Solar inverter gateway (plant data logger) · Modbus register map
Huawei SmartLogger plant data logger (Modbus TCP) Modbus register map
Updated 17 November 2026
The SmartLogger is Huawei's plant data logger. Over Modbus TCP it answers for itself with logical device ID 0 and reaches inverters, power meters and environment monitors behind it by their RS485 addresses. This map covers the SmartLogger's own registers: clock, power on/off and transfer trip, active and reactive power adjustment, plant totals for power, current, voltage and energy, plant status, scheduling modes and targets, capacity values, DI status and alarm bit words.
This page lists 70 Modbus registers for the Huawei SmartLogger plant data logger (Modbus TCP) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Huawei’s own free documentation (linked below) and checked against it.
- Manufacturer
- Huawei
- Model
- SmartLogger plant data logger (Modbus TCP)
- Equipment type
- Solar inverter gateway (plant data logger)
- Registers
- 70 (25 writable)
- Transport
- Modbus TCP
- Default unit ID
- 0
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- SmartLogger V100R001C00 / V100R002C00 / V200R001C00 / V300R001C00 or later
- Also known as
- Huawei SmartLogger
Integration notes: Huawei SmartLogger plant data logger (Modbus TCP)
Connect over Modbus TCP and read plant totals with logical device ID 0: active power at 40525, input power at 40521 and daily/total yield at 40562/40560. Limit the total output of all inverters by writing 40420 (kW x 10) or 40428 (% x 10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40525 | Active power | INT32 ABCD | Plant active power | Read |
| HR 40521 | Input power | UINT32 ABCD | Plant input power | Read |
| HR 40560 | Total energy yield (E-Total) | UINT32 ABCD | Total energy yield | Read |
| HR 40562 | Daily energy yield (E-Daily) | UINT32 ABCD | Daily energy yield | Read |
| HR 40428 | Active power adjustment by percentage | UINT16 | Active power limit in % | Read/write |
| HR 40737 | Active power control mode | UINT16 | Active power control mode | Read |
Enable Modbus control & writes
The document does not describe how to enable Modbus TCP.
Byte order & addressing
- Logical device ID 0 addresses the SmartLogger itself; other IDs reach connected devices.
- Gains are divisors (10, 100, 1000).
- Several 'Plant status' registers are used only in specific Chinese regions (Qinghai, Xinjiang, Ningxia); pick the one your site uses.
Network setup
- Modbus TCP on port 502.
- Function codes: 03 read, 06 write single, 10 write multiple, 2B device identification.
Watch out for
- Power on/off registers act on all inverters at once.
- Out-of-range power adjustment values are discarded.
Huawei SmartLogger plant data logger (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40000 | Date and time | UTC epoch seconds. | UINT32 | ABCD | s | Read/write | ||
| HR | 40004 | Daylight saving time | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 40005 | Time zone | Offset in seconds. | INT32 | ABCD | s | Read | ||
| HR | 40007 | DST state | UINT16 | Read | 0 = Not in DST; 1 = In DST | ||||
| HR | 40008 | DST offset | UINT16 | min | Read | ||||
| HR | 40009 | Local time | Local-time epoch seconds. | UINT32 | ABCD | s | Read | ||
| HR | 40200 | Power on all inverters | Write 0. | UINT16 | Write | ||||
| HR | 40201 | Power off all inverters | Write 0. | UINT16 | Write | ||||
| HR | 40202 | Power on/off all inverters | UINT16 | Write | 0 = Power off all; 1 = Power on all | ||||
| HR | 40203 | Power on/off all inverters (inverted) | UINT16 | Write | 0 = Power on all; 1 = Power off all | ||||
