- Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Solar inverter · Modbus register map
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) Modbus register map
Updated 17 November 2026
The US GEN24 map carries the same SunSpec models as the rest-of-world map (common, inverter 101/103, nameplate, settings, status, controls, MPPT 160, storage 124) and then the IEEE 1547-2018 information models 701-713. This map covers the 16-bit values and controls of models 1-124 plus the AC measurement (701), capacity ratings (702), enter-service (703), AC controls (704) and storage capacity (713) blocks; the voltage/frequency trip and curve models 705-712 are left out.
This page lists 236 Modbus registers for the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) — 43 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fronius’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fronius
- Model
- Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
- Equipment type
- Solar inverter
- Registers
- 236 (43 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- Register map archive 1.2.7-2 (bundled with GEN24 firmware 1.36.x); manual 42,0410,2649 rev. 034-28092026.
- Also known as
- Primo GEN24 Plus US, Symo GEN24 Plus US, Primo GEN24 10.0 208-240, Primo GEN24 3.8 208-240, Primo GEN24 6.0 208-240
Integration notes: Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Enable the Modbus TCP server in the inverter web UI with int+SF and Allow Control, then poll unit ID 1. Live data is in models 103 (40070-40109) and 701; power limits can be written either through model 123 or the IEEE 1547 controls in model 704.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40069 | Inverter ID | UINT16 | Inverter model ID (101/103) - confirms int+SF layout | Read |
| HR 40083 | W | INT16 | AC power | Read |
| HR 40084 | W_SF | INT16 | AC power scale factor | Read |
| HR 40107 | St | UINT16 | Operating state | Read |
| HR 40351 | ChaState | UINT16 | Battery state of charge | Read |
| HR 40365 | ChaState_SF | INT16 | SoC scale factor | Read |
| HR 40232 | WMaxLimPct | UINT16 | Active power limit % (model 123) | Read/write |
| HR 40236 | WMaxLim_Ena | UINT16 | Enable the power limit | Read/write |
| HR 40609 | WMaxLimPctEna | UINT16 | IEEE 1547 active power limit enable (model 704) | Read/write |
Enable Modbus control & writes
Inverter web interface > Communication > Modbus: choose TCP Server and/or RTU Server, set SunSpec Model Type int+SF, and activate 'Allow Control' for power, power factor, reactive power and battery commands.
Communication loss & watchdog
Model 123 controls have *_RvrtTms fallback timers (0-28800 s) that restart with every Modbus message; model 124 has InOutWRte_RvrtTms. Model 704 holds reversion setpoints (the *Rvrt registers) that apply when its reversion timer expires; those timers are 32-bit and not included here.
Byte order & addressing
- Off-by-one: SunSpec registers are numbered from 40001; request number minus one.
- Switching float/int+SF changes the address of every model after the inverter model.
- Battery power appears as MPPT inputs 3 (charge) and 4 (discharge).
Network setup
- TCP: inverter unit ID is always 1; port 502 or 1502 selectable in the web UI.
- RTU: set Inverter address (1-247, factory 1), baud and parity in the web UI.
Watch out for
- Query sequentially (at most 2 requests in parallel) with a response timeout of at least 1 s.
- After changing a value of an active mode, re-write the matching enable register with 1.
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40002doc 40003 | Common ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40003doc 40004 | Common L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40004doc 40005 | Mn | Manufacturer name, reads Fronius. | STRING[32] | Read | ||||
| HR | 40020doc 40021 | Md | Inverter model name, e.g. . | STRING[32] | Read | ||||
| HR | 40044doc 40045 | Vr | Inverter software version. | STRING[16] | Read | ||||
| HR | 40052doc 40053 | SN | Serial number (may fall back to a controller ID). | STRING[32] | Read | ||||
| HR | 40068doc 40069 | DA | Modbus device address (unit ID). | UINT16 | Read | ||||
| HR | 40069doc 40070 | Inverter ID | Model ID of this block. | UINT16 | Read | 101 = Single phase; 103 = Three phase | |||
