Solar inverter gateway (smart dongle) · Modbus register map

Huawei SDongleA smart dongle (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The SDongleA is Huawei's smart dongle. It acts as a Modbus TCP server for itself (logical device ID 100) and for the inverters, power meter and other devices it manages (IDs 1-247). This map covers the dongle's own registers: identity, network and traffic status, plant-level input, load, grid and battery power, time settings, management-server and NTP settings, and the reset and device-search commands.

This page lists 46 Modbus registers for the Huawei SDongleA smart dongle (Modbus TCP) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Huawei’s own free documentation (linked below) and checked against it.

Manufacturer
Huawei
Model
SDongleA smart dongle (Modbus TCP)
Equipment type
Solar inverter gateway (smart dongle)
Registers
46 (23 writable)
Transport
Modbus TCP
Default unit ID
100
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
V100R001C00SPC100 or later
Also known as
SDongleA-01, SDongleA-02-CN, SDongleA-03-EU, SDongleA-03-AU, SDongleA-03-KR, SDongleA-03-JP, SDongleA-03-CN
Source document
SDongleA V100R001C00 MODBUS Interface Definitions · Issue 05 · rev. 2022-07-06 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Huawei SDongleA smart dongle (Modbus TCP)

Integration in brief

Connect over Modbus TCP and use logical device ID 100 for the dongle; read plant power at 37498-37517. IDs 1-247 reach the inverters and other devices the dongle manages.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 37498Total input powerUINT32 ABCDTotal PV input powerRead
HR 37500Load powerUINT32 ABCDLoad powerRead
HR 37502Grid powerINT32 ABCDGrid import/export powerRead
HR 37504Total battery powerINT32 ABCDBattery powerRead
HR 37516Total active powerINT32 ABCDTotal active powerRead
HR 37410Dongle typeUINT16Dongle typeRead

Enable Modbus control & writes

The document does not describe an enable step.

Byte order & addressing

Network setup

Watch out for

Huawei SDongleA smart dongle (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Huawei SDongleA smart dongle (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR30015SNDongle serial number.STRING[20]Read
HR30050OS versionSTRING[30]Read
HR30068Protocol versionMain version in the high byte, release version in the low byte.UINT32ABCDRead
HR31200Registration keySTRING[20]Read
HR35104Wireless router signal strength-100 to 0 (weak to strong); 0x7FFF disconnected, 0x7FFE auth failure. Not on 4G model.INT16Read
HR35116Monthly used trafficSDongleA-4G only.UINT32ABCD× 0.01MBRead
HR35118Monthly remaining trafficSDongleA-4G only.UINT32ABCD× 0.01MBRead
HR35120Average daily used trafficSDongleA-4G only.UINT32ABCD× 0.01MBRead
HR35122Traffic statusSDongleA-4G only.UINT16Read0 = Normal; 1 = Warning; 2 = Used up; 255 = No package configured
HR35254IMEISDongleA-4G only.STRING[20]Read
HR35264Mobile signal strength0 (no signal) to 5. SDongleA-4G only.UINT16Read
HR37410Dongle typeUINT16Read0 = N/A; 2 = WLAN; 3 = 4G; 5 = WLAN-FE
HR37411Device search statusUINT16Read0 = Search completed; 1 = Searching; 2 = Search failed
HR37412Device change sequence numberUINT16Read
HR37429Maximum number of devices allowedUINT16Read
HR37430Mobile systeme.g. 2G, 3G, 4G. SDongleA-4G only.STRING[20]Read
HR37440CarrierSDongleA-4G only.STRING[30]Read
HR37498Total input powerPlant PV input power.UINT32ABCD× 0.001kWRead
HR37500Load powerUINT32ABCD× 0.001kWRead
HR37502Grid powerPositive = buying from grid, negative = selling.INT32ABCD× 0.001kWRead
HR37504Total battery powerPositive = charging, negative = discharging.INT32ABCD× 0.001kWRead
HR37516Total active powerINT32ABCD× 0.001kWRead
HR40205ResetWrite 0 to reset the dongle.UINT16Write
HR40500System timeUTC epoch seconds, 2000-01-01 to 2068-12-31.UINT32ABCDsWrite
HR42900Daylight saving timeUINT16Read/write0 = Disabled (default); 1 = Enabled
HR43006Time zone-720 to 840 minutes; default 480 (GMT+8).INT16minRead/write
HR43064Application heartbeat period1-65535, default 30.UINT16minRead/write
HR43065TCP heartbeat period0xFFFF = no heartbeat; 0 = default (3 minutes).UINT16sRead/write
HR43067NMS serverManagement server domain or IP.STRING[60]Read/write
HR43097NMS server port 1Default 27250.UINT16Read/write
HR43098SSL encryptionUINT16Read/write0 = Disabled; 1 = Enabled (default)
HR43099NMS server port 2Default 27251.UINT16Read/write
HR43100Port modeUINT16Read/write0 = Dual ports (default); 1 = Single port
HR43101Registration statusUINT16Read/write0 = Unregistered (default); 1 = Registered
HR43134Unsolicited report interval5-120 in steps of 5; 0xFFFF not supported.UINT16minRead/write
HR43135Reported data record period5 (default), 15, 30 or 60.UINT16minRead/write
HR43311NTP time synchronisationUINT16Read/write0 = Disabled (default); 1 = Enabled
HR43312NTP server addressSTRING[60]Read/write
HR43342NTP server portDefault 123.UINT16Read/write
HR43343NTP sync interval1-1440, default 5.UINT16minRead/write
HR43386SIM card number (ICCID)SDongleA-4G only.STRING[20]Read
HR43430Network modeSDongleA-4G only.UINT16Read/write0 = 4G/3G/2G auto (default); 1 = 3G/2G auto; 2 = 2G only
HR43564Traffic packageSDongleA-4G only.UINT32ABCD× 0.01MBRead/write
HR43566Monthly used traffic (correction)Write to correct the counter. SDongleA-4G only.UINT32ABCD× 0.01MBRead/write
HR45038Connection portUINT16Write1 = Port 1; 2 = Port 2
HR47413Start device searchWrite 0 to start searching for devices.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Huawei SDongleA smart dongle (Modbus TCP)

What Modbus registers does the Huawei SDongleA smart dongle (Modbus TCP) have?

This map lists 46 registers: 46 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Huawei SDongleA smart dongle (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are sent as printed. The read example puts 0x89C0 (35264, the mobile signal-strength register) in the request, so 35264 goes on the wire unchanged.

What byte order does the Huawei SDongleA smart dongle (Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Huawei SDongleA smart dongle (Modbus TCP)?

Start with HR 37498 Total input power (Total PV input power); HR 37500 Load power (Load power); HR 37502 Grid power (Grid import/export power); HR 37504 Total battery power (Battery power); HR 37516 Total active power (Total active power); HR 37410 Dongle type (Dongle type).

How do I enable Modbus control of the Huawei SDongleA smart dongle (Modbus TCP)?

The document does not describe an enable step.

Where is the official Huawei SDongleA smart dongle (Modbus TCP) Modbus documentation?

The source is SDongleA V100R001C00 MODBUS Interface Definitions (Issue 05), revision 2022-07-06. Huawei doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.symcon.de/uploads/short-url/qyJdcRAZ1Ks4UonBY9Ddh3kXA4Y.pdf. It may be an older revision, so check it against the live unit.

More Huawei Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: SDongleA V100R001C00 MODBUS Interface Definitions · Issue 05 · rev. 2022-07-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.