| HR | 40204 | Transfer trip | In fault outage the plant ignores start-up requests. | UINT16 | Read/write | 0 = Run; 1 = Fault outage | |||
| HR | 40205 | Array reset | Write 0. | UINT16 | Write | ||||
| HR | 40420 | Active power adjustment | Total active power limit for all inverters; out-of-range values discarded. | UINT32 | ABCD | × 0.1 | kW | Read/write | |
| HR | 40422 | Reactive power adjustment | Total reactive power for all inverters. | INT32 | ABCD | × 0.1 | kvar | Read/write | |
| HR | 40424 | Active power adjustment (2) | Second register for total active power adjustment. | UINT32 | ABCD | × 0.1 | kW | Read/write | |
| HR | 40426 | Reactive power adjustment (2) | Second register for total reactive power adjustment. | INT32 | ABCD | × 0.1 | kvar | Read/write | |
| HR | 40428 | Active power adjustment by percentage | 0-100 % for all inverters. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 40429 | Power factor adjustment | (-1, -0.8] or [0.8, 1]. | INT16 | × 0.001 | Read/write | |||
| HR | 40500 | DC current | Sum over all inverters on the SmartLogger. Use 40554 if it overflows. | INT16 | × 0.1 | A | Read | ||
| HR | 40521 | Input power | Sum over all inverters on the SmartLogger. | UINT32 | ABCD | × 0.001 | kW | Read | |
| HR | 40523 | CO2 reduction | Sum over all inverters on the SmartLogger. | UINT32 | ABCD | × 0.1 | kg | Read | |
| HR | 40525 | Active power | Sum over all inverters on the SmartLogger. | INT32 | ABCD | × 0.001 | kW | Read | |
| HR | 40532 | Power factor | Sum over all inverters on the SmartLogger. | INT16 | × 0.001 | Read | |||
| HR | 40543 | Plant status (Qinghai) | UINT16 | Read | 1 = Unlimited operation; 2 = Limited operation; 3 = Idle; 4 = Outage; 5 = Communication interrupt | ||||
| HR | 40544 | Reactive power | Sum over all inverters on the SmartLogger. | INT32 | ABCD | × 0.001 | kvar | Read | |
| HR | 40550 | CO2 reduction (64-bit) | Wider-range copy of 40523. | UINT64 | ABCD | × 0.01 | kg | Read | |
| HR | 40554 | DC current 2 | Wider-range copy of 40500. | INT32 | ABCD | × 0.1 | A | Read | |
| HR | 40560 | Total energy yield (E-Total) | Sum over all inverters on the SmartLogger. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 40562 | Daily energy yield (E-Daily) | Sum over all inverters on the SmartLogger. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 40564 | Daily generation duration | UINT32 | ABCD | × 0.1 | h | Read | ||
| HR | 40566 | Plant status (Xinjiang) | UINT16 | Read | 0 = Idle; 1 = On-grid; 2 = On-grid, self derating; 3 = On-grid, power limit; 4 = Planned outage; 5 = Power limit outage; 6 = Fault outage; 7 = Communication interrupt | ||||
| HR | 40567 | Plant status (Ningxia) | UINT16 | Read | 1 = On-grid; 2 = Outage; 3 = Maintenance; 4 = Idle | ||||
| HR | 40568 | Active alarm sequence number | UINT32 | ABCD | Read | ||||
| HR | 40570 | Historical alarm sequence number | UINT32 | ABCD | Read | ||||
| HR | 40572 | Phase A current | Sum over all inverters on the SmartLogger. | INT16 | A | Read | |||
| HR | 40573 | Phase B current | Sum over all inverters on the SmartLogger. | INT16 | A | Read | |||
| HR | 40574 | Phase C current | Sum over all inverters on the SmartLogger. | INT16 | A | Read | |||
| HR | 40575 | Uab | UINT16 | × 0.1 | V | Read | |||
| HR | 40576 | Ubc | UINT16 | × 0.1 | V | Read | |||
| HR | 40577 | Uca | UINT16 | × 0.1 | V | Read | |||
| HR | 40685 | Inverter efficiency | UINT16 | × 0.01 | % | Read | |||
| HR | 40693 | Max. reactive adjustment | Total max power of parallel inverters x 60 %. | UINT32 | ABCD | × 0.1 | kvar | Read | |
| HR | 40695 | Min. reactive adjustment | Total max power x 60 % x -1. | INT32 | ABCD | × 0.1 | kvar | Read | |
