Sensor (battery-powered electromagnetic water flowmeter) · Modbus register map

KROHNE IFC 070 signal converter (Modbus) Modbus register map

Updated 17 November 2026

Short answer

The IFC 070 is KROHNE's battery-powered electromagnetic water meter converter, with an optional mains (FlexPower) supply and an RS-485 Modbus RTU add-on. Flow, totalizers, pressure and temperature are offered three times: as doubles, floats and integers. This map covers the double and float banks, the integer litre counters, alarms, coil commands and the Modbus settings.

This page lists 78 Modbus registers for the KROHNE IFC 070 signal converter (Modbus) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.

Manufacturer
KROHNE
Model
IFC 070 signal converter (Modbus)
Equipment type
Sensor (battery-powered electromagnetic water flowmeter)
Registers
78 (23 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Electronic revision 5.1.0; Modbus 1.1.1 (battery) / 1.1.0 (FlexPower)
Also known as
WATERFLUX 3070, IFC070, IFC 070 FlexPower
Source document
IFC 070 Supplementary Instructions - Battery powered electromagnetic water meter with optional FlexPower · 4005415902 - AD IFC 070 Modbus R02 en · rev. 2022-05 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KROHNE IFC 070 signal converter (Modbus)

Integration in brief

Read the double bank 3000-3071 or the float bank 4000-4035 in one request each. Keep the data format at big endian so multi-register values decode high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4002Volume flow (float)FLOAT32 ABCDVolume flow (float)Read
HR 4008Total volume counter (float)FLOAT32 ABCDTotal volume counter (float)Read
HR 3016Total volume counterFLOAT64 ABCDTotal volume counter (double precision)Read
HR 4022Error/warning states (32-bit)UINT32 ABCDError and warning bitsRead
HR 4028Battery remaining (float)FLOAT32 ABCDBattery remainingRead
HR 4030Flow direction (32-bit)UINT32 ABCDFlow directionRead

Enable Modbus control & writes

The Modbus add-on is configured in the local menu: slave address (default 1), baud rate (default 9600), parity (default even), stop bits, data format (default big endian), transmission delay and reception interval.

Byte order & addressing

Network setup

Watch out for

KROHNE IFC 070 signal converter (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

