Solar inverter gateway (smart dongle) · Modbus register map
Huawei SDongleA smart dongle (Modbus TCP) Modbus register map
Updated 17 November 2026
The SDongleA is Huawei's smart dongle. It acts as a Modbus TCP server for itself (logical device ID 100) and for the inverters, power meter and other devices it manages (IDs 1-247). This map covers the dongle's own registers: identity, network and traffic status, plant-level input, load, grid and battery power, time settings, management-server and NTP settings, and the reset and device-search commands.
This page lists 46 Modbus registers for the Huawei SDongleA smart dongle (Modbus TCP) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Huawei’s own free documentation (linked below) and checked against it.
- Manufacturer
- Huawei
- Model
- SDongleA smart dongle (Modbus TCP)
- Equipment type
- Solar inverter gateway (smart dongle)
- Registers
- 46 (23 writable)
- Transport
- Modbus TCP
- Default unit ID
- 100
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V100R001C00SPC100 or later
- Also known as
- SDongleA-01, SDongleA-02-CN, SDongleA-03-EU, SDongleA-03-AU, SDongleA-03-KR, SDongleA-03-JP, SDongleA-03-CN
Integration notes: Huawei SDongleA smart dongle (Modbus TCP)
Connect over Modbus TCP and use logical device ID 100 for the dongle; read plant power at 37498-37517. IDs 1-247 reach the inverters and other devices the dongle manages.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 37498 | Total input power | UINT32 ABCD | Total PV input power | Read |
| HR 37500 | Load power | UINT32 ABCD | Load power | Read |
| HR 37502 | Grid power | INT32 ABCD | Grid import/export power | Read |
| HR 37504 | Total battery power | INT32 ABCD | Battery power | Read |
| HR 37516 | Total active power | INT32 ABCD | Total active power | Read |
| HR 37410 | Dongle type | UINT16 | Dongle type | Read |
Enable Modbus control & writes
The document does not describe an enable step.
Byte order & addressing
- Logical device ID 100 addresses the dongle; 1-247 address devices behind it.
- Powers are in kW with gain 1000.
- Grid power is positive when buying, negative when selling.
Network setup
- Read with function 03, write with 06 or 16; function 2B reads device identifiers.
Watch out for
- Several registers are marked as supported only on the 4G dongle.
- Writing 0 to 40205 sends the reset command.
Huawei SDongleA smart dongle (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 30015 | SN | Dongle serial number. | STRING[20] | Read | ||||
| HR | 30050 | OS version | STRING[30] | Read | |||||
| HR | 30068 | Protocol version | Main version in the high byte, release version in the low byte. | UINT32 | ABCD | Read | |||
| HR | 31200 | Registration key | STRING[20] | Read | |||||
| HR | 35104 | Wireless router signal strength | -100 to 0 (weak to strong); 0x7FFF disconnected, 0x7FFE auth failure. Not on 4G model. | INT16 | Read | ||||
| HR | 35116 | Monthly used traffic | SDongleA-4G only. | UINT32 | ABCD | × 0.01 | MB | Read | |
| HR | 35118 | Monthly remaining traffic | SDongleA-4G only. | UINT32 | ABCD | × 0.01 | MB | Read | |
| HR | 35120 | Average daily used traffic | SDongleA-4G only. | UINT32 | ABCD | × 0.01 | MB | Read | |
| HR | 35122 | Traffic status | SDongleA-4G only. | UINT16 | Read | 0 = Normal; 1 = Warning; 2 = Used up; 255 = No package configured | |||
| HR | 35254 | IMEI | SDongleA-4G only. | STRING[20] | Read | ||||
| HR | 35264 | Mobile signal strength | 0 (no signal) to 5. SDongleA-4G only. | UINT16 | Read | ||||
| HR | 37410 | Dongle type | UINT16 | Read | 0 = N/A; 2 = WLAN; 3 = 4G; 5 = WLAN-FE | ||||
| HR | 37411 | Device search status | UINT16 | Read | 0 = Search completed; 1 = Searching; 2 = Search failed | ||||
| HR | 37412 | Device change sequence number | UINT16 | Read | |||||
| HR | 37429 | Maximum number of devices allowed | UINT16 | Read | |||||
| HR | 37430 | Mobile system | e.g. 2G, 3G, 4G. SDongleA-4G only. | STRING[20] | Read | ||||
| HR | 37440 | Carrier | SDongleA-4G only. | STRING[30] | Read | ||||
| HR | 37498 | Total input power | Plant PV input power. | UINT32 | ABCD | × 0.001 | kW | Read | |
| HR | 37500 | Load power | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 37502 | Grid power | Positive = buying from grid, negative = selling. | INT32 | ABCD | × 0.001 | kW | Read | |
| HR | 37504 | Total battery power | Positive = charging, negative = discharging. | INT32 | ABCD | × 0.001 | kW | Read | |
| HR | 37516 | Total active power | INT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 40205 | Reset | Write 0 to reset the dongle. | UINT16 | Write | ||||
| HR | 40500 | System time | UTC epoch seconds, 2000-01-01 to 2068-12-31. | UINT32 | ABCD | s | Write | ||
| HR | 42900 | Daylight saving time | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 43006 | Time zone | -720 to 840 minutes; default 480 (GMT+8). | INT16 | min | Read/write | |||
| HR | 43064 | Application heartbeat period | 1-65535, default 30. | UINT16 | min | Read/write | |||
| HR | 43065 | TCP heartbeat period | 0xFFFF = no heartbeat; 0 = default (3 minutes). | UINT16 | s | Read/write | |||