| HR | 40070doc 40071 | Inverter L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40071doc 40072 | A | Total AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40072doc 40073 | AphA | Phase A AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40073doc 40074 | AphB | Phase B AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40074doc 40075 | AphC | Phase C AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40075doc 40076 | A_SF | Scale factor (power of ten) for A. | INT16 | Read | ||||
| HR | 40076doc 40077 | PPVphAB | Line voltage A-B. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40077doc 40078 | PPVphBC | Line voltage B-C. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40078doc 40079 | PPVphCA | Line voltage C-A. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40079doc 40080 | PhVphA | Phase A to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40080doc 40081 | PhVphB | Phase B to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40081doc 40082 | PhVphC | Phase C to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40082doc 40083 | V_SF | Scale factor (power of ten) for V. | INT16 | Read | ||||
| HR | 40083doc 40084 | W | AC active power. | INT16 | × 10^SF (HR 40084) | W | Read | ||
| HR | 40084doc 40085 | W_SF | Scale factor (power of ten) for W. | INT16 | Read | ||||
| HR | 40085doc 40086 | Hz | Grid frequency. | UINT16 | × 10^SF (HR 40086) | Hz | Read | ||
| HR | 40086doc 40087 | Hz_SF | Scale factor (power of ten) for Hz. | INT16 | Read | ||||
| HR | 40087doc 40088 | VA | AC apparent power. | INT16 | × 10^SF (HR 40088) | VA | Read | ||
| HR | 40088doc 40089 | VA_SF | Scale factor (power of ten) for VA. | INT16 | Read | ||||
| HR | 40089doc 40090 | VAr | AC reactive power. | INT16 | × 10^SF (HR 40090) | var | Read | ||
| HR | 40090doc 40091 | VAr_SF | Scale factor (power of ten) for VAr. | INT16 | Read | ||||
| HR | 40091doc 40092 | PF | Power factor. | INT16 | × 10^SF (HR 40092) | Pct | Read | ||
| HR | 40092doc 40093 | PF_SF | Scale factor (power of ten) for PF. | INT16 | Read | ||||
| HR | 40095doc 40096 | WH_SF | Scale factor (power of ten) for WH. | INT16 | Read | ||||
| HR | 40100doc 40101 | DCW | Total DC input power. | INT16 | × 10^SF (HR 40101) | W | Read | ||
| HR | 40101doc 40102 | DCW_SF | Scale factor (power of ten) for DCW. | INT16 | Read | ||||
| HR | 40102doc 40103 | TmpCab | Cabinet temperature. | INT16 | × 10^SF (HR 40106) | C | Read | ||
| HR | 40106doc 40107 | Tmp_SF | Scale factor (power of ten) for Tmp. | INT16 | Read | ||||
| HR | 40107doc 40108 | St | SunSpec operating state. | UINT16 | Read | 1 = Off; 2 = Sleeping (auto shutdown); 3 = Starting; 4 = Producing normally (MPPT); 5 = Throttled (power reduction); 6 = Shutting down; 7 = Fault; 8 = Standby | |||
| HR | 40108doc 40109 | StVnd | Vendor operating state; the map says it mirrors St. | UINT16 | Read | 1 = Off; 2 = Sleeping (auto shutdown); 3 = Starting; 4 = Producing normally (MPPT); 5 = Throttled (power reduction); 6 = Shutting down; 7 = Fault; 8 = Standby | |||
| HR | 40121doc 40122 | Nameplate ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40122doc 40123 | Nameplate L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40123doc 40124 | DERTyp | Device type; this map lists 82 (PV_STOR). | UINT16 | Read | ||||
| HR | 40124doc 40125 | WRtg | Rated continuous active power. | UINT16 | × 10^SF (HR 40125) | W | Read | ||
| HR | 40125doc 40126 | WRtg_SF | Scale factor (power of ten) for WRtg. | INT16 | Read | ||||
| HR | 40126doc 40127 | VARtg | Rated apparent power. | UINT16 | × 10^SF (HR 40127) | VA | Read | ||
| HR | 40127doc 40128 | VARtg_SF | Scale factor (power of ten) for VARtg. | INT16 | Read | ||||
| HR | 40128doc 40129 | VArRtgQ1 | Rated reactive power, quadrant 1. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40129doc 40130 | VArRtgQ2 | Rated reactive power, quadrant 2. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40130doc 40131 | VArRtgQ3 | Rated reactive power, quadrant 3. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40131doc 40132 | VArRtgQ4 | Rated reactive power, quadrant 4. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40132doc 40133 | VArRtg_SF | Scale factor (power of ten) for VArRtg. | INT16 | Read | ||||
| HR | 40133doc 40134 | ARtg | Rated AC current. | UINT16 | × 10^SF (HR 40134) | A | Read | ||
| HR | 40134doc 40135 | ARtg_SF | Scale factor (power of ten) for ARtg. | INT16 | Read | ||||
