Solar inverter gateway (plant data logger) · Modbus register map

Huawei SmartLogger plant data logger (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The SmartLogger is Huawei's plant data logger. Over Modbus TCP it answers for itself with logical device ID 0 and reaches inverters, power meters and environment monitors behind it by their RS485 addresses. This map covers the SmartLogger's own registers: clock, power on/off and transfer trip, active and reactive power adjustment, plant totals for power, current, voltage and energy, plant status, scheduling modes and targets, capacity values, DI status and alarm bit words.

This page lists 70 Modbus registers for the Huawei SmartLogger plant data logger (Modbus TCP) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Huawei’s own free documentation (linked below) and checked against it.

Manufacturer
Huawei
Model
SmartLogger plant data logger (Modbus TCP)
Equipment type
Solar inverter gateway (plant data logger)
Registers
70 (25 writable)
Transport
Modbus TCP
Default unit ID
0
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
SmartLogger V100R001C00 / V100R002C00 / V200R001C00 / V300R001C00 or later
Also known as
Huawei SmartLogger
Source document
SmartLogger ModBus Interface Definitions · Issue 35 · rev. 2020-02-20 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Huawei SmartLogger plant data logger (Modbus TCP)

Integration in brief

Connect over Modbus TCP and read plant totals with logical device ID 0: active power at 40525, input power at 40521 and daily/total yield at 40562/40560. Limit the total output of all inverters by writing 40420 (kW x 10) or 40428 (% x 10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40525Active powerINT32 ABCDPlant active powerRead
HR 40521Input powerUINT32 ABCDPlant input powerRead
HR 40560Total energy yield (E-Total)UINT32 ABCDTotal energy yieldRead
HR 40562Daily energy yield (E-Daily)UINT32 ABCDDaily energy yieldRead
HR 40428Active power adjustment by percentageUINT16Active power limit in %Read/write
HR 40737Active power control modeUINT16Active power control modeRead

Enable Modbus control & writes

The document does not describe how to enable Modbus TCP.

Byte order & addressing

Network setup

Watch out for

Huawei SmartLogger plant data logger (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

