Sensor (battery-powered electromagnetic water flowmeter) · Modbus register map
KROHNE IFC 070 signal converter (Modbus) Modbus register map
Updated 17 November 2026
The IFC 070 is KROHNE's battery-powered electromagnetic water meter converter, with an optional mains (FlexPower) supply and an RS-485 Modbus RTU add-on. Flow, totalizers, pressure and temperature are offered three times: as doubles, floats and integers. This map covers the double and float banks, the integer litre counters, alarms, coil commands and the Modbus settings.
This page lists 78 Modbus registers for the KROHNE IFC 070 signal converter (Modbus) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.
- Manufacturer
- KROHNE
- Model
- IFC 070 signal converter (Modbus)
- Equipment type
- Sensor (battery-powered electromagnetic water flowmeter)
- Registers
- 78 (23 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Electronic revision 5.1.0; Modbus 1.1.1 (battery) / 1.1.0 (FlexPower)
- Also known as
- WATERFLUX 3070, IFC070, IFC 070 FlexPower
Integration notes: KROHNE IFC 070 signal converter (Modbus)
Read the double bank 3000-3071 or the float bank 4000-4035 in one request each. Keep the data format at big endian so multi-register values decode high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4002 | Volume flow (float) | FLOAT32 ABCD | Volume flow (float) | Read |
| HR 4008 | Total volume counter (float) | FLOAT32 ABCD | Total volume counter (float) | Read |
| HR 3016 | Total volume counter | FLOAT64 ABCD | Total volume counter (double precision) | Read |
| HR 4022 | Error/warning states (32-bit) | UINT32 ABCD | Error and warning bits | Read |
| HR 4028 | Battery remaining (float) | FLOAT32 ABCD | Battery remaining | Read |
| HR 4030 | Flow direction (32-bit) | UINT32 ABCD | Flow direction | Read |
Enable Modbus control & writes
The Modbus add-on is configured in the local menu: slave address (default 1), baud rate (default 9600), parity (default even), stop bits, data format (default big endian), transmission delay and reception interval.
Byte order & addressing
- Addresses are protocol addresses (0-based).
- Changing the data format register flips byte and/or word order for every multi-register value.
- Reading an alarm-state register acknowledges the alarm.
Network setup
- Default RTU settings: address 1, 9600 baud, even parity, 1 stop bit.
- On battery-powered units the bus is not isolated and is limited to about 100 m without termination.
Watch out for
- On battery units Modbus may be off after a mains loss (8007 default off) or listening only at the reception interval: a master that polls at random times gets no answer.
- Setting writes stay pending until coil 1002 (Apply changes) is set.
KROHNE IFC 070 signal converter (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000 | Restart device | Write 1 to restart. | BIT | Write | ||||
| CO | 1001 | Reset errors | Write 1 to clear errors. | BIT | Write | ||||
| CO | 1002 | Apply changes | Write 1 to commit pending setting changes. | BIT | Write | ||||
| CO | 1003 | Discard changes | Write 1 to drop pending setting changes. | BIT | Write | ||||
| CO | 1004 | Load factory defaults | Write 1; needs Supervisor login. | BIT | Write | ||||
| CO | 2000 | Flow measurement warning/error | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2001 | Battery low (<10 % left) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2002 | Pressure measurement warning/error | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2003 | Temperature measurement warning/error | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2004 | EEPROM error | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2005 | Empty pipe | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2006 | Add-on to main board communication error | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2007 | Pressure above maximum alarm | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2008 | Pressure below minimum alarm | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2009 | Temperature above maximum alarm | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2010 | Temperature below minimum alarm | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 2011 | Flow direction | BIT | Read | 0 = Forward flow; 1 = Reverse flow | ||||