| HR | 40135doc 40136 | PFRtgQ1 | Minimum power factor capability, quadrant 1. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40136doc 40137 | PFRtgQ2 | Minimum power factor capability, quadrant 2. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40137doc 40138 | PFRtgQ3 | Minimum power factor capability, quadrant 3. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40138doc 40139 | PFRtgQ4 | Minimum power factor capability, quadrant 4. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40139doc 40140 | PFRtg_SF | Scale factor (power of ten) for PFRtg. | INT16 | Read | ||||
| HR | 40140doc 40141 | WHRtg | Rated storage energy. | UINT16 | × 10^SF (HR 40141) | Wh | Read | ||
| HR | 40141doc 40142 | WHRtg_SF | Scale factor (power of ten) for WHRtg. | INT16 | Read | ||||
| HR | 40144doc 40145 | MaxChaRte | Maximum battery charge power. | UINT16 | × 10^SF (HR 40145) | W | Read | ||
| HR | 40145doc 40146 | MaxChaRte_SF | Scale factor (power of ten) for MaxChaRte. | INT16 | Read | ||||
| HR | 40146doc 40147 | MaxDisChaRte | Maximum battery discharge power. | UINT16 | × 10^SF (HR 40147) | W | Read | ||
| HR | 40147doc 40148 | MaxDisChaRte_SF | Scale factor (power of ten) for MaxDisChaRte. | INT16 | Read | ||||
| HR | 40149doc 40150 | Settings ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40150doc 40151 | Settings L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40151doc 40152 | WMax | Maximum active power setting. | UINT16 | × 10^SF (HR 40171) | W | Read | ||
| HR | 40152doc 40153 | VRef | Reference voltage at the grid connection point. | UINT16 | × 10^SF (HR 40172) | V | Read | ||
| HR | 40153doc 40154 | VRefOfs | Voltage offset between grid connection point and inverter. | INT16 | × 10^SF (HR 40173) | V | Read | ||
| HR | 40156doc 40157 | VAMax | Maximum apparent power setting. | UINT16 | × 10^SF (HR 40175) | VA | Read | ||
| HR | 40157doc 40158 | VArMaxQ1 | Reactive power limit, quadrant 1. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40158doc 40159 | VArMaxQ2 | Reactive power limit, quadrant 2. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40159doc 40160 | VArMaxQ3 | Reactive power limit, quadrant 3. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40160doc 40161 | VArMaxQ4 | Reactive power limit, quadrant 4. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40162doc 40163 | PFMinQ1 | Minimum power factor setting, quadrant 1. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40163doc 40164 | PFMinQ2 | Minimum power factor setting, quadrant 2. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40164doc 40165 | PFMinQ3 | Minimum power factor setting, quadrant 3. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40165doc 40166 | PFMinQ4 | Minimum power factor setting, quadrant 4. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40171doc 40172 | WMax_SF | Scale factor (power of ten) for WMax. | INT16 | Read | ||||
| HR | 40172doc 40173 | VRef_SF | Scale factor (power of ten) for VRef. | INT16 | Read | ||||
| HR | 40173doc 40174 | VRefOfs_SF | Scale factor (power of ten) for VRefOfs. | INT16 | Read | ||||
| HR | 40175doc 40176 | VAMax_SF | Scale factor (power of ten) for VAMax. | INT16 | Read | ||||
| HR | 40176doc 40177 | VArMax_SF | Scale factor (power of ten) for VArMax. | INT16 | Read | ||||
| HR | 40178doc 40179 | PFMin_SF | Scale factor (power of ten) for PFMin. | INT16 | Read | ||||
| HR | 40181doc 40182 | Status ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40182doc 40183 | Status L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40183doc 40184 | PVConn | PV inverter connection status bits. | BITMAP16 | Read | bit 0 = Connected; bit 1 = Available; bit 2 = Operating | |||
| HR | 40184doc 40185 | StorConn | Storage connection status bits. | BITMAP16 | Read | bit 0 = Connected; bit 1 = Available; bit 2 = Operating | |||
| HR | 40185doc 40186 | ECPConn | Grid feed-in status. | BITMAP16 | Read | bit 0 = Connected to grid (feeding) | |||
| HR | 40218doc 40219 | TmSrc | STRING[8] | Read | |||||
| HR | 40225doc 40226 | Ris | Insulation resistance. | UINT16 | × 10^SF (HR 40226) | ohms | Read | ||
| HR | 40226doc 40227 | Ris_SF | Scale factor (power of ten) for Ris. | INT16 | Read | ||||