70 of 70 shown
Huawei SmartLogger plant data logger (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR40000Date and timeUTC epoch seconds.UINT32ABCDsRead/write
HR40004Daylight saving timeUINT16Read/write0 = Disabled; 1 = Enabled
HR40005Time zoneOffset in seconds.INT32ABCDsRead
HR40007DST stateUINT16Read0 = Not in DST; 1 = In DST
HR40008DST offsetUINT16minRead
HR40009Local timeLocal-time epoch seconds.UINT32ABCDsRead
HR40200Power on all invertersWrite 0.UINT16Write
HR40201Power off all invertersWrite 0.UINT16Write
HR40202Power on/off all invertersUINT16Write0 = Power off all; 1 = Power on all
HR40203Power on/off all inverters (inverted)UINT16Write0 = Power on all; 1 = Power off all
HR40204Transfer tripIn fault outage the plant ignores start-up requests.UINT16Read/write0 = Run; 1 = Fault outage
HR40205Array resetWrite 0.UINT16Write
HR40420Active power adjustmentTotal active power limit for all inverters; out-of-range values discarded.UINT32ABCD× 0.1kWRead/write
HR40422Reactive power adjustmentTotal reactive power for all inverters.INT32ABCD× 0.1kvarRead/write
HR40424Active power adjustment (2)Second register for total active power adjustment.UINT32ABCD× 0.1kWRead/write
HR40426Reactive power adjustment (2)Second register for total reactive power adjustment.INT32ABCD× 0.1kvarRead/write
HR40428Active power adjustment by percentage0-100 % for all inverters.UINT16× 0.1%Read/write
HR40429Power factor adjustment(-1, -0.8] or [0.8, 1].INT16× 0.001Read/write
HR40500DC currentSum over all inverters on the SmartLogger. Use 40554 if it overflows.INT16× 0.1ARead
HR40521Input powerSum over all inverters on the SmartLogger.UINT32ABCD× 0.001kWRead
HR40523CO2 reductionSum over all inverters on the SmartLogger.UINT32ABCD× 0.1kgRead
HR40525Active powerSum over all inverters on the SmartLogger.INT32ABCD× 0.001kWRead
HR40532Power factorSum over all inverters on the SmartLogger.INT16× 0.001Read
HR40543Plant status (Qinghai)UINT16Read1 = Unlimited operation; 2 = Limited operation; 3 = Idle; 4 = Outage; 5 = Communication interrupt
HR40544Reactive powerSum over all inverters on the SmartLogger.INT32ABCD× 0.001kvarRead
HR40550CO2 reduction (64-bit)Wider-range copy of 40523.UINT64ABCD× 0.01kgRead
HR40554DC current 2Wider-range copy of 40500.INT32ABCD× 0.1ARead
HR40560Total energy yield (E-Total)Sum over all inverters on the SmartLogger.UINT32ABCD× 0.1kWhRead
HR40562Daily energy yield (E-Daily)Sum over all inverters on the SmartLogger.UINT32ABCD× 0.1kWhRead
HR40564Daily generation durationUINT32ABCD× 0.1hRead
HR40566Plant status (Xinjiang)UINT16Read0 = Idle; 1 = On-grid; 2 = On-grid, self derating; 3 = On-grid, power limit; 4 = Planned outage; 5 = Power limit outage; 6 = Fault outage; 7 = Communication interrupt
HR40567Plant status (Ningxia)UINT16Read1 = On-grid; 2 = Outage; 3 = Maintenance; 4 = Idle
HR40568Active alarm sequence numberUINT32ABCDRead
HR40570Historical alarm sequence numberUINT32ABCDRead
HR40572Phase A currentSum over all inverters on the SmartLogger.INT16ARead
HR40573Phase B currentSum over all inverters on the SmartLogger.INT16ARead
HR40574Phase C currentSum over all inverters on the SmartLogger.INT16ARead
HR40575UabUINT16× 0.1VRead
HR40576UbcUINT16× 0.1VRead
HR40577UcaUINT16× 0.1VRead
HR40685Inverter efficiencyUINT16× 0.01%Read
HR40693Max. reactive adjustmentTotal max power of parallel inverters x 60 %.UINT32ABCD× 0.1kvarRead
HR40695Min. reactive adjustmentTotal max power x 60 % x -1.INT32ABCD× 0.1kvarRead
HR40697Max. active adjustmentTotal max power of parallel inverters.UINT32ABCD× 0.1kWRead
HR40699LockedUnlocked when more than one inverter feeds the grid.UINT16Read0 = Locked; 1 = Unlocked
HR40700DI statusBITMAP16Readbit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 closed; bit 3 = DI4 closed; bit 4 = DI5 closed; bit 5 = DI6 closed; bit 6 = DI7 closed; bit 7 = DI8 closed
HR40713ESNSmartLogger serial number.STRING[20]Read
HR40723System resetResets the SmartLogger; value not checked.UINT16Write
HR40724Fast device accessStarts automatic address allocation and device search.UINT16Write
HR40736Device access statusUINT16Read0 = Search completed; 1 = Search in progress; 2 = Search failed
HR40737Active power control modeUINT16Read0 = No limit; 1 = DI active scheduling; 3 = Percentage fixed limit (open loop); 4 = Remote scheduling; 6 = Export limitation (kW); 200 = Remote output control; 65533 = Slave SmartLogger; 65534 = No scheduling
HR40738Active power scheduling targetUINT32ABCD× 0.1kWRead
HR40740Reactive power control modeUINT16Read0 = No output; 1 = DI reactive scheduling; 2 = Fixed reactive power; 3 = Fixed power factor; 4 = Q-U curve; 5 = cos(phi)-P/Pn curve; 6 = Q-U hysteresis curve (CEI0-16); 7 = Remote scheduling; 9 = PF closed loop (old); 10 = PF closed loop; 65533 = Slave SmartLogger; 65534 = No scheduling
HR40741Reactive power scheduling curve modeUINT16Read0 = Power factor; 1 = Fixed reactive power
HR40802Active scheduling percentage0-100.UINT32ABCD%Read
HR41124CO2 reduction coefficient0-10.UINT16× 0.001kg/kWhRead/write
HR41934PV module capacityUINT32ABCD× 0.001kWRead
HR41936Rated plant capacityUINT32ABCD× 0.001kWRead
HR41938Rated capacity of grid-connected invertersUINT32ABCD× 0.001kWRead
HR41940Conversion coefficientUINT32ABCD× 0.001Read
HR42017System time: year2000-2068, local time.UINT16Read/write
HR42018System time: month1-12, local time.UINT16Read/write
HR42019System time: day1-31, local time.UINT16Read/write
HR42020System time: hour0-23, local time.UINT16Read/write
HR42021System time: minute0-59, local time.UINT16Read/write
HR42022System time: second0-59, local time.UINT16Read/write
HR42730InspectionUINT16Write0 = Start; 1 = Stop
HR42779IV curve scanningUINT16Write0 = Stop; 1 = Start (64 points); 2 = Start (128 points); 3 = Start (256 points)
HR50000Alarm info 1BITMAP16Readbit 3 = 1100 Abnormal active schedule; bit 11 = 1101 Abnormal reactive schedule
HR50001Alarm info 2BITMAP16Readbit 1 = 1103 MCB disconnect; bit 2 = 1104 Abnormal cubicle; bit 3 = 1105 Device address conflict; bit 4 = 1106 AC SPD fault; bit 5 = 1107 DI1 custom alarm; bit 6 = 1108 DI2 custom alarm; bit 7 = 1109 DI3 custom alarm; bit 8 = 1110 DI4 custom alarm; bit 9 = 1111 DI5 custom alarm; bit 10 = 1112 DI6 custom alarm; bit 11 = 1113 DI7 custom alarm; bit 12 = 1114 DI8 custom alarm; bit 13 = 1115 24 V power failure; bit 14 = 1119 License expired

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Huawei SmartLogger plant data logger (Modbus TCP)

What Modbus registers does the Huawei SmartLogger plant data logger (Modbus TCP) have?

This map lists 70 registers: 70 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Huawei SmartLogger plant data logger (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are sent as printed: the read example requests register 32306 with address bytes 7E 32. In Modbus TCP the SmartLogger's own registers use logical device ID 0.

What byte order does the Huawei SmartLogger plant data logger (Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Huawei SmartLogger plant data logger (Modbus TCP)?

Start with HR 40525 Active power (Plant active power); HR 40521 Input power (Plant input power); HR 40560 Total energy yield (E-Total) (Total energy yield); HR 40562 Daily energy yield (E-Daily) (Daily energy yield); HR 40428 Active power adjustment by percentage (Active power limit in %); HR 40737 Active power control mode (Active power control mode).

How do I enable Modbus control of the Huawei SmartLogger plant data logger (Modbus TCP)?

The document does not describe how to enable Modbus TCP.

Where is the official Huawei SmartLogger plant data logger (Modbus TCP) Modbus documentation?

The source is SmartLogger ModBus Interface Definitions (Issue 35), revision 2020-02-20. Huawei doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.symcon.de/uploads/short-url/rIF4NzZBqBfB7S5WtTWW5jRamGn.pdf. It may be an older revision, so check it against the live unit.

More Huawei Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: SmartLogger ModBus Interface Definitions · Issue 35 · rev. 2020-02-20 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.