| HR | 40697 | Max. active adjustment | Total max power of parallel inverters. | UINT32 | ABCD | × 0.1 | kW | Read | |
| HR | 40699 | Locked | Unlocked when more than one inverter feeds the grid. | UINT16 | Read | 0 = Locked; 1 = Unlocked | |||
| HR | 40700 | DI status | BITMAP16 | Read | bit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 closed; bit 3 = DI4 closed; bit 4 = DI5 closed; bit 5 = DI6 closed; bit 6 = DI7 closed; bit 7 = DI8 closed | ||||
| HR | 40713 | ESN | SmartLogger serial number. | STRING[20] | Read | ||||
| HR | 40723 | System reset | Resets the SmartLogger; value not checked. | UINT16 | Write | ||||
| HR | 40724 | Fast device access | Starts automatic address allocation and device search. | UINT16 | Write | ||||
| HR | 40736 | Device access status | UINT16 | Read | 0 = Search completed; 1 = Search in progress; 2 = Search failed | ||||
| HR | 40737 | Active power control mode | UINT16 | Read | 0 = No limit; 1 = DI active scheduling; 3 = Percentage fixed limit (open loop); 4 = Remote scheduling; 6 = Export limitation (kW); 200 = Remote output control; 65533 = Slave SmartLogger; 65534 = No scheduling | ||||
| HR | 40738 | Active power scheduling target | UINT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 40740 | Reactive power control mode | UINT16 | Read | 0 = No output; 1 = DI reactive scheduling; 2 = Fixed reactive power; 3 = Fixed power factor; 4 = Q-U curve; 5 = cos(phi)-P/Pn curve; 6 = Q-U hysteresis curve (CEI0-16); 7 = Remote scheduling; 9 = PF closed loop (old); 10 = PF closed loop; 65533 = Slave SmartLogger; 65534 = No scheduling | ||||
| HR | 40741 | Reactive power scheduling curve mode | UINT16 | Read | 0 = Power factor; 1 = Fixed reactive power | ||||
| HR | 40802 | Active scheduling percentage | 0-100. | UINT32 | ABCD | % | Read | ||
| HR | 41124 | CO2 reduction coefficient | 0-10. | UINT16 | × 0.001 | kg/kWh | Read/write | ||
| HR | 41934 | PV module capacity | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 41936 | Rated plant capacity | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 41938 | Rated capacity of grid-connected inverters | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 41940 | Conversion coefficient | UINT32 | ABCD | × 0.001 | Read | |||
| HR | 42017 | System time: year | 2000-2068, local time. | UINT16 | Read/write | ||||
| HR | 42018 | System time: month | 1-12, local time. | UINT16 | Read/write | ||||
| HR | 42019 | System time: day | 1-31, local time. | UINT16 | Read/write | ||||
| HR | 42020 | System time: hour | 0-23, local time. | UINT16 | Read/write | ||||
| HR | 42021 | System time: minute | 0-59, local time. | UINT16 | Read/write | ||||
| HR | 42022 | System time: second | 0-59, local time. | UINT16 | Read/write | ||||
| HR | 42730 | Inspection | UINT16 | Write | 0 = Start; 1 = Stop | ||||
| HR | 42779 | IV curve scanning | UINT16 | Write | 0 = Stop; 1 = Start (64 points); 2 = Start (128 points); 3 = Start (256 points) | ||||
| HR | 50000 | Alarm info 1 | BITMAP16 | Read | bit 3 = 1100 Abnormal active schedule; bit 11 = 1101 Abnormal reactive schedule | ||||
| HR | 50001 | Alarm info 2 | BITMAP16 | Read | bit 1 = 1103 MCB disconnect; bit 2 = 1104 Abnormal cubicle; bit 3 = 1105 Device address conflict; bit 4 = 1106 AC SPD fault; bit 5 = 1107 DI1 custom alarm; bit 6 = 1108 DI2 custom alarm; bit 7 = 1109 DI3 custom alarm; bit 8 = 1110 DI4 custom alarm; bit 9 = 1111 DI5 custom alarm; bit 10 = 1112 DI6 custom alarm; bit 11 = 1113 DI7 custom alarm; bit 12 = 1114 DI8 custom alarm; bit 13 = 1115 24 V power failure; bit 14 = 1119 License expired |
Notes on this map
- Huawei hosts this document only behind a support-site login; the copy linked is a forum upload of the unaltered Huawei PDF.