| CO | 2500 | Counter 1 run | BIT | Read/write | 0 = Stopped; 1 = Running | ||||
| CO | 2501 | Counter 2 run | BIT | Read/write | 0 = Stopped; 1 = Running | ||||
| CO | 2502 | Reset counter 1 | Write 1 to reset. | BIT | Write | ||||
| CO | 2503 | Reset counter 2 | Write 1 to reset. | BIT | Write | ||||
| HR | 3000 | Flow speed | FLOAT64 | ABCD | m/s | Read | |||
| HR | 3004 | Volume flow | FLOAT64 | ABCD | m³/s | Read | |||
| HR | 3008 | Counter 1 | Can be read or preset. | FLOAT64 | ABCD | m³ | Read/write | ||
| HR | 3012 | Counter 2 | Can be read or preset. | FLOAT64 | ABCD | m³ | Read/write | ||
| HR | 3016 | Total volume counter | FLOAT64 | ABCD | m³ | Read | |||
| HR | 3020 | Forward volume counter | FLOAT64 | ABCD | m³ | Read | |||
| HR | 3024 | Reverse volume counter | FLOAT64 | ABCD | m³ | Read | |||
| HR | 3028 | Pressure | FLOAT64 | ABCD | mbar | Read | |||
| HR | 3032 | Temperature | FLOAT64 | ABCD | K | Read | |||
| HR | 3036 | Pressure alarm state | Reading acknowledges the alarm. | UINT64 | ABCD | Read | bit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error | ||
| HR | 3040 | Temperature alarm state | Reading acknowledges the alarm. | UINT64 | ABCD | Read | bit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error | ||
| HR | 3044 | Error/warning states | UINT64 | ABCD | Read | bit 0 = Flow measurement warning; bit 1 = Battery below 10 %; bit 2 = EEPROM error; bit 3 = Communication error; bit 4 = Empty pipe; bit 5 = Mains power failure | |||
| HR | 3048 | Battery type | UINT64 | ABCD | Read | 0 = None (mains supply); 1 = Internal 1 battery; 2 = Internal 2 battery; 3 = External battery pack | |||
| HR | 3052 | Battery capacity | FLOAT64 | ABCD | Ah | Read | |||
| HR | 3056 | Battery remaining | FLOAT64 | ABCD | Ah | Read | |||
| HR | 3060 | Flow direction | UINT64 | ABCD | Read | 0 = Forward flow; 1 = Reverse flow | |||
| HR | 3064 | Pressure | FLOAT64 | ABCD | bar | Read | |||
| HR | 3068 | Temperature | FLOAT64 | ABCD | °C | Read | |||
| HR | 4000 | Flow speed (float) | FLOAT32 | ABCD | m/s | Read | |||
| HR | 4002 | Volume flow (float) | FLOAT32 | ABCD | m³/s | Read | |||
| HR | 4004 | Counter 1 (float) | FLOAT32 | ABCD | m³ | Read/write | |||
| HR | 4006 | Counter 2 (float) | FLOAT32 | ABCD | m³ | Read/write | |||
| HR | 4008 | Total volume counter (float) | FLOAT32 | ABCD | m³ | Read | |||
| HR | 4010 | Forward volume counter (float) | FLOAT32 | ABCD | m³ | Read | |||
| HR | 4012 | Reverse volume counter (float) | FLOAT32 | ABCD | m³ | Read | |||
| HR | 4014 | Pressure (float) | FLOAT32 | ABCD | mbar | Read | |||
| HR | 4016 | Temperature (float) | FLOAT32 | ABCD | K | Read | |||
| HR | 4018 | Pressure alarm state (32-bit) | Reading acknowledges the alarm. | UINT32 | ABCD | Read | bit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error | ||
| HR | 4020 | Temperature alarm state (32-bit) | Reading acknowledges the alarm. | UINT32 | ABCD | Read | bit 0 = Minimum alarm active; bit 1 = Maximum alarm active; bit 2 = Unread old minimum alarm; bit 3 = Unread old maximum alarm; bit 4 = Sensor measurement error | ||
| HR | 4022 | Error/warning states (32-bit) | UINT32 | ABCD | Read | bit 0 = Flow measurement warning; bit 1 = Battery below 10 %; bit 2 = EEPROM error; bit 3 = Communication error; bit 4 = Empty pipe; bit 5 = Mains power failure | |||
| HR | 4024 | Battery type (32-bit) | UINT32 | ABCD | Read | 0 = None (mains supply); 1 = Internal 1 battery; 2 = Internal 2 battery; 3 = External battery pack | |||
| HR | 4026 | Battery capacity (float) | FLOAT32 | ABCD | Ah | Read | |||
| HR | 4028 | Battery remaining (float) | FLOAT32 | ABCD | Ah | Read | |||
| HR | 4030 | Flow direction (32-bit) | UINT32 | ABCD | Read | 0 = Forward flow; 1 = Reverse flow | |||