| HR | 40227doc 40228 | Controls ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40228doc 40229 | Controls L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40229doc 40230 | Conn_WinTms | Random start window for connect/disconnect commands. | UINT16 | Secs | Read/write | |||
| HR | 40230doc 40231 | Conn_RvrtTms | Fallback timer for the connect/disconnect command; 0 = no fallback. | UINT16 | Secs | Read/write | |||
| HR | 40231doc 40232 | Conn | Write 0 for standby (no feed-in), 1 to resume feed-in. | UINT16 | Read/write | 0 = Disconnected (standby); 1 = Connected (feeding grid) | |||
| HR | 40232doc 40233 | WMaxLimPct | Active power limit as percent of WMax. | UINT16 | × 10^SF (HR 40250) | % WMax | Read/write | ||
| HR | 40233doc 40234 | WMaxLimPct_WinTms | Random start window for the power limit. | UINT16 | Secs | Read/write | |||
| HR | 40234doc 40235 | WMaxLimPct_RvrtTms | Fallback timer for the power limit; restarts on every Modbus message, 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40235doc 40236 | WMaxLimPct_RmpTms | Ramp time to the new power limit. | UINT16 | Secs | Read/write | |||
| HR | 40236doc 40237 | WMaxLim_Ena | Starts (1) or ends (0) the power limit. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40237doc 40238 | OutPFSet | Fixed power factor setpoint (signed, see sign convention). | INT16 | × 10^SF (HR 40251) | cos() | Read/write | ||
| HR | 40238doc 40239 | OutPFSet_WinTms | Random start window for the power factor setpoint. | UINT16 | Secs | Read/write | |||
| HR | 40239doc 40240 | OutPFSet_RvrtTms | Fallback timer for the power factor setpoint; 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40240doc 40241 | OutPFSet_RmpTms | Ramp time to the new power factor. | UINT16 | Secs | Read/write | |||
| HR | 40241doc 40242 | OutPFSet_Ena | Starts (1) or ends (0) the fixed power factor mode. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40243doc 40244 | VArMaxPct | Fixed reactive power as percent of VArMax. | INT16 | × 10^SF (HR 40252) | % VArMax | Read/write | ||
| HR | 40245doc 40246 | VArPct_WinTms | Random start window for the reactive power setpoint. | UINT16 | Secs | Read/write | |||
| HR | 40246doc 40247 | VArPct_RvrtTms | Fallback timer for the reactive power setpoint; 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40247doc 40248 | VArPct_RmpTms | Ramp time to the new reactive power value. | UINT16 | Secs | Read/write | |||
| HR | 40248doc 40249 | VArPct_Mod | Reactive power limit mode (read-only). | UINT16 | Read | 2 = VAr limit as % of VArMax | |||
| HR | 40249doc 40250 | VArPct_Ena | Starts (1) or ends (0) the fixed reactive power mode. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40250doc 40251 | WMaxLimPct_SF | Scale factor (power of ten) for WMaxLimPct. | INT16 | Read | ||||
| HR | 40251doc 40252 | OutPFSet_SF | Scale factor (power of ten) for OutPFSet. | INT16 | Read | ||||
| HR | 40252doc 40253 | VArPct_SF | Scale factor (power of ten) for VArPct. | INT16 | Read | ||||
| HR | 40253doc 40254 | MPPT ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40254doc 40255 | MPPT L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40255doc 40256 | MPPT DCA_SF | Scale factor (power of ten) for DCA. | INT16 | Read | ||||
| HR | 40256doc 40257 | MPPT DCV_SF | Scale factor (power of ten) for DCV. | INT16 | Read | ||||
| HR | 40257doc 40258 | MPPT DCW_SF | Scale factor (power of ten) for DCW. | INT16 | Read | ||||
| HR | 40258doc 40259 | MPPT DCWH_SF | Scale factor (power of ten) for DCWH. | INT16 | Read | ||||
| HR | 40261doc 40262 | N | Number of DC inputs reported in this model (4 here). | UINT16 | Read | ||||
| HR | 40263doc 40264 | module/1/ID | Input number 1. | UINT16 | Read | ||||
| HR | 40264doc 40265 | module/1/IDStr | Label of DC input 1, reads MPPT 1. | STRING[16] | Read | ||||
| HR | 40272doc 40273 | module/1/DCA | DC current of input 1. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40273doc 40274 | module/1/DCV | DC voltage of input 1. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40274doc 40275 | module/1/DCW | DC power of input 1. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40283doc 40284 | module/2/ID | Input number 2. | UINT16 | Read | ||||
| HR | 40284doc 40285 | module/2/IDStr | Label of DC input 2, reads MPPT 2. | STRING[16] | Read | ||||