- Data encoding is big-endian for addresses and data (leftmost byte first), so 32- and 64-bit values are read high word first (ABCD).
- Gain is a divisor: a value with gain 10 in kW is read as raw / 10 kW.
- RO registers accept only function 03; WO registers accept only 06/16; RW accept all three.
- Left out: City (40002, no coding given), Reserved (40608), Device operation (40725, mixed ESN + command block), the reactive scheduling target (40742) whose gain is 10 or 1000 depending on mode, Japanese-utility communication registers 41942-41949 (gain marked N/A), current error during scanning (42150), and the power meter, weather station and remapped register sections.
- Alarm info 3 (50002, certificate alarms) appears only in the alarm table, so it is not listed.
- The document gives Modbus TCP port 502.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Huawei SmartLogger plant data logger (Modbus TCP)
What Modbus registers does the Huawei SmartLogger plant data logger (Modbus TCP) have?
This map lists 70 registers: 70 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Huawei SmartLogger plant data logger (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are sent as printed: the read example requests register 32306 with address bytes 7E 32. In Modbus TCP the SmartLogger's own registers use logical device ID 0.
What byte order does the Huawei SmartLogger plant data logger (Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Huawei SmartLogger plant data logger (Modbus TCP)?
Start with HR 40525 Active power (Plant active power); HR 40521 Input power (Plant input power); HR 40560 Total energy yield (E-Total) (Total energy yield); HR 40562 Daily energy yield (E-Daily) (Daily energy yield); HR 40428 Active power adjustment by percentage (Active power limit in %); HR 40737 Active power control mode (Active power control mode).
How do I enable Modbus control of the Huawei SmartLogger plant data logger (Modbus TCP)?
The document does not describe how to enable Modbus TCP.
Where is the official Huawei SmartLogger plant data logger (Modbus TCP) Modbus documentation?
The source is SmartLogger ModBus Interface Definitions (Issue 35), revision 2020-02-20. Huawei doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.symcon.de/uploads/short-url/rIF4NzZBqBfB7S5WtTWW5jRamGn.pdf. It may be an older revision, so check it against the live unit.
More Huawei Modbus register maps
Other solar & battery inverters register maps
- Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioTrack MPPT solar charge controller (via Xcom-485i)
Studer VarioTrack VT-40/65/80/HV MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VT-40, VT-65, VT-80, VT-HV, VarioTrack VT-65, Xcom-485i - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0 - Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Battery inverter
SMA Sunny Tripower Storage X / Sunny Island X (SMA Modbus, ennexOS)
Sunny Tripower Storage X 30/50 (incl. US variants) and Sunny Island X 30/50 (incl. US variants), queried through the System Manager over Modbus TCP.
Also known as: STPS30-20, STPS50-20, STPS27-US-20, STPS60-US-20, SI30-20, SI50-20, SI27-US208-20, SI40-US480-20, SI60-US480-20, Sunny Tripower Storage X 50, Sunny Island X 50 - Battery inverter system (lithium battery BMS interface)
Studer Innotec Xcom-CAN in BMS mode (lithium battery link, via Xcom-485i)
Studer Xcom-CAN set to BMS mode (CAN link to a lithium battery BMS), read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: Xcom-CAN, Xcom-CAN BMS, Xcom-485i
All solar & battery inverters Modbus register maps →
Source: SmartLogger ModBus Interface Definitions · Issue 35 · rev. 2020-02-20 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.