| HR | 4032 | Pressure (float) | FLOAT32 | ABCD | bar | Read | |||
| HR | 4034 | Temperature (float) | FLOAT32 | ABCD | °C | Read | |||
| HR | 5002 | Volume flow (integer) | UINT32 | ABCD | l/h | Read | |||
| HR | 5004 | Counter 1 (integer) | UINT32 | ABCD | l | Read/write | |||
| HR | 5006 | Counter 2 (integer) | UINT32 | ABCD | l | Read/write | |||
| HR | 5008 | Total volume counter (integer) | UINT32 | ABCD | l | Read | |||
| HR | 5010 | Forward volume counter (integer) | UINT32 | ABCD | l | Read | |||
| HR | 5012 | Reverse volume counter (integer) | UINT32 | ABCD | l | Read | |||
| HR | 8000 | Baud rate | 1200 to 115200; default 9600. Write needs unlocked access. | UINT32 | ABCD | baud | Read/write | ||
| HR | 8002 | Slave address | Write needs unlocked access. | UINT16 | Read/write | ||||
| HR | 8003 | Parity | UINT16 | Read/write | 0 = Even (default); 1 = Odd; 2 = None | ||||
| HR | 8004 | Data format | Byte/word order of multi-register values. | UINT16 | Read/write | 0 = Little endian; 1 = Big endian (default); 2 = Mixed, little-endian words; 3 = Mixed, big-endian words | |||
| HR | 8005 | Transmission delay | Allowed: 0, 5, 10, 20, 30, 40, 50. | UINT16 | ms | Read/write | |||
| HR | 8006 | Stop bits | UINT16 | Read/write | 1 = 1 stop bit; 2 = 2 stop bits | ||||
| HR | 8007 | Modbus when mains power lost | UINT16 | Read/write | 0 = Modbus off (default); 1 = Modbus on | ||||
| HR | 8008 | Reception interval | 0-3600; listen window period for battery saving. | UINT16 | s | Read/write | |||
| HR | 8499 | Uncommitted setting changes | Count of changes waiting for Apply. | UINT16 | Read | ||||
| HR | 8512 | Converter serial number | UINT32 | ABCD | Read | ||||
| HR | 8524 | System serial number | STRING[16] | Read | |||||
| HR | 8532 | Sensor serial number | STRING[16] | Read | |||||
| HR | 8548 | Converter software version | STRING[4] | Read | |||||
| HR | 9902 | Bus message count | UINT16 | Read | |||||
| HR | 9903 | Bus communication error count | UINT16 | Read |
Notes on this map
- This copy is hosted by the distributor Instrumart; it is KROHNE document 4005415902 (AD IFC 070 Modbus R02).
- Word order: the data-format setting (8004) offers little endian, big endian (default) and two mixed-endian modes, and the data encoding page says the most significant byte of any multi-byte quantity is sent first. In the default big-endian mode, 32- and 64-bit values are therefore ABCD (highest word first). If the data format is changed, the order changes too.
- The register banks can be read with function 03 or 04 and written with 16; coils with 01/02 and 05. The register section says every address can be read with any function code, so the coil addresses also read as unsigned integers.
- Left out: integer-format flow speed (5000), pressure (5014), temperature (5016, 5032) and battery capacity (5026/5028), because the manual gives no scaling for these integer values; the measurement-settings block 6000-6027, whose printed layout is too jumbled to tie each code to its address; and the string/array identity registers other than the serial numbers.
- Settings registers marked R/W* only accept writes after unlocking with the access-control register 9998 and with the special write option enabled; changes are held until 'Apply changes' (coil 1002).
- To save battery the Modbus interface can be switched off when mains power is lost (default off) and can be set to listen only at a reception interval.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KROHNE IFC 070 signal converter (Modbus)
What Modbus registers does the KROHNE IFC 070 signal converter (Modbus) have?
This map lists 78 registers: 21 coils, 57 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KROHNE IFC 070 signal converter (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables list the Modbus protocol (data) address, which goes on the wire unchanged: flow speed at 3000 is requested as 3000. In a 1-based or Modicon tool add 1 (3001 / 43001).
