write
HR12doc 40013Battery typeUINT16Read/write0 = Lead acid; 1 = NiCd
HR13doc 40014Charger mode settingUINT16Read/write0 = Shutdown; 1 = Battery open test; 2 = Float; 3 = Timed equalize
HR14doc 40015Ground fault critical setpoint1-50 kOhm.UINT16kOhmRead/write
HR15doc 40016Vgnd imbalance warning setpointUINT16VRead/write
HR16doc 40017Vgnd imbalance critical setpointUINT16VRead/write
HR17doc 40018Battery overtemp setpoint30-60 °C.UINT16× 0.1°CRead/write
HR18doc 40019Battery open test frequency1-180 days.UINT16daysRead/write
HR19doc 40020Battery open test duration1-8 minutes.UINT16minRead/write
HR20doc 40021Battery open test setpointUINT16VRead/write
HR21doc 40022-40023Date/timeSeconds since 2000-01-01; 40022 low word, 40023 high word.UINT32CDABsRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the HindlePower ATevo battery charger (Modbus communications adapter)

What Modbus registers does the HindlePower ATevo battery charger (Modbus communications adapter) have?

This map lists 114 registers: 10 coils, 59 discrete inputs, 23 input registers, 22 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the HindlePower ATevo battery charger (Modbus communications adapter) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables use Modicon references (00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers) and the implementation follows the Modicon PI-MBUS-300 guide, so 30001 is input register 0 on the wire and 40001 holding register 0.

What byte order does the HindlePower ATevo battery charger (Modbus communications adapter) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the HindlePower ATevo battery charger (Modbus communications adapter)?

Start with IR 5 Charger DC output voltage (DC output voltage, 0.1 V); IR 6 Charger DC output current (DC output current, 0.1 A); DI 6 Common alarm relay (CAR) alarm (Common alarm); DI 3 No AC input alarm (No AC input alarm); DI 2 DC output failure alarm (DC output failure); HR 0 Float voltage setpoint (Float voltage setpoint); HR 13 Charger mode setting (Charger mode).

How do I enable Modbus control of the HindlePower ATevo battery charger (Modbus communications adapter)?

Serial: MENU > COMMUNICATION > select the port > Protocol = Modbus, then set Address (1-247), Baud rate, Parity, Stop bits and Handshake (set none). Ethernet: MENU > COMMUNICATION > Ethernet setup > Modbus enabled, Port (default 502) and Address.

Where is the official HindlePower ATevo battery charger (Modbus communications adapter) Modbus documentation?

The source is ATevo Communications (online manual) - Modbus sections 6.1-6.6 (Version 1.3), revision 2026-08-28, published free by HindlePower at https://www.manula.com/manuals/hindlepower-inc/atevo-communications/1.3/en/topic/modbus-holding-registers.

More HindlePower Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: ATevo Communications (online manual) - Modbus sections 6.1-6.6 · Version 1.3 · rev. 2026-08-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.