| HR | 40292doc 40293 | module/2/DCA | DC current of input 2. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40293doc 40294 | module/2/DCV | DC voltage of input 2. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40294doc 40295 | module/2/DCW | DC power of input 2. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40303doc 40304 | module/3/ID | Input number 3. | UINT16 | Read | ||||
| HR | 40304doc 40305 | module/3/IDStr | Label of DC input 3, reads StCha 3 (battery charge path). | STRING[16] | Read | ||||
| HR | 40312doc 40313 | module/3/DCA | Battery charge current; 0 while discharging. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40313doc 40314 | module/3/DCV | Battery port voltage. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40314doc 40315 | module/3/DCW | Battery charge power; 0 while discharging. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40323doc 40324 | module/4/ID | Input number 4. | UINT16 | Read | ||||
| HR | 40324doc 40325 | module/4/IDStr | Label of DC input 4, reads StDisCha 4 (battery discharge path). | STRING[16] | Read | ||||
| HR | 40332doc 40333 | module/4/DCA | Battery discharge current; 0 while charging. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40333doc 40334 | module/4/DCV | Battery port voltage. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40334doc 40335 | module/4/DCW | Battery discharge power; 0 while charging. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40343doc 40344 | Storage ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40344doc 40345 | Storage L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40345doc 40346 | WChaMax | Reference power for InWRte/OutWRte: max of charge and discharge rating; 0 without battery. | UINT16 | × 10^SF (HR 40361) | W | Read | ||
| HR | 40346doc 40347 | WChaGra | Maximum charge ramp. | UINT16 | × 10^SF (HR 40362) | % WChaMax/sec | Read | ||
| HR | 40347doc 40348 | WDisChaGra | Maximum discharge ramp. | UINT16 | × 10^SF (HR 40362) | % WChaMax/sec | Read | ||
| HR | 40348doc 40349 | StorCtl_Mod | Activates the charge and/or discharge limit window. | BITMAP16 | Read/write | bit 0 = Charge limit (InWRte) active; bit 1 = Discharge limit (OutWRte) active | |||
| HR | 40350doc 40351 | MinRsvPct | Minimum battery reserve, percent of capacity. | UINT16 | × 10^SF (HR 40364) | % WChaMax | Read/write | ||
| HR | 40351doc 40352 | ChaState | Battery state of charge. | UINT16 | × 10^SF (HR 40365) | % AhrRtg | Read | ||
| HR | 40354doc 40355 | ChaSt | Battery operating status. | UINT16 | Read | 1 = Off; 2 = Empty; 3 = Discharging; 4 = Charging; 5 = Full; 6 = Holding; 7 = Testing | |||
| HR | 40355doc 40356 | OutWRte | Discharge limit, percent of WChaMax; negative forces charging. | INT16 | × 10^SF (HR 40368) | % WChaMax | Read/write | ||
| HR | 40356doc 40357 | InWRte | Charge limit, percent of WChaMax; negative forces discharging. | INT16 | × 10^SF (HR 40368) | % WChaMax | Read/write | ||
| HR | 40358doc 40359 | InOutWRte_RvrtTms | Fallback timer for the charge/discharge window (0-28800 s). | UINT16 | Secs | Read/write | |||
| HR | 40360doc 40361 | ChaGriSet | Allows or blocks battery charging from the grid. | UINT16 | Read/write | 0 = PV only (grid charging disabled); 1 = Grid charging enabled | |||
| HR | 40361doc 40362 | WChaMax_SF | Scale factor (power of ten) for WChaMax. | INT16 | Read | ||||
| HR | 40362doc 40363 | WChaDisChaGra_SF | Scale factor (power of ten) for WChaDisChaGra. | INT16 | Read | ||||
| HR | 40364doc 40365 | MinRsvPct_SF | Scale factor (power of ten) for MinRsvPct. | INT16 | Read | ||||
| HR | 40365doc 40366 | ChaState_SF | Scale factor (power of ten) for ChaState. | INT16 | Read | ||||
| HR | 40368doc 40369 | InOutWRte_SF | Scale factor (power of ten) for InOutWRte. | INT16 | Read | ||||
| HR | 40369doc 40370 | DERMeasureAC ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40370doc 40371 | DERMeasureAC L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40371doc 40372 | ACType | AC wiring type. | UINT16 | Read | 0 = Single Phase; 1 = Split Phase | |||
| HR | 40372doc 40373 | St | Operating state (off/on). | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 40373doc 40374 | InvSt | Inverter state. | UINT16 | Read | 0 = Off; 1 = Sleeping; 2 = Starting; 3 = Running; 4 = Throttled; 5 = Shutting Down; 6 = Fault; 7 = Standby | |||
| HR | 40374doc 40375 | ConnSt | Grid connection state. | UINT16 | Read | 0 = Disconnected; 1 = Connected | |||