What byte order does the KROHNE IFC 070 signal converter (Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KROHNE IFC 070 signal converter (Modbus)?
Start with HR 4002 Volume flow (float) (Volume flow (float)); HR 4008 Total volume counter (float) (Total volume counter (float)); HR 3016 Total volume counter (Total volume counter (double precision)); HR 4022 Error/warning states (32-bit) (Error and warning bits); HR 4028 Battery remaining (float) (Battery remaining); HR 4030 Flow direction (32-bit) (Flow direction).
How do I enable Modbus control of the KROHNE IFC 070 signal converter (Modbus)?
The Modbus add-on is configured in the local menu: slave address (default 1), baud rate (default 9600), parity (default even), stop bits, data format (default big endian), transmission delay and reception interval.
Where is the official KROHNE IFC 070 signal converter (Modbus) Modbus documentation?
The source is IFC 070 Supplementary Instructions - Battery powered electromagnetic water meter with optional FlexPower (4005415902 - AD IFC 070 Modbus R02 en), revision 2022-05. KROHNE doesn't publish it on its own website, so this map was re-typed from a free copy at https://core.instrumart.com/assets/krohne-ifc-070-v3-signal-converter-supplementary-instructions.pdf. It may be an older revision, so check it against the live unit.
More KROHNE Modbus register maps
- Sensor (electromagnetic flowmeter)
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
IFC 100 signal converter with the Modbus option, supplementary instructions 4001410101 R01 (08/2014).
Also known as: IFC100, IFC 100 Modbus, KROHNE IFC 100 - Sensor (Coriolis mass flowmeter)
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).
Also known as: MFC300, KROHNE MFC 300 - Sensor (ultrasonic flowmeter)
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
UFC 400 signal converter with Modbus, electronic revision ER 2.2.0_, Modbus version 2.1.0_, supplementary instructions 4002744801 R01 (05/2013).
Also known as: UFC400, KROHNE UFC 400, UFC 400 Modbus
Other solar & battery inverters register maps
- Battery inverter
SMA Sunny Tripower Storage X / Sunny Island X (SMA Modbus, ennexOS)
Sunny Tripower Storage X 30/50 (incl. US variants) and Sunny Island X 30/50 (incl. US variants), queried through the System Manager over Modbus TCP.
Also known as: STPS30-20, STPS50-20, STPS27-US-20, STPS60-US-20, SI30-20, SI50-20, SI27-US208-20, SI40-US480-20, SI60-US480-20, Sunny Tripower Storage X 50, Sunny Island X 50 - Battery inverter system (lithium battery BMS interface)
Studer Innotec Xcom-CAN in BMS mode (lithium battery link, via Xcom-485i)
Studer Xcom-CAN set to BMS mode (CAN link to a lithium battery BMS), read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: Xcom-CAN, Xcom-CAN BMS, Xcom-485i - Solar inverter
Fronius Tauro 50-3 (SunSpec int+SF)
Fronius Tauro 50-3-P / 50-3-D commercial inverters (rest-of-world map, 3 MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro, Tauro 50-3-P, Tauro 50-3-D - Solar charge controller (PWM, dual battery)
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver Duo through the MSC MeterBus-to-RS-232 adapter; Modbus specification V04 (19 March 2019). 16-bit registers only.
Also known as: SunSaver Duo, SSDuo - Solar inverter gateway (PV plant data logger)
SMA Sunny WebBox Modbus gateway (plant and gateway unit IDs 1-2)
Sunny WebBox firmware 1.52 or later with Modbus enabled, SMA Modbus profile as documented in WEBBOX_MODBUS-TB-US-EN-19 v1.9 (legacy product).
Also known as: Sunny WebBox, WebBox, SWEBBOX, Sunny WebBox with Bluetooth - Battery inverter (off-grid inverter-charger)
Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)
Studer Xtender XTH, XTM and XTS inverter-chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: XTH, XTM, XTS, Xtender XTH, Xtender XTM, Xtender XTS, Xcom-485i
All solar & battery inverters Modbus register maps →
Source: IFC 070 Supplementary Instructions - Battery powered electromagnetic water meter with optional FlexPower · 4005415902 - AD IFC 070 Modbus R02 en · rev. 2022-05 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.