78 of 78 shown
KROHNE IFC 070 signal converter (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1000Restart deviceWrite 1 to restart.BITWrite
CO1001Reset errorsWrite 1 to clear errors.BITWrite
CO1002Apply changesWrite 1 to commit pending setting changes.BITWrite
CO1003Discard changesWrite 1 to drop pending setting changes.BITWrite
CO1004Load factory defaultsWrite 1; needs Supervisor login.BITWrite
CO2000Flow measurement warning/errorBITRead0 = No alarm; 1 = Alarm
CO2001Battery low (<10 % left)BITRead0 = No alarm; 1 = Alarm
CO2002Pressure measurement warning/errorBITRead0 = No alarm; 1 = Alarm
CO2003Temperature measurement warning/errorBITRead0 = No alarm; 1 = Alarm
CO2004EEPROM errorBITRead0 = No alarm; 1 = Alarm
CO2005Empty pipeBITRead0 = No alarm; 1 = Alarm
CO2006Add-on to main board communication errorBITRead0 = No alarm; 1 = Alarm
CO2007Pressure above maximum alarmBITRead0 = No alarm; 1 = Alarm
CO2008Pressure below minimum alarmBITRead0 = No alarm; 1 = Alarm
CO2009Temperature above maximum alarmBITRead0 = No alarm; 1 = Alarm
CO2010Temperature below minimum alarmBITRead0 = No alarm; 1 = Alarm
CO2011Flow directionBITRead0 = Forward flow; 1 = Reverse flow
CO2500Counter 1 runBITRead/write0 = Stopped; 1 = Running
CO2501Counter 2 runBITRead/write0 = Stopped; 1 = Running
CO2502Reset counter 1Write 1 to reset.BITWrite
CO2503Reset counter 2Write 1 to reset.BITWrite
HR3000Flow speedFLOAT64ABCDm/sRead
HR3004Volume flowFLOAT64ABCDm³/sRead
HR3008Counter 1Can be read or preset.FLOAT64ABCDm³Read/write
HR3012Counter 2Can be read or preset.FLOAT64ABCDm³Read/write
HR3016Total volume counterFLOAT64ABCDm³Read
HR3020Forward volume counterFLOAT64ABCDm³Read
HR3024Reverse volume counterFLOAT64ABCDm³Read
HR3028PressureFLOAT64ABCDmbarRead
HR3032TemperatureFLOAT64ABCDKRead
HR3036Pressure alarm stateReading acknowledges the alarm.UINT64ABCDReadbit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error
HR3040Temperature alarm stateReading acknowledges the alarm.UINT64ABCDReadbit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error
HR3044Error/warning statesUINT64ABCDReadbit 0 = Flow measurement warning; bit 1 = Battery below 10 %; bit 2 = EEPROM error; bit 3 = Communication error; bit 4 = Empty pipe; bit 5 = Mains power failure
HR3048Battery typeUINT64ABCDRead0 = None (mains supply); 1 = Internal 1 battery; 2 = Internal 2 battery; 3 = External battery pack
HR3052Battery capacityFLOAT64ABCDAhRead
HR3056Battery remainingFLOAT64ABCDAhRead
HR3060Flow directionUINT64ABCDRead0 = Forward flow; 1 = Reverse flow
HR3064PressureFLOAT64ABCDbarRead
HR3068TemperatureFLOAT64ABCD°CRead
HR4000Flow speed (float)FLOAT32ABCDm/sRead
HR4002Volume flow (float)FLOAT32ABCDm³/sRead
HR4004Counter 1 (float)FLOAT32ABCDm³Read/write
HR4006Counter 2 (float)FLOAT32ABCDm³Read/write
HR4008Total volume counter (float)FLOAT32ABCDm³Read
HR4010Forward volume counter (float)FLOAT32ABCDm³Read
HR4012Reverse volume counter (float)FLOAT32ABCDm³Read
HR4014Pressure (float)FLOAT32ABCDmbarRead
HR4016Temperature (float)FLOAT32ABCDKRead
HR4018Pressure alarm state (32-bit)Reading acknowledges the alarm.UINT32ABCDReadbit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error
HR4020Temperature alarm state (32-bit)Reading acknowledges the alarm.UINT32ABCDReadbit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error
HR4022Error/warning states (32-bit)UINT32ABCDReadbit 0 = Flow measurement warning; bit 1 = Battery below 10 %; bit 2 = EEPROM error; bit 3 = Communication error; bit 4 = Empty pipe; bit 5 = Mains power failure
HR4024Battery type (32-bit)UINT32ABCDRead0 = None (mains supply); 1 = Internal 1 battery; 2 = Internal 2 battery; 3 = External battery pack
HR4026Battery capacity (float)FLOAT32ABCDAhRead
HR4028Battery remaining (float)FLOAT32ABCDAhRead
HR4030Flow direction (32-bit)UINT32ABCDRead0 = Forward flow; 1 = Reverse flow
HR4032Pressure (float)FLOAT32ABCDbarRead
HR4034Temperature (float)FLOAT32ABCD°CRead
HR5002Volume flow (integer)UINT32ABCDl/hRead
HR5004Counter 1 (integer)UINT32ABCDlRead/write
HR5006Counter 2 (integer)UINT32ABCDlRead/write
HR5008Total volume counter (integer)UINT32ABCDlRead
HR5010Forward volume counter (integer)UINT32ABCDlRead
HR5012Reverse volume counter (integer)UINT32ABCDlRead
HR8000Baud rate1200 to 115200; default 9600. Write needs unlocked access.UINT32ABCDbaudRead/write
HR8002Slave addressWrite needs unlocked access.UINT16Read/write
HR8003ParityUINT16Read/write0 = Even (default); 1 = Odd; 2 = None
HR8004Data formatByte/word order of multi-register values.UINT16Read/write0 = Little endian; 1 = Big endian (default); 2 = Mixed, little-endian words; 3 = Mixed, big-endian words
HR8005Transmission delayAllowed: 0, 5, 10, 20, 30, 40, 50.UINT16msRead/write
HR8006Stop bitsUINT16Read/write1 = 1 stop bit; 2 = 2 stop bits
HR8007Modbus when mains power lostUINT16Read/write0 = Modbus off (default); 1 = Modbus on
HR8008Reception interval0-3600; listen window period for battery saving.UINT16sRead/write
HR8499Uncommitted setting changesCount of changes waiting for Apply.UINT16Read
HR8512Converter serial numberUINT32ABCDRead
HR8524System serial numberSTRING[16]Read
HR8532Sensor serial numberSTRING[16]Read
HR8548Converter software versionSTRING[4]Read
HR9902Bus message countUINT16Read
HR9903Bus communication error countUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KROHNE IFC 070 signal converter (Modbus)

What Modbus registers does the KROHNE IFC 070 signal converter (Modbus) have?

This map lists 78 registers: 21 coils, 57 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KROHNE IFC 070 signal converter (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables list the Modbus protocol (data) address, which goes on the wire unchanged: flow speed at 3000 is requested as 3000. In a 1-based or Modicon tool add 1 (3001 / 43001).

What byte order does the KROHNE IFC 070 signal converter (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KROHNE IFC 070 signal converter (Modbus)?

Start with HR 4002 Volume flow (float) (Volume flow (float)); HR 4008 Total volume counter (float) (Total volume counter (float)); HR 3016 Total volume counter (Total volume counter (double precision)); HR 4022 Error/warning states (32-bit) (Error and warning bits); HR 4028 Battery remaining (float) (Battery remaining); HR 4030 Flow direction (32-bit) (Flow direction).

How do I enable Modbus control of the KROHNE IFC 070 signal converter (Modbus)?

The Modbus add-on is configured in the local menu: slave address (default 1), baud rate (default 9600), parity (default even), stop bits, data format (default big endian), transmission delay and reception interval.

Where is the official KROHNE IFC 070 signal converter (Modbus) Modbus documentation?

The source is IFC 070 Supplementary Instructions - Battery powered electromagnetic water meter with optional FlexPower (4005415902 - AD IFC 070 Modbus R02 en), revision 2022-05. KROHNE doesn't publish it on its own website, so this map was re-typed from a free copy at https://core.instrumart.com/assets/krohne-ifc-070-v3-signal-converter-supplementary-instructions.pdf. It may be an older revision, so check it against the live unit.