| HR | 40379doc 40380 | W | Total active power; positive when exporting. | INT16 | × 10^SF (HR 40485) | W | Read | ||
| HR | 40381doc 40382 | Var | Total reactive power. | INT16 | × 10^SF (HR 40488) | Var | Read | ||
| HR | 40384doc 40385 | LLV | Average line-to-line voltage of active phases. | UINT16 | × 10^SF (HR 40483) | V | Read | ||
| HR | 40385doc 40386 | LNV | Average line-to-neutral voltage of active phases. | UINT16 | × 10^SF (HR 40483) | V | Read | ||
| HR | 40415doc 40416 | VL1L2 | Voltage L1-L2. | UINT16 | × 10^SF (HR 40483) | V | Read | ||
| HR | 40416doc 40417 | VL1 | Voltage L1-N. | UINT16 | × 10^SF (HR 40483) | V | Read | ||
| HR | 40439doc 40440 | VL2 | Voltage L2-N. | UINT16 | × 10^SF (HR 40483) | V | Read | ||
| HR | 40483doc 40484 | V_SF | Scale factor (power of ten) for V values in this block. | INT16 | Read | ||||
| HR | 40484doc 40485 | Hz_SF | Scale factor (power of ten) for Hz values in this block. | INT16 | Read | ||||
| HR | 40485doc 40486 | W_SF | Scale factor (power of ten) for W values in this block. | INT16 | Read | ||||
| HR | 40488doc 40489 | Var_SF | Scale factor (power of ten) for Var values in this block. | INT16 | Read | ||||
| HR | 40524doc 40525 | DERCapacity ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40525doc 40526 | DERCapacity L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40526doc 40527 | WMaxRtg | Maximum active power rating at unity power factor. | UINT16 | × 10^SF (HR 40569) | W | Read | ||
| HR | 40527doc 40528 | WOvrExtRtg | Active power rating at the over-excited power factor. | UINT16 | × 10^SF (HR 40569) | W | Read | ||
| HR | 40528doc 40529 | WOvrExtRtgPF | Over-excited power factor for that rating. | UINT16 | × 10^SF (HR 40570) | Read | |||
| HR | 40529doc 40530 | WUndExtRtg | Active power rating at the under-excited power factor. | UINT16 | × 10^SF (HR 40569) | W | Read | ||
| HR | 40530doc 40531 | WUndExtRtgPF | Under-excited power factor for that rating. | UINT16 | × 10^SF (HR 40570) | Read | |||
| HR | 40531doc 40532 | VAMaxRtg | Maximum apparent power rating. | UINT16 | × 10^SF (HR 40571) | VA | Read | ||
| HR | 40532doc 40533 | VarMaxInjRtg | Maximum injected reactive power rating. | UINT16 | × 10^SF (HR 40572) | Var | Read | ||
| HR | 40533doc 40534 | VarMaxAbsRtg | Maximum absorbed reactive power rating. | UINT16 | × 10^SF (HR 40572) | Var | Read | ||
| HR | 40534doc 40535 | WChaRteMaxRtg | Maximum battery charge power (0 without battery). | UINT16 | × 10^SF (HR 40569) | W | Read | ||
| HR | 40535doc 40536 | WDisChaRteMaxRtg | Maximum battery discharge power (0 without battery). | UINT16 | × 10^SF (HR 40569) | W | Read | ||
| HR | 40536doc 40537 | VAChaRteMaxRtg | Maximum apparent charge power (0 without battery). | UINT16 | × 10^SF (HR 40571) | VA | Read | ||
| HR | 40538doc 40539 | VNomRtg | Nominal AC voltage rating. | UINT16 | × 10^SF (HR 40573) | V | Read | ||
| HR | 40539doc 40540 | VMaxRtg | Maximum AC voltage rating. | UINT16 | × 10^SF (HR 40573) | V | Read | ||
| HR | 40540doc 40541 | VMinRtg | Minimum AC voltage rating. | UINT16 | × 10^SF (HR 40573) | V | Read | ||
| HR | 40544doc 40545 | ReactSusceptRtg | Reactive susceptance left connected when idle. | UINT16 | × 10^SF (HR 40575) | S | Read | ||
| HR | 40545doc 40546 | NorOpCatRtg | IEEE 1547 normal operating category. | UINT16 | Read | ||||
| HR | 40546doc 40547 | AbnOpCatRtg | IEEE 1547 abnormal operating category. | UINT16 | Read | ||||
| HR | 40569doc 40570 | W_SF | Scale factor (power of ten) for W values in this block. | INT16 | Read | ||||
| HR | 40570doc 40571 | PF_SF | Scale factor (power of ten) for PF values in this block. | INT16 | Read | ||||
| HR | 40571doc 40572 | VA_SF | Scale factor (power of ten) for VA values in this block. | INT16 | Read | ||||
| HR | 40572doc 40573 | Var_SF | Scale factor (power of ten) for Var values in this block. | INT16 | Read | ||||
| HR | 40573doc 40574 | V_SF | Scale factor (power of ten) for V values in this block. | INT16 | Read | ||||
| HR | 40575doc 40576 | S_SF | Scale factor (power of ten) for S values in this block. | INT16 | Read | ||||
| HR | 40576doc 40577 | DEREnterService ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40577doc 40578 | DEREnterService L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40578doc 40579 | ES | Permits the inverter to enter service. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40579doc 40580 | ESVHi | Enter-service upper voltage, percent of nominal. | UINT16 | × 10^SF (HR 40593) | Pct | Read/write | ||