| HR | 43067 | NMS server | Management server domain or IP. | STRING[60] | Read/write | ||||
| HR | 43097 | NMS server port 1 | Default 27250. | UINT16 | Read/write | ||||
| HR | 43098 | SSL encryption | UINT16 | Read/write | 0 = Disabled; 1 = Enabled (default) | ||||
| HR | 43099 | NMS server port 2 | Default 27251. | UINT16 | Read/write | ||||
| HR | 43100 | Port mode | UINT16 | Read/write | 0 = Dual ports (default); 1 = Single port | ||||
| HR | 43101 | Registration status | UINT16 | Read/write | 0 = Unregistered (default); 1 = Registered | ||||
| HR | 43134 | Unsolicited report interval | 5-120 in steps of 5; 0xFFFF not supported. | UINT16 | min | Read/write | |||
| HR | 43135 | Reported data record period | 5 (default), 15, 30 or 60. | UINT16 | min | Read/write | |||
| HR | 43311 | NTP time synchronisation | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 43312 | NTP server address | STRING[60] | Read/write | |||||
| HR | 43342 | NTP server port | Default 123. | UINT16 | Read/write | ||||
| HR | 43343 | NTP sync interval | 1-1440, default 5. | UINT16 | min | Read/write | |||
| HR | 43386 | SIM card number (ICCID) | SDongleA-4G only. | STRING[20] | Read | ||||
| HR | 43430 | Network mode | SDongleA-4G only. | UINT16 | Read/write | 0 = 4G/3G/2G auto (default); 1 = 3G/2G auto; 2 = 2G only | |||
| HR | 43564 | Traffic package | SDongleA-4G only. | UINT32 | ABCD | × 0.01 | MB | Read/write | |
| HR | 43566 | Monthly used traffic (correction) | Write to correct the counter. SDongleA-4G only. | UINT32 | ABCD | × 0.01 | MB | Read/write | |
| HR | 45038 | Connection port | UINT16 | Write | 1 = Port 1; 2 = Port 2 | ||||
| HR | 47413 | Start device search | Write 0 to start searching for devices. | UINT16 | Write |
Notes on this map
- Huawei publishes this document only behind a support-site login; the copy linked is a forum upload of the unaltered Huawei PDF.
- Data encoding is big-endian for addresses and data, with the leftmost byte sent first, so 32-bit values are read high word first (ABCD).
- Gain is a divisor: power has gain 1000 in kW (so 1 count = 1 W) and traffic gain 100 in MB.
- The read example's text names register 32306 but its frame bytes request 0x89C0 (35264); the frame bytes were used to settle the numbering.
- Left out: Device operation (47402, 11 registers mixing an SN string with a command word), whose layout is better taken from the source directly.
- The TCP port is not stated in this document.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Huawei SDongleA smart dongle (Modbus TCP)
What Modbus registers does the Huawei SDongleA smart dongle (Modbus TCP) have?
This map lists 46 registers: 46 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Huawei SDongleA smart dongle (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are sent as printed. The read example puts 0x89C0 (35264, the mobile signal-strength register) in the request, so 35264 goes on the wire unchanged.
What byte order does the Huawei SDongleA smart dongle (Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Huawei SDongleA smart dongle (Modbus TCP)?
Start with HR 37498 Total input power (Total PV input power); HR 37500 Load power (Load power); HR 37502 Grid power (Grid import/export power); HR 37504 Total battery power (Battery power); HR 37516 Total active power (Total active power); HR 37410 Dongle type (Dongle type).
How do I enable Modbus control of the Huawei SDongleA smart dongle (Modbus TCP)?
The document does not describe an enable step.
Where is the official Huawei SDongleA smart dongle (Modbus TCP) Modbus documentation?
The source is SDongleA V100R001C00 MODBUS Interface Definitions (Issue 05), revision 2022-07-06. Huawei doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.symcon.de/uploads/short-url/qyJdcRAZ1Ks4UonBY9Ddh3kXA4Y.pdf. It may be an older revision, so check it against the live unit.
More Huawei Modbus register maps
Other solar & battery inverters register maps
- Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioString MPPT solar charge controller (via Xcom-485i)
Studer VarioString VS-70 and VS-120 MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VS-70, VS-120, VarioString VS-120, Xcom-485i - Solar inverter
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Fronius Primo/Symo GEN24 (Plus) US variants with a battery configured, SunSpec Model Type int+SF; the US map appends IEEE 1547 models 701-713 after storage model 124.
Also known as: Primo GEN24 Plus US, Symo GEN24 Plus US, Primo GEN24 10.0 208-240, Primo GEN24 3.8 208-240, Primo GEN24 6.0 208-240 - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioTrack MPPT solar charge controller (via Xcom-485i)
Studer VarioTrack VT-40/65/80/HV MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VT-40, VT-65, VT-80, VT-HV, VarioTrack VT-65, Xcom-485i - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0
All solar & battery inverters Modbus register maps →
Source: SDongleA V100R001C00 MODBUS Interface Definitions · Issue 05 · rev. 2022-07-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.