| HR | 40580doc 40581 | ESVLo | Enter-service lower voltage, percent of nominal. | UINT16 | × 10^SF (HR 40593) | Pct | Read/write | ||
| HR | 40593doc 40594 | V_SF | Scale factor (power of ten) for V values in this block. | INT16 | Read | ||||
| HR | 40594doc 40595 | Hz_SF | Scale factor (power of ten) for Hz values in this block. | INT16 | Read | ||||
| HR | 40595doc 40596 | DERCtlAC ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40596doc 40597 | DERCtlAC L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40597doc 40598 | PFWInjEna | Enables the fixed power factor while exporting. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40598doc 40599 | PFWInjEnaRvrt | Enables the reversion power factor setting. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40609doc 40610 | WMaxLimPctEna | Enables the active power limit. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40610doc 40611 | WMaxLimPct | Active power limit, percent of rated power. | UINT16 | × 10^SF (HR 40649) | Pct | Read/write | ||
| HR | 40611doc 40612 | WMaxLimPctRvrt | Active power limit used after the reversion timer. | UINT16 | × 10^SF (HR 40649) | Pct | Read/write | ||
| HR | 40612doc 40613 | WMaxLimPctEnaRvrt | Enables the reversion active power limit. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40630doc 40631 | VarSetEna | Enables the fixed reactive power setting. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40631doc 40632 | VarSetMod | Reactive power setting mode (0-3). | UINT16 | Read/write | ||||
| HR | 40632doc 40633 | VarSetPri | Reactive power priority. | UINT16 | Read/write | 1 = Reactive | |||
| HR | 40637doc 40638 | VarSetPct | Reactive power setpoint, percent. | INT16 | × 10^SF (HR 40653) | Pct | Read/write | ||
| HR | 40638doc 40639 | VarSetPctRvrt | Reactive power setpoint used after the reversion timer. | INT16 | × 10^SF (HR 40653) | Pct | Read/write | ||
| HR | 40639doc 40640 | VarSetEnaRvrt | Enables the reversion reactive power setting. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40648doc 40649 | PF_SF | Scale factor (power of ten) for PF values in this block. | INT16 | Read | ||||
| HR | 40649doc 40650 | WMaxLimPct_SF | Scale factor (power of ten) for WMaxLimPct values in this block. | INT16 | Read | ||||
| HR | 40653doc 40654 | VarSetPct_SF | Scale factor (power of ten) for VarSetPct values in this block. | INT16 | Read | ||||
| HR | 40654doc 40655 | PFWInj/PF | Power factor setpoint while exporting. | UINT16 | × 10^SF (HR 40648) | Read/write | |||
| HR | 40655doc 40656 | PFWInj/Ext | Excitation for that setpoint. | UINT16 | Read/write | 0 = Over Excited; 1 = Under Excited | |||
| HR | 40656doc 40657 | PFWInjRvrt/PF | Reversion power factor setpoint. | UINT16 | × 10^SF (HR 40648) | Read/write | |||
| HR | 40657doc 40658 | PFWInjRvrt/Ext | Excitation for the reversion setpoint. | UINT16 | Read/write | 0 = Over Excited; 1 = Under Excited | |||
| HR | 41880doc 41881 | DERStorageCapacity ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 41881doc 41882 | DERStorageCapacity L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 41884doc 41885 | SoC | Battery state of charge. | UINT16 | × 10^SF (HR 41888) | Pct | Read | ||
| HR | 41888doc 41889 | Pct_SF | Scale factor (power of ten) for Pct values in this block. | INT16 | Read | ||||
| HR | 41889doc 41890 | End ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 41890doc 41891 | End L | Length of this block in registers. | UINT16 | Read |
Notes on this map
- Register table from Fronius' official XLSX 'Gen24_Primo_Symo_Inverter_Register_Map_Int&SF_storage_US.xlsx' in gen24-modbus-api-external-docs.zip; changelog 1.2.4-0 says the US files add the 7xx series. Behaviour and settings from the PDF.
- Models 1-124 sit at the same addresses as in the rest-of-world storage map; the 7xx models start at 40370 and the end block is at 41890.
- Word order: neither the PDF nor the XLSX states the order of 32/64-bit values, so every 32/64-bit point is left out (SID, WH, event fields, ActWh, StActCtl, Tms, MPPT DCWH/Tms, and the 32-bit points of models 701-713 such as frequency, energy counters and timers).
- Left out: inverter-model DCA/DCV (40097-40100), every point the XLSX marks not supported, and the trip/curve models 705-712 (volt-var, volt-watt, LV/HV/LF/HF trip, frequency droop, watt-var).
- Many scale factors are auto-scaled: read each value and its SF in the same request. Unsupported values read int16 0x8000, uint16/enum16 0xFFFF.
- Ranges marked 'may vary based on inverter configuration or country setup' (voltage ratings, power factor limits, enter-service thresholds) are installation dependent.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
What Modbus registers does the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) have?
This map lists 236 registers: 236 holding registers. 43 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Fronius numbers SunSpec registers from 40001 and says to send the register number minus one: register 40001 is read at address 40000 (0x9C40). The manual's RTU example reads register 40005 (Mn) with address bytes 9C 44 (40004).
What are the minimum Modbus registers to integrate the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)?
Start with HR 40069 Inverter ID (Inverter model ID (101/103) - confirms int+SF layout); HR 40083 W (AC power); HR 40084 W_SF (AC power scale factor); HR 40107 St (Operating state); HR 40351 ChaState (Battery state of charge); HR 40365 ChaState_SF (SoC scale factor); HR 40232 WMaxLimPct (Active power limit % (model 123)); HR 40236 WMaxLim_Ena (Enable the power limit); HR 40609 WMaxLimPctEna (IEEE 1547 active power limit enable (model 704)).
How do I enable Modbus control of the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)?
Inverter web interface > Communication > Modbus: choose TCP Server and/or RTU Server, set SunSpec Model Type int+SF, and activate 'Allow Control' for power, power factor, reactive power and battery commands.
What happens when the Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) loses Modbus communication?
Model 123 controls have *_RvrtTms fallback timers (0-28800 s) that restart with every Modbus message; model 124 has InOutWRte_RvrtTms. Model 704 holds reversion setpoints (the *Rvrt registers) that apply when its reversion timer expires; those timers are 32-bit and not included here.
Where is the official Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models) Modbus documentation?
The source is Fronius GEN24 Modbus TCP & RTU (operating instructions) + Gen24_Primo_Symo_Inverter_Register_Map_Int&SF_storage_US.xlsx (42,0410,2649 (034-28092026)), revision 2026-09, published free by Fronius at https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2649.pdf.
More Fronius Modbus register maps
- Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Energy meter
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
An energy meter wired to a Fronius Datamanager (or Hybridmanager) over Modbus RTU and republished by it, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0 - Solar inverter
Fronius Tauro 50-3 (SunSpec int+SF)
Fronius Tauro 50-3-P / 50-3-D commercial inverters (rest-of-world map, 3 MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro, Tauro 50-3-P, Tauro 50-3-D - Solar inverter
Fronius Tauro ECO 50-100 (SunSpec int+SF)
Fronius Tauro ECO 50-100 kW commercial inverters (rest-of-world map, single MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro ECO, Tauro ECO 50-3-P, Tauro ECO 99-3-D, Tauro ECO 100-3-P, Tauro ECO 100-3-D
Other solar & battery inverters register maps
- Solar inverter gateway (plant data logger)
Huawei SmartLogger plant data logger (Modbus TCP)
Huawei SmartLogger (V100R001C00 to V300R001C00 firmware families) per ModBus Interface Definitions issue 35; the document names only 'SmartLogger', so check the issue that matches your hardware and firmware.
Also known as: Huawei SmartLogger - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioTrack MPPT solar charge controller (via Xcom-485i)
Studer VarioTrack VT-40/65/80/HV MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VT-40, VT-65, VT-80, VT-HV, VarioTrack VT-65, Xcom-485i - Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Battery inverter
SMA Sunny Tripower Storage X / Sunny Island X (SMA Modbus, ennexOS)
Sunny Tripower Storage X 30/50 (incl. US variants) and Sunny Island X 30/50 (incl. US variants), queried through the System Manager over Modbus TCP.
Also known as: STPS30-20, STPS50-20, STPS27-US-20, STPS60-US-20, SI30-20, SI50-20, SI27-US208-20, SI40-US480-20, SI60-US480-20, Sunny Tripower Storage X 50, Sunny Island X 50 - Battery inverter system (lithium battery BMS interface)
Studer Innotec Xcom-CAN in BMS mode (lithium battery link, via Xcom-485i)
Studer Xcom-CAN set to BMS mode (CAN link to a lithium battery BMS), read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: Xcom-CAN, Xcom-CAN BMS, Xcom-485i
All solar & battery inverters Modbus register maps →
Source: Fronius GEN24 Modbus TCP & RTU (operating instructions) + Gen24_Primo_Symo_Inverter_Register_Map_Int&SF_storage_US.xlsx · 42,0410,2649 (034-28092026) · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.